BLDG. 25 ENLARGED MECHANICAL
REVISED SECTION
SCALE: 1/4" = 1'-0"
BLDG. 25 ENLARGED FIRST FLOOR
MECHANICAL REVISED SECTION
SCALE: 1/4" = 1'-0"
E
E
PLAN NOTES:
1. CONNECT NEW 18"x 12" TO EXISTING 30"x 12".
2. FIRE DAMPER AND 14"x 14" DUCT ACCESS DOOR.
3. SIDE MOUNTED PRE-FILTER SECTION.
4. 67"x44"x6" O.A. PLENUM ON NECK OF EXISTING LOUVER.
5. MOTORIZED DAMPER WITH MANUAL DAMPER; SEE DETAIL E8/25-MH-112.
6. TRANSITION FROM 18"x 18" TO 12'x 18".
7. 25-SH-1.
8. SEE FIRE DAMPER DETAIL F5/00-MH-002.
9. 14"x 14" ACCESS DOOR IN BOTTOM OF DUCT.
10. 25-EAHU-1 FACTORY CONTROL PANEL MOUNTED ON WALL BELOW LOUVER.
11. MOUNT UNIT ON 4" CONCRETE PAD THAT IS DOWELED INTO EXISTING
CONCRETE FLOOR.
3RD FLOOR
2ND FLOOR
1ST FLOOR
32"x 36" O.A.18"x 34"
26"x 46" SA
18"x 40" RA
25-EAHU-1
12"x 34" M
3RD FLOOR
2ND FLOOR
1ST FLOOR
EX 30"x 12"
12"x 18"
EX 30"x 12"
12"x 18"
FD
"x
2"
FD
EX 30"x 12"
12"x 18"
34"x 18" SA
40"x 18" OA
36"x 32" OA
25-1FBC
EX OUTSIDE
AIR LOUVER
CRAWL
SPACE ROOM 108ROOM 108
FINISHED CEILING IN
CORRIDOR AND
OFFICES BEYOND
REVISED HVAC SECTIONS
BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MH-301
BID DOCUMENTS
28 36
MEN
TOILET
G12
STORAGE
G13
WASH
ROOM
G13A
TRASH
ROOM
G13B
BATTERY
STORAGE
G13C
STORAGE
G14
WOMEN
LOCKER
G15
WOMEN
TOILET
G16
MECHANICAL
ROOM
G17
EP
FEC
C O
N N
EC
TI
N G
C O
R R
ID
O
R C
O N
N
EC
TI
N
G C
O R
R
ID
O R
CONFERENCE
ROOM
G04
WORK
ROOM
G05
OFFICE
G01A
DME SUPPLY/
DISTRIBUTION
G01
ELECT
ROOM
G03
MECH.
ROOM
G02
CORRIDOR
H003
ELEVATOR
E-1
STAIRWELL
NO. 1
S1
STAIRWELL
NO. 2
S2
CHARGING
STATION
G07
STORAGE
G08
FES
STORAGE
G09A
FES
STORAGE
G09
SAFETY
OFFICE
G10
MALE
LOCKER
G11
IN-HOUSE
CONSTRUCTION/
STORAGE
G23
PROSTHETICS
STORAGE
G26
CORRIDOR
H002
OI&T
CLOSET
H002A
DOCK
AREA
CORRIDOR
H001
PROSTHETICS
STORAGE
G25
BASEMENT MECHANICAL PIPING
REVISED PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. RECONNECT CHWS&R PIPING AND CONDENSATE
DRAIN TO FAN COIL.
2. NEW FAN COIL IN EXISTING LOCATION.
3. NEW FAN COIL LOCATION.
4. EXTEND 34" LPS & CR TO NEW FAN COIL.
5. NEW 34" CHWS & CHWR. CONNECT TO BOTTOM OF
EXISTING MAINS.
6. PROVIDE AND INSTALL A HEAVY DUTY CONDENSATE
PUMP, BASIS OF DESIGN: LITTLE GIANT VCL-14ULS,
1/50 HP, 120V/1PH, 170 GPH AT 5 FT HD. INSTALL
WILL WALL MOUNT FRAME.
7. 1/2" DIA. COPPER PIPE TO EXISTING CONDENSATE
DRAIN AS REQUIRED. KEEP PIPING TIGHT TO WALL
AS POSSIBLE.
8. EXISTING CONDENSATE DRAIN IN CORNER.
9. SEE ENLARGED PLAN THIS SHEET.
10. CONNECT NEW 3/4" LPS AND CR TO EXISTING PIPING
AS REQUIRED.
