2024 01 29 Drawings Mechanical.pdf
PDF 6 MB Posted
- Solicitation number
- 36C24825R0127
About this file
The submitted file is a set of mechanical engineering design drawings for a Department of Veterans Affairs (VA) medical facility renovation project located in Lake City, Florida. The drawings comprehensively detail mechanical systems modifications for the second and third floors of the facility, including:
The mechanical drawings cover multiple critical system aspects, including air handling unit (AHU) configurations, ductwork layouts, piping plans, control diagrams, and equipment schedules. Key mechanical systems include variable air volume (VAV) terminal units, exhaust fans, chilled water and heating water piping, steam systems, and control strategies for air handling units. The project involves completely renovating approximately 30,000 square feet on the 2nd floor while maintaining utilities and systems for other floors, with an estimated 689 calendar day performance period. The mechanical design supports the broader patient privacy improvement project, which is set aside for small business contractors and has an estimated value between $10-15 million.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ONE HALF HOUR FIRE RATING
ONE HOUR FIRE RATING
TWO HOUR FIRE RATING
THREE HOUR FIRE RATING
FOUR HOUR FIRE RATING
SMOKE BARRIER (SB), SMOKE
PARTITION (SP), OR PARTITION
CAPABLE OF RESISTING THE
PASSAGE OF SMOKE (S), AS NOTED
(SB)
RATED PARTITION LEGEND
GENERAL DUCTWORK
ABOVE FINISHED FLOORAFF
AIR DIRT SEPARATORAS
ARCHITECTURALARCH
DIAMETERDIA
DRAWINGDWG
AUTOMATIC AIR VENT
VALVES AND ACCESSORIES
AUTOMATIC FLOW CONTROL VALVE
BALL VALVE
PIPE TEE DOWN
BUTTERFLY VALVE
CAPPED PIPE
CHECK VALVE
CLEAN OUT
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
FLANGED CONNECTION
FLEXIBLE CONNECTION
FLOW METER
GLOBE VALVE
PIPE ANCHOR
PIPE GUIDE
PIPE SLEEVE
PITCH DOWN IN DIRECTION OF ARROW
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
PRESSURE GAUGE WITH GAUGE COCK
SQUARE HEAD COCK
STEAM TRAP
STRAINER
STRAINER W/BLOW DOWN VALVE
THREE WAY CONTROL VALVE
TWO WAY CONTROL VALVE
THERMOMETER
UNION
VACUUM BREAKER
CONTROLS
ANALOG INPUT (TO PANEL)
ANALOG OUTPUT (OUT OF PANEL)
DIGITAL INPUT (TO PANEL)
DIGITAL OUTPUT (OUT OF PANEL)
DIFFERENTIAL PRESSURE
DIFFERENTIAL PRESSURE SENSOR
DUCT SMOKE DETECTOR
AI
DI
DO
FLOW MEASURING SYSTEM
FREEZESTAT
MOTOR
PIPING
MECHANICAL LEGEND
AO
GATE VALVE
PIPE TEE UP
PIPE TURNING DOWN
PIPE TURNING UP
MANUAL AIR VENT
NEEDLE VALVE
PLUG VALVE
PRESSURE/TEMPERATURE TEST PLUG
FIRE DAMPER
MOTORIZED DAMPER
AIR FLOW
M
FLAT OVAL DUCTWORK15x9Ø
RECTANGULAR DUCTWORK14x14
ROUND DUCTWORK14Ø
FLEXIBLE DUCTWORK
EXHAUST REGISTER OR GRILLE
RETURN OR TRANSFER REGISTER OR GRILLE
SUPPLY DIFFUSER, REGISTER OR GRILLE
MITERED ELBOW WITH TURNING VANES
MANUAL VOLUME DAMPER
CHILLED WATER SUPPLYCWS
CHILLED WATER RETURNCWR
CONDENSATE DRAIND
DIRECTION OF FLOW
HEATING WATER SUPPLYHWS
HEATING WATER RETURNHWR
LOW PRESSURE STEAM, 10psigLPS
LOW PRESSURE STEAM CONDENSATELPC
PUMPED STEAM CONDENSATEPC
CARBON DIOXIDE SENSOR
CONTROL DAMPER
CONTROL VALVE
CURRENT SENSING RELAY
CO2
CD
CV
CRS
DP
DPS
DSD
FMS
FZ
H HUMIDISTAT
M
NORMALLY CLOSED
NORMALLY OPEN
NC
NO
CONDENSATE PUMPCP
SP STATIC PRESSURE SENSOR
T TEMPERATURE SENSOR
THERMOSTATT
START/STOPSS
EXPANSION TANKET
ENERGY RECOVERY VENTILATORERV
GAUGEGA
MISCELLANEOUSMISC
FAN COIL UNITFCU
ELECTRICALELEC
HEAT EXCHANGERHX
HEATING WATER PUMPHWP
EXHAUST AIREA
OUTSIDE AIROA
# CONSTRUCTION NOTE
xx-x (cfm)
TYPICAL
UNDERWRITERS LABORATORIESUL
TYP
RETURN AIRRA
RELATIVE HUMIDITYRH
SUPPLY AIRSA
PLUMBINGPLMB
DIFFUSER, GRILLE AND REGISTER DESIGNATION
(WITH CFM INDICATED)
ISOLATION VALVE
FAN SPEED CONTROL SWITCHS
HIGH PRESSURE STEAM, 85psigHPS
HIGH PRESSURE STEAM CONDENSATEHPC
BYPASS CONTROL VALVEBCV
GENERAL
1. ALL MECHANICAL EQUIPMENT AND INSTALLATIONS SHALL YIELD COMPLETE OPERATIONAL SYSTEMS THAT CONFORM TO THE REQUIREMENTS OF THE APPLICABLE LOCAL ORDINANCES AND CODES INCLUDING BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODES AND UNDERWRITERS LABORATORIES OR ETL.
2. THE CONTRACT DOCUMENTS ARE BASED ON EQUIPMENT OF SPECIFIC MANUFACTURERS. IF THE CONTRACTOR SUBMITS OR PROPOSES TO USE EQUIPMENT OTHER THAN THAT USED ON THE CONTRACT DOCUMENTS THEN THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DESIGN AND INSTALLATION REVISIONS AT NO ADDITIONAL COST TO THE PROJECT. REVISIONS INCLUDE, BUT ARE NOT LIMITED TO, CHANGES IN EQUIPMENT DIMENSIONS OR WEIGHT, ACCESS REQUIREMENTS, ORIENTATION AND CONNECTIONS, AND ELECTRICAL REQUIREMENTS.
3. EQUIPMENT OF A SIMILAR TYPE SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER.
4. DO NOT SCALE DRAWINGS. DRAWINGS ARE DIAGRAMMATIC.
5. THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL BE
PERFORMED IN THE PRESENCE OF THE GOVERNMENT UNLESS OTHERWISE WAIVED IN WRITING.
6. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USE OF
SPACE.
7. ALL EQUIPMENT AND MATERIAL REMOVED DURING DEMOLITION SHALL BECOME THE PROPOERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE UNLESS OTHERWISE NOTED.
8. EXISTING DUCT, PIPE AND EQUIPMENT SIZES NOTED ARE ONLY FOR THE CONVENIENCE OF THE CONTRACTOR AND ARE NOT WARRANTED TO BE CORRECT. THE CONTRACTOR SHALL FIELD
VERIFY ALL EXISTING PIPE, DCUTWORK, AND EQUIPMENT SIZES AND THEIR LOCATIONS BEFORE PROCEEDING WITH ANY WORK.
9. PRIOR TO SUBMITTING A PROPOSAL THE CONTRATOR IS STRONGLY ENCOURAGED TO VISIT THE SITE AND THOROUGHLY INSPECT ALL EXISTING CONDITIONS TO ENSURE THE WORK DEPICTED ON
THE DRAWINGS CAN BE INSTALLED AS INDICATED.
10. COORDINATE ALL HVAC SYSTEM OUTAGES WITH THE GOVERNMENT PROVIDNG ADVANCED NOTICE OF ALL SUCH OUTAGES.
11. SHOP DRAWINGS INCLUDING, BUT NOT LIMITED TO, PRODUCT INFORMATION SHALL BE SUBMITTED TO AND APPROVED BY THE ARCHITECT BEFORE ANY MECHANICAL EQUIPMENT IS ORDERED, PURCHASED, RELEASED, OR FABRICATED. SHOP DRAWINGS AND SUBMITTALS SHALL INCLUDE PRODUCT INFORMATION FOR ALL EQUIPMENT SPECIFIED OR SCHEDULED ON THE DRAWINGS.
12. ALL MECHANICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS’ RECOMMENDATIONS AND INSTALLATION INSTRUCTIONS USING MANUFACTURER
RECOMMENDED ACCESSORIES AND ASSOCIATED MATERIALS.
13. ALL EQUIPMENT AND MATERIALS INSTALLED IN AIR PLENUMS SHALL BE COMPLIANT WITH THE REQUIREMENTS FOR PLENUM INSTALLATIONS.
14. BEFORE THE PROJECT IS CONSIDERED SUBSTANTIALLY COMPLETE, THE ENTIRE HVAC SYSTEM SHALL BE TESTED, ADJUSTED, AND BALANCED (TAB) IN ACCORDANCE WITH AABC OR NEBB
STANDARDS, TO DELIVER THE AIR AND WATER FLOW QUANTITIES SHOWN ON THE DRAWINGS. FOR TAB ACTIVITIES DIRTY FILTER RESISTANCE SHALL BE SIMULATED. A CERTIFIED TEST AND BALANCE REPORT SHALL BE SUBMITTED TO, AND APPROVED BY, THE ENGINEER. FURNISH AND INSTALL ADJUSTMENT AND BALANCING DEVICES, (DAMPERS, VALVES, AND SHEAVES) AS REQUIRED
AT NO ADDITIONAL COST TO THE PROJECT.
15. PERMANENTLY MARK FINAL SETTINGS ON BALANCING DEVICES.
16. AT SUBSTANTIAL COMPLETION ALL FILTERS IN ALL MECHANICAL EQUIPMENT SHALL BE NEW AND CLEAN AND ONE COMPLETE EXTRA NEW SET OF FILTERS SHALL BE PROVIDED TO THE OWNER.
