Part 5A - Drawings 657-20-109JB Building 23 and 25 HVAC.pdf

PDF 7 MB Posted

Attached to
Z2DA--FCA - Replace Mechanical Equipment in Buildings 23 and 25 PN: 657-20-109JB
Solicitation number
36C25522R0021
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CEILING DIFFUSER

EXIST..

ELEC.

EF

EP

ECC

DWG

DPT

DN

Db

DCP

CR

dB

CW

CP

CONN

COND

CHR

CH

CFM

CC

BLDG

AHU

AFMS

ABV

AC

EXISTING

ELECTRICAL

EXHAUST FAN

ELECTRICAL/PNEUMATIC

ENGINEERING CONTROL CENTER

DRAWINGS

DIFFERENTIAL PRESSURE TRANSMITTER

DOWN

DECIBELS

DRY BULB TEMPERATURE, (DEGREES)

DISTRIBUTED CONTROL PANEL

CONDENSATE RETURN

COLD WATER

CONDENSATE PUMP

CONNECT

CONDENSATE

CHILLED WATER RETURN (PIPING)

CHILLED WATER SUPPLY (PIPING)

CUBIC FEET PER MINUTE

COOLING COIL

BUILDING

AIR HANDLING UNIT

AIR FLOW MEASURING STATION

ABOVE

AIR CONDITIONING UNIT

WFMD

WF

WC

Wb

VAV

VTR

VSMC

TYP

TEMP

T'STAT

SYS

SQ/FT

SPT

SPS

SPEC.

SP

SHT

RV

RM

RET

REQ'D

PRV

PSI

PL

PHC

PD

O.C.

N.O.

NO

O.L.

NC

WATER FLOW MEASURING DEVICE

WATER FILTER

WATER COLUMN

WET BULB

VARIABLE AIR VOLUME

VENT THROUGH ROOF

VARIABLE SPEED MOTOR CONTROLLER

TYPICAL

TEMPERATURE

THERMOSTAT

SYSTEM

SQUARE FEET

STATIC PRESSURE SENSOR

SPECIFICATION

STATIC PRESSURE (INCHES OF WATER)

STATIC PRESSURE TRANSMITTER

SHEET

RELIEF VENT

ROOM

RETURN

REQUIRED

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH

PLACES

PREHEAT COIL

OVER LOAD

ON CENTERS

NORMALLY OPEN

PRESSURE DROP (FEETWATER)

NUMBER

NOISE CRITERIA

MT'D

MFG

MIN.

MECH

MAX.

MVD

LBS/HOUR

LTCP

LPS

LPR

KWH

IN

HWP

MOUNTED

KW

MANUFACTURER

MINIMUM

MECHANICAL

MAXIMUM

MANUAL VOLUME DAMPER

POUNDS PER HOUR

LOCAL TEMPERATURE CONTROL PANEL

LOW PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM RETURN

KILOWATT HOUR

KILOWATT

INCHES

HOT WATER PUMP

HAND-OFF-AUTOHOA

O.A./OSA

SF

E

RAG

CD

R

S

HWHR

HWH

HPR

HPS

HP

HORIZ.

HC

G.P.M.

FEET PER MINUTE

FLANGED (SEE DWG'S)

FLEXIBLE CONNECTOR

FD FLOOR DRAIN

FPM

FLNG'D

FLEX. CONN.

FLEX

FLR.

FF

EXH

FLEXIBLE

FLOOR

FINAL FILTER

EXHAUST AIR

GA.

