PN 636-25-301 Drawings Part 1 - 22 pages.pdf
PDF 6 MB Posted
- Solicitation number
- 36C326326B0031
About this file
This document is a set of construction drawings for the U.S. Department of Veterans Affairs facility at the Nebraska Western Iowa Healthcare System in Omaha, Nebraska. The project (636-25-301) focuses on correcting HVAC deficiencies at the facility located at 4101 Woolworth Avenue.
The construction documents include comprehensive architectural, structural, mechanical, electrical, plumbing, and fire protection drawings for Buildings 6 and 17. Key work includes replacement of internal components in air handling units (AHU-1 and AHU-3), with AHU-1 work priced as Additive Bid Item I. The project requires installation of new housekeeping pads for mechanical equipment, ductwork modifications, hydronic piping updates, and associated mechanical controls. The scope encompasses basement, mezzanine, and third-level work in Building 17, with limited scope in Building 6. Special requirements include hazardous materials abatement (asbestos and lead-based paint), Class IV ICRA containment protocols during construction, negative air pressure maintenance with HEPA filtration, fire protection system modifications to accommodate new ductwork, and coordination of sprinkler piping relocation. The building is designated fully sprinklered with special purpose industrial occupancy classification. Construction must comply with 2024 International Building Code, NFPA 101 Chapter 40 egress requirements, and all applicable federal, state, and local regulations. Site coordination requirements include field verification of existing conditions, parking lot management, and advance notification for material deliveries and lift operations.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
6 & 17
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
GI001
COVER SHEET / INDEX OF DRAWINGS
12/24/2025
CONSTRUCTION
DOCUMENTS
NEBRASKA WESTERN IOWA
HEALTHCARE SYSTEM
U.S. Department of Veterans Affairs
6-
-3
C
O R
R E
C T
H V
A C
D E
F
IC
IE
N
C
IE
S
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
2/
/2
636-25-301 CORRECT HVAC DEFICIENCIES
4101 WOOLWORTH AVE
OMAHA, NE 68105
BUILDING 17
INDEX OF DRAWINGS
GI001 COVER SHEET / INDEX OF DRAWINGS
17-GI101 BUILDING 17 - BASEMENT LEVEL AND MEZZANINE LEVEL - LIFE SAFETY PLAN
17-GI102 BUILDING 17 - THIRD LEVEL - LIFE SAFETY PLAN
6-GI101 BUILDING 06 - LIFE SAFETY PLAN
GI103 CAMPUS SITE PLAN
17-GI104 BUILDING 17 - SITE PLAN
17-GI105 BUILDING 17 - PROJECT AREA ACCESS PLAN
6-GI106 BUILDING 06 - SITE PLAN
17-HA101-A BUILDING 17 - BASEMENT LEVEL - HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1
17-HA102 BUILDING 17 - MEZZANINE LEVEL - HAZARDOUS MATERIALS
17-HA102-A BUILDING 17 - MEZZANINE LEVEL - HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1
17-HA103 BUILDING 17 - THIRD LEVEL - HAZARDOUS MATERIALS
SG001 STRUCTURAL GENERAL NOTES
17-SF101 BUILDING 17 - MEZZANINE LEVEL - FRAMING PLAN
17-SF102 BUILDING 17 - ROOF FRAMING PLAN
17-SJ501 STRUCTURAL DETAILS
AG001 ARCHITECTURAL ABBREVIATIONS, LEGENDS AND NOTES
17-AE101 BUILDING 17 - MEZZANINE LEVEL AND THIRD LEVEL
17-AE201 EXTERIOR ELEVATION AND ROOF DETAIL
6-AE101 BUILDING 06 - BASEMENT LEVEL AND FIRST LEVEL - FLOOR PLAN
FX001 FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
17-FD102 BUILDING 17 - MEZZANINE LEVEL - FIRE PROTECTION - DEMOLITION
17-FD102-A BUILDING 17 - MEZZANINE LEVEL - FIRE PROTECTION - DEMOLITION - ADDITIVE BID ITEM I
1-FD103 BUILDING 01 - THIRD LEVEL - FIRE PROTECTION - DEMOLITION
17-FX102 BUILDING 17 - MEZZANINE LEVEL - FIRE PROTECTION
17-FX102-A BUILDING 17 - MEZZANINE LEVEL - FIRE PROTECTION - ADDITIVE BID ITEM I
1-FX103 BUILDING 01 - THIRD LEVEL - FIRE PROTECTION
PP001 PLUMBING SYMBOLS AND ABBREVIATIONS
17-PD101 BUILDING 17 - MEZZANINE LEVEL - PLUMBING - DEMOLITION
17-PD101-A BUILDING 17 - MEZZANINE LEVEL - PLUMBING - DEMOLITION - ADDITIVE BID ITEM I
17-PD102 BUILDING 17 - BASEMENT LEVEL - PLUMBING - DEMOLITION
17-PD102-A BUILDING 17 - BASEMENT LEVEL - PLUMBING - DEMOLITION - ADDITIVE BID ITEM I
17-PP101 BUILDING 17 - BASEMENT LEVEL - PLUMBING
17-PP101-A BUILDING 17 - BASEMENT LEVEL - PLUMBING - ADDITIVE BID ITEM I
17-PP102 BUILDING 17 - MEZZANINE LEVEL - PLUMBING
17-PP102-A BUILDING 17 - MEZZANINE LEVEL - PLUMBING - ADDITIVE BID ITEM I
6-PP101 BUILDING 06 - PLUMBING - OVERALL PLAN - ADDITIVE BID ITEM II
6-PP401 BUILDING 06 - BASEMENT LEVEL - PLUMBING - ENLARGED PLANS - ADDITIVE BID ITEM II
6-PP501 BUILDING 06 - PLUMBING DETAILS - ADDITIVE BID ITEM II
MH001 MECHANICAL SYMBOLS AND ABBREVIATIONS
17-MD101-A BUILDING 17 - BASEMENT LEVEL - MECHANICAL - ADDITIVE BID ITEM I
17-MD102 BUILDING 17 - MEZZANINE LEVEL - MECHANICAL - DEMOLITION
17-MD102-A BUILDING 17 - MEZZANINE LEVEL - MECHANICAL - DEMOLITION - ADDITIVE BID ITEM I
1-MD103 BUILDINGS 01 AND 17 - THIRD LEVEL AND ROOF- MECHANICAL - DEMOLITION OF TEMPORARY
17-MH102 BUILDING 17 - MEZZANINE LEVEL - DUCTWORK
17-MH102-A BUILDING 17 - MEZZANINE LEVEL - DUCTWORK - ADDITIVE BID ITEM I
1-MH103 BUILDINGS 01 AND 17 - THIRD LEVEL - DUCTWORK
17-MP101-A BUILDING 17 - BASEMENT LEVEL - HYDRONIC PIPING - ADDITIVE BID ITEM I