17. FURNISH AND INSTALL DUCTWORK TRANSITIONS REQUIRED AT EQUIPMENT CONNECTIONS.
18. CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL MECHANICAL EQUIPMENT, DUCTWORK, ETC. TO FIT WITHIN THE SPACE ALLOWED BY THE ARCHITECTURAL AND STRUCTURAL
CONDITIONS. CUTTING OR OTHERWISE ALTERING ANY STRUCTURAL MEMBERS SHALL NOT BE PERMITTED WITHOUT WRITTEN PERMISSION FROM THE ARCHITECT.
19. LOCATE ALL EQUIPMENT TO PRODUCE UNOBSTRUCTED ACCESS TO EQUIPMENT ACCESS PANELS, CONTROLS, AND VALVING.
20. FURNISH AND INSTALL ACCESS DOORS AND PANELS IN NON-ACCESSIBLE CEILINGS AND IN WALL STRUCTURES TO YIELD ADEQUATE SPACE FOR MAINTENANCE OF EQUIPMENT AND BALANCING OF
SYSTEMS. ACCESS DOORS AND PANELS SHALL BE INSTALLED WHERE SHOWN ON THE DRAWINGS OR AS NECESSARY TO PRODUCE ACCESS TO DAMPERS, VALVES, ETC. COORDINATE EXACT LOCATION OF ALL ACCESS PANELS AND DOORS WITH THE ARCHITECT DURING THE SHOP DRAWING PROCESS.
21. INSTALL DUCT MOUNTED ACCESS DOORS AND PANELS FOR INSPECTION AND REPAIR AT ALL DUCT MOUNTED FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE AND SMOKE DAMPERS, SMOKE DETECTORS, AND MOTOR OPERATED DAMPERS. INSTALL ACCESS DOORS AND PANELS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT. INSTALL DOORS TO SWING AGAINST DUCT STATIC PRESSURE. MINIMUM ACCESS PANEL OR DOOR SIZE SHALL BE 6-INCHES BY 8-INCHES. SIZE PANELS AND DOORS 2-INCHES SMALLER
THAN THE DUCT DIMENSION IN WHICH THE DOOR IS INSTALLED UP TO 24-INCHES MAXIMUM.
22. INSTALL ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WHERE THE MANUFACTURER’S RECOMMENDED MINIMUM LENGTHS OF STRAIGHT
DUCTWORK OR PIPE ARE PROVIDED UPSTREAM AND DOWNSTREAM OF THE DEVICE.
23. FURNISH AND INSTALL A THERMOSTAT, OR IF CONTROL IS THROUGH A CONTROL SYSTEM, THEN A TEMPERATURE SENSOR, FOR ANY EQUIPMENT OR DEVICE REQUIRING A THERMOSTAT OR SENSOR FOR CONTROL WHETHER THE THERMOSTAT OR SENSOR IS INDICATED ON THE DRAWINGS OR NOT.
24. PRIOR TO INSTALLATION OBTAIN APPROVAL FROM ARCHITECT FOR LOCATIONS OF ALL THERMOSTATS AND SENSORS THAT WILL BE LOCATED EXPOSED IN FINISHED AREAS.
25. PRIOR TO INSTALLATION, THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES THE LOCATIONS OF AIR CONDITIONING EQUIPMENT INSTALLED OUTDOORS.
26. AIR CONDITIONING AND MECHANICAL EQUIPMENT INSTALLED OUTDOORS AT GRADE SHALL BE INSTALLLED ON 4-INCH THICK REINFORCED CONCRETE PADS THAT EXTEND 6-INCHES BEYOND THE
PERIMETER OF THE EQUIPMENT.
27. AIR CONDITIONING AND MECHANICAL EQUIPMENT INSTALLED INDOORS SHALL BE INSTALLED ON 4-INCH THICK CONCRETE HOUSEKEEPING PADS WITH DIMENSIONS NOT LESS THAN 6-INCHES
LARGER IN ALL DIRECTIONS THAN SUPPORTED EQUIPMENT. CONCRETE IS TO BE REINFORCED AND HAVE CHARACTERISTICS AS SPECIFIED IN DIVISON 3.
28. FREEZESTATS OR LOW LIMIT SENSORS FOR AIRSTREAMS ARE TO BE SERPENTINE TUBE TYPE INSTALLED IN A VERTICAL PLANE TO DETECT TEMPERATURE ACROSS THE CROSS SECTIONAL PLANE
OF THE ARIFLOW.
29. ESP (EXTERNAL STATIC PRESSURE) VALUES ON THE DRAWINGS ARE ESTIMATES. DEVIATIONS FROM THE CONTRACT DRAWINGS AND OTHER SYSTEM EFFECTS CREATED BY THE INSTALLATION, SUCH AS PROXIMITY OF FITTINGS WITH EACH OTHER AND EQUIPMENT MAY RESULT IN INSTALLED SYSTEM STATIC PRESSURES THAT ARE DIFFERENT THAN THE VALUES ON THE DRAWINGS. FAN MOTOR HORSEPOWERS LISTED ON THE DRAWINGS, AND PROVIDED WITH THE EQUIPMENT, AND FAN SELECTIONS ARE TO PROVIDE ADDITIONAL CAPACITY TO ACCOUNT FOR INCREASES DUE TO DIFFERENCES BETWEEN INSTALLED SYSTEMS AND THE CONTRACT DRAWINGS. EQUIPMENT IS TO BE CAPABLE OF USING THE TOTAL HORSEPOWER OF THE FAN MOTORS.
30. ESP (EXTERNAL STATIC PRESSURE) VALUES ON THE CONTRACT DOCUMENTS DO NOT INCLUDE FILTER REISTANCE. FILTER RESISTANCE IS TO BE COUNTED IN THE (INTERNAL) STATIC PRESSURE RESISTANCE OF THE EQUIPMENT AND THE FILTER RESISTANCE IS TO BE COUNTED AS THE RESISTANCE OF DIRTY FILTERS.
ELECTRICAL COORDINATION
1. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH THE ELECTRICAL DRAWINGS AND ELECTRICAL CONTRACTOR BEFORE ANY PRODUCT INFORMATION OR SHOP DRAWINGS ARE SUBMITTED AND BEFORE ANY EQUIPMENT IS ORDERED. THE ELECTRICAL CHARACTERISTICS (VOLTAGE, PHASE, OVERLOAD PROTECTION, ETC.) OF THE EQUIPMENT FURNISHED SHALL BE COMPATIBLE WITH THE ELECTRICAL CHARACTERISTICS SHOWN ON THE DRAWINGS. ON SHOP DRAWING SUBMITTALS THE MECHANICAL CONTRACTOR SHALL STATE THAT THE ELECTRICAL CHARACTERISITICS OF ALL EQUIPMENT HAS BEEN COORDINATED WITH THE ELECTRICAL CONTRACT DOCUMENTS AND THE
ELECTRICAL CONTRACTOR.
2. ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE INSTALLED WITH DISCONNECT SWITCHES AND STARTERS WHETHER THEY ARE AN INTEGRAL COMPONENT OF THE MANUFACTURER’S EQUIPMENT OR NOT. COORDINATE SWITCH TYPE (FUSED OR NON-FUSED) WITH EQUIPMENT CHARACTERISTICS, MANUFACTURER'S RECOMMENDATIONS, ELECTRICAL
DRAWINGS, AND ELECTRICAL CONTRACTOR.
3. ALL REQUIRED CONTROL WIRING FOR HVAC AND PLUMBING, INCLUDING POWER WIRING REQUIRED FOR CONTROL PANELS, ACTUATORS, DEVICES, ETC., SHALL BE INCLUDED AS PART OF THE MECHANICAL WORK. WIRING, INCLUDING THAT IN HVAC PLENUM SPACES, SHALL BE INSTALLED ACCORDING TO CODE REQUIREMENTS.
4. UNLESS NOTED OTHERWISE, STARTERS, TRANSFORMERS, CONTROLS, AND CONTROL WIRING REQUIRED FOR ALL MECHANICAL SYSTEMS SHALL BE FURNISHED AND INSTALLED BY THE
MECHANICAL CONTRACTOR. SEE ELECTRICAL SPECIFICATIONS FOR WIRING REQUIREMENTS.
SMOKE DETECTION AND FIRE AND SMOKE DAMPERS
1. DUCT SMOKE DETECTORS SHALL BE INSTALLED (A) WHERE INDICATED ON THE DRAWINGS, (B) IN THE RETURN AIR PATH OF ALL FAN SYSTEMS SUPPLYING MORE THAN 2000 CFM OF AIR EXCEPT WHERE THE AIR DISTRIBUTION SYSTEM IS INCAPABLE OF SPREADING SMOKE BEYOND THE ENCLOSING WALLS, FLOOR, AND CEILING OF THE SPACE OR ROOM BEING SERVED.
2. DUCT SMOKE DETECTOR SELECTION AND LOCATION SHALL BE COORDINATED WITH THE ELECTRICAL CONTRACTOR AND ENGINEER. SMOKE DETECTORS SHALL BE WIRED TO STOP THEIR AFFILIATED FAN, OR FANS. UPON DETECTION OF SMOKE, THE SMOKE DETECTORS SHALL COMMUNICATE TO THE BUILDING FIRE ALARM PANEL THAT THE COMMAND TO CLOSE THE DAMPER HAS BEEN GENERATED. SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE IDENTIFIED AS AIR DUCT DETECTOR TROUBLE. SMOKE DETECTORS SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR, MOUNTED IN THE DUCTS BY THE MECHANICAL CONTRACTOR, AND WIRED BY THE ELECTRICAL CONTRACTOR.
