Part 6A - Drawings 657-20-109JB Building 23 and 25 HVAC.pdf

PDF 6 MB Posted

Attached to
Z2DA--FCA - Replace Mechanical Equipment in Buildings 23 and 25 PN: 657-20-109JB
Solicitation number
36C25522R0021
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEGEND

F

CONTROL AND INDICATION

AIR HUMIDITY TO DCP FOR

SENSES AND TRANSMITS

G FILTER CONDITION INDICATORPRESSURE GAUGE

DUCT SMOKE DETECTORS

(FURNISHED AND WIRED TO

FIRE ALARM PANEL BY ELECTRICAL)

MONITOR RETURN AIR FOR PRODUCTS

OF COMBUSTION AND DE-ENERGIZES

SUPPLY FAN AND RETURN AIR FANSD

ECC ENGINEERING CONTROL CENTER

LOCATED IN BUILDING 25

FOR MONITORING OF

SYSTEM OPERATIONS.

DCP DISTRIBUTED CONTROL PANEL

CONTROLS OPERATION OF AIR

WITH THE SEQUENCE OF OPERATION.

HANDLING UNIT IN ACCORDANCE

DIFFERENTIAL PRESSURE SENSOR

TRANSMITS DIFFERENTIAL PRESSURE

CONDITIONS AND STATUS OF FANS.

TO DCP TO INDICATE FILTER P

SUPPLY AIR TEMPERATURE

SENSOR

SENSES AND TRANSMITS SUPPLY

AIR DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

T-2

COIL IN RESPONSE TO DCP.

V-1 CHILLED WATER TO COOLING

PROPORTIONS FLOW OFCHILLED WATER CONTROL VALVE

TYPE

TWO WAY MODULATING

REHEAT CONTROL VALVEV-3

SENSES AND TRANSMITS

VELOCITY PRESSURE TO DCP.

RETURN FANS MOTOR SPEED

IN RESPONSE TO DCP.

CONTROLS SUPPLY AND

CONTROLLER WITH MOTOR

VARIABLE SPEED MOTOR

STARTER

VPS

VSMC

VELOCITY PRESSURE SENSOR

MC MOTOR STARTER ENERGIZES MOTOR

H-2 ROOM HUMIDITY SENSOR

T-1

C O

IL

C

O O

LI

N

G C

H R

A

V-1

C H

P

VSMC

B

T-2

P

AF

TE

R

FI

LT

ER

SUPPLY

FAN

1 2 3 4 5 6

A B

INPUT

DCP

OUTPUT

(DDC)

CONTROL SCHEMATIC - COOLING ONLY - FAN COILS (FC-1,2,3,4,5,6)

VPS

PIEZO RING

FAN VOLUME

NO SCALE

2-WAY

VALVE

RETURN AIR

PROPORTIONS FLOW OF

STEAM TO PREHEAT COIL

IN RESPONSE TO DCP.

T-1

C O

IL

C

O O

LI

N

G C

H R

A

V-1

C H

P

VSMC

C

T-2

P

FI

LT

ER

SUPPLY

FAN

1 2 3 4 5 6

A B C

INPUT

DCP

OUTPUT

(DDC)

CONTROL SCHEMATIC - HEATING/COOLING - FAN COILS (FC-7,8)

VPS

PIEZO RING

FAN VOLUME

NO SCALE

2-WAY

VALVE

RETURN AIR

B

M

PS

V-3

R

EH

EA

T

C O

IL

VOLUME FANCOIL UNITS:

CONSTANT AIR

FANCOIL

SUPPLY FAN

SUPPLY AIR

REHEAT COIL - STEAM (UNITS WITH HEAT)

COOLING COIL - CHILLED WATER

FILTERS

HUMIDITY SENSORS

M

ED

IC

AL

G

AS

ES

LE

AK

D

ET

EC

TI

ON

SM

OK

E

DE

TE

CT

IO

N/

FI

RE

A

LA

RM

PU

M

P

FA

IL

UR

E

VA

CU

UM

IN

-H g

LOCATION:SERVICE:

DESCRIPTION

VETERANS

AFFAIRS

DA

M

PE

R

PO

SI

TI

ON

SU

PP

LY

A

IR

T

EM

PE

RA

TU

RE

RU

N

TI

M

E M

AI

NT

EN

AN

CE

CH

IL

L.