FEC
CONFERENCE
ROOM
G04
WORK
ROOM
G05
ENLARGED G04 & G05 MECHANICAL
PIPING REVISED PLAN
SCALE: 1/4" = 1'-0"
BASEMENT MECHANICAL
PIPING REVISED PLAN
BUILDING 23
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
23-MP-1B1
29 36
PLAN NOTES:
1. CONNECT NEW 2" CHWS AND CHWR TO EXISTING AS REQUIRED.
2. DROP PIPING DOWN AND RUN UNDER EXISTING CATWALK.
3. 1-1/2"LPS TO HUMIDIFIER; SEE DETAIL F1/00-MG-003.
4. DROP 1-1/2"LPS DOWN TO STEAM COIL and 1"CR; SEE DETAIL
D9/00-MG-003.
5. 1-1/4" COPPER CONDENSATE DRAIN WITH P-TRAP; SEE DETAIL
D3/00MG-003.
6. NEW CONDENSATE PUMP 25-SCP-1, SEE DETAIL D3/00-MG-004 AND
ENLARGED PLAN F2 ON THIS SHEET.
7. CONNECT NEW 3" LPS AND 1-1/4" CR TO EXISTING AS REQUIRED.
8. SEE DETAIL F3/00-MG-003 FOR IFBC COIL DETAIL.
9. SEE DETAIL E8/00-MG-003 FOR WATER COIL DETAIL.
10. SEE DETAIL F7 THIS SHEET FOR RECONNECTION OF EXISTING
STEAM CONDENSATE RETURN.
11. IF CONDENSATE PUMP COMES WITH RECEIVER, THEN THIS PIPE
CAN BE ELIMINATED.
GENERAL PLAN NOTES:
A. LABEL ALL PIPING. SEE SPECS.
B. EVERYTHING SHOWN IS NEW UNLESS NOTED OTHERWISE.
BLDG. 25 ENLARGED FIRST FLOOR
MECHANICAL PIPING REVISED PLAN
SCALE: 1/2" = 1'-0"
F
EXISTING LPS
CHWS
CHWR
EX-CHWS
PUMP
REVISED STEAM CONDENSATE
RETURN PIPING ISOMETRIC
SCALE: NTS
EX COND. RETURN
NEW 1" CR
NEW 1-1/4" CR
UP TO TOP FLOOR
DOWN FROM TOP
FLOOR
EX-CHWS
PUMP
NEW 2"Ø CHILLED WATER
SUPPLY AND RETURN
EX-CR
F
EX CONDENSATE RETURN
CONDENSATE PIPING AND
TRAPS TO BE DEMO'D
FROM DEMO'D AHU
25-CSP-1
1"CR
EX-FD
25-IFBC
25-SH-1
NEW PIPING ISOMETRIC
SCALE: NTS
25-IF
BC
1-1/2"LPS
1"CR
1-1/4"CD
EX FD
2"CHWS
2"CHWR
25-EAHU-1
3"LPS
1-1/4"CR EX COND.
3/4"CR
1-1/2"LPS2LPS
1" C
R
EX LPS
1- 1/
2" L
PS
25-CSP-1
25-SH-1
36"Øx24" STEEL PIPE
WITH WELDED ENDS
C
CH
W
S
CH
W
R
1-1/4"CR
1-1/2"LPS
1"CR
25-EAHU-1
1"CR
MECHANICAL PIPING
REVISED PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MP-112
30 36
SURFACE/RECESSED 2 x 4 LED LIGHT FIXTURE
SURFACE/RECESSED 1 x 4 LED LIGHT FIXTURE
SWITCHES
LED LIGHT FIXTURE CONNECTED TO EMERGENCY POWER
EXIT LIGHT FIXTURE WALL MOUNTED, LED
EXIT LIGHT FIXTURE CEILING MOUNTED, LEDEMERGENCY BATTERY UNIT
SWITCH, SINGLE POLE
SWITCH, THREE-WAY
BATTERY OPERATED EMERGENCY LIGHT - WALL MOUNTED
SWITCH, FOUR-WAY
RECEPTACLE, DUPLEX WEATHERPROOF
RECEPTACLE, QUADPLEX
RECEPTACLE, DUPLEX
RECEPTACLE, SINGLE
SWITCH, MANUAL TIMER
SWITCH, PILOT LIGHT
SWITCH, KEYED
SWITCH, CONTROLLING FIXTURES MARKED WITH a
SWITCH, DIMMER
FLUSH FLOOR BOX, THREE GANG
WIRING CONCEALED IN CEILING OR WALL
RECEPTACLE SPECIAL, NEMA CONFIGURATION
FLUSH FLOOR OUTLET
DUPLEX RECEPTACLE SPLIT WIRED
FIRE ALARM, FLOW SWITCH
DISCONNECT SWITCH FOR MOTORS OVER 1/2HP
ELECTRICAL MOTOR CONNECTION - VERIFY HP, AND PHASE
FLUSH OR SURFACE MOUNTED BRANCH PANELBOARDS