3. INSTALL FIRE DAMPERS AS INDICATED AND AS REQUIRED IN ALL PENETRATIONS THROUGH RATED ASSEMBLIES, WALLS, FLOORS, CEILINGS, ETC. TO MAINTAIN THE INTEGRITY OF THE RATED ASSEMBLY. INSTALL SMOKE DAMPERS IN ALL DUCT PENETRATIONS THROUGH SMOKE RATED ASSEMBLIES, WALLS, FLOORS, CEILINGS, ETC. INSTALL COMBINATION FIRE AND SMOKE DAMPERS WHERE DUCTS PENETRATE ASSEMBLIES THAT ARE BOTH FIRE AND SMOKE RATED. FIRE, SMOKE, AND COMBINATION FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
4. ALL PIPE AND DUCT PENETRATIONS OF FIRE-, SMOKE-, OR FIRE- AND SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO PRODUCE A RATED ASSEMBLY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M CO., HILTI INC., OR OTHER APPROVED MANUFACTURER. ACCEPTABLE PRODUCTS ARE HILTI FS-ONE, CP 606, CP648 WRAP STRIP, OR CP680 CAST- IN DEVICE SYSTEMS, OR AS RECOMMENDED BY THE MANUFACTURER FOR A PARTICULAR APPLICATION, OR AN EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.
5. DUCTWORK THAT IS ROUTED PARALLEL TO RATED WALLS SHALL BE INSTALLED A MINIMUM OF 6-INCHES FROM RATED WALLS.
6. FOR DUCTWORK PENETRATING FIRE RATED WALLS INSTALL ADDITIONAL SUPPORTS FOR DUCTWORK LOCATED ON EITHER SIDE OF, AND WITHIN 18-INCHES OF, FIRE RATED WALLS. DUCTWORK OR
PIPING SHALL NOT BE SUPPORTED FROM ANY FIRE RATED WALL.
GENERAL DUCTWORK AND AIR DISTRIBUTION
1. LOCATIONS OF AIR DISTRIBUTION DEVICES, GRILLES, REGISTERS, AND DIFFUSERS, SHOWN ON THE DRAWINGS ARE APPROXIMATE. COORDINATE EXACT LOCATIONS WITH LIGHTS, CEILING GRID, SPRINKLER PIPING, ETC., AND WITH THE ARCHITECTURAL CEILING PLAN.
2. LOCATE AIR SUPPLIES AND RETURNS A MINIMUM OF 3-FEET DISTANCE FROM AREA SMOKE DETECTORS.
3. FLEX CONNECTORS SHALL BE USED FOR ALL CONNECTIONS BETWEEN SHEET METAL DUCTWORK AND MOTOR DRIVEN EQUIPMENT AND AT ALL LOCATIONS WHERE DUCTWORK CROSSES BUILDING
EXPANSION JOINTS. FLEX CONNECTORS SHALL NOT BE USED FOR HIGH HEAT CONNECTIONS. WHERE EXPANSION COMPENSATION (FLEXIBLE CONNECTORS OR FLEXIBLE DUCT WHERE OTHERWISE ACCEPTABLE) IS INSTALLED AT BUILDING EXPANSION JOINTS THE EXPANSION COMPENSATION SHALL HAVE MOVEMENT CAPABILITY EQUAL TO, OR GREATER THAN, THE MAXIMUM
MOVEMENT OF THE BUILDING MOVEMENT.
4. PORTIONS OF DUCTWORK THAT ARE VISIBLE THROUGH AIR DISTRIBUTION DEVICES LOCATED IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.
5. ALL DUCTWORK SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING TILES OR THE CEILING SUPPORT STRUCTURE. DUCT SUPPORTS AND ATTACHMENTS TO
THE STRUCTURE SHALL BE PER SMACNA STANDARDS.
6. DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
7. EXCEPT FOR SUPPLY DUCTWORK BETWEEN AIR HANDLERS AND VAV TERMINAL UNITS, BALANCING DAMPERS SHALL BE INSTALLED WHERE THE BRANCH DUCT JOINS THE MAIN FOR ALL BRANCHES
WHETHER THE DAMPER IS SHOWN ON THE DRAWINGS OR NOT.
8. CONCENTRIC AND ECCENTRIC TRANSITIONS SHALL BE MADE IN MAIN DUCTS UPSTREAM OF CONVERGING BRANCHES AND DOWNSTREAM OF DIVERGING BRANCHES. IN THE CONVERGING
SITUATION THE DUCT AREA SHALL INCREASE BEFORE THE BRANCH AIRFLOW JOINS THE MAIN FLOW AND IN THE DIVERGING SITUATION THE DUCT AREA SHALL DECREASE AFTER THE BRANCH AIRFLOW LEAVES THE MAIN AIRFLOW. A MINIMUM OF SIX INCHES OF STRAIGHT DUCT SHALL BE BETWEEN THE BRANCH AND THE TRANSITION FITTINGS. THE MAXIMUM ANGLE FOR CONCENTRIC TRANSITIONS SHALL BE 45 DEGREES FOR DIVERGING AND 60 DEGREES FOR CONVERGING AND THE MAXIMUM ANGLE FOR ECCENTRIC TRANSITIONS SHALL BE 30 DEGREES.
9. DUCTWORK OR PLENUMS INTO WHICH MOISTURE, OR PRECIPITATION, MAY ENTER OR ACCUMULATE, SUCH AS DUCTWORK CONNECTED TO LOUVERS, SHALL BE INSTALLED TO PRODUCE A MEANS OF DRAINAGE. MEANS OF DRAINAGE MAY INCLUDE, BUT NOT BE LIMITED TO, SLOPING AND DRAINS
10. OVERHEAD DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE WITH SPACE ALLOWED FOR INSULATION, UNLESS NOTED OTHERWISE.
11. IN ALL AREAS EXCEPT MECHANICAL ROOMS, DUCTWORK THAT IS EXPOSED AND SHOWN ON THE PLANS AS ROUND OR FLAT OVAL SHALL BE SPIRAL TYPE. IF THE SERVICE REQUIRES THERMAL
INSULATION, THE DUCTWORK SHALL BE DOUBLE WALL SPIRAL WITH INSULATION BETWEEN THE WALLS. IF THE SERVICE DOES NOT REQUIRE INSULATION, DUCTWORK SHALL BE SINGLE WALL
SPIRAL.
12. WHERE DRAWINGS INDICATE THAT OPEN ENDS OF DUCTWORK ARE TO BE COVERED BY MESH, WIRE MESH, OR SCREEN, THE WIRE MESH SHALL BE 1/2-INCH BY 1/2-INCH ALUMINUM WITH WIRE
THICKNESS 0.063-INCHES UNLESS OTHERWISE NOTED.
MECHANICAL GENERAL NOTES
HVAC AIR DUCT LEAKAGE
1. PORTIONS OR SYSTEMS IDENTIFIED TO BE LEAK TESTED SHALL BE LEAK TESTED IN ACCORDANCE WITH SMACNA UNLESS OTHER OR ADDITIONAL PROCEDURES ARE INDICATED OR SPECIFIED. IF A PORTION OF DUCTWORK IS IDENTIFIED TO BE LEAK TESTED THE TEST IS TO INCLUDE THE DUCTWORK AND ALL DEVICES AND EQUIPMENT IN THE PORTION OF DUCT.
2. LEAKAGE TESTS AND NECESSARY REPAIR OF DUCTWORK SHALL BE COMPLETED PRIOR TO CONCEALMENT OF DUCTS.
3. FOR PORTIONS OR SYSTEMS OF DUCTWORK NOT IDENTIFIED TO BE LEAK TESTED THE FOLLOWING SHALL APPLY. AT THE BEGINNING OF THE WORK PRIOR TO CONSTRUCTING OTHER DUCTWORK
THE CONTRACTOR SHALL CONSTRUCT, ERECT, AND LEAK TEST TWO REPRESENTATIVE PORTIONS OR SPECIMENS OF DUCTWORK. ONE SPECIMEN SHALL BE A PORTION THAT HAS THE LARGEST POSITIVE PRESSURE CLASSIFICATION LISTED IN THE DUCT CONSTRUCTION AND LEAK CLASSIFICATION SCHEDULE FOR THE PROJECT, AND THE OTHER SPECIMEN SHALL BE A PORTION THAT HAS THE LARGEST NEGATIVE PRESSURE CLASSIFICATION LISTED FOR THE PROJECT. EACH REPRESENTATIVE SPECIMEN SHALL INCLUDE AT LEAST FIVE TRANSVERSE JOINTS, TYPICAL SEAMS, AT LEAST TWO TYPICAL BRANCH CONNECTIONS, ONE ELBOW, A FIRE DAMPER IF FIRE DAMPERS ARE INCLUDED IN THE PROJECT, AND A SMOKE OR FIRE/SMOKE DAMPER IF SMOKE OR FIRE/SMOKE DAMPERS ARE INCLUDED IN THE PROJECT. FOR ALL TESTED DUCTWORK SYSTEMS THE LEAKAGE AMOUNT SHALL NOT EXCEED THE ALLOTTED AMOUNT FOR THE PRESSURE CLASS OR THE ALLOTTED AMOUNT FOR THAT PORTION OF THE SYSTEM, WHICHEVER IS APPLICABLE. IF A TESTED SPECIMEN FAILS TO MEET SPECIFIED AIR LEAKAGE CRITERIA, THE CONTRACTOR SHALL MODIFY FABRICATION METHODS TO BRING CONSTRUCTION INTO COMPLIANCE AND SHALL RETEST SPECIMENS UNTIL ACCEPTABLE DUCT AIR LEAKAGE IS DEMONSTRATED.
METAL AND FLEXIBLE DUCTWORK MATERIALS AND CONSTRUCTION
1. MINIMUM THICKNESS FOR HVAC METAL DUCTWORK IS 24 GAUGE.
2. RADIUS OF CURVATURE FOR ROUND AND RECTANGULAR DUCTWORK SHALL BE NO LESS THAN 2 TIMES THE DUCT WIDTH.
3. ALL JOINTS AND SEAMS IN ALL NON-WELDED SHEET METAL DUCTWORK SHALL BE SEALED WITH DUCT SEALER.
4. THE BRANCH DUCTS CONNECTED TO OUTLETS, INLETS, VAV TERMINAL UNITS, FANS, AND OTHER EQUIPMENT SHALL BE THE SIZE OF THE EQUIPMENT OR THE SIZE INDICTED ON THE DRAWINGS, WHICHEVER IS LARGER. SEE GENERAL NOTE 2.
