DUCT LEAKAGE CLASSIFICATION AND ALLOWABLE LEAKAGE
SEAL CLASSDUCT PRESSURE
C
APPLICABLE SEALINGS SMACNA LEAKAGE CLASS
CLASS, W.G.
3" B TRAVERSE JOINTS AND SEAMS 12
4", 6", 10" A JOINTS, SEAMS AND ALL WALL PENETRATIONS6 3
12TRAVERSE JOINTS ONLY
RECTANGULAR
DUCT DUCT
ROUND
FAN
SYSTEM
REMARKSS.P.
DROPMAX.MIN.
CFM
HW
LOCATION
AIR FLOW MEASURING DEVICES
UNIT
NO.
DUCT SIZE
TYPE
DUCT
N 2"
P 4"
SUPPLY
FROM ROOM OUTLETS TO EXHAUST FAN.
FROM TERMINAL BOXES TO ROOM OUTLETS.
2"NCOIL.
FROM OUTSIDE AIR LOUVER OR RETURN SMOKE DAMPER TO
CLASS W.G.
PRESSURE
MINUMUM
PRESSURE
OR NEGATIVE (N)
POSITIVE (P)
DUCT INVOLVEDFAN TYPE
DUCT PRESSURE CLASSES
FROM FAN DISCHARGE TO TERMINAL BOXES.
AFMS-OA1 60 32 O.A. 25-EAHU-1.06
1. MOUNT AIR FLOW STATIONS AT INLETS TO FAN USING PROBE ARRAY DESIGNED FOR THE PURPOSE.
P 2"
1/2", 1", 2"
NOTE:
N 2"FROM RA GRILLE TO AHU INLET
DESIGN ALTITUDE 538 FT.
AIR CONDITIONING DESIGN DATA-
%RH.
INSIDE
D.B.W.B.D.B.
OUTSIDE
SUMMER
D.B. W.B.
DESIGN
AREA OUTSIDE
D.B.
INSIDE
WINTER
%RH.
50693.04.096 75 5069LAB AREAS
OFFICE AREAS 40703.04.05075
DUCTWORK -
FAN
EXHAUST
FAN
RETURN
AIR FAN
96 75
100% O.A. AIR HANDLING UNIT SCHEDULE - (BASIS OF DESIGN)
PIPING INSULATION SCHEDULE (INDOOR)
MECHANICAL SCHEDULES
BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MG-602
BID DOCUMENTS
19 36
BASEMENT MECHANICAL PIPING
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. DISCONNECT CHWS&R PIPING AND CONDENSATE DRAIN FROM FAN COIL,
PREPARE PIPING FOR NEW UNITS AS REQUIRED.
2. REMOVE FAN COIL AND PREPARE PIPING AND SPACE FOR INSTALLATION OF
NEW FAN COIL.
3. DEMO CHWS&R BRANCH PIPING BACK TO THIS POINT AND CAP.
4. REMOVE FAN COIL, CONTROLS, HANGERS COMPLETE.
5. DISCONNECT FAN COIL FROM EXISTING SA PLENUM AND DUCTWORK AS
REQUIRED TO REPLACE FAN COIL.
6. DISCONNECT PIPING AND CAP IN THIS LOCATION.
7. SEE ENLARGED PLAN, THIS SHEET, FOR MORE DETAIL.
8. REMOVE EXISTING UNIT HEATER AND CONTROLS COMPLETE.
9. EXISTING PIPING TO REMAIN; TYPICAL.
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING MECHANICAL
EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND DUCTWORK WAS OBTAINED
FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY FIELD OBSERVATION, HOWEVER,
ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING
THE LOCATION OF THE EXISTING MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING,
PLUMBING AND DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S)
AND DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT HAS
BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER, ALL EXISTING
WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS
OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN
THESE PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE
ENGINEER FOR VERIFICATION AND/OR CORRECTION.
MEN
TOILET
G12
STORAGE
G13
WASH
ROOM
G13A
TRASH
ROOM
G13B
BATTERY
STORAGE
G13C
STORAGE
G14
WOMEN
LOCKER
G15
WOMEN
TOILET
G16
MECHANICAL
ROOM
G17
EP
FEC
C O
N N
EC
TI
N G
C O
R R
ID
O
R C
O N
N
EC
TI
N
G C
O R
R
ID
O R
CONFERENCE
ROOM
G04
WORK
ROOM
G05
OFFICE
G01A
DME SUPPLY/
DISTRIBUTION
G01
ELECT
ROOM
G03
MECH.