MAIN DISTRIBUTION OR POWER PANELBOARDS
JUNCTION BOX 4 11/16 x 4 11/16 x 2 1/8"
FIRE ALARM, TAMPER SWITCH
PANIC BUTTON
PUSH BUTTON "UP-DOWN-DN"
FIRE ALARM ANNUNICATOR PANEL
FIRE ALARM CONTROL PANEL
PUSH BUTTON CONTROL STATION
SPEAKER, FLUSH CEILING MOUNTED
SPEAKER, WALL MOUNTED
FIRE ALARM, IONIZATION DUCT DETECTOR
CLOCK OUTLET
SECURITY TELEVISION CAMERA
TRANSFORMER, 120V TO LOW VOLTAGE
TELEVISION OUTLET
DOORBELL PUSH BUTTON
DOOR BELL CHIME
POLE MOUNTED LIGHT FIXTURE - SINGLE HEAD
SURFACE / RECESSED HID FIXTURE
WALL MOUNTED LED
UNLESS NOTED OTHERWISE
THERMAL DETECTOR 135° FIXED
SMOKE DETECTOR-PHOTO ELECTRIC TYPE
HORN STROBE
STROBE UNIT 30CD
IONIZATION SMOKE DETECTOR
PULL STATION
A= GROUND; B= NEUTRAL; C= HOT
HOMERUN
WALL MOUNTED HID FIXTURE
SURFACE MOUNTED OR RECESSED LED
TELEPHONE OUTLET BOX AND COVER PLATE
TELEPHONE OUTLET BOX, AND COVER PLATE, WALL
TELE/DATA OUTLET W (2) OUTLETS
COMMUNICATION
TELEDATA OUTLET
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION
XP
WW
WT
WP
WHM
W
VA
V
UPS
UON
UG
TYP
TX
TTC
TTB
TPS
TP
T
SYM
SWBD
SW
STD
SSC
SPST
SN
SHT
SEC
SCIC
RVS
RMC
RMS
RM
REQD
(RR)
(R)
PWR
PVC
PT
PRI
PNL
PH, O
PF
PB
PAR
PA
P
OD
OC
NTS
NOR
NO
NL
NIC
NF
NC
(N)
MTG
MTD
MT
MOM
MIN
MH
MECH
MCP
MCM
MCC
MC
MAX
MATV
LV
LTG
LT
LRA
LCL
KWH
KW
KVA
KV
KEC
KCMIL
KA
JB
INC
IMT
ID
HZ
HV
HPS
HP
HOA
HID
HH
GRD
GFR
GFI
GENR
GALV
FT
FLUOR
FLEX
FA
F
(F)
EST
EQUIP
EQ
E.T.R.
EMT
EMER
ELEC
(ER)
(E)
DWG
DTL
DPST
DPDT
DP
DIA
DGP
DF
CX
CW
CU
CT
CRT
CONTR
COMM
CO
CLG
CKT
CCTV
CB
CAB
C
BFG
BLDG
BIL
AWG
AUTO
ATS
AT
AIC
AFG
AFF
AF
ACCP
AC
A
2SP
EXPLOSION PROOF
WARM WHITE
WATERTIGHT
WEATHERPROOF
WATT HOUR METER
WIRE/WATTS
VOLTAMPERES
VOLT
UNINTERRUPTIBLE POWER SYSTEM
UNLESS OTHERWISE NOTED
UNDERGROUND
TYPICAL
TRANSFORMER
TELEPHONE TERMINAL CABINET
TELEPHONE TERMINAL BOARD
TWISTED PAIR SHIELDED
TWISTED PAIR
THROW
SYMMETRICAL
SWITCHBOARD
SWITCH
STANDARD
SOUND SYSTEM CABINET
SINGLE POLE SINGLE THROW
SOLID NEUTRAL
SHEET
SECONDARY
REVERSE
RIGID METALLIC CONDUIT
ROOT MEAN SQUARE
ROOM
REQUIRED
REMOVE AND RELOCATE
REMOVE
POWER
POLYVINYL CHLORIDE DUCT
POTENTIAL TRANSFORMER
PRIMARY
PANEL
PHASE
POWER FACTOR
PULL BOX
PERSONAL ALARM RECEIVER
PUBLIC ADDRESS
POLE
OUTSIDE DIAMETER
ON CENTER
NOT TO SCALE
NORMAL
NORMALLY OPEN/NUMBER
NIGHT LIGHT
NOT IN CONTRACT
NON-FUSED
NORMALLY CLOSED
NEW
MOUNTING
MOUNTED
EMPTY
MOMENTARY
MINIMUM
MANHOLE/METAL HALIDE
MECHANICAL
MOTOR CURRENT PROTECTOR
THOUSAND CIRCULAR MILS
MOTOR CONTROL CENTER
MOTOR CONTROLLER
MAXIMUM
MASTER ANTENNAE TELEVISION
LOW VOLTAGE
LIGHTING
LIGHT
LOCKED ROTOR AMPS
LONG CONTINUOUS LOAD
KILOWATT HOURS
KILOWATT
KILOVOLT AMPERES
KILOVOLT
KITCHEN EQUIPMENT CONTRACTOR
THOUSAND CIRCULAR MILS
KILOAMPERES
JUNCTION BOX
INCANDESCENT
INTERMEDIATE METAL TUBING
INSIDE DIAMETER