5. SELECT THE SIZES OF FLEXIBLE DUCT TO MATCH THE NECK SIZE OF THE DEVICE TO WHICH IT IS CONNECTED. INSTALL ADAPTORS, INCLUDING RECTANGULAR-TO-ROUND OR SQUARE-TO-ROUND
ADAPTERS OR BOOTS, FOR CONNECTION OF ROUND FLEXIBLE DUCTS TO AIR DEVICE NECKS WHEN REQUIRED. INSTALL ROUND GALVANIZED STEEL DUCT RUNOUTS TO ACHIEVE FLEXIBLE DUCT
LENGTHS OF 5'-0" OR LESS.
6. FLEXIBLE DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE AND SHALL BE ROUTED AND SUPPORTED WITHOUT FORMING CRIMPS OR OTHER AIRFLOW RESTRICTIONS.
7. FLEXIBLE DUCTWORK SHALL NOT BE USED TO MAKE DIRECTIONAL CHANGES GREATER THAN 45 DEGREES.
8. FLEXIBLE DUCTWORK SHALL NOT BE USED WHERE THE RADIUS OF CURVATURE IS REQUIRED TO BE SMALLER THAN TWO TIMES THE DIAMETER OF THE FLEXIBLE DUCT.
9. FLEXIBLE DUCTWORK SHALL NOT BE USED IN PATIENT CARE AREAS.
10. FLEXIBLE DUCTWORK SHALL BE INSTALLED WITH BAND HANGERS MINIMUM 1-INCH WIDE. MAXIMUM SAG SHALL NOT EXCEED ONE HALF-INCH PER FOOT OF LENGTH. MAXIMUM DISTANCE BETWEEN
SUPPORTS SHALL BE 5-FEET.
11. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED THROUGH FIRE, SMOKE, OR FIRE AND SMOKE RATED PARTITIONS.
COOLING COIL CONDENSATE
1. CONDENSATE FROM ALL AIR CONDITIONING EQUIPMENT SHALL BE TRAPPED, SLOPED TO DRAIN, AND ROUTED TO DISCHARGE WHERE INDICATED, IF NO LOCATION IS INDICATED DISCHARGE AT THE NEAREST FLOOR DRAIN UNLESS INDICATED OTHERWISE. WHERE INDICATED TO BE PUMPED, CONDENSATE MAY BE PUMPED WITH CONTROLS INCLUDED AS REQUIRED BY CODE. DRAIN LINES SHALL BE ROUTED TO AVOID INTERFERENCE WITH PASSAGEWAYS AND MAINTENANCE AND TO AVOID CREATING TRIPPING HAZARDS.
2. THE MINIMUM PIPE SIZE FOR CONDENSATE DRAIN LINES SHALL BE 3/4-INCHES DIAMETER.
3. ALL CONDENSATE PRODUCING AIR HANDLING UNITS, FAN COIL UNITS, AND EQUIPMENT LOCATED ABOVE THE FINISHED CEILING OF THE LOWEST LEVEL SHALL BE INSTALLED WITH A CODE
COMPLIANT CONDENSATE DRAINAGE SYSTEM. THE SYSTEM MAY CONSIST OF ONE OF THE FOLLOWING: (A) A CODE COMPLIANT AUXILIARY DRAIN PAN LOCATED UNDER THE COILS EQUIPPED WITH A UL508 WATER LEVEL SWITCH LOCATED IN THE PAN THAT DE-ACTIVATES THE UNIT UPON DETECTION OF WATER PRIOR TO OVERFLOW OF THE PAN; OR IF ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION THE FOLLOWING MAY BE USED IN LIEU OF THE AUXILIARY PAN, (B) A CODE COMPLIANT DEVICE AND INSTALLATION INCLUDING AN ELECTRONIC WATER DETECTOR WIRED TO
SHUTDOWN THE UNIT IN THE EVENT THAT THE PRIMARY DRAIN LINE IS BLOCKED.
ROOFTOP EQUIPMENT AND LOUVERS
1. ALL ROOF MOUNTED EQUIPMENT SHALL BE INSTALLED LEVEL. CONTRACTOR SHALL COORDINATE ROOF SLOPE WITH ARCHITECTURAL DRAWINGS TO PRODUCE AN INSTALLATION WITH
EQUIPEMNT LEVEL.
2. UNLESS NOTED OTHERWISE, ROOF CURBS SHALL BE CUSTOM CURB OR APPROVED EQUAL. ROOF CURBS SUPPLIED AS STANDARD BY THE MANUFACTURER OF THE MECHANICAL EQUIPMENT BEING INSTALLED ON THE CURB ARE ACCEPTABLE. SUBMIT ROOF CURB INFORMATION WITH PRODUCT DATA AND SHOP DRAWINGS. VIBRATION/SOUND ATTENUATING ROOF CURBS, WHERE SCHEDULED OR NOTED, SHALL BE MASON RSC-A (2-1/2-INCHES) OR EQUAL WITH ACOUSTICAL PACKAGE.
3. ROOFTOP HVAC UNITS SHALL BE INSTALLED SUCH THAT THE ROOF DECK IS COMPLETE AND CONTINUOUS UNDER THE BOTTOM OF THE HVAC UNITS, AND SO THAT THE ROOF DECK IS CUT ONLY FOR THE UNIT SUPPLY AND RETURN OPENINGS. THE SPACE INSIDE OF ROOF CURBS BETWEEN THE ROOF DECK AND THE BOTTOM OF THE ROOFTOP HVAC UNITS SHALL BE FILLED WITH HIGH-
DENSITY ACOUSTICAL INSULATION.
4. UNLESS NOTED OTHERWISE, UN-USED PORTIONS OF LOUVERS ARE TO BE BLANKED OFF. INSTALL BLANK OFF PANEL ON ROOM SIDE OF LOUVER. BLANK OFF PANEL SHALL BE CONSTRUCTED OF GLASS FIBER INSULATION SANDWICHED BETWEEN TWO SHEETS OF 22-GAUGE GALVANIZED SHEET METAL. THE INSULATION SHALL BE COMPLETELY ENCLOSED AND THE ENCLOSURE SEALED.
THE INSULATION SHALL BE 6 LB. PER CU. FT. DENSITY MINIMUM 2-INCHES THICK. THE INSULATION SHALL BE SECURED IN PLACE WITH MECHANICAL FASTENERS 6-INCHES ON CENTER.
REFRIGERANT PIPING FOR HVAC EQUIPMENT
1. INSTALL REFRIGERANT PIPING AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER. WHEN THE ACCUMULATED EQUIVALENT LENGTH OF REFRIGERANT LINES BETWEEN PIECES OF EQUIPMENT EXCEEDS THE MANUFACTURER’S RECOMMENDED LENGTHS FOR LINES WITH STANDARD DIAMETER SIZES THEN FURNISH AND INSTALL A MANUFACTURER’S APPROVED REFRIGERANT PIPING SYSTEM CONSISTENT WITH A DIAGRAM FOR TYPICAL SYSTEMS SHOWING RECOMMENDED PIPE SIZES AND COMPONENTS SUCH AS SUCTION LINE ACCUMULATORS WHEN REQUIRED.
SUBMIT THE DIAGRAM FOR REVIEW AND INCLUSION IN THE O&M.
2. INSTALL EXPANSION COMPENSATION IN PIPING THAT CROSSES BUILDING EXPANSION JOINTS. EACH INSTALLED EXPANSION COMPENSATION SYSTEM SHALL HAVE MOVEMENT CAPABILITY EQUAL TO OR GREATER THAN THE MAXIMUM MOVEMENT OF THE BUILDING MOVEMENT AT ITS LOCATION.
HYDRONIC PIPING
1. INSTALL PIPING WITH SUFFICIENT SLOPE TO YIELD AIR VENTING TO HIGH POINTS AND DRAINING TO LOW POINTS.
2. INSTALL DRAIN TEES WITH MANUAL FULL-PORT VALVES AT LOW POINTS OF ALL CIRCULATING HYDRONIC (WATER AND GLYCOL) PIPING SYSTEMS.
3. BRANCHES FOR HYDRONIC PIPING SHALL COME OFF THE TOP OF HORIZONTAL MAINS IF THE AIR VENT AFFILIATED WITH THE EQUIPMENT BEING SERVED BY THE BRANCH IS ABOVE THE MAIN.
BRANCHES SERVING EQUIPMENT LOCATED BELOW THE HORIZONTAL MAIN SHALL COME OFF THE SIDE OR 45 DEGREES BELOW THE HORIZONTAL CENTERLINE OF THE MAIN.
4. TUBING FOR PRESSURE GAUGES, DP SENSORS, AND OTHER SENSORS THAT IS CONNECTED TO HORIZONTAL PIPES SHALL BE CONNECTED TO THE SIDE OF THE HORIZONTAL PIPES CONTAINING
THE MATERIAL BEING SENSED.
5. PIPING AT PUMPS AND EQUIPMENT SHALL BE SUPPORTED SO THAT NO PIPING OR ACCESSORY WEIGHT IS CARRIED BY THE PUMP, EQUIPMENT, OR FLEX CONNECTOR.
6. FOR ALL HYDRONIC PIPING THE MINIIMUM PIPE SIZE SHALL BE 3/4 NPS (3/4-INCHES DIAMETER). LONG RADIUS ELBOWS SHALL BE USED.
7. UNLESS INDICATED OTHERWISE, PIPING SHALL BE INSTALLED BELOW DUCTWORK.
8. PIPING SHALL BE SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
9. VALVES AND SPECIALTIES SHALL BE LINE SIZE UNLESS INDICATED OTHERWISE.
10. VALVES SHALL BE INSTALLED IN LOCATIONS SO THAT THE VALVES REMAIN IN SERVICE AND CONNECTED TO THE PIPING, WHEN THE EQUIPMENT OR PIPING IS REMOVED.