ROOM
G02
CORRIDOR
H003
ELEVATOR
E-1
STAIRWELL
NO. 1
S1
STAIRWELL
NO. 2
S2
CHARGING
STATION
G07
STORAGE
G08
FES
STORAGE
G09A
FES
STORAGE
G09
SAFETY
OFFICE
G10
MALE
LOCKER
G11
IN-HOUSE
CONSTRUCTION/
STORAGE
G23
PROSTHETICS
STORAGE
G26
CORRIDOR
H002
OI&T
CLOSET
H002A
DOCK
AREA
CORRIDOR
H001
PROSTHETICS
STORAGE
G25
FEC
CONFERENCE
ROOM
G04
WORK
ROOM
G05
ENLARGED G04 & G05 MECHANICAL
PIPING DEMO PLAN
SCALE: 1/4" = 1'-0"
GENERAL PLAN NOTES:
1. RE-INSULATE EXISTING PIPING THAT HAD PIPE INSULATION ABATED. SEE HA
SERIES DRAWINGS FOR MORE INFORMATION ON ABATED PIPING. ALL WALL
PENETRATIONS TO BE FIRE STOPPED. SEE SPECIFICATION SECTION 07 84 00.
2. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING THE EE NUMBERS OF ALL
EQUIPMENT REMOVED FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT, THE CONTRACTOR WILL
PRESENT THE COR WITH A LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING, MOVING, AND
STORING FURNITURE AND MOVABLE EQUIPMENT, AND RETURNING IT TO THE
SPACE WHEN WORK IS COMPLETE. ANY NON-MOVABLE EQUIPMENT IN THE
SPACE WILL BE COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT DAMAGE
FROM DUST AND WATER DAMAGE AT ALL TIMES DURING CONSTRUCTION.
BASEMENT MECHANICAL
PIPING DEMOLITION PLAN
BUILDING 23
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
23-MD-1B1
20 36
H101H103
109 110 111 112
114 115 116
113A
H103A
112A
112B
H103A
BLDG. 25 ENLARGED FIRST FLOOR
MECHANICAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
PLAN NOTES:
1. DEMO EXISTING AHU COMPLETE INCLUDING HANGER. UNIT
IS SUSPENDED FROM CEILING.
2. DISCONNECT AND REMOVE STEAM AND CONDENSATE
PIPING FROM AHU. CAP ALL PIPING. SEE DETAIL
F7/25-MP-112.
3. DEMO OA DUCT CONNECTED TO LOUVER COMPLETE.
PREPARE LOUVER FOR NEW DUCT / FILTER CONNECTION.
4. DEMO SUPPLY DUCT TO TRANSITION. 30"X 12" DUCT
SHALL REMAIN. PREPARE FOR CONNECTION TO NEW
SUPPLY DUCT.
5. AHU HANGERS ARE EXISTING TO BE REMOVED COMPLETE.
6. DEMO CHILLED WATER SUPPLY AND RETURN
CONNECTIONS BACK TO RESPECTIVE MAINS AND CAP.
7. DEMO STEAM PIPING BACK TO MAIN AND CAP.
8. DEMO STEAM CONDENSATE BACK TO MAIN AND CAP. SEE
DETAIL F7/25-MP-112.
9. EXISTING PIPING AND EQUIPMENT ARE EXISTING TO
REMAIN, UNLESS NOTED OTHERWISE.
10. EXISTING FIRE PROTECTION DEVICES TO BE REMOVED
AND RELOCATED IN NEW DUCTWORK AS REQUIRED.
BLDG. 25 FIRST FLOOR MECHANICAL
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
FIELD VERIFY:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK WAS OBTAINED FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY
FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT
AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S) AND
DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT
HAS BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER,
ALL EXISTING WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT
LOCATIONS, DIRECTIONS OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING
CONSTRUCTION. ANY CONFLICT BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER FOR
VERIFICATION AND/OR CORRECTION.
C
C
SEE ENLARGED
PLAN C7
EX 30"X 12"
EXISTING LPS
CHWS
CHWR
EX-CHWS
PUMP
EX-CHWS
PUMP
GENERAL PLAN NOTES:
1. RE-INSULATE EXISTING PIPING THAT HAD PIPE
INSULATION ABATED. SEE HA SERIES DRAWINGS
FOR MORE INFORMATION ON ABATED PIPING.
2. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING
THE EE NUMBERS OF ALL EQUIPMENT REMOVED
FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT,
THE CONTRACTOR WILL PRESENT THE COR WITH A
LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
3. THE CONTRACTOR IS RESPONSIBLE FOR
PROTECTING, MOVING, AND STORING FURNITURE
AND MOVABLE EQUIPMENT, AND RETURNING IT TO
THE SPACE WHEN WORK IS COMPLETE. ANY
NON-MOVABLE EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT
DAMAGE FROM DUST AND WATER DAMAGE AT ALL
TIMES DURING CONSTRUCTION.
EXISTING LOUVER
TO REMAIN
FIRST FLOOR HVAC AND
MECHANICAL PIPING
DEMOLITION PLAN BULDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MD-112
21 36
H203
212A
H201
H203
212A
210 209
209A
209B
209C 209D
207 205
208A
208B
PLAN NOTES:
1. DEMO EXISTING AHU. UNIT IS
SUSPENDED FROM CEILING.
EX 16"X 14" SUPPLY
DUCT
MECHANICAL PIPING
DETAIL HEATING SIDE
BLDG. 25 SECOND FLOOR
MECHANICAL DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
PLAN NOTES:
1. DEMO EXISTING AHU COMPLETE INCLUDING
HANGERS.
2. DISCONNECT AND REMOVE STEAM AND
CONDENSATE PIPING FROM AHU. CAP AT RISERS.
INSULATE ALL CAPS.
3. DEMO CONNECTED DUCT COMPLETE.
4. DEMO SUPPLY DUCT TO TRANSITION. 30"X 12" DUCT
SHALL REMAIN. PREPARE FOR CONNECTION TO NEW
SUPPLY DUCT.
5. DEMO CHWS, CHWR, AND COOLING CONDENSATE TO
THIS POINT AND CAP. INSULATE ALL CAPS.
6. DEMO DUCTWORK COMPLETE.
7. EXISTING WINDOW/LOUVER TO REMAIN. BLANK OFF
LOUVER WITH SHEET METAL THAT IS INSULATED
WITH 2" THICK BEARD INSULATION.
8. EXISTING PIPING TO REMAIN.
9. DEMO PIPING FROM EXISTING AHU ON THIS FLOOR.
CAP AT THIS POINT.
10. EXISTING FIRE PROTECTION DEVICES TO BE
REMOVED AND RELOCATED IN NEW DUCTWORK AS
REQUIRED.
BLDG. 25 SECOND FLOOR
MECHANICAL DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
SEE ENLARGED
PLAN C7
C
C
FIELD VERIFY:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK WAS OBTAINED FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY
FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT
AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S) AND
DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT
HAS BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER,
ALL EXISTING WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT
LOCATIONS, DIRECTIONS OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING
CONSTRUCTION. ANY CONFLICT BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER FOR
VERIFICATION AND/OR CORRECTION.
EX SUPPLY AIR
DUCT
MECHANICAL PIPING
DETAIL COOLING SIDE
GENERAL PLAN NOTES:
1. RE-INSULATE EXISTING PIPING THAT HAD PIPE
INSULATION ABATED. SEE HA SERIES DRAWINGS
FOR MORE INFORMATION ON ABATED PIPING.
2. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING
THE EE NUMBERS OF ALL EQUIPMENT REMOVED
FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT,
THE CONTRACTOR WILL PRESENT THE COR WITH A
LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
3. THE CONTRACTOR IS RESPONSIBLE FOR
PROTECTING, MOVING, AND STORING FURNITURE
AND MOVABLE EQUIPMENT, AND RETURNING IT TO
THE SPACE WHEN WORK IS COMPLETE. ANY
NON-MOVABLE EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT
DAMAGE FROM DUST AND WATER DAMAGE AT ALL
TIMES DURING CONSTRUCTION.
SECOND FLOOR HVAC AND
MECHANICAL PIPING DEMOLITION
PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MD-123
22 36
303A
304 305 306
308A
308B 308C
309 310
312304A 307A
309A
BLDG. 25 THIRD FLOOR MECHANICAL
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
303A
304 305 306 304A
BLDG. 25 THIRD FLOOR MECHANICAL
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
FIELD VERIFY:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK WAS OBTAINED FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY
FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE NOT
AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE EXISTING
MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND
DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S) AND
DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT
HAS BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER,
ALL EXISTING WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT
LOCATIONS, DIRECTIONS OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING
CONSTRUCTION. ANY CONFLICT BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE ENGINEER FOR
VERIFICATION AND/OR CORRECTION.