HERTZ
HIGH VOLTAGE
HIGH PRESSURE SODIUM
HORSEPOWER
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
HANDHOLE
GROUND
GROUND FAULT RELAY
GROUND FAULT INTERRUPTER
GENERATOR
GALVANIZED
FOOT/FEET
FLUORESCENT
FLEXIBLE METAL CONDUIT
FIRE ALARM
FUSED
FUTURE
ESTIMATE
EQUIPMENT
EQUAL
EXISTING TO REMAIN
ELECTRICAL METALLIC TUBING CONDUIT
EMERGENCY
ELECTRIC/ELECTRICAL
EXISTING RELOCATE
EXISTING
DRAWING
DETAIL
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DOUBLE POLE
DIAMETER
DATA GATHERING PANEL
DRINKING FOUNTAIN
COAXIAL CABLE
COOL WHITE
COPPER
CURRENT TRANSFORMER
CATHODE RAY TUBE (MONITOR)
CONTRACTOR
COMMUNICATIONS
CONDUIT ONLY
CEILING
CIRCUIT
CLOSED CIRCUIT TELEVISION
CIRCUIT BREAKER
CABINET
CONDUIT
BELOW FINISHED GRADE
BUILDING
BASIC IMPULSE LEVEL
AMERICAN WIRE GAUGE
AUTOMATIC
AUTOMATIC TRANSFER SWITCH
AMPS-TRIP
AMP INTERRUPTING CURRENT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AMPS-FRAME
ACCESS PANEL
ALTERNATING CURRENT
AMPERE (AMPS)
2 SPEED
NUMBER
SPECIAL COMMUNICATIONS INTERFACE CAB.
EXISTINGEX
FLA FULL LOAD AMPS
MFR MANUFACTURER
IV INVERT ELEVATION
FACP FIRE ALARM CONTROL PANEL
DESCRIPTIONSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLSYMBOL DESCRIPTION
INTERCOMM HANDSET
SINGLE CIRCUIT PIR WALL SENSOR 'SCHNEIDER ELECTRIC'
#SLSPWS1277UX(COLOR).
DUAL CIRCUIT PIR WALL SENSOR 'SCHNEIDER ELECTRIC'
#SLSPWD1277UX(COLOR).
LOW VOLTAGE ULTRASONIC CEILING SENSOR 'SCHNEIDER ELECTRIC'
#SLSCUS2000 (SENSOR); 'SCHNEIDER ELECTRIC' #SLSPP1277 (POWER
PACK)
LOW VOLTAGE CEILING MOUNT PIR OCCUPANCY SENSOR 'SCHNEIDER
ELECTRIC' #SLSCI2000 (SENSOR); 'SCHNEIDER ELECTRIC' #SLSPP1277
(POWER PACK).
LOW VOLTAGE CEILING MOUNT DUAL-TECHNOLOGY OCCUPANCY
SENSOR 'SCHNEIDER ELECTRIC' #SLSCDT2000 (SENSOR); 'SCHNEIDER
ELECTRIC' #SLSPP1277 (POWER PACK).
CARD-ACCESS KEY DEVICE
NURSE CALL (PATIENT STATION); WEST CALL #C-STATION PROVIDE ALL
NECESSARY DEVICES, ACCESSORIES, AND FRONT-END EQUIPMENT FOR
A COMPLETE SYSTEM
NURSE CALL (NURSE STATION); WEST CALL #STF-2000 PROVIDE ALL
NECESSARY DEVICES, ACCESSORIES, AND FRONT-END EQUIPMENT
FOR A COMPLETE SYSTEM
PULL STATION
TELE/DATA OUTLET W (4) OUTLETS
NURSE CALL LIGHT
FIELD VERIFY:
COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT SWITCH
MANUAL MOTOR STARTER
EXISTING ELECTRICAL EQUIPMENT WAS OBTAINED FROM SIMILAR
BUILDING DRAWINGS AND CURSORY FIELD OBSERVATION,
HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE,
CERTAIN INFORMATION CONCERNING THE LOCATION OF THE
EXISTING ELECTRICAL WORK MUST BE VERIFIED IN THE FIELD TO
DETERMINE THE EXACT LOCATIONS, DEPTH, SIZE, ETC. PRIOR TO
STARTING CONSTRUCTION ANY CONFLICT BETWEEN THESE PLANS
AND THE ACTUAL CONDITIONS SHALL BE REPORTED IMMEDIATELY
TO THE ARCHITECT FOR VERIFICATION AND/OR CORRECTION.