11. VALVES SHALL HAVE POSITION INDICATORS. BALANCING VALVES SHALL HAVE ADJUSTABLE MEMORY STOPS.
12. AT EQUIPMENT AND PUMP CONNECTIONS WHERE THE EQUIPMENT CONNECTION IS DIFFERENT THAN THE INDICATED PIPE SIZE, LOCATE PIPING TRANSITIONS (REDUCERS) NEAREST THE
EQUIPMENT, BETWEEN THE EQUIPMENT AND THE NEXT NEAREST VALVE, STRAINER, OR APPURTENANCE.
13. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND IT SHALL NOT REST ON CEILING TILES OR THE CEILING SUPPORT STRUCTURE.
14. PIPING HUNG FROM JOISTS AND TRUSSES SHALL BE HUNG FROM THE TOP CHORD OF THE JOIST OR TRUSS.
15. ISOLATION VALVES SHALL BE INCLUDED AND INSTALLED IN ALL PIPING CONNECTED TO EACH PIECE OF EQUIPMENT AND EACH PIPING ACCESSORY FOR WHICH MAINTENANCE OR REPLACEMENT
OF THE EQUIPMENT OR ACCESSORY IS REQUIRED.
STEAM PIPING
1. PIPE TRANSITIONS FOR STEAM LINES SHALL BE ECCENTRIC TRANSITIONS WITH THE FLAT SIDE ON THE BOTTOM.
2. INSTALL PIPING WITH SUFFICIENT SLOPE TO YIELD AIR VENTING TO HIGH POINTS AND DRAINING TO LOW POINTS.
3. INSTALL DRAIN TEES WITH MANUAL FULL-PORT VALVES AT LOW POINTS OF ALL STEAM AND STEAM CONDENSATE PIPING SYSTEMS.
4. BRANCHES FOR STEAM PIPING SHALL COME OFF THE TOP OF MAINS.
5. BRANCHES FOR STEAM CONDENSATE FLOWING INTO MAINS SHALL CONNECT ON THE TOP OF MAINS, OR IF CONNECTION ON TOP IS NOT POSSIBLE THEN THE CONNECTION SHALL BE ABOVE THE
CENTER LINE OF THE MAIN.
6. TUBING FOR PRESSURE GAUGES, DP SENSORS, AND OTHER SENSORS THAT IS CONNECTED TO HORIZONTAL PIPES SHALL BE CONNECTED TO THE SIDE OR ABOVE THE CENTER LINE OF THE
HORIZONTAL PIPES CONTAINING THE MATERIAL BEING SENSED.
7. PIPING AT PUMPS AND EQUIPMENT SHALL BE SUPPORTED SO THAT NO PIPING OR ACCESSORY WEIGHT IS CARRIED BY THE PUMP, EQUIPMENT, OR FLEX CONNECTOR.
8. FOR ALL STEAM AND STEAM CONDENSATE PIPING THE MINIIMUM PIPE SIZE SHALL BE 3/4 NPS (3/4-INCHES DIAMETER). LONG RADIUS ELBOWS SHALL BE USED.
9. UNLESS INDICATED OTHERWISE, PIPING SHALL BE INSTALLED BELOW DUCTWORK.
10. PIPING SHALL BE SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
11. VALVES AND SPECIALTIES SHALL BE LINE SIZE UNLESS INDICATED OTHERWISE.
12. VALVES SHALL BE INSTALLED IN LOCATIONS SO THAT THE VALVES REMAIN IN SERVICE, CONNECTED TO THE PIPING, WHEN THE EQUIPMENT OR PIPING IS REMOVED.
13. VALVES SHALL HAVE POSITION INDICATORS. BALANCING VALVES SHALL HAVE ADJUSTABLE MEMORY STOPS.
14. AT EQUIPMENT AND PUMP CONNECTIONS WHERE THE EQUIPMENT CONNECTION IS DIFFERENT THAN THE INDICATED PIPE SIZE, LOCATE PIPING TRANSITIONS (REDUCERS) NEAREST THE
EQUIPMENT, BETWEEN THE EQUIPMENT AND THE NEXT NEAREST VALVE, STRAINER, OR APPURTENANCE.
15. ALL PIPING ABOVE GRADE SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND IT SHALL NOT REST ON CEILING TILES OR THE CEILING SUPPORT STRUCTURE. PIPING HUNG FROM JOISTS
AND TRUSSES SHALL BE HUNG FROM THE TOP CHORD OF THE JOIST OR TRUSS.
16. ISOLATION VALVES SHALL BE INCLUDED AND INSTALLED IN ALL PIPING CONNECTED TO EACH PIECE OF EQUIPMENT AND EACH PIPING ACCESSORY FOR WHICH MAINTENANCE OR REPLACEMENT
OF THE EQUIPMENT OR ACCESSORY IS REQUIRED.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
MECHANICAL LEGEND AND NOTES CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
M001
573 A4-18-603
January 29, 2024 RWHDAC
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
NG I NEE
R
2 4 7 42 44 479 52
13 20 24 28 33 3726 38
40 46 50 53
EXIST. SA DUCT
FROM RISER
SERVING EXIST.
UNIT 64-AC-52
SA SERVING UNRENOVATED AREA
REMOVE ALL SA
DUCTWORK, DIFFUSERS,
ETC. BEYOND THIS POINT
CAP & SEAL AIR-TIGHT
REMOVE ALL EA
DUCTWORK, GRILLES,
ETC. BEYOND THIS POINT
CAP & SEAL AIR-TIGHT
REMOVE ALL EA
DUCTWORK, GRILLES,
ETC. BEYOND THIS POINT
CAP & SEAL AIR-TIGHT
REMOVE ALL EA
DUCTWORK, GRILLES,
ETC. BEYOND THIS POINT
CAP & SEAL AIR-TIGHT
REMOVE EXIST. FCU INCLUDING
PIPES, VALVES, ETC.
EXCLUSIVELY SERVING THE FCU,
PIPING SERVING OTHER FCUs TO
REMAIN & CAPPED WHERE PIPES
HAVE BEEN REMOVED, TYP. FOR
RENOVATED AREAS
X
Y
Z
2 (TYPICAL)2 (TYPICAL) 2(TYPICAL)2(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
S
Q
O
1. EXISTING EXHAUST DUCTWORK RISER TO REMAIN TO SERVE EXISTING
SPACES NOT BEING RENOVATED. REMOVE ALL EXHAUST DUCT BACK TO
WHERE DUCTWORK EXITS THE CHASE. CAP AND SEAL DUCTWORK AIR-
TIGHT.
PRIOR TO CONSTRUCTION MEASURE AND RECORD ALL EXHAUST AIR INLETS
SERVED BY EXISTING FAN CONNECTED TO SPACES NOT BEING RENOVATED.
AFTER DUCTWORK IS REMOVED, CAPPED, AND SEALED AIR-TIGHT, ADJUST
AND BALANCE FAN TO PREVIOUSLY MEASURED AIRFLOWS SO THAT FAN CAN
REMAIN IN SERVICE.
2. REMOVE EXISTING CONSOLE UNIT WITH STEAM HEAT. CAP BRANCH STEAM &
STEAM CONDENSATE PIPES AT RISER. STEAM RISERS FROM BELOW AND UP
TO FLOOR 4 TO REMAIN TO SERVE EXISTING EQUIPMENT TO REMAIN ON
UNRENOVATED FLOORS.
3. EXISTING AHU 64-AC-52 DUCTWORK MAIN TO REMAIN TO SERVE
UNRENOVATED PORTION OF BUILDING.
PRIOR TO CONSTRUCTION CONTRACTOR SHALL MEASURE AND RECORD ALL
SUPPLY AIR OUTLETS SERVED BY EXISTING AHU LOCATED IN PENTHOUSE
SERVING EXISTING SPACES NOT BEING RENOVATED. PORTION OF
DUCTWORK BEING REMOVED SHALL BE CAPPED AND SEALED AIR-TIGHT SO
THAT SYSTEM CAN MAINTAIN CONDITIONING TO SPACES NOT BEING
RENOVATED. EXISTING AHU SHALL BE ADJUSTED AND BALANCED TO
ACHIEVE PREVIOUSLY MEASURED AIRFLOW RATES.
FLOOR PLAN KEY NOTES 1
3/32" = 1' - 0" 0 5' 10' 20' 40'
GRAPHIC SCALE(S)
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
SECOND FLOOR PLAN - OVERALL
DEMOLITION
CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MD101
573 A4-18-603
January 29, 2024 CMDDAC
KEY PLAN
B64A
PLAN
NORTH
TRUE
NORTH
3/32" = 1' - 0" 0 5' 10' 20' 40'
SCALE: 3/32" = 1'-0"
SECOND FLOOR DEMOLITION PLAN
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
2 4 7 42 44 47
101 13
20 24 28 33 3726 38
46 50 53REMOVE ALL EA
DUCTWORK, GRILLES,
ETC. BEYOND THIS POINT
SA & EA DUCTWORK SERVING
UNRENOVATED AREAS TO REMAIN
SA & EA DUCTWORK SERVING
UNRENOVATED AREAS TO REMAIN
SA DUCTWORK SERVING
UNRENOVATED AREAS
TO REMAIN
REMOVE EXIST. FCU INCLUDING PIPES, VALVES, ETC.
EXCLUSIVELY SERVING THE FCU, PIPING SERVING
OTHER FCUs TO REMAIN & CAPPED WHERE PIPES
HAVE BEEN REMOVED, TYP. FOR RENOVATED AREAS
REMOVE ALL EA DUCTWORK,
GRILLES, ETC. BEYOND THIS POINT
X
Y
Z
(TYPICAL)
(TYPICAL)
S
Q
O
1. EXISTING EXHAUST DUCTWORK RISER TO REMAIN TO SERVE EXISTING
SPACES NOT BEING RENOVATED.
2. REMOVE EXISTING CONSOLE UNIT WITH STEAM HEAT. CAP BRANCH STEAM &
STEAM CONDENSATE PIPES AT RISER. STEAM RISERS FROM BELOW AND UP
TO FLOOR 4 TO REMAIN TO SERVE EXISTING EQUIPMENT TO REMAIN ON
UNRENOVATED FLOORS.
3. EXISTING AHU 64-AC-52 DUCTWORK MAIN TO REMAIN TO SERVE
UNRENOVATED PORTION OF BUILDING.
