PR9071_Attachment_C_OUC_Specs.pdf
PDF 713 KB Posted
- Attached to
- Wire & Cable
- Solicitation number
- PR9071
- Issued by
- Florida
About this file
OUC Technical Specifications Summary
This document comprises technical specification sheets for the Orlando Utilities Commission (OUC) establishing manufacturing and performance standards for underground primary electrical cables at 15 kV, 25 kV, and 35 kV voltage ratings. The specifications cover single-conductor cables in cross-linked polyethylene (TR-XLPE) and ethylene propylene rubber (EPR) insulation types, with conductor materials in aluminum and copper, ranging from #2 AWG through 1000 kcm. Each specification sheet details conductor composition, insulation thickness (165-205 mils for 15 kV cables; 330-400 mils for 35 kV cables), shielding requirements, jacket specifications with identifying markings and sequential footage labeling every 2 feet, and packaging requirements on non-returnable wooden reels with specified arbor hole sizes and flange dimensions. All cables must be manufactured in compliance with ANSI/ICEA S-94-649 and AEIC CS8 standards, with triple extrusion processes required for conductor shields, insulation, and insulation shields applied in a single pass. Minimum reel lengths range from 1,500 feet to 3,000 feet depending on conductor size, and delivery must occur via open flat-bed truck with forklift-capable unloading arrangements.
Comprehensive testing requirements include water blocking resistance testing per ICEA T-31-610 or T-34-664 at 5 psi with certified test reports, and connection integrity testing per ANSI C119.4 demonstrating stable resistance and temperature performance of compression-type sleeves and terminals. Approved manufacturers for TR-XLPE cables include General Cable, Hendrix, LS Cable, Nexan, Prysmian, and Southwire, while EPR cable manufacturers include Kerite, Okonite, and Prysmian. All cables must feature water-blocking compounds in conductor interstices, strippable insulation shields with specified pulling tension limits, and black polyethylene jackets with three equally-spaced red stripes. Jacket identification must include conductor size designation, insulation type designation (175 MIL TR-XLPE or 260-345 MIL EPR), manufacturer name, and year of manufacture. Heat shrink end seals are required on all cable ends to prevent moisture entry during storage and shipment, with both ends securely fastened to the reel.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT C
OUC TECHNICAL SPECIFICATIONS
ORLANDO UTILITIES COMMISSION
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03001
CABLE, SINGLE, CROSSLINKED POLYETHYLENE, 15 kV, #2 AWG ALUMINUM
Except as noted, this cable shall be manufactured and tested in accordance with the latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene-jacketed #2 AWG, filled-strand stranded aluminum, 15 kV tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (seven strand) concentric-lay-stranded (compressed optional) aluminum. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H19 (full hard) in accordance with ASTM specification B609.
The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a tree retardant crosslinked polyethylene compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral shall consist of ten (10) strands of #14 AWG coated or uncoated (preferred) copper wire (full neutral). The concentric neutral wires shall be applied in accordance with ANSI/ICEA S-94-649.
Jacket: The cable is to be protected with an extruded black insulating linear low-density polyethylene jacket covering and filling the spaces between the neutral wires. This shall fit tightly against the semiconducting but strip freely away from the insulation shield.
Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "2 AL” and "175 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, water pressure shall be at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 3000 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 2" diameter arbor. Reels must have a maximum outside width, (including protrusions) and flange diameter (height) not to exceed 37 inches and 54 inches respectively. Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
Shipping: Delivery shall be by open flat bed truck with reels arranged such that they can be unloaded using a forklift.
Mark Hoover Staff Engineer System Planning & Reliability Engineering January 12, 2012
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03021
CABLE, SINGLE, CROSSLINKED POLYETHYLENE, 15 kV, 2/0 AWG ALUMINUM latest ANSI/ICEA S-94-649 and AEIC standards.