SEE ENLARGED
PLAN C7
C
C
PLAN NOTES:
EX 16"X 14" SUPPLY
DUCT
PLAN NOTES:
1. DEMO EXISTING AHU. UNIT IS
SUSPENDED FROM CEILING.
MECHANICAL PIPING
DETAIL HEATING SIDE
MECHANICAL PIPING
DETAIL COOLING SIDE
GENERAL PLAN NOTES:
1. RE-INSULATE EXISTING PIPING THAT HAD PIPE
INSULATION ABATED. SEE HA SERIES DRAWINGS
FOR MORE INFORMATION ON ABATED PIPING.
2. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING
THE EE NUMBERS OF ALL EQUIPMENT REMOVED
FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT,
THE CONTRACTOR WILL PRESENT THE COR WITH A
LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
3. THE CONTRACTOR IS RESPONSIBLE FOR
PROTECTING, MOVING, AND STORING FURNITURE
AND MOVABLE EQUIPMENT, AND RETURNING IT TO
THE SPACE WHEN WORK IS COMPLETE. ANY
NON-MOVABLE EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT
DAMAGE FROM DUST AND WATER DAMAGE AT ALL
TIMES DURING CONSTRUCTION.
1. DEMO EXISTING AHU COMPLETE INCLUDING
HANGERS.
2. DISCONNECT AND REMOVE STEAM AND
CONDENSATE PIPING FROM AHU. CAP AT RISERS.
INSULATE ALL CAPS.
3. DEMO CONNECTED DUCT COMPLETE.
4. DEMO SUPPLY DUCT TO TRANSITION. 30"X 12" DUCT
SHALL REMAIN. PREPARE FOR CONNECTION TO NEW
SUPPLY DUCT.
5. DEMO CHWS, CHWR, AND COOLING CONDENSATE TO
THIS POINT AND CAP. INSULATE ALL CAPS.
6. DEMO DUCTWORK COMPLETE.
7. EXISTING WINDOW/LOUVER TO REMAIN. BLANK OFF
LOUVER WITH SHEET METAL THAT IS INSULATED
WITH 2" THICK BEARD INSULATION.
8. EXISTING PIPING TO REMAIN.
9. DEMO PIPING FROM EXISTING AHU ON THIS FLOOR.
CAP AT THIS POINT.
10. EXISTING FIRE PROTECTION DEVICES TO BE
REMOVED AND RELOCATED IN NEW DUCTWORK AS
REQUIRED.
THIRD FLOOR HVAC AND
MECHANICAL PIPING
DEMOLITION PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MD-134
23 36
MEN
TOILET
G12
STORAGE
G13
WASH
ROOM
G13A
TRASH
ROOM
G13B
BATTERY
STORAGE
G13C
STORAGE
G14
WOMEN
LOCKER
G15
WOMEN
TOILET
G16
MECHANICAL
ROOM
G17
EP
FEC
C O
N N
EC
TI
N G
C O
R R
ID
O
R C
O N
N
EC
TI
N
G C
O R
R
ID
O R
CONFERENCE
ROOM
G04
WORK
ROOM
G05
OFFICE
G01A
DME SUPPLY/
DISTRIBUTION
G01
ELECT
ROOM
G03
MECH.
ROOM
G02
CORRIDOR
H003
ELEVATOR
E-1
STAIRWELL
NO. 1
S1
STAIRWELL
NO. 2
S2
CHARGING
STATION
G07
STORAGE
G08
FES
STORAGE
G09A
FES
STORAGE
G09
SAFETY
OFFICE
G10
MALE
LOCKER
G11
IN-HOUSE
CONSTRUCTION/
STORAGE
G23
PROSTHETICS
STORAGE
G26
CORRIDOR
H002
OI&T
CLOSET
H002A
DOCK
AREA
CORRIDOR
H001
PROSTHETICS
STORAGE
G25
BASEMENT MECHANICAL
HVAC REVISED PLAN
1. LOCATE UNIT AT APPROXIMATELY 7'-6" AFF TO
BOTTOM OF UNIT IN THIS APPROXIMATE OPEN
SPACE ON WALL.