F&T

FT

OUTDOOR AIR

SUPPLY FAN

EXHAUST CFM

RETURN AIR GRILLE

CEILING DIFFUSER

RETURN CFM

SUPPLY CFM

HOT WATER RETURN

HOT WATER SUPPLY

HIGH PRESSURE RETURN

HIGH PRESSURE STEAM

HORSEPOWER

HORIZONTAL

HEATING COIL

GALLONS PER MINUTE

GAGE

FLOAT AND THERMOSTATIC

FEET

BALL VALVE

P/T TEST PLUG (PRESSURE/TEMPERATURE)

MANUAL AIR VENT

PRESSURE REDUCING VALVE

SAFETY OR PRESSURE RELIEF VALVE

THREE-WAY MODULATING CONTROL VALVE

STRAIGHT-THRU TWO POSITION CONTROL VALVE

STRAIGHT-THRU MODULATING CONTROL VALVE

CIRCUIT SETTER

BALANCING VALVE

BUTTERFLY-VALVE

CHECK VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

GLOBE VALVE

ANGLE GLOBE VALVE

GATE VALVE

FLAT OVAL DUCT DOWN

FLAT OVAL DUCT UP

CEILING SUPPLY DIFFUSER W/ CFM INDICATED (FOUR WAY THROW)

LD LINEAR DIFFUSER

WITH CFM INDICATED

6"

FC

D

R

EXHAUST CEILING REGISTER OR GRILLE

FLEXIBLE CONNECTION

INCLINED DROP, IN DIRECTION OF AIR FLOW

INCLINED RISE, IN DIRECTION OF AIR FLOW

EXHAUST OR RETURN TOP REGISTER OR GRILLE (WALL TYPE)

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

VANE TURN ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

V.D.

MANUAL VOLUME DAMPER

LOUVER

SPIN-N-TAP WITH MVD DAMPER

DOUBLE WALL SOUND

STANDARD RADIUS ELBOW

VANED ELBOW (SHORT RADIUS)

ELBOWS WITH VANES EVEN IF SYMBOL IS MISSING)

VANED ELBOW (PROVIDE ALL SQUARE OR RECTANGULAR

DUCTWORK ELBOW UNLESS NOTED OTHERWISE.

THICKNESS VANES. VANES REQUIRED IN ALL

SQUARE TYPE ELBOW WITH DOUBLE

UP

UP

7:1 RATIO FOR HIGH PRESSURE.

TRANSITION. 4:1 RATIO FOR LOW PRESSURE,

ELBOW TURNED DOWN WITH TURNING VANES

ELBOW TURNED UP WITH TURNING VANES

RETURN AIR DUCT

EXHAUST AIR DUCTDOWN

OUTSIDE AIR DUCT

SUPPLY AIR DUCTDOWN

12X10

6"0M.V.D.

RECTANGULAR DUCT (WXH)

RND DUCT TAKE OFF WITH SPIN-IN EXTRACTOR

MANUAL VOLUME DAMPER

FLEXIBLE DUCT (MAXIMUM 5'-0" IN LENGTH)

MOTORIZED DAMPER (OPPOSED BLADE) W/INTERLOCK

R

DN.

DIRECTION OF AIR FLOW

INCLINED RISE IN RESPECT TO

DIRECTION OF AIR FLOW

INCLINED DROP IN RESPECT TO

100S

MOTORIZED DAMPER (PARALLEL BLADE) W/INTERLOCK

ROOM CONTROL: THERMOSTAT, HUMIDISTATT H

T REMOTE BULB THERMOSTAT

DUCT OR PIPE THERMOSTAT (NOTE: PROVIDE 12" MINT

LENGTH IN DUCT WHEN SPACE PERMITS)

DUCT OR PIPE TEMP. SENSOR SEE NOTE ABOVE.T

H

DUCT STATIC PRESSURE SENSOR

DUCT HUMIDITY SENSOR

SP

F SMOKE DETECTOR (SEE ELECTRICAL DWGS)

SD

C HOLDING COIL IN MOTOR STARTER

CONTACT, NORMALLY OPEN (N.O.)

CONTACT, NORMALLY CLOSED (N.C.)