PRIOR TO CONSTRUCTION CONTRACTOR SHALL MEASURE AND RECORD ALL
SUPPLY AIR OUTLETS SERVED BY EXISTING AHU LOCATED IN PENTHOUSE
SERVING EXISTING SPACES NOT BEING RENOVATED. PORTION OF
DUCTWORK BEING REMOVED SHALL BE CAPPED AND SEALED AIR-TIGHT SO
THAT SYSTEM CAN MAINTAIN CONDITIONING TO SPACES NOT BEING
RENOVATED. EXISTING AHU SHALL BE ADJUSTED AND BALANCED TO
ACHIEVE PREVIOUSLY MEASURED AIRFLOW RATES.
4. REMOVE EXISTING BRANCH DUCTWORK BACK TO DUCTWORK MAIN SERVING
EXISTING SPACES BEING RENOVATED. CAP AND SEAL DUCTWORK AIR-TIGHT
SO THAT EXISTING AHU CAN REMAIN IN USE TO SERVE SPACES NOT BEING
RENOVATED.
5. PRIOR TO CONSTRUCTION CONTRACTOR SHALL MEASURE AND RECORD ALL
EXHAUST AIR INLETS SERVED BY EXISTING FAN CONNECTED TO SPACES
NOT BEING RENOVATED. PORTION OF DUCTWORK BEING REMOVED SHALL
BE CAPPED AND SEALED AIR-TIGHT SO THAT EXHAUST FROM SPACES NOT
BEING RENOVATED CAN REMAIN IN SERVICE. EXISTING EXHAUST FAN SHALL
BE ADJUSTED AND BALANCED TO ACHIEVE PREVIOUSLY MEASURED
AIRFLOWS.
FLOOR PLAN KEY NOTES 1
3/32" = 1' - 0" 0 5' 10' 20' 40'
GRAPHIC SCALE(S)
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
THIRD FLOOR - OVERALL
DEMOLITION
CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MD102
573 A4-18-603
January 29, 2024 CMDDAC
SCALE: 3/32" = 1'-0"
B64A - THIRD FLOOR OVERALL DEMOLIION
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
A.I.I.
BEDROOM
2NB-1
A.I.I.
BARIATRIC
BEDROOM
2NA-1
STERILE
SUPPLY
MSD
HAC
STAIR #1
S1.2 NURSE
MANAGER
2NN-1
A.I.I.
BEDROOM
2NC-1 A.I.I.
BEDROOM
2ND-1
A.I.I.
BEDROOM
2NE-1
EQUIPMENT
STORAGE
A213
MED. PREP
2NN-5
NOURISH
2NN-4
STAIR #2
S2.2
CORRIDOR-1
C2-3-1
CORRIDOR
C2-4
SOILED
UTILITY RM
CLEAN
UTILITY RM
PUBLIC
ELEVATOR
LOBBY
C2-1
MED. GAS
STORAGE
A.I.I.
BEDROOM
2NF-1
A.I.I.
BEDROOM
2NJ-1
A.I.I.
BEDROOM
2NG-1
A.I.I.
BEDROOM
2NH-1
ONCOLOGY
EXAM
MD OFFICE
EXISTING
INFUSION
CLINIC
TELECOM
ROOM
CLEAN
LINEN
EXISTING
ELECTRICAL
ROOM
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
FAMILY
LOUNGE
MED. PREP
2SN-5
NOURISH
2SN-4
CLEAN
UTILITY RM
NURSE
ASSIST
MANAGER
2SN-1
A.I.I.
BEDROOM
2SJ-1
A.I.I.
BEDROOM
2SH-1
SERVICE
ELEVATOR
LOBBY
C2-2
A.I.I.
BEDROOM
2SG-1
A.I.I.
BEDROOM
2SF-1
SOILED
UTILITY RM
A.I.I.
BEDROOM
2SE-1
HAC
STERILE
SUPPLY
MSD
A.I.I.
BARIATRIC
BEDROOM
2SA-1
A.I.I.
BEDROOM
2SB-1
A.I.I.
BEDROOM
2SC-1
A.I.I.
BEDROOM
2SD-1
2 4 7 42 44 479 5217101 13 20 24 28 33 3726 38 40 46 50 53
EXIST. SA DUCT
FROM RISER
SERVING EXIST.
UNIT 64-AC-52
SA SERVING UNRENOVATED AREA
NURSE
STATION-NORTH
2NN-2
CORRIDOR-2
C2-3-2 CORRIDOR
C2-5
NURSE
STATION-SOUTH
2SN-2
MED. GAS
STORAGE
X
Y
Z
P
STAIR #3
S3.2
MH102
MH103
AHU-1
LOWER LEVEL ROOF
FIRST FLOOR ROOF
FIRST FLOOR ROOF
AHU-3
AHU-2
AHU-4
EF-9
EF-1
EF-10
S
Q
D H
-1
DH-3
DH-4
DH-2
EF-2
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
SECOND FLOOR PLAN - OVERALL CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH101
573 A4-18-603
January 29, 2024 CMDDAC
KEY PLAN
B64A
PLAN
NORTH
TRUE
NORTH
SCALE: 3/32" = 1'-0"
SECOND FLOOR RENOVATION PLAN
GRAPHIC SCALE(S)
## KEY NOTES
GENERAL NOTES
KEY PLAN
3/32" = 1' - 0" 0 5' 10' 20' 40'
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
42 44 47 5224 28 33 3726 38 40 46 50 53
X
Y
Z
P
U
EXISTING
INFUSION
CLINIC
TELECOM
ROOM
CLEAN
LINEN
EXISTING
ELECTRICAL
ROOM
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
CORRIDOR
C2-5
PUBLIC
ELEVATOR
LOBBY
C2-1
SERVICE
ELEVATOR
LOBBY
C2-2
CORRIDOR
C2-8A
FAMILY
LOUNGE
FAM. TLT
FAM. TLT
CLEAN
UTILITY RM
MED. GAS
STORAGE
A.I.I.
BEDROOM
2SJ-1
PATIENT
ISOLATION
TLT
2SJ-3
A.I.I. ANTE
ROOM
2SJ-2
A.I.I. ANTE
ROOM
2SH-2
PATIENT
ISOLATION
TLT
2SH-3
A.I.I.
BEDROOM
2SH-1
A.I.I.
BEDROOM
2SG-1
PATIENT
ISOLATION
TLT
2SG-3
A.I.I. ANTE
ROOM
2SG-2
A.I.I. ANTE
ROOM
2SF-2
PATIENT
ISOLATION
TLT
2SF-3
A.I.I.
BEDROOM
2SF-1 SOILED
UTILITY RM
PATIENT
ISOLATION
TLT
2SE-3
A.I.I. ANTE
ROOM
2SE-2
A.I.I.
BEDROOM
2SE-1
A.I.I.
BEDROOM
2SD-1
PATIENT
ISOLATION
TLT
2SD-3
PATIENT
ISOLATION
TLT
2SC-3
A.I.I. ANTE
ROOM
2SD-2
A.I.I. ANTE
ROOM
2SC-2
A.I.I.
BEDROOM
2SC-1
CORRIDOR
C2-6
A.I.I.
BEDROOM
2SB-1
PATIENT
ISOLATION
TLT
2SB-3
BARIATRIC
ISOLATION
TLT
2SA-3
A.I.I. ANTE
ROOM
2SB-2
A.I.I.
BARIATRIC
ANTE
ROOM
2SA-2
A.I.I.
BARIATRIC
BEDROOM
2SA-1
STERILE
SUPPLY
MSD
HAC
STAIR #3
S3.2
38x18
16x14
32x20
AC-1 AC-1
STAFF TLT
204A
CD-1
CD-1
EG-1
EG-1
CD-1
CD-1
CD-1
CD-1
RG-1
CD-1
145 RG-1
RG-1
CD-1
CD-1
EG-1
EG-1
CD-1
CD-1
EG-1
CD-1
90EG-1
EG-1
100 CD-1
EG-1
CD-1
CD-1
130 CD-1
EG-1
CD-1
EG-1
EG-1
CD-1
EG-1
CD-1
EG-1
CD-1
CD-1
EG-1
EG-1
CD-1
CD-1
EG-1
CD-1
CD-1
CD-1
EG-1
EG-1
100 EG-1
CD-1
CD-1
CD-1
EG-1
EG-1
RG-1
RG-1
CD-1
CD-1
EG-1
RG-1
CD-1
CD-1
RG-1
CD-1
260RG-1
240CD-1
CD-1
CD-1
CD-1
240CD-1
CD-1
CD-1
EG-1
38x18 x1
ECV-2-5
CD-1
EG-1
ECV-2-6
ECV-2-8
ECV-2-7
ECV-2-9
ECV-2-1ECV-2-2
ECV-2-3 ECV-2-4
CD-1
C A
V -2
-1
VAV-2-1
CAV-2-2
VAV-2-4
CAV-2-3
CAV-2-4
VAV-2-8
VAV-2-2
VAV-2-3
VAV-2-5
VAV-2-6
VAV-2-7
CAV-2-5
CAV-2-7
CAV-2-8
CAV-2-6
CAV-2-9
CAV-2-10
CAV-2-11CAV-2-12
CAV-2-14CAV-2-13
10x8
18x10
22x10
36x12 EA 30x12 EA
18x12
30x12 EA
18x12
12x12
12x12
16x14
12x10
22x12 SA
20x14 SA
16x14 SA
12x12 SA
6ø
6ø
12x10
6ø
10x8
10x8
12x8
12x10 x1
12x10
12x12
12x10
10x10
10x10
10x10
12x10
EF-10
10x8
10x10
8ø
6ø
8ø
8ø
8ø
8ø
8x6
8ø
8x6
8x8
8x6
10x10
12x12 12x12
10x10
8x6
8x68x6
8x6
10x10
8x6 8x6
12x12
CD-1
8x6
12x6
12x10
10x10
8x6 12x12
8x6
8x6
8x6
10x10
12x12
8x6
10x108x6 8x6
8x6 8x6
10x10 8x6
8x6
12x12
8x6
8x6
10x10
8x6 8x6
12x12
8x8
12x10
8x8
8x6
8ø
EG-1
8x8
CD-1
8x8
8x6
14x10 14x6
6ø
8x6
8x610x10
8x8
8x6
NURSE
ASSIST
MANAGER
2SN-1
8ø
8x8
10x10
S
Q
D H
-2
DH-4
AHU-2
AHU-4
x3
46x14
15ø
16x14
26x28
4 3
HP-1
HP-1
HP-1
14x16
14x16
16x14 x1 x1
32x20
14x16
14x16
16x14
CD-1
DUCTWORK ON
PENTHOUSE ROOF
1. AHU FRESH AIR INTAKES SHALL BE A MINIMUM OF 20 FEET FROM ANY
PLUMBING OF EXHAUST VENTS.