W

TR

. P

L'T O

PT

IM

IZ

O.

A.

D

AM

PE

R

PO

SI

TI

ON

VA

R.

S

PE

ED

D

RI

VE

M

OD

EX

HA

US

T.

A

IR

H

UM

ID

IT

Y

RH

DI

FF

. P

RE

SS

. F

T-

HD

DI

FF

. P

RE

SS

. I

N.

W

T' R.

DI

SC

HA

RG

E

AI

R

TE

M P.

ST

AT

IC

P

RE

SS

. I N.

W T'

R

IN

LE

T

PR

ES

S.

P

SI

G

IN

LE

T

TE

M P.

D

EG

. F

LO

W

L

EV

EL

ON

-O

FF

DA

M

PE

R-

OP

EN

/C

LO

SE

D

CO

NT

RO

L

VA

LV

E

CO

NT

RO

L

DA

M

PE

R

W

AT

ER

T

EM

P.

D

EG

. F

AI

R

TE

M

P.

D

EG

. F

ON

-O

FF

FR

EE

ZE

ST

AT

HI

GH

L

EV

EL

OU

TL

ET

T

EM

P.

D

EG

. F

OU

TL

ET

P

RE

SS

. P

SI

G

FL

OW

, G

PM

CF

M

A

IR

F

LO

W

EX

HA

US

T

AI

R

TE

M

P.

OU

TS

ID

E

AI

R

TE

M

P.

CO

OL

. C

OI

L

VA

LV

E

PO

SI

TI

ON

HE

AT

C

OI

L

VA

LV

E

PO

S.

O.

A.

A

IR

H

UM

ID

IT

Y

RH

DI

SC

H.

A

IR

H

UM

ID

IT

Y

RH

SP

AC

E

TE

M P.

D

EG

. F

SP

AC

E

HU

M

ID

IT

Y

RH

PO

W

ER

K

W

FR

EE

ZE

ST

AT

FA

N

FA

IL

UR

E

FI

LT

ER

H

IG

H

LI

M

IT

HI

GH

T

EM

PE

RA

TU

RE

LO

W

T

EM

PE

RA

TU

RE

HI

GH

H

UM

ID

IT

Y

LO

W

H

UM

ID

IT

Y

HI

GH

P

RE

SS

UR

E

LO

W

P

RE

SS

UR

E

HI

GH

L

EV

EL

LO

W

L

EV

EL

RU

N

TI

M

E

EC

ON

OM

IZ

ER

C

ON

TR

OL

TI

M

E

SC

HE

DU

LI

NG

OP

TI

M

UM

S

TA

RT

/S

TO

P

EV

EN

T

PR

OG

RA

M

RE

SE

T

AU

TO

M

AT

IC

R

ES

TA

RT

GR

AP

HI

CS

SM

OK

E

DE

TE

CT

IO

N

AI

R

VO

LU

M E

CO

NT

RO

L

PR

ES

SU

RE

MEDICAL

CENTER

BUILDING 23

INTERIOR

NOTES: 1. SIGNAL VIA UNIT-MOUNTED PITOT TUBE. SEE DETAIL.

2. SEE PLANS FOR T'STAT AND TERMINAL UNIT LOCATIONS.

3. EXISTING FLOOR PLAN GRAPHICS AND ASSOCIATED

EQUIPMENT RELATIONSHIPS SHALL BE UPDATED TO

REFLECT AS BUILT CONDITIONS.

SYSTEM POINT

EX

HA

US

T

DA

M

PE

R

PO

SI

TI

ON

RE

SE

T W

AT

ER

T

EM

P.

TR

EN

DI

NG

(SEE NOTE 3)

T-1 RETURN AIR TEMPERATURE

SENSOR

T-3 ROOM TEMPERATURE SENSOR

SENSES AND TRANSMITS SUPPLY

AIR DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

SENSES AND TRANSMITS SUPPLY

AIR DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

T-3

H-1

T-3

H-1

MECHANICAL CONTROLS,

BUILDING 25

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-005

BID DOCUMENTS

15 36

F

FSD-1 SUPPLY AIR FIRE/SMOKE DAMPER

CLOSES WHEN EF IS SHUT

OFF OR WHENEVER SMOKE

IS DETECTED BY F SD.