17-MP102 BUILDING 17 - MEZZANINE LEVEL - HYDRONIC PIPING
17-MP102-A BUILDING 17 - MEZZANINE LEVEL - HYDRONIC PIPING - ADDITIVE BID ITEM I
1-MP103 BUILDING 01 - THIRD LEVEL - HYDRONIC PIPING
17-M401 BUILDING 17 - MECHANICAL SECTIONS
17-M402 BUILDING 17 - MECHANICAL SECTIONS - ADDITIVE BID ITEM I
17-M403 BUILDING 17 - BUILDING 17 - MECHANICAL SECTIONS - AHU-3
17-M404 BUILDING 17 - MECHANICAL SECTIONS - ADDITIVE BID ITEM I
17-M501 BUILDING 17 - MECHANICAL CONTROLS - AHU-3
17-M502 BUILDING 17 - MECHANICAL CONTROLS - AHU-1 - ADDITIVE BID ITEM I
17-M503 BUILDING 17 - MECHANICAL CONTROLS TEMPORARY UNIT(S)
17-M504 BUILDING 17 - MECHANICAL DETAILS - PHOTOS
17-M505 BUILDING 17 - MECHANICAL DETAILS
17-M601 BUILDING 17 - MECHANICAL SCHEDULES
6-MP101 BUILDING 06 - MECHANICAL - OVERALL FLOOR PLANS - ADDITIVE BID ITEM II
6-MP401 BUILDING 06 - BASEMENT LEVEL - MECHANICAL - ENLARGED PLANS - ADDITIVE BID ITEM II
6-MP402 BUILDING 06 - FIRST LEVEL - MECHANICAL - ENLARGED PLANS - ADDITIVE BID ITEM II
6-MP501 BUILDING 06 - MECHANICAL DETAILS - PHOTOS - ADDITIVE BID ITEM II
6-MP502 BUILDING 06 - MECHANICAL DETAILS - ADDITIVE BID ITEM II
6-MP503 BUILDING 06 - HOT WATER SCHEMATICS - ADDITIVE BID ITEM II
6-MP601 BUILDING 06 - MECHANICAL SCHEDULES - ADDITIVE BID ITEM II
EK001 ELECTRICAL SYMBOLS AND ABBREVIATIONS
17-ED102 BUILDING 17 - MEZZANINE LEVEL - ELECTRICAL - DEMOLITION
1-ED103 BUILDING 01 - THIRD LEVEL - ELECTRICAL - EXISTING CONDITIONS
17-EP102 BUILDING 17 - MEZZANINE LEVEL - ELECTRICAL PLAN
1-EP103 BUILDING 01 - THIRD LEVEL - ELECTRICAL PLAN
17-EP104 BUILDING 17 - ROOF LEVEL - LIGHTNING PROTECTION PLAN
17-EP501 ELECTRICAL DETAILS
17-EP601 BUILDING 17 - ONE-LINE DIAGRAM - DEMOLITION
17-EP602 BUILDING 17 - ONE-LINE DIAGRAM - NEW
17-EP603 BUILDING 17 - ELECTRICAL SCHEDULES
6-ED101 BUILDING 06 - BASEMENT LEVEL - ELECTRICAL - DEMOLITION - ADDITIVE BID ITEM II
6-EP101 BUILDING 06 - BASEMENT LEVEL - ELECTRICAL PLAN - ADDITIVE BID ITEM II
6-EP601 BUILDING 06 - ELECTRICAL SCHEDULES - ADDITIVE BID ITEM II
BUILDING 06
DESIGNATOR SHEET NAME
Mark Revisions: Date:
HZ HZ HZ
H Z
H Z
H Z
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
2-HOUR FIRE BARRIER
EGRESS PATH
K
L
M
N
13 14 15 16 1712 18
17.1
17.2
17.3
17.A 17.B 17.C 17.D
92' - 7"
21 sec
BLDG 17
AIR CONDITIONING
ELEVATOR
ELEVATOR
ELEVATOR
LOBBY
B113
STORAGE
PLUMBING
-STAIR
OFFICE A/C
OPERATORS
A101
K
L
M
N
13 14 15 16 1712 18
17.1
17.2
17.3
17.A 17.B 17.C 17.D
102' - 0"
23 sec
AHU - 3AHU - 1
GRATE
1.
LIFE SAFETY LEGEND
STAIR IS NOT ENCLOSED. TRAVEL DISTANCE IS MEASURED FROM
FURTHEST POINT TO EXIT ON FIRST FLOOR.
1.
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
17-GI101
BUILDING 17 - BASEMENT LEVEL AND
MEZZANINE LEVEL- LIFE SAFETY PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
LIFE SAFETY NOTES
1. EXISTING FIRE-RATED WALL - VERIFY RATING. NOTIFY OWNER OF
ANY DEVIATIONS AND/OR BREAKS WITH THE STATED WALL RATING
2 ALL FLOORS TO BE CLASSIFIED AS SPECIAL PURPOSE, INDUSTRIAL
OCCUPANCY. ALL EGRESS TO COMPLY WITH NFPA 101(24)
CHAPTER 40.
1/8" = 1'-0"1
BUILDING 17 - BASEMENT/ FIRST LEVEL - LIFE SAFETY PLAN
N N
1/8" = 1'-0"2
BUILDING 17 - MEZZANINE LEVEL - LIFE SAFETY PLAN
HIGH
VOLTAGE
ELECTRIC
STAIR
SHAFT
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
2-HOUR FIRE BARRIER
EGRESS PATH
K
L
M
N
13 14 15 16 17
19 20 22
12 18
21'
17.1
17.2
17.3
17.A 17.B 17.C 17.D
K.5
L.6
M.4
M.9
M.11M.12
ICRA WALL TO BE IN PLACE DURING INSTALLATION AND DEMOLITION OF
TEMPORARY UNITS. ICRA WALL TO BE REMOVED WHILE TEMPORARY UNITS
ARE IN PLACE.
107' - 11"
25 sec
135' - 8"
31 sec
DOOR IS KEY ACCESS ONLY. DOOR IS TO REMAIN
UNLOCKED FOR EGRESS PURPOSES DURING WORK
PERFORMED ON THIRD FLOOR IN COORDINATION
WITH VA COR.
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
17-GI102
BUILDING 17 - THIRD LEVEL - LIFE
SAFETY PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
LIFE SAFETY NOTES
1. EXISTING FIRE-RATED WALL - VERIFY RATING. NOTIFY OWNER OF
ANY DEVIATIONS AND/OR BREAKS WITH THE STATED WALL RATING
2 ALL FLOORS TO BE CLASSIFIED AS SPECIAL PURPOSE, INDUSTRIAL
OCCUPANCY. ALL EGRESS TO COMPLY WITH NFPA 101(24)
CHAPTER 40.
1/8" = 1'-0"1
BUILDING 17 - THIRD LEVEL - LIFE SAFETY PLAN
N
21' - 2"
5 sec
17' - 10"
4 sec
MECHANICAL
ROOM
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
2-HOUR FIRE BARRIER
EGRESS PATH
• EXISTING BUILDING BEYOND PROJECT LIMITS
• SHOWN FOR CONTEXT ONLY, NO WORK IS PROPOSED
• GRAY AREA IS BUSINESS OCCUPANCY ON FIRST FLOOR AND
OUT OF SCOPE AREA IN THE BASEMENT.
• PROJECT AREA IN BUILDING 6 IS TO BE CLASSIFIED AS
SPECIAL PURPOSE INDUSTRIAL OCCUPANCY. ALL EGRESS
TO COMPLY WITH NFPA 101(24) CHAPTER 40.
LEGEND
NOT IN SCOPE
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
6-GI101
BUILDING 06 - LIFE SAFETY PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
1/8" = 1'-0"2
BUILDING 6 - FIRST LEVEL - LIFE SAFETY PLAN
1/8" = 1'-0"1
BUILDING 6 - BASEMENT LEVEL - LIFE SAFETY PLAN
LIFE SAFETY NOTES
1. EXISTING FIRE-RATED WALL - VERIFY RATING. NOTIFY OWNER OF
ANY DEVIATIONS AND/OR BREAKS WITH THE STATED WALL RATING
2 ALL FLOORS TO BE CLASSIFIED AS SPECIAL PURPOSE, INDUSTRIAL
OCCUPANCY. ALL EGRESS TO COMPLY WITH NFPA 101(24)
CHAPTER 40.