This specification is for polyethylene-jacketed 2/0 AWG, filled-strand stranded aluminum, 15 kV tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (19 strand) concentric-lay-stranded (compressed optional) aluminum. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H19 (full hard) in accordance with ASTM specification B609.
The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a tree retardant crosslinked polyethylene compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral shall consist of eight (8) strands of #14 AWG coated or uncoated (preferred) copper wire. (The ampacity of these 8 wires amounts to slightly more than one third the conductor ampacity). The concentric neutral wires shall be applied in accordance with ANSI/ICEA S-94-649.
Jacket: The cable is to be protected with an extruded black insulating linear low-density polyethylene jacket covering and filling the spaces between the neutral wires.
This shall fit tightly against the semiconducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "2/0 AL" and "175 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, water pressure shall be at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 1500 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 2" diameter arbor. Reels must have a maximum outside width, (including protrusions) and flange diameter (height) not to exceed 37 inches and 54 inches respectively. Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
Shipping: Delivery shall be by open flat bed truck with reels arranged such that they can be unloaded using a forklift.
Mark Hoover
January 17, 2012
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03022
CABLE, SINGLE, CROSSLINKED POLYETHYLENE, 15 kV, 2/0 AWG COPPER
Except as noted, this cable shall be manufactured and tested in accordance with the latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene-jacketed 2/0 AWG, filled-strand stranded copper, 15 kV tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (19 strand) concentric-lay-stranded (compressed optional) annealed copper wires according to ASTM specifications B-3 and B-
8. Compact conductor is not acceptable. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a tree retardant crosslinked polyethylene compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral shall consist of twelve (12) strands of #14 AWG coated or uncoated (preferred) copper wire. (The ampacity of these 12 wires amounts to slightly more than one third the conductor ampacity). The concentric neutral wires shall be
Jacket: The cable is to be protected with an extruded black insulating linear low density polyethylene jacket covering and filling the spaces between the neutral wires. This shall fit tightly against the semiconducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "2/0 CU" and "175 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, with water pressure shall be at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 1500 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 2" diameter arbor. Reels must have a maximum outside width, (including protrusions) and flange diameter (height) not to exceed 37 inches and 54" respectively.
Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
Shipping: Delivery shall be by open flat bed truck with reels arranged such that they can be unloaded using a forklift.
Mark Hoover
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03042
CABLE, SINGLE, EPR or CROSSLINKED POLYETHYLENE, 15 kV, 4/0 AWG COPPER latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene-jacketed 4/0 AWG, filled-strand stranded copper, 15 kV with EPR or a tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (19 strand) concentric-lay-stranded (compressed optional) annealed copper wires according to ASTM specifications B-3 and B-
8. Compact conductor is not acceptable. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be EPR or a tree retardant crosslinked polyethylene compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral shall consist of eleven (11) strands of #14 AWG coated or uncoated (preferred) copper wire. (The ampacity of these 11 wires amounts to slightly more than one third the conductor ampacity). The concentric neutral wires shall be
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03042
Jacket: The cable is to be protected with an extruded black insulating linear low density polyethylene jacket covering and filling the spaces between the neutral wires.
This shall fit tightly against the semiconducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "4/0 CU" and "175 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, with water pressure at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycles). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 1500 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 2" diameter arbor. Reels must have a maximum outside width, (including protrusions) and flange diameter (height) not to exceed 37 inches and 54 inches respectively. Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
Shipping: Delivery shall be by open flat bed truck with reels arranged such that they can be unloaded using a forklift.
Mark Hoover Senior Engineer
September 1, 2020
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03500
CABLE, SINGLE, ETHYLENE PROPYLENE, 15 kV, 500 kcm COPPER
Except as noted, this cable shall be manufactured and tested in accordance with the latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene jacketed 500 kcm, filled-strand stranded copper 15 kV ethylene propylene rubber insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (37 strand) concentric-lay-stranded compressed optional) annealed copper wires according to ASTM specification B-3 and B-8.