ELECTRICAL SYMBOLS &
ABBREVIATIONS
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
00-EG-001
23 & 25
31 36
PULL
STATION
SWITCH
NOTE: ALL DIMENSIONS ARE
TYPICAL FOR GIVEN DEVICE UNLESS
OTHERWISE NOTED ON PLANS.
RECEPTACLEVOICE/DATA
OUTLET
FINISHED FLOOR
HORN/STROBE
48"
18" 18"
48"
80"
6" A
B O
V E
C O
U N
T E
R
COUNTER
OUTLETS
LP2-5 BPA-15
CKT.S
LP4-13,15,17
LABEL CKT. NO. OF EACH DEVICE ON
FRONT SIDE OF COVER PLATE. USE
PERMANENT MARKER PEN,
BRADY MARKING SYSTEM OR OTHER
METHOD APPROVED BY THE ENGINEER
JUNCTION BOXES (EXPOSED OR
CONCEALED ABOVE ACCESSIBLE CEILING)
LABEL COVERS WITH CKT.'S CONTAINED
WITHIN. USE PERMANENT MARKER PEN
OR OTHER APPROVED METHOD.
FOR J.B.'S CONTAINING OTHER THAN
POWER
OR LIGHTING CKT.'S LABEL COVERS
INDICATING SYSTEM TYPE AND ZONES.
LABEL EXAMPLES:
"FIRE ALARM-ZONES 2&3"
"P.A. ZONES 4,5,&6"
"DATA CIRCUITS A&B"
"EXIT SIGNS-EMI&2"
"EMERG. CKTS. BPEM-3,4"
FRONT SIDE OF
PLATE
FRONT
DUPLEX RECEPTACLE PLATE
STANDARD
TOGGLE
SWITCH PLATE
FRONT
FRONT SIDE OF PLATE
DEVICE MOUNTING HEIGHT DETAIL
ELECTRICAL IDENTIFICATION DETAILB
D
STAINLESS STEEL CLAMPS BY E.C.
CONDUIT BY E.C.
SPUN ALUMINUM FLASHING
BASE BY E.C.
BUILT-UP
ROOF DECK
CONDUIT BY E.C.
ROOFING
STEPPED PVC
BOOT BY E.C.
TYPICAL ROOF PENETRATION
HANGER OR EQUAL
BASIS OF DESIGN; B-LINE #B3373 CONDUIT
B
SCHEDULE OF CONDUIT APPLICATIONS
CONDUIT LOCATION OR
APPLICATION
IN CONCRETE SLAB
(NOT LARGER THAN 1"C)
R
IG
ID
CONDUIT TYPE
NOTE:
- TYPE OF CONDUIT TO BE USED.
- E.M.T. SHALL NOT BE USED IN SIZES LARGER THAN 2 INCH.
- CONVERT TO RIGID OR INTER. THROUGH SLAB.
- USE THREADED FITTINGS ONLY.
BELOW LOWEST FLOOR SLAB
CONCEALED IN WALLS, ABOVE
CEILINGS AND IN FURRED SPACES
INSIDE, ABOVE BOTTOM OF
ROOF STEEL
FEEDER, POWER AND SIGNAL
CIRCUITS RUN EXPOSED
FINAL CONNECTION TO EQUIP.
SUBJECT TO VIBRATION
FINAL CONNECTION TO EQUIP.
IN DAMP LOCATIONS
SHORT CONNECTIONS WHERE
NON-FLEXIBLE CONDUIT IS
IMPRACTICAL
3 1
IN
TE
R M
ED
IA
TE
E.
M
.T
FL
EX
IB
LE
FL
EX
IB
LE
W / W
.P
JA
CK
ET
P.