OUTSIDE AIR HUMIDITY SENSORH-1

CONTROL AND INDICATION

AIR HUMIDITY TO DCP FOR

SENSES AND TRANSMITS SUPPLY

G FILTER CONDITION INDICATORPRESSURE GAUGE

DUCT SMOKE DETECTORS

(FURNISHED AND WIRED TO

FIRE ALARM PANEL BY ELECTRICAL)

MONITOR RETURN AIR FOR PRODUCTS

OF COMBUSTION AND DE-ENERGIZES

SUPPLY FAN AND RETURN AIR FANSD

ECC ENGINEERING CONTROL CENTER

LOCATED IN BUILDING 25

FOR MONITORING OF

SYSTEM OPERATIONS.

DCP DISTRIBUTED CONTROL PANEL

CONTROLS OPERATION OF AIR

WITH THE SEQUENCE OF OPERATION.

HANDLING UNIT IN ACCORDANCE

DIFFERENTIAL PRESSURE SENSOR

TRANSMITS DIFFERENTIAL PRESSURE

CONDITIONS AND STATUS OF FANS.

TO DCP TO INDICATE FILTER

AFMS AIR FLOW MEASURING DEVICE

MONITORS AIR FLOW RATE

FOR TRANSMITTAL TO DCP.

PROVIDES VELOCITY PRESSURE

STATIC PRESSURE SENSORS

(SEE FLOOR PLANS FOR

LOCATION)

SPS-

2,3,4

P

SENSOR

HIGH LIMIT STATIC PRESSURE SENSES AND TRANSMITS DUCT

STATIC PRESSURE NEAR AHU TOSPS-1

SUPPLY AIR TEMPERATURE

SENSOR

SENSES AND TRANSMITS SUPPLY

AIR DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

SENSOR

SENSES AND TRANSMITS OUTSIDE

AIR DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

T-5

T-1

AIR TEMPERATURE SENSOR

LEAVING PREHEAT STEAM COIL AIR

DCP FOR CONTROL AND INDICATION.

AIR DRY BULB TEMPERATURE TO

SENSES AND TRANSMITS PREHEAT

T-2

T-3

V-2

OUTSIDE AIR TEMPERATURE

SENSOR

AIR TEMPERATURE

LEAVING COOLING COIL

DCP FOR INDICATION ONLY.

COIL DRY BULB TEMPERATURE TO

SENSES AND TRANSMITS COOLING

COIL IN RESPONSE TO DCP.

V-1 CHILLED WATER TO COOLING

PROPORTIONS FLOW OFCHILLED WATER CONTROL VALVE

TYPE

TWO WAY MODULATING

STEAM CONTROL VALVE

MODULATING TWO WAY

PROPORTIONS FLOW OF

STEAM TO PREHEAT COIL

IN RESPONSE TO DCP.

REHEAT CONTROL VALVEV-3

SENSES AND TRANSMITS

VELOCITY PRESSURE TO DCP.

RETURN FANS MOTOR SPEED

IN RESPONSE TO DCP.

CONTROLS SUPPLY AND

CONTROLLER WITH MOTOR

VARIABLE SPEED MOTOR

STARTER

VPS

VSMC

VELOCITY PRESSURE SENSOR

OUTSIDE AIR DAMPER (MODULATING)D-1

MODULATING DAMPER FOR

PREHEAT COILD-2

MC MOTOR STARTER ENERGIZES MOTOR

F-1 FREEZE STAT

T-4

SENSOR

AIR TEMPERATURE

LEAVING HEATING COIL

DCP FOR INDICATION ONLY.