Compact conductor is not acceptable. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a suitable tacky semiconducting water blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall consist of Type II thermosetting ethylene propylene rubber compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649. A 120 mesh screen or finer shall be used in the final mixing operation of the compound.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a triple extrusion process.
Concentric Neutral: The neutral copper wires shall consist of numerous strands of #14 (preferred) or #12 AWG uncoated (preferred) or coated copper wire. (The ampacity of these copper wires amounts to one third the conductor ampacity). The concentric neutral wires shall be applied in accordance with ANSI/ICEA S-94-649.
fit tightly against the semiconducting but strip freely away from the insulation shield.
Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "500 CU" and "175 MIL EPR" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-34-664, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, with water pressure at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, 3000 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 5" diameter arbor. Reels must not exceed an outside width (including protrusions) of 67 inches for metal and 64 inches for wood, and a flange diameter (height) of 96 inches.
Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
Senior Engineer
November 23, 2020
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03750
CABLE, SINGLE, CROSSLINKED POLYETHYLENE, 15kV, 750 kcm ALUMINUM
Except as noted, this cable shall be manufactured and tested in accordance with the latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene jacketed 750 kcm, filled-strand stranded aluminum, 15 kV tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (61 strand) compressed concentric-lay-stranded aluminum. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H14 (half hard) or AL 1350-H16 (three-quarter hard) in accordance with ASTM specification B609. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a suitable tacky semiconducting water blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a tree retardant crosslinked polyethylene compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral copper wire shield shall consist of twelve (12) strands of #14 AWG coated or uncoated (preferred) copper wire. The concentric neutral wires shall be applied in accordance with ANSI/ICEA S-94-649.
Jacket: The cable is to be protected with an extruded black insulating linear low density polyethylene jacket covering and filling the spaces between the neutral wires. This shall fit tightly against the semiconducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The min/max thickness of the jacket shall be in accordance with ANSI/ICEA S-94-649.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-03750
Identification: The jacket shall have repeatedly printed along its length "750 AL" and "175 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage at least every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, water pressure shall be at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 3000 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 3" diameter arbor. Reels must not exceed the following dimensions:
Flange Diameter Outside Width (Height)
Metal 96" 67"
Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04000
CABLE, SINGLE, ETHYLENE PROPYLENE, 15 kV, 1000 kcm COPPER
175 MIL INSULATION, CONCENTRIC NEUTRAL
latest AEIC CS8 and ANSI/ICEA S-94-649 standards.
This specification is for polyethylene jacketed 1000 kcm filled-strand stranded copper, 15 kV ethylene propylene rubber insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of 61 strands of class B compressed concentric-lay-stranded annealed copper wires according to ASTM specifications B-3 and B-8.
Compact conductor is not acceptable. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a suitable tacky semiconducting water blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall consist of a Type II thermosetting ethylene propylene rubber compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649. A 120 mesh screen or finer shall be used in the final mixing operation of the compound.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields. The minimum and maximum diameters over the insulation shield shall be in accordance with ANSI/ICEA S-94-649.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a triple extrusion process.
Concentric Neutral: The neutral copper wire shield shall consist of fifteen (15) strands of #12 AWG coated or uncoated (preferred) copper wire. The concentric neutral wires shall be applied in accordance with ICEA S-94-649. Water blocking agents are required. Water blocking agents shall be applied over the concentric neutral wires.
Jacket: The cable is to be protected with an extruded black insulating linear low-density polyethylene jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04000
Identification: The jacket shall have repeatedly printed along its length "1000 CU" and "175 MIL EPR" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage at least every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-34-664, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and the applicable standards referenced therein.
Packaging: Each reel shall consist of a single conductor of approximately 2000 feet.
Each reel shall have a round hole centered in each hub at least large enough to accommodate a 5" diameter arbor. Reels must be metal with a maximum flange diameter (height) of 96" and an outside width of 67".
Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. All cable ends shall be securely fastened to the cable reel.
November 4, 2020
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04003
CABLE, SINGLE, ETHYLENE PROPYLENE, 15 kV, 1000 kcm ALUMINUM
175 MIL INSULATION, CONCENTRIC NEUTRAL
latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene jacketed 1000 kcm filled-strand stranded aluminum, 15 kV ethylene propylene rubber insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of 61 strands of class B compressed concentric-lay-stranded aluminum according. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H19 (full hard) in accordance with ASTM specification B609. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall consist of a Type II thermosetting ethylene propylene rubber compound with a minimum point thickness of 165 mils and a maximum point thickness of 205 mils per ANSI/ICEA S-94-649. A 120 mesh screen or finer shall be used in the final mixing operation of the compound.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a triple extrusion process.
Concentric Neutral: The neutral copper wire shield shall consist of fifteen (15) strands of #12 AWG coated or uncoated (preferred) copper wire. The concentric neutral wires shall be applied in accordance with ANSI/ICEA S-94-649.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04003
density polyethylene jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "1000 AL" and "175 MIL EPR" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage at least every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, with water pressure at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor of approximately 2000 feet.
Each reel shall have a round hole centered in each hub at least large enough to accommodate a 5" diameter arbor. Reels must be metal with a maximum flange diameter (height) of 96" and an outside width of 67".
Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. All cable ends shall be securely fastened to the cable reel.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04010
CABLE, SINGLE, CROSSLINKED POLYETHYLENE, 35 kV, 1/0 AWG ALUMINUM latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene-jacketed 1/0 AWG, filled-strand stranded aluminum, 35 kV tree retardant crosslinked polyethylene insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (19 strand) concentric-lay-stranded (compressed optional) aluminum. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H19 (hard drawn) or AL 1350-H16 (three-quarter hard) in accordance with ASTM specification B609. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a tree retardant crosslinked polyethylene compound with a minimum point thickness of 330 mils and a maximum point thickness of 400 mils per ANSI/ICEA S-94-649.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649. The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a true triple extrusion process.
Concentric Neutral: The neutral shall consist of sixteen (16) strands of #14 AWG coated or uncoated (preferred) copper wire (full neutral). The concentric neutral wires shall be density polyethylene jacket covering and filling the spaces between the neutral wires.
This shall fit tightly against the semiconducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thicknesses of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: The jacket shall have repeatedly printed along its length "1/0 AL" and "345 MIL TR-XLPE" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage at least every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, water pressure shall be at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same type compound as will be used for this order if awarded. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycle). "Equivalent" testing as determined by OUC will be considered. Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 2500 feet in length. Each reel shall have a round hole centered in each hub at least large enough to accommodate a 2 1/2" diameter arbor, but with holes not over 3 1/4". Reels must have a maximum outside width (including protrusions), and flange diameter (height) not to exceed 58 inches and 68 inches respectively. Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04075
CABLE, SINGLE, ETHYLENE PROPYLENE, 35 kV, 750 kcm ALUMINUM latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for a polyethylene jacketed 750 kcm, filled-strand stranded copper 35 kV ethylene propylene rubber insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of class B (61 strand) concentric-lay-stranded (compressed optional) aluminum. Compact conductor is not acceptable. Conductor temper shall be AL 1350-H14 (half hard) or AL 1350-H16 (three quarter hard) in accordance with ASTM specification B609. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a powder or suitable tacky semi conducting water-blocking compound.
Conductor Shield: The conductor shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall be a Type II thermosetting ethylene propylene rubber compound with a minimum point thickness of 330 mils and a maximum point thickness of 400 mils per ANSI/ICEA S-94-649. A 120 mesh screen or finer shall be used in the final mixing operation of the compound.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The thickness shall be in accordance with ANSI/ICEA S-94-649.The insulation shield shall be strippable with pulling tensions within the limits provided in the most recent ANSI/ICEA S-94-649 standard for extruded insulation shields.