V
.C . S
CH
ED
A .C
. C A
BL
E
SERVICE ENTRANCE
THHN-THWN
EXPOSED FEEDERS
CONCEALED FEEDERS
FEEDERS BELOW
CONCRETE
FEEDERS UNDERGROUND
FEEDERS BELOW
RAISED FLOORING
FEEDERS IN CABLE TRAY
EXPOSED BRANCH CIRCUITS
CONCEALED BRANCH CIRCUITS
BRANCH CIRCUITS BELOW CONCRETE
BRANCH CIRCUITS UNDERGROUND
BRANCH CIRCUITS BELOW
RAISED FLOORING
BRANCH CIRCUITS IN
CABLE TRAY
CLASS 1 CONTROL CIRCUITS
CLASS 2 CONTROL CIRCUITS
XHHW MI NM MC UF AC
CONDUCTOR INSULATION AND
MULTICONDUCTOR SCHEDULE TABLE
SIZE (AWG OR KCMIL)
MINIMUM SIZE
EQUIPMENT
GROUNDING
CONDUCTORS FOR
GROUNDING RACEWAY
AND EQUIPMENT
AUTOMATIC OVER
CURRENT SETTING
(AMPS - NOT
EXCEEDING)
COOPER
ALUMINUM
OR COPPER
CLAD
ALUMINUM
15 14 12 20 12 10 60 10 8 100 8 6 200 6 4 300 4 2 400 3 1 500 2 1/0 600 1 2/0 800 1/0 3/0 1000 2/0 4/0 1200 3/0 250 1600 4/0 350 2000 250 400 2500 350 400 3000 400 600 4000 500 600 5000 700 750 6000 800 1200
SIZE AWG
OR KCMIL COOPER
12 25 20 10 35 30 8 50 40 6 65 50 4 85 65 3 100 75 2 115 90 1 130 100
1/0 150 120 2/0 175 135 3/0 200 155 4/0 230 180 250 255 205 300 285 230 350 310 250 400 335 270
CONDUCTOR
SIZING FOR RHW,
THHW, THW,
THWN, XHHW, USE,
ZW AT 167°F
ALUMINUM
CONDUCTOR INSULATION SCHEDULE B
CONDUIT APPLICATION SCHEDULED
CONDUCTOR SIZING SCHEDULE
F
CONDUIT, TYP
MINERAL WOOL
(FIRMLY
PACKED)
FIRESTOP SEALANT
PER SECTION 07 84
00, FIRESTOPPING
JUNCTION BOX
OR PULL BOX
(SIZE AS
REQUIRED)
CONDUIT
FITTING
SPRING NUT, TYP
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL, TYP.
CONCRETE
FLOOR SLAB, TYP.
STEEL
EXPANSION
ANCHOR, TYP
9.52mm
FLOOR SLAB PENETRATION DETAIL
F
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 915mm (36")
SHALL BE INSTALLED WITH A CENTER SUPPORT ROD. SUPPORT RODS SHALL NOT BE
GREATER THAN 457mm (18") APART.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION 26 05
33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
CONDUIT CLAMP. SIZE
AS REQUIRED
INTEGRAL GALVANIZED LIPPED STEEL
MOUNTING CHANNEL
LOCKING SQUARE WASHER & LOCKNUT
9.52mm (3/8") MIN GALVANIZED
THREADED ROD, TYP.
WASHER
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED
STEEL
MOUNTING
CHANNEL
9.52mm (3/8") MIN GALVANIZED
THREADED ROD, TYP.
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
CONDUIT TRAPEZE MOUNTING DETAIL
D
5/16"x3"x3" STEEL
ANGLE SEHPRED TO
CONDUIT HANGER
AND ROOF STARTER
TYPICAL FOR TWO
ELECTRICAL SYMBOLS &
ABBREVIATIONS
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
00-EG-002
23 & 25
32 36
G12
STORAGE
G13
WASH
ROOM
G13A
TRASH
ROOM
G13B
BATTERY
STORAGE
G13C
STORAGE
G14
WOMEN
LOCKER
G15
WOMEN
TOILET
G16
MECHANICAL
ROOM
G17
EP
FEC
C O
N N
EC
TI
N G
C O
R R
ID
O
R C
O N
N
EC
TI
N
G C
O R
R
ID
O R
CONFERENCE
ROOM
G04
WORK
ROOM
G05
OFFICE
G01A
DME SUPPLY/
DISTRIBUTION
G01
ELECT
ROOM
G03
MECH.
ROOM
G02
CORRIDOR
H003
ELEVATOR
E-1
STAIRWELL
NO. 1
S1
STAIRWELL
NO. 2
S2
CHARGING
STATION
G07
STORAGE
G08
FES
STORAGE
G09A
FES
STORAGE
G09
SAFETY
OFFICE
G10
MALE
LOCKER
G11
IN-HOUSE
CONSTRUCTION/
STORAGE
G23
PROSTHETICS
STORAGE
G26
CORRIDOR
H002
OI&T
CLOSET
H002A
DOCK
AREA
CORRIDOR
H001
PROSTHETICS
STORAGE
G25
FAN COIL-3
FAN COIL-1 FAN COIL-2 FAN COIL-4
FAN COIL-7
FAN COIL-8
FAN COIL-5
BASEMENT ELECTRICAL POWER
DEMOLITION PLAN BUILDING 23
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. DISCONNECT POWER FOR UNIT
DEMOLITION AND REPLACEMENT AS
REQUIRED.