2. RECONNECT THIS UNIT TO EXISTING SA PLENUM
AND DUCTWORK AS REQUIRED.
3. NEW UNIT IN EXISTING LOCATION; TYPICAL UNLESS
NOTED OTHERWISE
GENERAL PLAN NOTES:
1. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING
THE EE NUMBERS OF ALL EQUIPMENT REMOVED
FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT,
THE CONTRACTOR WILL PRESENT THE COR WITH A
LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
2. THE CONTRACTOR IS RESPONSIBLE FOR
PROTECTING, MOVING, AND STORING FURNITURE
AND MOVABLE EQUIPMENT, AND RETURNING IT TO
THE SPACE WHEN WORK IS COMPLETE. ANY
NON-MOVABLE EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT
DAMAGE FROM DUST AND WATER DAMAGE AT ALL
TIMES DURING CONSTRUCTION.
BASEMENT MECHANICAL
REVISED PLAN BUILDING 23
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
23-MH-1B1
24 36
BLDG. 25 FIRST FLOOR
MECHANICAL REVISED PLAN
SCALE: 1/4" = 1'-0"
PLAN NOTES:
1. MOTORIZED DAMPER AND MANUAL VOLUME DAMPER; TYPICAL. SEE DETAIL
B8/25-MH-112.
2. FIRE DAMPER AT WALL PENETRATION AND 14"x 14" DUCT ACCESS DOOR ON
SIDE OF DUCT IN MECH. ROOM.
3. CONNECT NEW DUCT TO EXISTING 30"X 12" DUCT TRANSITION IN THIS AREA
AS REQUIRED. INSTALL 14"x 14' ACCESS DOOR IN BOTTOM OF DUCT.
4. SIDE MOUNTED PRE-FILTER SECTION. SEE AIR FILTER SCHEDULE.
5. TRANSITION FROM FAN SUPPLY UP TO 34'x 18".
6. TRANSITION FROM 32"x 36" TO 18"x 36'.
7. 44"x67"x6" O.A. PLENUM ON NECK OF LOUVER.
8. SAW CUT FLOOR. CUT SHALL BE CENTERED ON CENTER OF CONCRETE PAN
BETWEEN CONCRETE WEBS; TYPICAL OF ALL FLOORS.
9. ACCESS PANEL.
10. DUCT TO BE MOUNTED ABOVE LIGHT FIXTURES AND BELOW FAN COIL
DUCTWORK. THIS WILL REQUIRE FIRE SPRINKLER PIPING, HANGERS, MISC.
ELECTRICAL CONDUIT TO BE RELOCATED.
11. 25-EAHU-1 FACTORY POWER CONTROL TERMINAL PANEL TO BE LOCATED ON
WALL ACROSS FROM AHU, UNDER LOUVER.
12. FLOOR PRESSURE SENSOR LOCATED ABOVE FINISHED CEILING, MOUNTED
TO WALL FOR FIRST FLOOR.
GENERAL PLAN NOTES:
1. SEE ELEVATION PLANS FOR MORE DETAILS, SHEET 25-MH-201.
2. EVERYTHING SHOWN IS NEW UNLESS OTHERWISE NOTED.
3. THE CONTRACTOR IS RESPONSIBLE FOR TRACKING THE EE NUMBERS OF ALL
EQUIPMENT REMOVED FROM THE SPACE AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE PROJECT, THE CONTRACTOR WILL
PRESENT THE COR WITH A LIST OF ALL EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
4. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING, MOVING, AND STORING
FURNITURE AND MOVABLE EQUIPMENT, AND RETURNING IT TO THE SPACE WHEN
WORK IS COMPLETE. ANY NON-MOVABLE EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO PREVENT DAMAGE FROM DUST AND
WATER DAMAGE AT ALL TIMES DURING CONSTRUCTION.
5. SEE DUCT CONNECTION DETAILS ON SHEET 00-MG-002.
6. FOR PICTURE REFERENCES ON THIS SHEET; SEE SHEET 00-GR-002.
B8 DUCT DAMPER DETAIL
NO SCALE
M
MOTORIZED FLOOR
DAMPER
MANUAL VOLUME
DAMPER
H103
109 110 111 112
H103A
EX 30"X 12"
BLDG. 25 FIRST FLOOR
PICTURE REFERENCE PLAN
SCALE: 1/4" = 1'-0"
H103
109 110 111 112
H103A
EX 30"X 12"
SUPPLY AIR DUCTWORK TO RUN
ABOVE LIGHT FIXTURES AND
BELOW FAN COIL DUCTING.