N N
G
G
G
M
Center Street n d S tr e e t
Woolworth Avenue
N
IM
IT
Z D
R
IV
E
E
IS
E N
H O
W E
R D
R
IV
E
W A
E S
C H
E D
R
IV
E
E
IS
E N
H O
W E
R D
R
IV
E
PULLER DRIVE
FISHER
HOUSE
PARKING
GARAGE
BUILDING 17
PROJECT
LOCATION
17-GI104
6-GI106
BUILDING 6
SITE ACCESS
BUILDING 6
PROJECT LOCATION
PRIMARY ROUTE ANTICIPATED
LOADING AND UNLOADING
AREA COORDINATE WITH VA
ON USAGE
AHU TOWER
ROUTE FOR
TEMPORARY LIFT ACCESS
BUILDING 17
SITE ACCESS
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
6 & 17
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
GI103
CAMPUS SITE PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
1" = 60'-0"1
CAMPUS SITE PLAN
GENERAL SITE NOTES
1 CONTRACTOR SHALL FIELD VARIFY EXISTING SITE CONDITIONS. HALT WORK AND NOTIFY COR
REGARDING ANY INCONSISTENCIES OR VARIATIONS BETWEEN FIELD CONDITIONS AND THESE PLANS.
WORK WILL NOT COMMENCE UNTIL APPROVED BY THE COR ALL FIELD ADJUSTMENTS AND REVISIONS TO
THE PLANS MUST BE APPROVED BY THE COR PRIOR TO INSTALLATION.
2 CONTRACTOR TO REPAIR LANDSCAPE NOT LIMITED TO TURF GRASS IMMEDIATELY ADJACENT TO NEW
SIDEWALKS AND OTHER SITE IMPROVEMENTS.
3 CONTRACTOR TO PROVIDE SIGNAGE AT FACILITY ENTRANCES AND THE JOBSITE DIRECTING PEOPLE AND VEHICLES DURING CONSTRUCTION ACTIVITIES. ANY SIGNS THAT MUST BE REMOVED DURING THE
DEMOLITION PHASE ARE TO BE REPLACED UPON COMPLETION OF CONSTRUCTION.
4 CONTRACTOR TO USE LIKE MATERIALS FOR ALL EXTENSIONS OR PATCH BACK OF SIDEWALKS, DRIVES, AND CURB AND GUTTER, UNLESS NOTED OTHERWISE.
5 WORK WILL TAKE PLACE IN DESIGNATED AREAS OF BUILDINGS 6, 17, OR AS NOTED.
6 NECESSARY PARKING LOT CLOSURES AND ACCESS TO JOB SITE TO BE COORDINATED WITH VA BY
CONTRACTOR
7 CONTRACTOR TO COORDINATE WITH VA FOR STORAGE AND DELIVERY OF MATERIALS TO WORKSITE.
8 CONTRACTOR TO COORDINATE WITH THE VA WITHIN 14 CALANDAR DAYS OF ANY DISRUPTION TO
AUTOMOBILE AND PEDESTRIAN TRAFFICE WHEN PROVIDING LIFT AND MATERIAL DROP OFF.
9 ADDITIONALLY CONTRACTOR TO COORDINATE AND COMFIRM NO LESS THAN 3 BUSINESS DAYS IN
ADVANCE OF USE OF LOADING DOCKS.
ELEVATOR 7 AND 8 ARE TO BE UTILIZED BY CONTRACTOR.
ELEVATOR LOBBY FOR 3RD LEVEL KITCHEN AREA IS TO BE
WALLED OFF FROM KITCHEN. COORDINATE WITH VA COR.
ICRA WALL TO REMAIN IN PLACE FOR DURATION OF
TEMPORARY UNIT INSTALLATION AND REMOVAL. ICRA WALL
TO BE REMOVED WHILE TEMPORARY UNITS ARE FUNCTIONAL.
BUILDING 17
EXISTING BOLLARDS
ANTICIPATED TEMPORARY
LIFT LOCATION
AHU TOWER
BUILDING 1
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:0
P
M
17-GI104
BUILDING 17 SITE PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
1" = 20'-0"1
BUILDING 17 - SITE PLAN
HZ HZ HZ
H Z
H Z
H Z F
F
F
F
K
H
L
M
N
13 14 15 16 17 18' 19 20 21 22 23 2412
17.1
17.2
17.3
17.A 17.B 17.C 17.D
J
G
K.5
L.6
M.4
M.9
M.10M.11
RECEIVING
AREA
CORRIDOR
ELEVATOR
LOBBY
B113
ELEVATOR
ELEVATOR
STORAGE
PLUMBING
MAIL ROOM
B009
CANTEEN
STORAGE
ACCESS ROUTE 1
OFFICE
WAREHOUSE
B070
BLDG. 17
-AIR CONDITIONING
B007B005
LOCK SHOP
B119
B080
B094
B095STAIRS
TO FIRST LEVEL
AND MEZZANINE
RECEIVING
AREA
K
H
L
M
N
13 14 15 16 17 18' 19 20 21 2212
18 21'
17.1
17.2
17.3
17.A 17.B 17.C 17.D
J
G
K.5
L.6
M.4
M.9
M.11M.12
STAIRS
TO MEZZANINE
K
H
L
M
N
13 14 15 16 1712
17.1
17.2
17.3
17.A 17.B 17.C 17.D
J
G
STAIRS
FROM BASEMENT
TO MEZZANINE
AHU 1 AHU 3
K
H
L
M
N
13 14 15 16 17 18' 19 20 2112
18 21'
17.1
17.2
17.3
17.A 17.B 17.C 17.D
J
G
K.5
L.6
M.4
M.9
1.
17-AE201 2
ACCESS PATH
SYMBOL
PROJECT AREA ACCESS LEGEND
DESCRIPTION
STARTING POINT OF LEVEL
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
2-HOUR FIRE BARRIER
EGRESS PATH
ICRA LEGEND
ICRA WALL ONLY TO BE INSTALLED DURING EQUIPMENT INSTALLATION AND
DEMOLITION AND TO BE REMOVED WHEN ALL WORK HAS BEEN COMPLETED
FOR EACH PHASE OF WORK.
1.
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:1
P
M
17-GI105
BUILDING 17 - PROJECT AREA ACCESS
PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"1
BUILDING 17 - BASEMENT LEVEL - ACCESS PLAN
1/16" = 1'-0"2
BUILDING 17 - FIRST LEVEL - ACCESS PLAN
1/16" = 1'-0"3
BUILDING 17 - MEZZANINE LEVEL - ACCESS PLAN
1/16" = 1'-0"4
BUILDING 17 - ROOF/ BUILDING 1 - ACCESS PLAN
N N
NN
n d S tr e e t
E
IS
E N
H O
W E
R D
R
IV
E
BASEMENT ACCESS
FIRST LEVEL ACCESS
BUILDING 6
PROJECT AREA UNDER
CONSTRUCTION BY OTHERS
GENERATOR
ENCLOSURE
BUILDING 24
BUILDING 01
BUILDING 6 SITE
ACCESS
RICHARD
JOSEPH
ONKEN
A-5125
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
12/24/2025
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
NE COA NUMBER: CA-1620
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 NRG IJM
A u to d e s k D o c s /1
-2
-3
A E
C o rr e c t H
V A
C D e fi c ie n c ie s /6
-2
-3
.B
.B
.A rc h
R
-A
E C o rr e c t H
V A
C D e fi c ie n c ie s .r v t
/1
/2
:3
:1
P
M
6-GI106
BUILDING 06 - SITE PLAN
12/24/2025
CONSTRUCTION
DOCUMENTS
1" = 20'-0"1
BUILDING 6 - SITE PLAN
GENERAL SITE NOTES
1 CONTRACTOR SHALL FIELD VARIFY EXISTING SITE CONDITIONS. HALT WORK AND NOTIFY COR
REGARDING ANY INCONSISTENCIES OR VARIATIONS BETWEEN FIELD CONDITIONS AND THESE PLANS.