2. EXTERIOR DUCTWORK SHALL BE SUPPORTED W/ DUCTWORK SUPPORTS
ATTACHED TO THE ROOF.
3. ALL DUCTWORK LOCATED OUTDOORS OR EXPOSED TO THE WEATHER
SHALL BE DOUBLE WALL, SMOOTH INSIDE AND OUTSIDE, INSULATED WITH
INSULATION OF SUFFICIENT THICKNESS TO YIELD A MINIMUM INSTALLED
VALUE OF R-8, WITH FLANGED CONNECTIONS. THE OUTSIDE PANEL SHALL
BE PAINTED WITH WEATHER RESISTANT PAINT OR BE CONSTRUCTED OF
STAINLESS STEEL. JOINTS SHALL BE INSULATED. TOP SURFACE OF
HORIZONTAL DUCTS IS TO BE SLOPED 1/8-INCH PER FOOT FOR DRAINAGE.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
SECOND FLOOR PLAN - SOUTH CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH102
573 A4-18-603
January 29, 2024 CMDDAC
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - 2 SOUTH
KEY PLAN
B64A
GRAPHIC SCALE(S)
## KEY NOTES
GENERAL NOTES
KEY PLAN
1/8" = 1' - 0" 0 5' 10' 15' 30'
1 SA DUCTWORK FROM AHU-4 UP TO FLOOR 3. SECURE VERTICAL DUCT TO
EXTERIOR WALL.
2 RA DUCT FROM FLOOR ABOVE TO AHU-4. SECURE VERTICAL DUCT TO
EXTERIOR WALL.
3 EXHAUST DUCT FROM EF-5 & EF-6 ABOVE.
4 EXHAUST DUCT FROM CEILING SPACE OF FLOOR 2 THRU EXTERIOR WALL.
FLASH & SEAL WALL PENETRATION WATER-TIGHT.
5 SA DUCTWORK FROM AHU-2 THRU EXTERIOR WALL INTO THE CEILING
SPACE OF FLOOR 2. FLASH & SEAL WATER-TIGHT.
6 RA DUCTWORK FROM CEILING SPACE OF FLOOR 2 THRU EXTERIOR WALL
TO AHU-2. FLASH & SEAL WATER-TIGHT.
7 INSTALL WALL-MOUNTED AIR HANDLING UNIT CENTERED ABOVE DOOR.
ROUTE 1-INCH CONDENSATE TO NEAREST SANITARY DRAIN (MOP SINK).
PUMP CONDENSATE AS REQUIRED.
8 ROUTE REFRIGERANT PIPING FROM CU-1 TO AFFILIATED AC ON FLOOR 2.
INSTALL CU-1 ON ROOF CURB OR ROOF SUPPORT. SECURE TO ROOF CURB
OR SUPPORT.
9 ROUTE REFRIGERANT PIPING FROM CU-1 TO AFFILIATED AC ON FLOOR 3.
INSTALL CU-1 ON ROOF CURB OR ROOF SUPPORT. SECURE TO ROOF CURB
OR SUPPORT.
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
2 4 7 9 17101 13 20 24 2826
A.I.I.
BEDROOM
2NB-1
A.I.I.
BEDROOM
2NC-1
PATIENT
ISOLATION
TLT
2NC-3
PATIENT
ISOLATION
TLT
2NB-3
BARIATRIC
ISOLATION
TLT
2NA-3
A.I.I. ANTE
ROOM
2NB-2
A.I.I.
BARIATRIC
ANTE
ROOM
2NA-2
A.I.I.
BARIATRIC
BEDROOM
2NA-1
CORRIDOR-2
C2-3-2
A.I.I. ANTE
ROOM
2NC-2
A.I.I. ANTE
ROOM
2ND-2
PATIENT
ISOLATION
TLT
2ND-3
A.I.I.
BEDROOM
2ND-1
A.I.I.
BEDROOM
2NE-1
PATIENT
ISOLATION
TLT
2NE-3
A.I.I. ANTE
ROOM
2NE-2
HAC
STERILE
SUPPLY
MSD
STAIR #1
S1.2
NURSE
MANAGER
2NN-1
NURSE
STATION-NORTH
2NN-2
MED. PREP
2NN-5
NOURISH
2NN-4
A.I.I.
BEDROOM
2NF-1
A.I.I.
BEDROOM
2NJ-1
MED. GAS
STORAGE
CLEAN
UTILITY RM
ONCOLOGY
EXAM
CORRIDOR-1
C2-3-1
CORRIDOR
C2-4
A.I.I.
BEDROOM
2NG-1
A.I.I.
BEDROOM
2NH-1
PATIENT
ISOLATION
TLT
2NG-3
PATIENT
ISOLATION
TLT
2NF-3
A.I.I. ANTE
ROOM
2NF-2
A.I.I. ANTE
ROOM
2NG-2
A.I.I. ANTE
ROOM
2NH-2
PATIENT
ISOLATION
TLT
2NH-3
A.I.I. ANTE
ROOM
2NJ-2
PATIENT
ISOLATION
TLT
2NJ-3
MD OFFICE
EXISTING
INFUSION
CLINIC
STAIR #2
S2.2
EQUIPMENT
STORAGE
A213
PUBLIC
ELEVATOR
LOBBY
C2-1
SOILED
UTILITY RM
X
Y
Z
P
U
44x14
CD-1
CD-1
EG-1
EG-1
CD-1
RG-1
AC-1
CD-1
CD-1
RG-1
CD-1
CD-1
EG-1
EG-1
CD-1
CD-1
EG-1
CD-1
EG-1
EG-1
CD-1
EG-1
CD-1
EG-1
CD-1
CD-1
EG-1
CD-1
EG-1
RG-1
RG-1
CD-1
EG-1
RG-1
RG-1
RG-1
CD-1
CD-1
CD-1
CD-1
RG-1
CD-1
110CD-1
CD-1
EG-1
CD-1
135 EG-1
CD-1
EG-1
CD-1
CD-1
CD-1
CD-1
EG-1
CD-1
CD-1
x1 x1
C A
V -2
-1
CD-1
CD-1
CD-1
135CD-1
EG-1
EG-1
CD-1
CD-1
CAV-1-13CAV-1-12
EG-1
EG-1
EG-1
EG-1
CD-1
CD-1
CD-1
EG-1
EG-1
CAV-1-11CAV-1-10
CD-1
CD-1
VAV-1-5
VAV-1-4
VAV-1-3
VAV-1-1
VAV-1-2
CAV-1-7
VAV-1-7
CAV-1-8
VAV-1-6
CAV-1-9
CAV-1-6
CAV-1-5
CAV-1-3
CAV-1-4
CAV-1-1
CAV-1-2
RG-1
ECV-1-1
ECV-1-2
ECV-1-3
ECV-1-4 ECV-1-5
ECV-1-9 ECV-1-8
ECV-1-6ECV-1-7
AHU-1
12x10
6ø
12x8
8x6
14x8
8x8
14x14 12x12
14x6
8x6
12x12 10x10
14x10
30x12 EA 22x10 SA x1
E
A x1
S A
8x6
10x10 10x10
10x10
10x10
10x10
30x12 EA 16x14 SA
18x12 EA
12x12 SA
EF-1
36x12 EA 20x14 SA
EF-9
10x10
12x12
8x6
8x6
8x6
8x6
12x10 SA 12x10 SA
8x6
8x6 10x10
12x10 10x10 8x6
12x12
8x6
8x6
8x8
6ø
8x6
TELECOM
ROOM
8x8 8x6
8x6
8x8
8x6
8x6
12x12 12x12
8x6
8x6 8x6
8x6
12x12
12x12 8x6
12x1012x10
10x10 10x10
8x6
10x10 x8
8x8
8ø 8ø
6ø 8x6
8x8
8x6
8ø
8ø
6ø 8ø6ø
8ø
8x6
6ø
8x8
10x8
12x8
8x6
10x10
12x12
12x10
S
Q
EF-2
20x24
23ø
23ø
15ø
14x12
AHU-3
DH-3
D H
-1
CD-1
4 3
44x14 x1
32x18
14x14 x1
14x14
1. AHU FRESH AIR INTAKES SHALL BE A MINIMUM OF 20 FEET FROM ANY
PLUMBING OF EXHAUST VENTS.
2. EXTERIOR DUCTWORK SHALL BE SUPPORTED W/ DUCTWORK SUPPORTS
ATTACHED TO THE ROOF.
3. ALL DUCTWORK LOCATED OUTDOORS OR EXPOSED TO THE WEATHER
SHALL BE DOUBLE WALL, SMOOTH INSIDE AND OUTSIDE, INSULATED WITH
INSULATION OF SUFFICIENT THICKNESS TO YIELD A MINIMUM INSTALLED
VALUE OF R-8, WITH FLANGED CONNECTIONS. THE OUTSIDE PANEL SHALL
BE PAINTED WITH WEATHER RESISTANT PAINT OR BE CONSTRUCTED OF
STAINLESS STEEL. JOINTS SHALL BE INSULATED. TOP SURFACE OF
HORIZONTAL DUCTS IS TO BE SLOPED 1/8-INCH PER FOOT FOR DRAINAGE.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
SECOND FLOOR PLAN - NORTH CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH103
573 A4-18-603
January 29, 2024 CMDDAC
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - 2 NORTH
KEY PLAN
B64A
GRAPHIC SCALE(S)
## KEY NOTES
GENERAL NOTES
KEY PLAN
1/8" = 1' - 0" 0 5' 10' 15' 30'
1 SA DUCT FROM AHU-1 BELOW AHU-3 SA DUCT.
2 SA DUCT FROM AHU-3 UP TO LEVEL 3. SECURE VERTICAL DUCT TO
EXTERIOR WALL. SA DUCT FROM AHU-1 THRU EXTERIOR INTO ABOVE
CEILING SPACE OF FLOOR 2. FLASH & SEAL WALL PENETRATION
WATER-TIGHT.