2. SERVED BY PANEL PE, FIELD VERIFY..
3. SERVED BY PANEL CR, FIELD VERIFY.
4. DISCONNECT POWER AND PULL WIRE
BACK TO PANEL. THIS CIRCUIT WILL
BE EXTENDED TO NEW LOCATION.
FIELD VERIFY:
EXISTING ELECTRICAL EQUIPMENT WAS OBTAINED FROM SIMILAR
BUILDING DRAWINGS AND CURSORY FIELD OBSERVATION,
HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE,
CERTAIN INFORMATION CONCERNING THE LOCATION OF THE
EXISTING ELECTRICAL WORK MUST BE VERIFIED IN THE FIELD TO
DETERMINE THE EXACT LOCATIONS, DEPTH, SIZE, ETC. PRIOR TO
STARTING CONSTRUCTION ANY CONFLICT BETWEEN THESE PLANS
AND THE ACTUAL CONDITIONS SHALL BE REPORTED IMMEDIATELY
TO THE ARCHITECT FOR VERIFICATION AND/OR CORRECTION.
EX PANEL CR
EX PANEL PE
1 3 1 3 1 3
1 2 1 2
1 3
1 4
BASEMENT ELECTRICAL
POWER DEMOLITION PLAN
BUILDING 23
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
23-ED-1B1
33 36
H301
303A
304 305 306
308A
308B 308C
309 310
312304A 307A
309A
H101
H102
H103
109 110 111 112
114 115 116
113A
H103A
112A
123A
106A
112B
H201
H203
212A
210 209
209A
209B
209C 209D
201A
207 205
208A
204D
208B
AHU-2
AHU-3
BLDG. 25 SECOND FLOOR POWER
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
BLDG. 25 THIRD FLOOR POWER
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
BLDG. 25 FIRST FLOOR POWER
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
AHU-1
FIELD VERIFY:
EXISTING ELECTRICAL EQUIPMENT WAS OBTAINED FROM SIMILAR
BUILDING DRAWINGS AND CURSORY FIELD OBSERVATION,
HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE,
CERTAIN INFORMATION CONCERNING THE LOCATION OF THE
EXISTING ELECTRICAL WORK MUST BE VERIFIED IN THE FIELD TO
DETERMINE THE EXACT LOCATIONS, DEPTH, SIZE, ETC. PRIOR TO
STARTING CONSTRUCTION ANY CONFLICT BETWEEN THESE PLANS
AND THE ACTUAL CONDITIONS SHALL BE REPORTED IMMEDIATELY
TO THE ARCHITECT FOR VERIFICATION AND/OR CORRECTION.
PLAN NOTES:
1. DISCONNECT ELECTRICAL CONNECTIONS TO AIR HANDLER.
REMOVE WIRING BACK TO PANEL IN ROOM 126 AS
REQUIRED. CONDUIT TO REMAIN.
2. DISCONNECT ELECTRICAL CONNECTIONS TO AIR HANDLER.
REMOVE WIRING BACK TO PANEL 25-E1 IN ROOM AS
REQUIRED. CONDUIT TO REMAIN.
3. DISCONNECT ELECTRICAL CONNECTIONS TO AIR HANDLER.
REMOVE WIRING BACK TO PANEL IN ROOM AS REQUIRED.
CONDUIT TO REMAIN.
4. REMOVE MOTOR STARTER, ANALOG CONTROL PANEL,
JOHNSON CONTROLS METASYS CONTROL PANEL, AND
POWER SUPPLY COMPLETE. GIVE THESE ITEMS TO THE COR.
SEE PICTURE E7/00-GR-001.
5. DISCONNECT SMOKE DETECTOR FROM FIRE ALARM SYSTEM
AS REQUIRED AND RELOCATE IN NEW DUCT WORK AS
REQUIRED.
6. REMOVE MOTOR STARTER AND VERIFY WITH CONTROLS
CONTRACTOR IF THE ANALOG CONTROL PANEL, JOHNSON
CONTROLS METASYS CONTROL PANEL, AND POWER SUPPLY
NEED TO BE REMOVED OR IF THEY WILL BE REUSING THESE
ITEMS. IF NOT REUSED, REMOVE COMPLETE. GIVE THESE
ITEMS TO THE COR. SEE PICTURE E7/00-GR-001.