Extrusion: The application of the above referenced three layers of extruded compound shall be by means of a single pass with a triple extrusion process.
Concentric Neutral: The neutral shall consist of fifteen (15) strands of #10 AWG (or as an alternate, twenty four (24) strands of #12 AWG) coated or uncoated (preferred) copper wire (one third neutral). The concentric neutral wires shall be applied in accordance with
ANSI/ICEA S-94-649.
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04075
polyethylene jacket covering and filling the spaces between the neutral wires. This shall fit tightly against the semi-conducting insulation shield but strip freely away from the insulation shield. Three red stripes, equally spaced, shall be extruded into the jacket. The minimum and maximum thickness of the jacket shall be in accordance with ANSI/ICEA S-94-649.
Identification: Repeatedly, along the jacket’s length, shall be printed - "1000 AL" and "260 MIL EPR" along with the manufacturer name and year made. The jacket shall also be labeled with a sequential footage at least every 2 feet.
Testing of Water Blocking: Production testing and qualification testing shall be done in accordance with ICEA T-31-610, “Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables”, with water pressure at 5 psi. All cable supplied must be accompanied by certified test reports showing passing results.
Connection Test: A test report shall be supplied with (or prior to) the bid demonstrating the connection integrity of normal compression type sleeves and terminals when applied to a regular production cable made with conductor filled with the same compound as will be used for this cable. The test should be in accordance with ANSI C119.4, formerly IEEE TDJ 162 (500 cycles). "Equivalent" testing as determined by OUC will be considered.
Approval to bid "equivalent" tested cable must be secured a minimum of two weeks prior to bid opening. The test results should show that the temperature of an insulated splice connector is equal to or less than the insulated conductor to which it is connected, and that the resistance is stable in comparison to initial resistance measurements.
Testing: All testing shall be in accordance with ANSI/ICEA S-94-649 and AEIC CS8 standards referenced therein.
Packaging: Each reel shall consist of a single conductor, a minimum of 2000 feet in length. Each reel shall have a 5" minimum diameter round hole centered in each hub.
Reels must have a maximum outside width, (including protrusions) and flange diameter (height) not to exceed 67 inches and 96 inches respectively. Heat shrink end seals shall be installed over the cable ends (including jacket) so as to prevent any moisture entry during storage and shipment. Both cable ends shall be securely fastened to the cable reel.
January 15, 2026
SPECIFICATION SHEET FOR O.U.C. STOCK #018-04151
CABLE, SINGLE, ETHYLENE PROPYLENE, 35 kV, 500 kcm COPPER latest ANSI/ICEA S-94-649 and AEIC CS8 standards.
This specification is for polyethylene jacketed 500 kcm filled-strand stranded copper, 35 kV ethylene propylene rubber insulated, single conductor cable further described as follows:
Conductor: The conductor shall consist of 37 strands of class B compressed concentric-lay-stranded annealed copper wires according to ASTM specifications B-3 and B-8.
Compact conductor is not acceptable. The center strand wire shall be indented with an abbreviation of manufacturer name and year made. The inner interstices shall be filled with a suitable tacky semiconducting water blocking compound.
Conductor Shield: The conductor shield shall consist of an extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation. The application of this layer shall be so as to produce a smooth, uniform cylindrical outer surface bonded to the insulation. The thickness of the conductor shield shall be in accordance with ANSI/ICEA S-94-649.
Insulation: The insulation shall consist of Type II thermosetting ethylene propylene rubber compound with a minimum point thickness of 330 mils and a maximum point thickness of 400 mils per ANSI/ICEA S-94-649. A 120 mesh screen or finer shall be used in the final mixing operation of the compound.
Insulation Shield: The insulation shield shall consist of extruded semiconducting thermosetting compound, compatible with and having the same (or better) thermal characteristics as the major insulation.