25-EAHU-1
25-1FBC
EX OUTSIDE
AIR LOUVER
25-EAHU-1
EX OUTSIDE
AIR LOUVER
25-1FBC
25-SH-1
UP TO SECOND
FLOOR; SEE
SHEET 25-MH-12334"x 12"
FD
34"x 18"
M 18 "x
2"
H
E7
E3
FSD
FIRE SMOKE
DETECTOR
P
FIRST FLOOR HVAC REVISED
PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MH-112
25 36
BLDG. 25 SECOND FLOOR
SCALE: 1/4" = 1'-0"
PLAN NOTES:GENERAL PLAN NOTES:
1. EVERYTHING SHOWN IS NEW UNLESS
OTHERWISE NOTED.
3. THE CONTRACTOR IS RESPONSIBLE FOR
TRACKING THE EE NUMBERS OF ALL
EQUIPMENT REMOVED FROM THE SPACE
AND ALL NEW EQUIPMENT BEING
INSTALLED. AT THE COMPLETION OF THE
PROJECT, THE CONTRACTOR WILL
PRESENT THE COR WITH A LIST OF ALL
EQUIPMENT REMOVED AND ALL NEW
EQUIPMENT ADDED.
4. THE CONTRACTOR IS RESPONSIBLE FOR
PROTECTING, MOVING, AND STORING
FURNITURE AND MOVABLE EQUIPMENT,
AND RETURNING IT TO THE SPACE WHEN
WORK IS COMPLETE. ANY NON-MOVABLE
EQUIPMENT IN THE SPACE WILL BE
COVERED IN 6 MIL PLASTIC AND TAPED TO
PREVENT DAMAGE FROM DUST AND
WATER DAMAGE AT ALL TIMES DURING
CONSTRUCTION.
5. SEE DUCT CONNECTION DETAILS ON
SHEET 00-MG-002.
1. 12"x 34" DOWN TO FIRST FLOOR AND UP TO THIRD FLOOR.
2. NEW 18"X 12" DUCT.
3. CONNECT NEW DUCT TO EXISTING 30"X 12" DUCT
TRANSITION IN THIS AREA AS REQUIRED.
4. MOTORIZED DAMPER AND MANUAL VOLUME DAMPER;
TYPICAL. SEE DETAIL B8/25-MH-112.
5. FLOOR PRESSURE SENSOR LOCATED ABOVE FINISHED
CEILING, MOUNTED TO WALL FOR FIRST FLOOR.
H203
212A
209A
EX-SA DUCT
M P
SECOND FLOOR HVAC
REVISED PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MH-123
26 36
BLDG. 25 THIRD FLOOR
SCALE: 1/8" = 1'-0"
PLAN NOTES:GENERAL PLAN NOTES:
1. EVERYTHING SHOWN IS NEW UNLESS
OTHERWISE NOTED.
1. 12"x 34" DOWN TO SECOND FLOOR.
2. NEW 18"x 12" DUCT.
3. CONNECT NEW DUCT TO EXISTING 30"X 12" DUCT
TRANSITION IN THIS AREA AS REQUIRED.
4. MOTORIZED DAMPER AND MANUAL VOLUME
DAMPER; TYPICAL. SEE DETAIL B8/25-MH-112.
5. FLOOR PRESSURE SENSOR LOCATED ABOVE
FINISHED CEILING, MOUNTED TO WALL FOR FIRST
FLOOR.
303A
304 305 30 304A
EX-SA DUCT
M
P
THIRD FLOOR HVAC
REVISED PLAN BUILDING 25
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
FCA - REPLACE MECHANICAL
EQUIPMENT IN BUILDINGS 23 & 25
657-20-109JB
www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393
Mechanical, Electrical, and Energy Engineering
DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
07-09-2021 DEH MV
ARCHITURA CORPORATION
9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384
PH: (317) 348-1000
POC: Michael Conly, AIA, NCARB, President
P R O F E S S I O N A L E N G I N E E R
PE-2021014461
HANNAH
ROSE
KIGER
S
TA
TE
OF MI SSOUR
I
25-MH-134
27 36