FIRST, SECOND, AND THIRD
FLOOR POWER DEMOLITION
PLANS BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-ED-11232
34 36
G12
STORAGE
G13
WASH
ROOM
G13A
TRASH
ROOM
G13B
BATTERY
STORAGE
G13C
STORAGE
G14
WOMEN
LOCKER
G15
WOMEN
TOILET
G16
MECHANICAL
ROOM
G17
EP
FEC
C O
N N
EC
TI
N G
C O
R R
ID
O
R C
O N
N
EC
TI
N
G C
O R
R
ID
O R
CONFERENCE
ROOM
G04
WORK
ROOM
G05
OFFICE
G01A
DME SUPPLY/
DISTRIBUTION
G01
ELECT
ROOM
G03
MECH.
ROOM
G02
CORRIDOR
H003
ELEVATOR
E-1
STAIRWELL
NO. 1
S1
STAIRWELL
NO. 2
S2
CHARGING
STATION
G07
STORAGE
G08
FES
STORAGE
G09A
FES
STORAGE
G09
SAFETY
OFFICE
G10
MALE
LOCKER
G11
IN-HOUSE
CONSTRUCTION/
STORAGE
G23
PROSTHETICS
STORAGE
G26
CORRIDOR
H002
OI&T
CLOSET
H002A
DOCK
AREA
CORRIDOR
H001
PROSTHETICS
STORAGE
G25
FAN COIL-3
FAN COIL-1 FAN COIL-2 FAN COIL-4
FAN COIL-7
FAN COIL-8
FAN COIL-5
FAN COIL-6
BASEMENT MECHANICAL HVAC
REVISED PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. RE-CONNECT EXISTING ELECTRICAL
POWER TO NEW FANCOIL UNIT IN
SAME LOCATION.
2. EXTEND EXISTING CIRCUIT FROM
DEMO'D FANCOIL TO NEW UNIT
LOCATION IN NEW 1/2" CONDUIT AS
REQUIRED.
3. RUN NEW #12 CONDUCTORS AND
GROUND 1/2" CONDUIT TO NEW FC-5
FROM SPARE 20 AMP CIRCUIT IN
PANEL CR AS REQUIRED.
4. INSTALL A NEW DUPLEX
RECEPTACLE NEXT TO UNIT FOR
NEW CONDENSATE PUMP,
CONNECTING TO A NEW 20 AMP
BREAKER IN EXISTING PANEL CR AS
REQUIRED.
EX PANEL CR
GENERAL NOTES:
1. ALL FIRE ALARM CONTROLS ARE
SIEMENS. DISCONNECT AND
RECONNECT ALL DEVICES AFFECTED
BY THIS PROJECT.
1 1 1
EX PANEL PE
BASEMENT ELECTRICAL
POWER REVISED PLAN
BUILDING 23
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
23-EP-1B1
35 36
H101
H102
H103
109 110 111 112
114 115 116
113A
H103A
112A
123A
106A
112B
BLDG. 25 FIRST FLOOR POWER
REVISED PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. INSTALL A NEW 30A-3P CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW FEED TO NEW
25-EAHU-1. NEW BREAKER SHALL BE
COMPATIBLE WITH EXISTING PANEL.
2. CONTROL CONTRACTOR TO EXTEND NEW
CONTROLS TO 25-EAHU-1 FROM EXISTING
CONTROL CABINET AS REQUIRED.
3. 3-#8, 1-#8 GND IN A 3/4" CONDUIT.
4. ROUTE BEST WAY ABOVE CORRIDOR CEILING.
5. NEW 25-EAHU-1 ELECTRICAL CONTROL PANEL,
PANEL PROVIDED BY AHU MANUFACTURER
AND MOUNTED BY MECHANICAL
CONTRACTOR. MOUNTED ON WALL UNDER
LOUVER. CONDUIT FROM CONTROL PANEL
OVER TO AIR HANDLER SHALL BE MOUNTED
TO THE BOTTOM OF DUCTWORK AS REQUIRED
TO KEEP THE CONDUIT A MINIMUM OF 7'-0" AFF.
H201
H203
212A
210 209
209A
209B
209C 209D
201A
207 205
208A
204D
208B
BLDG. 25 SECOND FLOOR POWER
REVISED PLAN
SCALE: 1/8" = 1'-0"
EX-PANEL-25-L1B
DOWN TO
FIRST FLOOR
UP TO SECOND
FLOOR
GENERAL NOTES:
1. EXISTING PANEL 25-L1B IS 225A,
208V/3P AND A G.E. A SERIES PANEL.
2. ALL FIRE ALARM CONTROLS ARE
SIEMENS. RECONNECT ALL DEVICES
AFFECTED BY THIS PROJECT.
Diameter
Width
He ig ht
Width
He ig ht25-EAHU-1
13 4
FIRST AND SECOND FLOOR POWER
REVISED PLANS BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-EP-1121
36 36
File details come from the government source that posted it. Updated .