COIL DRY BULB TEMPERATURE TO

SENSES AND TRANSMITS HEATING

AFMS AIR FLOW METER STATION SEE SCHEDULES, SHEET MQ002

H-2 SUPPLY AIR HUMIDITY SENSOR

T- 1 5

P

C

PR

E-

FIL

TE

R

M

PS

V-2

T-2PR

EH

EA

T

ST

EA

M C

O

IL

C O

IL

C

O O

LI

N

G C

H R

D

V-1

C H

T-4

P

VSMC

F

T-5

P

AF

TE

R

FI

LT

ER

SPS-1 F

J

M 19

SPS-4

SUPPLY

FAN

LOCATE OUTSIDE

UNDER SHIELD 1 2 3 4 5 6 7 8 9 10 11 12 13 14

A B C D E F G

INPUT

DCP

OUTPUT

(DDC)

CONTROL SCHEMATIC RTU-1

VPS

AF

M

S

M

A

VPS

H

D-1

SD

PIEZO RING

FAN VOLUME

NO SCALE

M

B

D-2

2-WAY

VALVE

OUTSIDE AIR

F1

E

M

PS

V-3

R

EH

EA

T

C O

IL

T-3

LOCATE ON

EXTERIOR OF

BUILDING.

COORDINATE

WITH COR.

T-7

AIR TEMPERATURE SENSOR

DUCT SENSES AND TRANSMITS

DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

CONTROL AND INDICATION

AIR HUMIDITY TO DCP FOR

SENSES AND TRANSMITS RETURN

H-1

PROPORTIONS FLOW OF

STEAM TO PREHEAT COIL

IN RESPONSE TO DCP.

T-8

AIR TEMPERATURE SENSOR

DUCT SENSES AND TRANSMITS

DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

T-6

AIR TEMPERATURE SENSOR

DUCT SENSES AND TRANSMITS

DRY BULB TEMPERATURE TO

DCP FOR CONTROL AND INDICATION.

T-8

I

M

T-7

H

M

T-6

LOCATE IN

DUCT

LOCATE IN

DUCT

LOCATE IN

DUCT

1ST FLOOR

2ND FLOOR

3RD FLOOR

D-3

D-4

D-5

I J

H-2

K

H U

M

ID

IF

IE

R

LP

SV-4

MODULATING DAMPER FOR FLOOR

CONTROL

D-3

MODULATING DAMPER FOR FLOOR

CONTROL

D-4

MODULATING DAMPER FOR FLOOR

CONTROLD-5

HUMIDIFIER STEAM CONTROL

VALVE, MODULATING TWO-WAY

V-4

PROPORTIONS FLOW OF

STEAM TO HUMIDIFIER

IN RESPONSE TO DCP.

Air Handling Unit 25-EAHU

A. General:

1. Unit is normally started and stopped by the DCP or remotely at the ECC. H-O-A switch shall be kept in the “AUTO” position. “HAND” and “OFF” shall be used only for maintenance. When unit is “OFF”, motorized dampers D-1 and FSD-1 shall be fully closed. When unit is “ON” dampers D-1 and FSD-1 shall be fully open.

2. Fan shall operate continuously.

B. Air Flow Control

1. The supply air flow shall be controlled by the DCP modulating supply fan variable speed motor controller (VSMC) to maintain the duct static pressure setpoint (set at 1.25 inches static pressure) as sensed by SPS static pressure sensor (see plans for location). Fan speed shall not be allowed to drop below 2,000 CFM output air flow per Zone Damper (damper at each floor) D-3, D-4, and D-5. Each floor is to get 2,000 CFM.

2. The DCP using high pressure sensor SPS-2 located at the supply fan discharge shall prevent the supply fan from developing over 4.0” w.g. of static pressure. If static pressure at SPS-2 exceeds 4.0” w.g. supply fan shall shut “OFF” and an alarm sent. If static pressure at SPS-2 falls below 0.35” w.g. an alarm shall be sent.

3. Outside air flow shall be measured by an air flow measuring station located in the respective ducts.

C.Filters

1. Pre filter differential pressure shall be monitored at the DCP terminal in addition to local manometer, service notice shall be displayed with differential pressure exceeds 0.65” wg., alarm shall sound if differential pressure exceeds 1.0” wg.

2. Post filter differential pressure shall be monitored at the DCP terminal in addition to local manometer, service notice shall be displayed with differential pressure exceeds 1.25” wg., alarm shall sound if differential pressure exceeds 1.5” wg.