WORK WILL NOT COMMENCE UNTIL APPROVED BY THE COR ALL FIELD ADJUSTMENTS AND REVISIONS TO
THE PLANS MUST BE APPROVED BY THE COR PRIOR TO INSTALLATION.
2 CONTRACTOR TO REPAIR LANDSCAPE NOT LIMITED TO TURF GRASS IMMEDIATELY ADJACENT TO NEW
SIDEWALKS AND OTHER SITE IMPROVEMENTS.
3 CONTRACTOR TO PROVIDE SIGNAGE AT FACILITY ENTRANCES AND THE JOBSITE DIRECTING PEOPLE AND VEHICLES DURING CONSTRUCTION ACTIVITIES. ANY SIGNS THAT MUST BE REMOVED DURING THE
DEMOLITION PHASE ARE TO BE REPLACED UPON COMPLETION OF CONSTRUCTION.
4 CONTRACTOR TO USE LIKE MATERIALS FOR ALL EXTENSIONS OR PATCH BACK OF SIDEWALKS, DRIVES, AND CURB AND GUTTER, UNLESS NOTED OTHERWISE.
5 WORK WILL TAKE PLACE IN DESIGNATED AREAS OF BUILDINGS 6, 17, OR AS NOTED.
6 NECESSARY PARKING LOT CLOSURES AND ACCESS TO JOB SITE TO BE COORDINATED WITH VA BY
CONTRACTOR
7 CONTRACTOR TO COORDINATE WITH VA FOR STORAGE AND DELIVERY OF MATERIALS TO WORKSITE.
8 CONTRACTOR TO COORDINATE WITH THE VA WITHIN 14 CALANDAR DAYS OF ANY DISRUPTION TO
AUTOMOBILE AND PEDESTRIAN TRAFFICE WHEN PROVIDING LIFT AND MATERIAL DROP OFF.
9 ADDITIONALLY CONTRACTOR TO COORDINATE AND COMFIRM NO LESS THAN 3 BUSINESS DAYS IN
ADVANCE OF USE OF LOADING DOCKS.
12 13 14 1517.A 17.B 17.C 17.D
(E)3" GHWR
(E)3" GHWS
P-8
P-10
HX-1
HX-3
(E )3
" G
HW
R (E
)3 " G
HW
R
(E)4" GHWS
(E)4" GHWR
ASBESTOS NOTES:
1. ESTABLISH REGULATED AREAS (RA) AND NEGATIVE PRESSURE ENCLOSURES (NPE) AND PERFORM
REMOVAL IN ACCORDANCE WITH VA MASTER SPECIFICATION SECTION 02 82 13.13, GLOVEBAG ASBESTOS ABATEMENT. FINALIZE LIMITS OF REGULATED AREAS, LOCATIONS OF NEGATIVE AIR MACHINES (NAM), PERSONAL DECONTAMINATION FACILITIES (PDF), AND WASTE DECONTAMINATION FACILITIES (WDF) BASED ON SITE CONDITIONS, BEST PRACTICES, PHASING REQUIREMENTS AND AS COORDINATED WITH
THE VA FACILITY.
2. THE ABATEMENT CONTRACTOR MUST COMPLY WITH ALL APPLICABLE REQUIREMENTS OF 29 CFR 1926.1101, 40 CFR PART 61 SUBPART M, AND ANY OTHER APPLICABLE STATE (NEBRASKA), AND FEDERAL
REGULATIONS FOR ASBESTOS ABATEMENT. THIS INCLUDES PROPER NOTIFICATION, HANDLING,
REMOVAL, DISPOSAL OF ASBESTOS CONTAINING MATERIALS, ENSURING WORKER SAFETY (TRAINING, PPE, MEDICAL SURVEILLANCE), AIR MONITORING (INTERIM AND FINAL), AND PROJECT RECORD-KEEPING .
COORDINATE ALL WORK ACTIVITIES WITH THE NEBRASKA DEPARTMENT OF ENVIRONMENTAL QUALITY (NDEQ) AND EPA REGION 7, AS APPLICABLE. UPDATE THE PROJECT PLAN AND NOTIFICATIONS TO
REFLECT SITE-SPECIFIC COMPLIANCE MEASURES.
3. ASSUME 50% EFFICIENCY WHEN CALCULATING NAM REQUIREMENTS FOR ACHIEVING FOUR (4) AIR CHANGES PER HOUR AND PROVIDED GREATER THAN -0.02” WCG PRESSURE. CONFIGURE AND PLACE NAMS AS NEEDED TO MAXIMIZE AIR MOVEMENT AND PREVENT DEAD AIR SPACE. COORDINATE NEGATIVE
AIR DISCHARGE LOCATIONS WITH GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE , AND VA
PROFESSIONAL INDUSTRIAL HYGIENIST, IF NEEDED.
4. ALL WASTE LOADOUT SHALL OCCUR AFTER HOURS. COORDINATE LOADOUT ROUTES AND TIMES WITH
THE GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE, AND VA PROFESSIONAL INDUSTRIAL
HYGIENIST.
5. WHITE PIPE INSULATION MASTIC (2% CHRYSOTILE) WILL BE IMPACTED BY RENOVATION. REMOVE PER THE VA SPECIFICATION FOR GLOVEBAG ABATEMENT. PERFORM WITHIN REGULATED AREA, USING WET
REMOVAL METHODS AND PROPER CONTAINMENT.
6. REFER TO THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE INFORMATION CONCERNING THE PRESENCE OF ASBESTOS-CONTAINING MATERIALS IN THE PROJECT AREAS. THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT CAN BE
FOUND IN VOLUME 5 - REPORTS.
ASBESTOS ABATEMENT PHASING:
1. THE ABATEMENT CONTRACTOR SHALL WORK CLOSELY WITH THE GENERAL CONTRACTOR,
CONTRACTING OFFICER, OWNER OR OWNER'S REPRESENTATIVE, AND/OR THE VA PROFESSIONAL
INDUSTRIAL HYGIENIST TO COORDINATE REMOVAL OF ASBESTOS CONTAINING MATERIALS IN
ACCORDANCE WITH PROJECT SCHEDULING, SEQUENCING, AND PHASING REQUIREMENTS. ALL
ABATEMENT WORK WILL BE DONE AFTER HOURS. PHASING IS SUBJECT TO CHANGE TO ACCOMMODATE
SITE CONDITIONS AND FACILITY OPERATIONS.
LEAD-BASED PAINT & LEAD-CONTAINING PAINT:
1. THE PROJECT AREA WAS RECENTLY SURVEYED FOR LEAD-BASED PAINT. REFER TO THE HAZARDOUS
BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE
INFORMATION CONCERNING THE PRESENCE OF LEAD-BASED PAINT IN THE PROJECT AREAS.
2. NO SUSPECT PAINT APPLICATIONS THAT WILL BE IMPACTED BY THE HVAC UPGRADES WERE IDENTIFIED
DURING THE HAZARDOUS BUILDING MATERIALS INSPECTION.