3 RA DUCT TO AHU-3 ABOVE RA DUCT TO AHU-1.
4 RA DUCT FROM FLOOR 3 TO AHU-3. SECURE VERTICAL DUCT TO EXTERIOR
WALL. RA DUCT FROM CEILING SPACE OF FLOOR 2 THRU EXTERIOR WALL
TO AHU-1. FLASH & SEAL WALL PENETRATION WATER-TIGHT.
5 EA DUCT FROM CEILING SPACE OF FLOOR 2 THRU EXTERIOR WALL TO EF-1
& EF-2. FLASH & SEAL WALL PENETRATION WATER-TIGHT.
6 EA DUCT FROM FLOOR 2 CEILING SPACE TO EF-9. FLASH & SEAL WALL
PENETRATION WATER-TIGHT.
7 INSTALL WALL-MOUNTED AIR HANDLING UNIT CENTERED ABOVE DOOR.
ROUTE 1-INCH CONDENSATE TO NEAREST SANITARY DRAIN (MOP SINK)
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
STAFF
LOUNGE
NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
STAFF
LOUNGE
COORIDOR-1
C3-8-1
SERVICE
ELEVATOR
LOBBY
C3-2
FAMILY
DINING
ROOM
FAMILY
TLT.
FAMILY
TLT.
EQUIPMENT
STORAGE
2 4 7
42 44 47
101 13
20 24 28 33 3726 38
46 50 53
X
Y
Z
P
U
MH105
S
Q
EXIST. DUCTWORK SERVING
UNRENOVATED AREA
EXIST. DUCTWORK
SERVING UNRENOVATED AREA
EXIST. DUCTWORK SERVING
UNRENOVATED AREA
O
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
THIRD FLOOR PLAN - OVERALL CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH104
573 A4-18-603
January 29, 2024 RWHDAC
KEY PLAN
B64A
PLAN
NORTH
TRUE
NORTH
SCALE: 3/32" = 1'-0"
B64A - THIRD FLOOR OVERALL
3/32" = 1' - 0" 0 5' 10' 20' 40'
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
421713 20 24 28 33 3726 38 40
U
STAFF
LOUNGE
311 NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
LAUNDRY
STAFF
LOUNGE
TOILET
304A
TOILET
311A
EQUIPMENT
STORAGE
FAMILY
DINING
ROOM
AC-1
CD-1
RG-1
RG-1
CD-1
EG-1
EG-1
CD-1
EG-1
CD-1
CD-1
RG-1
CD-1
CD-1
RG-1
CD-1
CD-1
RG-1
CD-1
CD-1
EG-1
EG-1
CD-1
EG-1
CD-1
CD-1
EG-1
CD-1
CD-1
CD-1
EG-1
EG-1
8x6
8x10
8ø
8ø
14x128x6
14x8
8x6 8x6
10x88x6
10x10
10x10
8x6 8x6 8x6
8x6
8x6 8x8 8x6
8x6
8x6 8x6
10x10
8x6
8x8
10x10 8x8
10x10 8x6
12x12
8x6
14x12
8x8
12x8
12x8
14x8
14x10
8x68x6
8x8
8x8
10x8
8ø
8x8
VAV-3-7
VAV-3-6
VAV-3-5
VAV-3-3
VAV-3-4
VAV-3-2
VAV-3-1
S
Q
24x20 8
26x28 6
16x14 x1
20x12
46x145
44x14
14x14
24x20
VAV-3-814x12
16x14
COORDINATE EXACT
LOCATION OF NEW
DUCTWORK WITH
EXISTING KITCHEN
HOOD DUCTWORK.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
THIRD FLOOR PARTIAL PLAN - 3
CENTRAL CORE
CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH105
573 A4-18-603
January 29, 2024 CMDDAC
SCALE: 1/8" = 1'-0"
THIRD FLOOR PARTIAL PLAN - 3 CENTRAL CORE
KEY PLAN
B64A
GRAPHIC SCALE(S)
## KEY NOTES
GENERAL NOTES
KEY PLAN
1/8" = 1' - 0" 0 5' 10' 15' 30'
1 EXHAUST DUCTWORK FROM EF-3 & EF-4 ABOVE CEILING SPACE OF FLOOR 3
THRU THE EXTERIOR WALL INTO THE CEILING SPACE OF FLOOR 3. FLASH
AND SEAL WALL PENETRATION WATER-TIGHT & CAP DUCT FOR FUTURE
TIE-IN.
2 SA FROM AHU-3 ON LOW ROOF. ROUTE DUCT THRU EXTERIOR WALL INTO
CEILING SPACE OF FLOOR 3. FLASH & SEAL WALL PENETRATION
WATER-TIGHT. CAP DUCT FOR FUTURE TIE-IN.
3 RA DUCT FROM CEILING SPACE OF FLOOR 3 THRU EXTERIOR WALL, DOWN
TO AHU-3 ON LOW ROOF. FLASH & SEAL WALL PENETRATION WATER-TIGHT.
CAP DUCT FOR FUTURE TIE-IN.
4 SA DUCT FROM AHU-4 ON LOW ROOF. ROUTE DUCT THRU EXTERIOR WALL
INTO ABOVE CEILING SPACE OF FLOOR 3. FLASH & SEAL WALL
PENETRATION WATER-TIGHT. DUCT SIZED FOR FUTURE TIE-IN FOR UPFIT
OF SOUTH WIING.
5 RA DUCT FROM ABOVE CEILING SPACE OF FLOOR 3, THRU EXTERIOR WALL,
DOWN TO AHU-4 ON LOW ROOF. FLASH & SEAL WALL PENETRATION
WATER-TIGHT.
6 EXHAUST DUCTWORK FROM FLOOR 2 AND UP TO EF-5 & EF-6 ON ROOF.
7 EXHAUST DUCTWORK FROM EF-11 ABOVE CEILING SPACE OF FLOOR 3
THRU THE EXTERIOR WALL INTO THE CEILING SPACE OF FLOOR 3. FLASH
AND SEAL WALL PENETRATION WATER-TIGHT & CAP DUCT FOR FUTURE
TIE-IN.
8 EXHAUST DUCT UP THRU ROOF TO EF-7 & EF-8. CAP DUCT FOR FURTURE
TIE-IN.
9 EXHAUST DUCTWORK FROM EF-12 ABOVE CEILING SPACE OF FLOOR 3
THRU THE EXTERIOR WALL INTO THE CEILING SPACE OF FLOOR 3. FLASH
AND SEAL WALL PENETRATION WATER-TIGHT.
10 INSTALL WALL-MOUNTED AIR HANDLING UNIT CENTERED ABOVE DOOR.
ROUTE 1-INCH CONDENSATE TO NEAREST SANITARY DRAIN (MOP SINK).
11 COORDINATE EXACT LOCATION OF NEW DUCTWORK WITH EXISTING
KITCHEN HOOD DUCTWORK.
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
42 44 47
9 1710 13 20 24 28 33 3726
38 40 46
U
EF-3
EF-5
EF-7
EF-11
EF-12
S
Q
EF-4
EF-6
EF-8
18x16
28x26
18x16 26x28
24x20
24x20
20x24
15ø ø ø
23ø
23ø
23ø 23ø x2
15ø
2 1
14x12
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
64A
ROOF PLAN CORRECT PATIENT PRIVACY
DEFICIENCIES - LAKE CITY
Lake City, FL
MH106
573 A4-18-603
January 29, 2024 CMDDAC
SCALE: 1/8" = 1'-0"
ROOF PLAN
KEY PLAN
B64A
GRAPHIC SCALE(S)
## KEY NOTES
GENERAL NOTES
KEY PLAN
1/8" = 1' - 0" 0 5' 10' 15' 30'
1 EXHAUST DUCTWORK FROM FLOOR 2 TO EF-5 AND EF-6.
2 EXHAUST DUCTWORK FROM FLOOR 3 TO EF-3 AND EF-4.
3 EXHAUST DUCTWORK FROM FLOOR 3 TO EF-11.
4 EXHAUST DUCTWORK FROM FLOOR 3 TO EF-7 AND EF-8.
5 EXHAUST DUCTWORK FROM FLOOR 3 TO EF-12.
N O
R T H
CARO
L I
N A
P R
O
FE
SS ION
A L
D W
A Y
NE
AL LAN
C A
R R
034339
SEAL
E
2 4 71
U
S
Q
CWP-1
CWP-2
6" CWR
6" CWS
6" CWS
8" CWS 8" CWR
CWS&R UP TO FIRST
FLOOR ROOF 3533 3726 34
R.5
Q
U
T
S
R
20 24 28 29
20 24 28 33 3726
U
S
Q
DN TO EXIST. PRESSURE
REDUCING STATION
HWP-2
HWP-1
HX-1
TAP INTO EXIST. 4" HPS
4" LPS
2" HPS
3" HWS
3" HWR
3" HWS
3" HWR
HWS&R DN TO FLOORS 2 & 3,
COORD. W/ EXIST. PIPES
HX-2
3" LPS
ADS-1
ET-1
SHOT FEEDER
PRESSURE REDUCING STATION
ST-2 ST-1PRESSURE RELIEF VALVE
6" VENT UP THRU
ROOF TO GOOSE NECK
ST-3
ST-4
ST-5
ST-6
NEW LPC PIPE TO
EXIST. RECEIVER TANK
EXIST. LPC
1. ALL EXTERIOR PIPING, INCLUDING CHILLED WATER HEATING WATER
AND DOMESTIC WATER, SHALL BE HEAT TRACED AT A MINIMUM OF 7
WATTS/LF, AND INSULATED. PROVIDE WITH AN EXTERIOR JACKET.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Of…
This is the start of the file's text. The full file is on GovTribe.