D. Heating and Cooling

1. Steam I FB steam preheat coil 2-way control valve (no) shall be modulated in sequence with face and bypass damper to maintain average coil discharge temperature of 40f. Should coil discharge temperature fall below 35f or rise above 55f, alarm shall sound at the DCP terminal. Should discharge air temperature fall below 35f, steam valve shall open 100% and second alarm notification shall sound.

2. Chilled water-cooling coil 2-way control valve (nc) and Steam reheat coil 2-way control valve shall be modulated to maintain coil discharge temperature at its setting of neutral air at 70f and 60% rH (maximum). Supply air temperature shall be monitored at the operator's terminal. Should discharge air temperature deviate from set point by 5f or 10% rH, an alarm shall sound at the CFP terminal.

E. Humidifier

1. Supply air duct humidity sensor shall modulate 2-way steam humidifier control valve (nc) to maintain supply air humidity at 45% rh. Supply air humidity shall be monitored at the DCP and ECC. Should discharge relative humidity exceed 90% rh alarm shall be sound at the DCP and ECC, humidification shall be discontinued.

Should exhaust air humidity fall below 25% rh, alarm shall sound at the DCP and ECC.

2. Should high level condensate be detected in the drain pan, steam control valve shall close, and alarm shall sound at the DCP and ECC.

F. Freeze Protection

1. If the air temperature as sensed by T-2 falls below 40f, an alarm signal shall be indicated at the DCP and ECC.

If this temperature falls below 35f, the unit supply fan shall shut “OFF” and damper D-1 shall fully close, valve V-1, V-2, and V-3 shall fully open. A critical alarm shall be indicated at the DCP and ECC.

G. Automatic Shutdown / Restart

1. When smoke is detected by duct smoke detectors, the supply fan shall shut “OFF” and an alarm shall be transmitted to the fire alarms system. For alarm purposes only, all dampers (D-1, D-3, D-4, D-5) in the supply ducts shall close. Supply fan shall restart, and fire/smoke dampers shall open when fire alarm circuit is reset.

H. Emergency Constant Speed Operation

1. On all VSMC fans in VAV systems upon failure of the VSMC the fans shall be started/stopped manually at the CDP or the ECC through the by-pass starter. Fans shall then be operated at the constant design speed.

General Information

A. All values shall be adjustable.

B. Existing floor plan graphics and associated equipment relationships shall be updated to reflect as-built conditions.

C. Coordinate all controls, sequences, and points list with Johnson Controls, the local VA Facility vendor, the COR, and VA maintenance personnel.

P

PR

E-

FIL

TE

R

17 18 19

SPS-3

SPS-2

2-POSITION FROM DCP LOCATED

IN AHU.

SENSES AND TRANSMIT BUILDING

FLOORS STATIC PRESSURE TO DCP.

UNITS SHALL BE REMOTE

MECHANICAL CONTROLS,

BUILDING 25

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-006

16 36

VOLUME SYSTEM

VARIABLE AIR

25-EAHU-1

SUPPLY FAN

SUPPLY AIR

PREHEAT COIL - STEAM

COOLING COIL - CHILLED WATER

PRE-FILTERS

AFTER FILTER

OUTSIDE AIR

HUMIDITY SENSORS

M

ED

IC

AL

G

AS

ES

LE

AK

D

ET

EC

TI

ON

SM

OK

E

DE

TE

CT

IO

N/

FI

RE

A

LA

RM

PU

M

P

FA

IL

UR

E

VA

CU

UM

IN

-H g

LOCATION:SERVICE:

DESCRIPTION

VETERANS

AFFAIRS

DA

M

PE

R

PO

SI

TI

ON

SU

PP

LY

A

IR

T

EM

PE

RA

TU

RE

RU

N

TI

M

E M

AI

NT

EN

AN

CE

CH

IL

L.

W

TR

. P

L'T O

PT

IM

IZ

O.

A.

D

AM

PE

R

PO

SI

TI

ON

VA

R.

S

PE

ED

D

RI

VE

M

OD

EX

HA

US

T.

A

IR

H

UM

ID

IT

Y

RH

DI

FF

. P

RE

SS

. F

T-

HD

DI

FF

. P

RE

SS

. I

N.

W

T' R.

DI

SC

HA

RG

E

AI

R

TE

M P.

ST

AT

IC

P

RE

SS

. I N.