3. IF SUSPECT PAINTED COMPONENTS ARE ENCOUNTERED DURING DEMOLITION OR CONSTRUCTION, STOP WORK IMMEDIATELY, NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE AND VA PROFESSIONAL
INDUSTRIAL HYGIENIST, AND AWAIT SAMPLING BEFORE RESUMING WORK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 12-24-2025
CONSTRUCTION
DOCUMENTS
C.L. MET
Au to de sk
D oc s:
//1
-2 5-
- A E
C or re ct
H
VA
C D ef ic ie nc ie s/
6-
-3
.B
.B
.A rc h_
R
_1
-A
E C or re ct H
VA
C
D ef ic ie nc ie s.
rv t 5/
7/
:3 2:
P
M
C.L. MET
Mark Revisions: Date:
1/4" = 1'-0"1 BUILDING 17- BASEMENT LEVEL - HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1N
17-HA101-A
BUILDING 17 - BASEMENT LEVEL -
HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1
C.L. MET
A1
A1
EL -
I
EL -
I
(E)4" LPS
(E)1" LPC
(E)4" GHWS
(E)4" GHWR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 12-24-2025
CONSTRUCTION
DOCUMENTS
C.L. MET
Au to de sk
D oc s:
//1
-2 5-
- A E
C or re ct
H
VA
C D ef ic ie nc ie s/
6-
-3
.B
.B
.A rc h_
R
_1
-A
E C or re ct H
VA
C
D ef ic ie nc ie s.
rv t 5/
7/
:3 2:
P
M
17-HA102
BUILDING 17 - MEZZANINE LEVEL -
HAZARDOUS MATERIALS
Mark Revisions: Date:
1/4" = 1'-0"1 BUILDING 17- MEZZANINE LEVEL - HAZARDOUS MATERIALSN
A1
A1
A1
ASBESTOS NOTES:
1. ESTABLISH REGULATED AREAS (RA) AND NEGATIVE PRESSURE ENCLOSURES (NPE) AND PERFORM
REMOVAL IN ACCORDANCE WITH VA MASTER SPECIFICATION SECTION 02 82 13.13, GLOVEBAG ASBESTOS ABATEMENT. FINALIZE LIMITS OF REGULATED AREAS, LOCATIONS OF NEGATIVE AIR MACHINES (NAM), PERSONAL DECONTAMINATION FACILITIES (PDF), AND WASTE DECONTAMINATION FACILITIES (WDF) BASED ON SITE CONDITIONS, BEST PRACTICES, PHASING REQUIREMENTS AND AS COORDINATED WITH
THE VA FACILITY.
2. THE ABATEMENT CONTRACTOR MUST COMPLY WITH ALL APPLICABLE REQUIREMENTS OF 29 CFR 1926.1101, 40 CFR PART 61 SUBPART M, AND ANY OTHER APPLICABLE STATE (NEBRASKA), AND FEDERAL
REGULATIONS FOR ASBESTOS ABATEMENT. THIS INCLUDES PROPER NOTIFICATION, HANDLING,
REMOVAL, DISPOSAL OF ASBESTOS CONTAINING MATERIALS, ENSURING WORKER SAFETY (TRAINING, PPE, MEDICAL SURVEILLANCE), AIR MONITORING (INTERIM AND FINAL), AND PROJECT RECORD-KEEPING .
COORDINATE ALL WORK ACTIVITIES WITH THE NEBRASKA DEPARTMENT OF ENVIRONMENTAL QUALITY (NDEQ) AND EPA REGION 7, AS APPLICABLE. UPDATE THE PROJECT PLAN AND NOTIFICATIONS TO
REFLECT SITE-SPECIFIC COMPLIANCE MEASURES.
3. ASSUME 50% EFFICIENCY WHEN CALCULATING NAM REQUIREMENTS FOR ACHIEVING FOUR (4) AIR CHANGES PER HOUR AND PROVIDED GREATER THAN -0.02” WCG PRESSURE. CONFIGURE AND PLACE NAMS AS NEEDED TO MAXIMIZE AIR MOVEMENT AND PREVENT DEAD AIR SPACE. COORDINATE NEGATIVE
AIR DISCHARGE LOCATIONS WITH GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE , AND VA
PROFESSIONAL INDUSTRIAL HYGIENIST, IF NEEDED.
4. ALL WASTE LOADOUT SHALL OCCUR AFTER HOURS. COORDINATE LOADOUT ROUTES AND TIMES WITH
THE GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE, AND VA PROFESSIONAL INDUSTRIAL
HYGIENIST.
5. WHITE PIPE INSULATION MASTIC (2% CHRYSOTILE) LOCATED ON THE CHILLED WATER PIPE INSULATION ASSOCIATED WITH #3 WILL BE IMPACTED BY RENOVATION. REMOVE PER THE VA SPECIFICATION FOR
GLOVEBAG ABATEMENT. PERFORM WITHIN REGULATED AREA, USING WET REMOVAL METHODS AND
PROPER CONTAINMENT.
6. REFER TO THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE INFORMATION CONCERNING THE PRESENCE OF ASBESTOS-CONTAINING MATERIALS IN THE PROJECT AREAS. THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT CAN BE
FOUND IN VOLUME 5 - REPORTS.
ASBESTOS ABATEMENT PHASING:
1. THE ABATEMENT CONTRACTOR SHALL WORK CLOSELY WITH THE GENERAL CONTRACTOR,
CONTRACTING OFFICER, OWNER OR OWNER'S REPRESENTATIVE, AND/OR THE VA PROFESSIONAL
INDUSTRIAL HYGIENIST TO COORDINATE REMOVAL OF ASBESTOS CONTAINING MATERIALS IN
ACCORDANCE WITH PROJECT SCHEDULING, SEQUENCING, AND PHASING REQUIREMENTS. ALL
ABATEMENT WORK WILL BE DONE AFTER HOURS. PHASING IS SUBJECT TO CHANGE TO ACCOMMODATE
SITE CONDITIONS AND FACILITY OPERATIONS.
LEAD-BASED PAINT & LEAD-CONTAINING PAINT:
1. THE PROJECT AREA WAS RECENTLY SURVEYED FOR LEAD-BASED PAINT. REFER TO THE HAZARDOUS
BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE
INFORMATION CONCERNING THE PRESENCE OF LEAD-BASED PAINT IN THE PROJECT AREAS.
2. NO SUSPECT PAINT APPLICATIONS THAT WILL BE IMPACTED BY THE HVAC UPGRADES WERE IDENTIFIED
DURING THE HAZARDOUS BUILDING MATERIALS INSPECTION.
3. IF SUSPECT PAINTED COMPONENTS ARE ENCOUNTERED DURING DEMOLITION OR CONSTRUCTION, STOP WORK IMMEDIATELY, NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE AND VA PROFESSIONAL
INDUSTRIAL HYGIENIST, AND AWAIT SAMPLING BEFORE RESUMING WORK.
ASBESTOS NOTES:
1. ESTABLISH REGULATED AREAS (RA) AND NEGATIVE PRESSURE ENCLOSURES (NPE) AND PERFORM
REMOVAL IN ACCORDANCE WITH VA MASTER SPECIFICATION SECTION 02 82 13.13, GLOVEBAG ASBESTOS ABATEMENT. FINALIZE LIMITS OF REGULATED AREAS, LOCATIONS OF NEGATIVE AIR MACHINES (NAM), PERSONAL DECONTAMINATION FACILITIES (PDF), AND WASTE DECONTAMINATION FACILITIES (WDF) BASED ON SITE CONDITIONS, BEST PRACTICES, PHASING REQUIREMENTS AND AS COORDINATED WITH
THE VA FACILITY.
2. THE ABATEMENT CONTRACTOR MUST COMPLY WITH ALL APPLICABLE REQUIREMENTS OF 29 CFR 1926.1101, 40 CFR PART 61 SUBPART M, AND ANY OTHER APPLICABLE STATE (NEBRASKA), AND FEDERAL
REGULATIONS FOR ASBESTOS ABATEMENT. THIS INCLUDES PROPER NOTIFICATION, HANDLING,
REMOVAL, DISPOSAL OF ASBESTOS CONTAINING MATERIALS, ENSURING WORKER SAFETY (TRAINING, PPE, MEDICAL SURVEILLANCE), AIR MONITORING (INTERIM AND FINAL), AND PROJECT RECORD-KEEPING .
COORDINATE ALL WORK ACTIVITIES WITH THE NEBRASKA DEPARTMENT OF ENVIRONMENTAL QUALITY (NDEQ) AND EPA REGION 7, AS APPLICABLE. UPDATE THE PROJECT PLAN AND NOTIFICATIONS TO
REFLECT SITE-SPECIFIC COMPLIANCE MEASURES.
3. ASSUME 50% EFFICIENCY WHEN CALCULATING NAM REQUIREMENTS FOR ACHIEVING FOUR (4) AIR CHANGES PER HOUR AND PROVIDED GREATER THAN -0.02” WCG PRESSURE. CONFIGURE AND PLACE NAMS AS NEEDED TO MAXIMIZE AIR MOVEMENT AND PREVENT DEAD AIR SPACE. COORDINATE NEGATIVE
AIR DISCHARGE LOCATIONS WITH GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE , AND VA
PROFESSIONAL INDUSTRIAL HYGIENIST, IF NEEDED.
4. ALL WASTE LOADOUT SHALL OCCUR AFTER HOURS. COORDINATE LOADOUT ROUTES AND TIMES WITH
THE GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE, AND VA PROFESSIONAL INDUSTRIAL
HYGIENIST.
5. WHITE PIPE INSULATION MASTIC (2% CHRYSOTILE) LOCATED ON THE CHILLED WATER PIPE INSULATION ASSOCIATED WITH AHUs #1 AND #3 WILL BE IMPACTED BY RENOVATION. REMOVE PER THE VA MASTER SPECIFICATION FOR GLOVEBAG ABATEMENT. PERFORM WITHIN REGULATED AREA, USING WET REMOVAL
METHODS AND PROPER CONTAINMENT.
6. YELLOW & GRAY DUCT SEAM MASTIC (2% CHRYSOTILE) LOCATED UNDER INSULATION ON THE SEAMS OF THE SUPPLY DUCT FOR AHU #1 WILL BE IMPACTED BY RENOVATION. REMOVE PER THE VA MASTER SPECIFICATION FOR GLOVEBAG ABATEMENT. PERFORM WITHIN REGULATED AREA, USING WET REMOVAL
METHODS AND PROPER CONTAINMENT.
7. REFER TO THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE INFORMATION CONCERNING THE PRESENCE OF ASBESTOS-CONTAINING MATERIALS IN THE PROJECT AREAS. THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT CAN BE
FOUND IN VOLUME 5 - REPORTS.
ASBESTOS ABATEMENT PHASING:
1. THE ABATEMENT CONTRACTOR SHALL WORK CLOSELY WITH THE GENERAL CONTRACTOR,
CONTRACTING OFFICER, OWNER OR OWNER'S REPRESENTATIVE, AND/OR THE VA PROFESSIONAL
INDUSTRIAL HYGIENIST TO COORDINATE REMOVAL OF ASBESTOS CONTAINING MATERIALS IN
ACCORDANCE WITH PROJECT SCHEDULING, SEQUENCING, AND PHASING REQUIREMENTS. ALL
ABATEMENT WORK WILL BE DONE AFTER HOURS. PHASING IS SUBJECT TO CHANGE TO ACCOMMODATE
SITE CONDITIONS AND FACILITY OPERATIONS.
LEAD-BASED PAINT & LEAD-CONTAINING PAINT:
1. THE PROJECT AREA WAS RECENTLY SURVEYED FOR LEAD-BASED PAINT. REFER TO THE HAZARDOUS
BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE
INFORMATION CONCERNING THE PRESENCE OF LEAD-BASED PAINT IN THE PROJECT AREAS.
2. NO SUSPECT PAINT APPLICATIONS THAT WILL BE IMPACTED BY THE HVAC UPGRADES WERE IDENTIFIED
DURING THE HAZARDOUS BUILDING MATERIALS INSPECTION.
3. IF SUSPECT PAINTED COMPONENTS ARE ENCOUNTERED DURING DEMOLITION OR CONSTRUCTION, STOP WORK IMMEDIATELY, NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE AND VA PROFESSIONAL
INDUSTRIAL HYGIENIST, AND AWAIT SAMPLING BEFORE RESUMING WORK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 12-24-2025
CONSTRUCTION
DOCUMENTS
C.L. MET
Au to de sk
D oc s:
//1
-2 5-
- A E
C or re ct
H
VA
C D ef ic ie nc ie s/
6-
-3
.B
.B
.A rc h_
R
_1
-A
E C or re ct H
VA
C
D ef ic ie nc ie s.
rv t 5/
7/
:3 2:
P
M
C.L. MET
Mark Revisions: Date:
1/4" = 1'-0"1 BUILDING 17- MEZZANINE LEVEL - HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1N
17-HA102-A
BUILDING 17 - MEZZANINE LEVEL -
HAZARDOUS MATERIALS - ADDITIVE BID ITEM 1
C.L. MET
A2
A2
A2 A2
A1
A1
A1
EL -
I
ASBESTOS NOTES:
1. DURING THE INVESTIGATION, IT WAS NOTED THAT PENETRATIONS WILL BE MADE IN THE ROOF OF
BUILDING 17 FOR HVAC DUCTWORK. THE ROOF WILL ALSO BE IMPACTED DURING THE INSTALLATION OF AIR TERMINALS. THE ROOF IS A RUBBER MEMBRANE ROOF, AND IT WAS NOT SAMPLED TO PREVENT POTENTIAL LEAKS FROM SAMPLING ACTIVITIES. THE ROOF LAYERS SHALL BE SAMPLED BY THE DESIGN TEAM IMMEDIATELY PRIOR TO PENETRATIONS BEING MADE DURING CONSTRUCTION ACTIVITIES TO CONFIRM THAT IT IS ASBESTOS-FREE. CAUTION SHOULD BE EXERCISED DURING ROOF-RELATED WORK
UNTIL SAMPLING IS CONDUCTED TO MITIGATE POTENTIAL ASBESTOS EXPOSURE RISKS
2. REFER TO THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED MARCH 28, 2025, FOR MORE INFORMATION CONCERNING THE PRESENCE OF ASBESTOS-CONTAINING MATERIALS IN THE PROJECT AREAS. THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT CAN BE
FOUND IN VOLUME 5 - REPORTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e e igh th inc h = on e f oo t thr ee in ch es on e f oo t
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6"
6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
Correct HVAC Deficiencies 636-25-301
4101 Woolworth Ave, Omaha, NE 68105
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
InfraStructure, LLC 6910 Pacific Street, Suite 310 Omaha, NE 68106 Phone: (402) 554-0234
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 12-24-2025
CONSTRUCTION
DOCUMENTS
C.L. MET
Au to de sk
D oc s:
//1
-2 5-
- A E
C or re ct
H
VA
C D ef ic ie nc ie s/
6-
-3
.B
.B
.A rc h_
R
_1
-A
E C or re ct H
VA
C
D ef ic ie nc ie s.