W T'

R

IN

LE

T

PR

ES

S.

P

SI

G

IN

LE

T

TE

M P.

D

EG

. F

LO

W

L

EV

EL

ON

-O

FF

DA

M

PE

R-

OP

EN

/C

LO

SE

D

CO

NT

RO

L

VA

LV

E

CO

NT

RO

L

DA

M

PE

R

W

AT

ER

T

EM

P.

D

EG

. F

AI

R

TE

M

P.

D

EG

. F

ON

-O

FF

FR

EE

ZE

ST

AT

HI

GH

L

EV

EL

OU

TL

ET

T

EM

P.

D

EG

. F

OU

TL

ET

P

RE

SS

. P

SI

G

FL

OW

, G

PM

CF

M

A

IR

F

LO

W

EX

HA

US

T

AI

R

TE

M

P.

OU

TS

ID

E

AI

R

TE

M

P.

CO

OL

. C

OI

L

VA

LV

E

PO

SI

TI

ON

HE

AT

C

OI

L

VA

LV

E

PO

S.

O.

A.

A

IR

H

UM

ID

IT

Y

RH

DI

SC

H.

A

IR

H

UM

ID

IT

Y

RH

SP

AC

E

TE

M P.

D

EG

. F

SP

AC

E

HU

M

ID

IT

Y

RH

PO

W

ER

K

W

FR

EE

ZE

ST

AT

FA

N

FA

IL

UR

E

FI

LT

ER

H

IG

H

LI

M

IT

HI

GH

T

EM

PE

RA

TU

RE

LO

W

T

EM

PE

RA

TU

RE

HI

GH

H

UM

ID

IT

Y

LO

W

H

UM

ID

IT

Y

HI

GH

P

RE

SS

UR

E

LO

W

P

RE

SS

UR

E

HI

GH

L

EV

EL

LO

W

L

EV

EL

RU

N

TI

M

E

EC

ON

OM

IZ

ER

C

ON

TR

OL

TI

M

E

SC

HE

DU

LI

NG

OP

TI

M

UM

S

TA

RT

/S

TO

P

EV

EN

T

PR

OG

RA

M

RE

SE

T

AU

TO

M

AT

IC

R

ES

TA

RT

GR

AP

HI

CS

SM

OK

E

DE

TE

CT

IO

N

AI

R

VO

LU

M E

CO

NT

RO

L

PR

ES

SU

RE

MEDICAL

CENTER

BUILDING 25

EXTERIOR

NOTES: 1. SIGNAL VIA UNIT-MOUNTED PITOT TUBE. SEE DETAIL.

2. SEE PLANS FOR T'STAT AND TERMINAL UNIT LOCATIONS.

3. EXISTING FLOOR PLAN GRAPHICS AND ASSOCIATED

EQUIPMENT RELATIONSHIPS SHALL BE UPDATED TO

REFLECT AS BUILT CONDITIONS.

SYSTEM POINT

MAKE UP AIR UNIT

DU

CT

D

AM

PE

R

PO

SI

TI

ON

RE

SE

T W

AT

ER

T

EM

P.

TR

EN

DI

NG

(SEE NOTE 3)

1ST FLOOR ZONE DAMPER

2ND FLOOR ZONE DAMPER

3RD FLOOR ZONE DAMPER

HUMIDIFIER

HU

M

ID

IF

IE

R

VA

LV

E

PO

SI

TI

ON

1ST FLOOR STATIC PRESSURE

2ND FLOOR STATIC PRESSURE

3RD FLOOR STATIC PRESSURE

MECHANICAL CONTROLS

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-007

17 36

DESIGN ALTITUDE 538 FT.

AIR CONDITIONING DESIGN DATA-

%RH.

INSIDE

D.B.W.B.D.B.

OUTSIDE

SUMMER

D.B. W.B.

DESIGN

AREA OUTSIDE

D.B.

INSIDE

WINTER

%RH.

50693.04.096 75 5069LAB AREAS

OFFICE AREAS 40703.04.0507596 75

PIPING INSULATION SCHEDULE (INDOOR)

MECHANICAL SCHEDULES

BUILDING 23

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

23-MG-601

18 36

File details come from the government source that posted it. Updated .