rv t 5/
7/
:3 2:
P
M
C.L. MET
Mark Revisions: Date:
1/4" = 1'-0"1 BUILDING 17- THIRD LEVEL - HAZARDOUS MATERIALSN
17-HA103
BUILDING 17 - THIRD LEVEL -
HAZARDOUS MATERIALS
C.L. MET
A3
2024 INTERNATIONAL BUILDING CODE
ACI 318-19
A.I.S.C. SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (LRFD) ANSI/AISC 360-22
A.W.S. D1.1, D1.3, D1.4
LIVE LOADS
LOCATION PSF
MECHANICAL ROOM FLOOR 150 (PER EXISTING DRAWINGS)
BUILDING 17 ROOF 50 (25 PSF SNOW AND 25 PSF PIPING PER EXISTING DRAWINGS)
PARTITIONS - (LATERAL LOAD) 5
STRUCTURE RISK CATEGORY: IV
ROOF LIVE LOAD 25 PSF (PER EXISTING DRAWINGS)
ROOF SNOW LOAD 24 PSF + DRIFT
Pg = 25 psf, Is = 1.2, Ct = 1.0, Ce = 1.0
WIND LOADS
BASIC WIND SPEED 125 MPH (ULTIMATE WIND SPEED)
97 MPH (SERVICE/NOMINAL WIND SPEED)
EXPOSURE CLASSIFICATION B
ENCLOSURE CLASSIFICATION ENCLOSED (GCpi = +/- 0.18)
SEISMIC LOADS
SEISMIC DESIGN CATEGORY C
IMPORTANCE FACTOR 1.5
SPECTRAL RESPONSE COEFFICIENT SDS = 0.077
SPECTRAL RESPONSE COEFFICIENT SD1 = 0.073
SITE CLASSIFICATION D
CONCRETE & REINFORCING
CONCRETE MIX f'c @ 28 DAYS) MAX. W/C RATIO
SLABS OVER METAL DECK 3000 PSI 0.48
WALLS AND CURBS 4000 PSI 0.45
CONCRETE NOT OTHERWISE SPECIFIED 3000 PSI 0.50
GRADE SUPPORTED SLABS 4000 PSI 0.48
SUSPENDED BEAMS, JOISTS, AND SLABS 4000 PSI 0.45
CEMENT TYPE PORTLAND TYPE I/II OR 1L
AGGREGATES REGULAR WT. HARDROCK TYPE - ASTM C33
REINFORCING STEEL ASTM A615, GRADE 60
WELDED WIRE FABRIC ASTM A1064
PREFORMED EXPN. JT. (1/2 IN) ASTM D1751
STEEL
STRUCTURAL STEEL (WIDE FLANGES) ASTM A992, GRADE 50
STRUCTURAL STEEL (ALL OTHER SHAPES) ASTM A36
STRUCTURAL STEEL PIPE ASTM A53, GRADE B (Fy = 35 KSI) STRUCTURAL SQUARE TUBING ASTM A500, GRADE C (Fy = 50 KSI)
ANCHOR RODS ASTM F1554, GRADE 36
BOLTED CONNECTIONS ASTM F3125, GRADE A325
WELDED CONNECTIONS E70XX ELECTRODES
HEADED CONCRETE ANCHORS (HCA) 1/2"Ø TO 1"Ø ASTM A108 TYPE B (Fu=65 KSI) DEFORMED BAR ANCHORS (DBA) ASTM A496 TYPE C (Fy = 80 KSI)
METAL ROOF DECK ASTM A1008
GALVANIZED METAL FLOOR DECK ASTM A653
ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE APPLICABLE BUILDING CODE.
THE STRUCTURAL WORK HAS BEEN DESIGNED TO RESIST DESIGN LOADS ONLY AS A COMPLETED
STRUCTURAL ASSEMBLY. APPLICATION OF ANY LOADS TO THE PARTIALLY COMPLETED STRUCTURE SHALL BE CONSIDERED BY THE CONTRACTOR AND SO INCLUDED IN THE DESIGN OF SHORING, BRACING, FORMWORK, AND ANY OTHER SUPPORTING ELEMENTS PROVIDED FOR CONSTRUCTION OF THE STRUCTURE.
WHERE CONSTRUCTION MATERIALS OR EQUIPMENT ARE TEMPORARILY STORED ON ROOF OR FLOOR
FRAMING, THEY SHALL BE DISTRIBUTED SO THAT THE DESIGN LIVE LOAD IS NOT EXCEEDED.
DETAILS ON THE DRAWINGS INDICATED AS "TYPICAL" APPLY IN ALL AREAS WHERE CONDITIONS SIMILAR TO
THE DETAIL OCCUR.
THE STRUCTURAL DRAWINGS ARE NOT INTENDED FOR USE AS SHOP ERECTION DRAWINGS. REPRODUCTION OF THESE DRAWINGS IN LIEU OF PREPARATION OF SHOP ERECTION DRAWINGS SIGNIFIES THE USERS' ACCEPTANCE THAT ALL INFORMATION SHOWN IS CORRECT AND APPROPRIATE FOR SHOP DRAWINGS AND THAT THE USER WILL BE FULLY RESPONSIBLE FOR EXPENSES THAT MAY OCCUR FROM SAID ACCEPTANCE.
UNLESS SPECIFICALLY NOTED, THERE ARE NO PROVISIONS MADE FOR FUTURE FLOORS, ROOFS, OR OTHER
LOADS.
CONCRETE PLACEMENT SHALL BE IN ACCORDANCE WITH THE LATEST EDITIONS OF ACI 117, ACI 301, AND CRSI's MANUAL OF STANDARD PRACTICE
CONCRETE BATCH DESIGN(S) SHALL BE PROPORTIONED AND PRODUCED IN ACCORDANCE WITH A.C.I. 318, IN PARTICULAR CHAPTER 5, AND A.C.I. 301. MIX AND DELIVER IN ACCORDANCE WITH ASTM C94.
SLUMP REQUIREMENTS:
CONCRETE W/ PLASTICIZERS MAX. 8 IN.
OTHER CONCRETE MIN. 1 IN. / MAX. 5 IN.
AIR ENTRAINMENT CONCRETE EXPOSED TO EARTH OR WEATHER - 5% MIN.
ADMIXTURES SUBMIT AS REQUIRED FOR APPROVAL
FLY ASH UP TO MAX. 25% OF CEMENT CONTENT
CONCRETE TEST CYLINDERS:
SAMPLING IN FIELD ASTM C172 & C31
CYLINDER STRENGTH TESTS ASTM C39
FREQUENCY OF STRENGTH TESTS ONE PER 100 CU. YDS. OR
MIN. ONCE FOR EA. 5000 S.F. OF SLABS OR WALLS OR
MIN. ONCE PER DAY FOR EACH TYPE OF MIX
ONE STRENGTH TEST = AVG. STRENGTHS OF (2) 6"x12" CYLINDERS OR (3) 4"x8" CYLINDERS @ 28 DAYS.
CYLINDERS TO BE TESTED: (2) @ 7 DAYS, (2) 6"x12" OR (3) 4"x8" @ 28 DAYS, (1) @ 56 DAYS (IF REQUIRED)
CONCRETE TO CONCRETE COLD JOINTS: PROVIDE 1/4” INTENTIONALLY ROUGHENED SURFACE AT ALL
HORIZONTAL JOINTS.
EXPOSED CORNERS: PROVIDE A 3/4" CHAMFER AT ALL EXPOSED CONCRETE CORNERS.
CURING: CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A MINIMUM OF SEVEN DAYS AFTER ITS PLACEMENT. IF FORMWORK IS REMOVED PRIOR TO SEVEN DAYS, APPLY MOIST CURING TO NEWLY EXPOSED SURFACES. APPROVED CURING COMPOUNDS MAY BE USED IN LIEU OF MOIST CURING PROVIDED
THEY ARE COMPLIANT WITH ANY SEALER OR ADMIXTURES.
REINFORCING BAR WELDING: ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND
REINFORCING BARS SHALL BE ALLOWED WITHOUT THE SPECIFIC APPROVAL OF THE ENGINEER.
MINIMUM CONCRETE CLEAR COVER: PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER OVER
REINFORCING (FACE OF CONCRETE TO EDGE OF BAR) UNLESS DETAILED OTHERWISE ON DRAWINGS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3”
CONCRETE EXPOSED TO EARTH OR WEATHER
• NO. 6 THROUGH NO. 18 BARS 2”
• NO. 5 BAR, W31 OR D31 WIRE & SMALLER 1 1/2”
CONCRETE NOT EXPOSED TO EARTH OR WEATHER
• SLABS, WALLS, JOISTS #11 BAR AND SMALLER 3/4”
• BEAMS & COLUMNS - TIES, STIRRUPS & SPIRALS 1 1/2”
BAR SUPPORT ACCESSORIES: SHALL BE PROVIDED IN ACCORDANCE WITH THE LATEST A.C.I. MANUAL OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES
BEAM REINFORCING ON BAR BOLSTERS @ 4 FT. O.C. MAX.
SLAB REINFORCING ON BAR BOLSTERS @ 4 FT. O.C. MAX.
WITH SAND PLATES AS REQUIRED
CONC EXPOSED TO VIEW PLASTIC COATED OR GALV. LEGS
CONCRETE W/ SANDBLAST FINISH STAINLESS STEEL SUPPORTS
• NO ROCKS, CLAY TILE, OR CLAY BRICK SHALL BE USED TO SUPPORT REINFORCING.
NON-METALLIC, SHRINKAGE-RESISTANT GROUT
PRE-MIXED, NON-METALLIC, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING SILICA SANDS, PORTLAND CEMENT, SHRINKAGE-COMPENSATING AGENTS, PLASTICIZING AND WATER-REDUCING AGENTS
(ASTM C-1107).
MINIMUM COMPRESSIVE STRENGTH @ 48 HOURS 2400 PSI
MINIMUM COMPRESSIVE STRENGTH @ 28 DAYS 7000 PSI
REINFORCING SHOP DRAWINGS: REINFORCING SUPPLIER SHALL PROVIDE COMPLETE PLACEMENT AND FABRICATION DRAWINGS FOR ALL REINFORCING INCLUDING THE LOCATION AND SIZE OF ALL ACCESSORIES
AND SUPPORTS.
DESIGN OF CONNECTIONS: BEAM CONNECTIONS SHALL BE AS DETAILED ON THE PLANS. ALTERNATIVE CONNECTIONS, DESIGNED BY A LICENSED ENGINEER FOR THE FABRICATOR, MAY BE UTILIZED PROVIDED THE ALTERNATIVE CONNECTION PROVIDES THE SAME LOAD CARRYING CAPACITY OF THE ORIGINAL DESIGN. ANY CHANGES OR DEVIATIONS FROM THE CONSTRUCTION DOCUMENT'S DESIGN OR DETAILING MUST BE
EXPLICITLY NOTED IN THE FABRICATOR'S SUBMITTAL DRAWINGS FOR REVIEW
STEEL PROTECTION: ALL STRUCTURAL STEEL SHALL BE CLEANED PER SSPC SP-2 HAND TOOL CLEANING OR SP-3 POWER TOOL CLEANING AND SHOP PAINTED WITH ONE COAT OF THE FABRICATOR'S STANDARD PRIMER (PAINT TYPE SSPC-PAINT 13 OR 25). TOUCH UP SCARRED AREAS WITH THE SAME PAINT AFTER
ERECTION.
SHOP DRAWINGS: STEEL FABRICATOR SHALL PROVIDE COMPLETE ERECTION AND FABRICATION DRAWINGS
SHOWING ALL MEMBERS AND CONNECTIONS.
WELDING: ALL WELDING SHALL BE PERFORMED BY QUALIFIED WELDERS PER AWS STANDARD
QUALIFICATION PROCEDURES.
HEADED CONCRETE ANCHORS (HCA): AUTOMATICALLY END WELDED IN THE SHOP OR FIELD IN
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANCHOR WELDS SHALL BE TESTED PER
AWS SECTION 7.7.
POST-INSTALLED MECHANICAL ANCHORS: SEE DETAILS
INSTALL USING MINIMUM TORQUE, EMBEDMENTS, EDGE DISTANCES AND SPACING (UNLESS OTHERWISE
NOTED) AS RECOMMENDED BY THE ANCHOR MANUFACTURER.
POST-INSTALLED ADHESIVE ANCHORS: SEE DETAILS
INSTALLATION TO MEET MANUFACTURER'S RECOMMENDATIONS (UNLESS NOTED OTHERWISE)
MIN. EMBEDMENTS, EDGE DISTANCES, SPACING, PROCEDURES, AND CURING TIME PRIOR TO LOADING.
POST-INSTALLED ANCHORS SHALL BE LOCATED PER THE DETAILS.
AVOID CUTTING OR DAMAGING EXISTING REINFORCING. SHOULD LOCATIONS OF DRILLED HOLES BE FOUND DIRECTLY ALIGNED WITH REINFORCING BARS, NOTIFY ENGINEER FOR NECESSARY ADJUSTMENTS TO THE
DESIGN.
POST-INSTALLED ANCHORS LOCATED IN PRESTRESSED OR POST-TENSIONED MEMBERS SHALL NOT BE DRILLED UNTIL EXACT LOCATIONS OF TENDONS OR STRANDS ARE DETERMINED USING NON-DESTRUCTIVE
METHODS.
DO NOT INSTALL POST-INSTALLED ANCHORS INTO CMU BLOCK WITHIN 1 1/2" FROM ANY VERTICAL MORTAR
JOINT
APPLICABLE DESIGN CODES AND STANDARDS
DESIGN LOADS
MATERIAL DATA
STRUCTURAL NOTES
CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AND REPORT ANY DISCREPANCIES TO THE
ENGINEER BEFORE PROCEEDING WITH ANY PHASE OF THE WORK.
ANY PROPRIETARY STRUCTURAL SYSTEMS THAT ARE COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND
ERECTION IN ACCORDANCE WITH THE INSTRUCTIONS PREPARED BY THE SUPPLIER.
CROSS REFERENCE STRUCTURAL DRAWINGS WITH ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, AND WITH ACTUAL EQUIPMENT SUPPLIED TO THE PROJECT, FOR THE LOCATION AND SIZE OF ALL SLAB OPENINGS, SLEEVES, FLOOR DEPRESSIONS, EMBEDS, SURFACE FINISHES, MASONRY CONTROL JOINTS, ETC.
COORDINATION / VERIFICATION
CONCRETE / REINFORCING
STRUCTURAL STEEL
ANCHORAGE
INSPECTION TASKS PRIOR TO WELDING
WELDER QUALIFICATION AND CONTINUITY RECORDS
WPS AVAILABLE
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
MATERIAL IDENTIFICATION
WELDER IDENTIFICATION SYSTEM
FIT-UP OF GROOVE WELDS
• JOINT PREPARATION
• DIMENSIONS
• CLEANLINESS
• TACKING
• BACKING TYPE AND FIT (IF APPLICABLE)
FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y-, AND K-JOINTS WITHOUT BACKING
• JOINT PREPARATION
• DIMENSIONS
• CLEANLINESS
• TACKING
CONFIGURATION AND FINISH OF ACCESS HOLES
FIT-UP OF FILLET WELDS
• DIMENSIONS
• CLEANLINESS
• TACKING
CHECK WELDING EQUIPMENT
QC QA
P O
P P
P P
O O
O O
O O
P O
O O
O O
O O
STRUCTURAL STEEL
INSPECTIONS, QUALITY CONTROL, AND QUALITY ASSURANCE SHALL BE PERFORMED PER ANSI/AISC 360 CHAPTER N: QUALITY CONTROL AND QUALITY ASSURANCE. FOR FABRICATORS NOT PARTICIPATING OR ENROLLED IN AISC'S QUALITY CERTIFICATION PROGRAM AND ARE NOT AN AISC CERTIFIED FABRICATOR, INSPECTIONS WILL BE PERFORMED AT THE FABRICATOR'S SHOP AT THE EXPENSE OF THE CONTRACTOR.
OBSERVE (O): THE…
This is the start of the file's text. The full file is on GovTribe.