SWITCH

SIGNAL FROM ECC OR DCP

SIGNAL TO ECC OR DCP

SIGNAL TO FIRE ALARM SYSTEM

PRESSURE TRANSMITTERP

HIGH PRESSURE STEAM (60 PSIG & ABOVE)

HIGH PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG & BELOW)

LOW PRESSURE STEAM CONDENSATE RETURN

CONDENSATE PUMP DISCHARGE

HOT WATER HEATING SUPPLY

HOT WATER HEATING SUPPLY

VENT LINE

THERE WILL BE COUNTER FLOW BETWEEN WATER AND AIR.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE SO

6. CEILING DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

DETAILS.

5. FOR TYPICAL STEAM, WATER & PIPING CONNECTIONS TO EQUIPMENT SEE STANDARD

UNITS, FILTERS, COILS, ETC.

TOTAL STATIC PRESSURE NOTED IN SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL

UNDER ARCHITECTURAL SPECIFICATIONS.

DAMPERS, CLEANOUTS, CONTROLS, ETC.,AND SHALL BE FURNISHED AND INSTALLED

3. ACCESS PANELS IN SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,

FURRED CHASE OR SUSPENDED CEILING.

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN

EX. PIPE TO BE REMOVED

WATER FLOW MEASURING DEVICE

THERMOMETER

STRAINER

THERMOSTATIC TRAP

FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING

ACCESSORIES (SEE STD. DETAIL)

ACCESSORIES (SEE STD. DETAIL)

INVERTED BUCKET TRAP SET INCLUDING PIPING

NEW AND EXISTING WORK ON REVISED SHEETS

POINT OF CONNECTION BETWEEN NEW

UNION

RISE OR DROP IN PIPE

SIDE CONNECTION

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

ECCENTRIC REDUCER

REDUCER OR INCREASER

ANCHOR (ALSO SEE "D" DWGS)

DIRECTION OF FLOW

DIRECTION OF PIPE PITCH (DOWN)

FLEXIBLE DUCT

4.

ECCENTRIC REDUCER

CONCENTRIC REDUCER

UNION

FINISHED FLOORFIN.

NEGATIVE PRESSURE RELIEF VENTNPR

NEGATIVE PRESSURE RELIEF VENT

FIRE SMOKE DAMPERFSD

F.S.D. FIRE/SMOKE DAMPER

F.S.D.

ANCHOR

OR

NORMALLY CLOSEDN.C.

100S

10 X 8 NEW DUCT-WIDTH X DEPTH

ATTENUATING DUCT

CHILLED WATER RETURN

CHILLED WATER SUPPLY

F.D.

F.D. FIRE DAMPER

POINT OF WHERE DEMOLITION STOPS AND

EXISTING IS TO REMAIN ON DEMO SHEETS

INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING

EQUIPMENT AND PIPING WAS OBTAINED FROM EXISTING DRAWINGS AND

CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE

NOT AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE

EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT

LOCATION(S) AND DIRECTION OF FLOW OF ALL EXISTING EQUIPMENT, ETC., IS

UNKNOWN. REASONABLE EFFORT HAS BEEN MADE TO ACCURATELY DEPICT THE

EXISTING CONDITIONS, HOWEVER, ALL EXISTING WORK MUST BE VERIFIED IN

THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS OF PIPE RUNS,

SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN THESE

PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO

THE ENGINEER FOR VERIFICATION AND/OR CORRECTION.

INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING

DUCTWORK AND DIFFUSERS WAS OBTAINED FROM EXISTING DRAWINGS AND

CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE

NOT AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE

EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT

LOCATION(S) AND DIRECTION OF FLOW OF ALL EXISTING EQUIPMENT, ETC., IS

UNKNOWN. REASONABLE EFFORT HAS BEEN MADE TO ACCURATELY DEPICT THE

EXISTING CONDITIONS, HOWEVER, ALL EXISTING WORK MUST BE VERIFIED IN

THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS OF DUCT RUNS,

SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN THESE

PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO

THE ENGINEER FOR VERIFICATION AND/OR CORRECTION.

FOR GENERAL DUCT CONSTRUCTION AND PIPING CONNECTIONS SEE DETAILS ON

ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE

TRADE, AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND

STANDARDS.

CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE,

HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES,

ENLARGED FOR CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR

APPURTENANCES REQUIRED TO PROVIDE A COMPLETE AND COORDINATED SYSTEM

SHALL BE BORNE BY THE CONTRACTOR.

BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE MAIN.

ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, UNIT HEATERS,

ETC. SHALL BE HUNG FROM THE TOP CHORD OF THE STRUCTURAL STEEL OR BY HANGERS

EACH MAIN DUCT PASSING THROUGH FLOOR SPACES SHALL BE FIRE DAMPERED.

ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.

CONTRACTORS ARE TO REVIEW EXISTING STRUCTURAL AND PLANS, WITH ACTUAL

LAYOUT OF BEAMS, JOISTS, ETC. TO AVOID CONFLICT BETWEEN DUCT. ADJUST DUCT

ROUTING TO ACCEPT STRUCTURAL CONDITIONS.

ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A

MINIMUM OF 25'-0" AWAY FROM OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL

AND STATE CODES MANDATE ADDITIONAL DISTANCE.

WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL

WATER-TIGHT ALL AROUND LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL

COORDINATE PAINTING REQUIREMENTS FOR LOUVERS WITH GENERAL CONTRACTOR

PRIOR TO SUBMITTING BID.

A.

B.

C.

D.

E.

F.

H.

I.

J.

K.

G.

THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

2.

THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

2.

H4

H7 A

DRAWING SYMBOLS

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

DRAWING NUMBER WHERE DRAWN

CROSS HATCHED AREAS ARE NOT IN

CONTRACT AND ARE EXISTING TO REMAIN,

UNLESS SPECIFICALLY NOTED OR SHOWN

OTHERWISE.

E.T.R.

THIS SYMBOL SHOWS THE APPROXIMATE POINT WHERE

NEW WORK STARTS AND EXISTING IS TO REMAIN.

CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL

EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON

ORDER

MECHANICAL DETAILS SHEET.

CONNECTED TO CONCRETE SLAB ABOVE AS REQUIRED.

FOR DEMOLITION THIS SYMBOL SHOW THE APPROXIMATE

POINT WHERE DEMOLITION STOPS AND EXISTING IS TO

REMAIN FOR REVISED WORK.

E.T.R. EXISTING TO REMAIN

MECHANICAL SYMBOLS &

ABBREVIATIONS

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-001

23 & 25

BID DOCUMENTS

11 36

TYPICAL ACCESS SECTION FOR ROUND/OVAL DUCT

DUCT TRANSITIONSB

D

SUPPLY DUCTWORK TAKE-OFFS VOLUME DAMPER DETAIL

FLEXIBLE DUCT CONNECTIONS

EXHAUST OR RETURN BRANCH DUCTWORK

ACCESS PANEL AND DOOR DETAIL

DUCTWORK RADIUS ELBOWSD

D

E

D

B

B

25-EAHU-1 LAYOUT

25-EAHU-1 LEGEND

F

SECTION THRU FIRE DAMPER INSTALLATIONF

MECHANICAL DETAILS, AIR SIDE

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-002

23 & 25

12 36

"A"

"A"

MIN. UPSTREAM LENGTH

OF STRAIGHT PIPE IN

PIPE DIAMETERS. SEE

SECTION "A-A"

SCHEDULE BELOW.

WATER FLOW

MEASURING

DEVICE

ANY FITTING

OR VALVEMIN. DOWNSTREAM LENGTH OF STRAIGHT PIPE IN

PIPE DIAMETERS. SEE SCHEDULE BELOW.

WATER FLOW MEASURING DEVICE INSTALLATION SCHEDULE

TYPE

MIN. UPSTREAM LENGTH

OF STRAIGHT PIPE IN

PIPE DIAMETERS PIPE IN PIE

MIN. DOWNSTREAM

LENGTH OF STRAIGHT

DIAMETERSFOR SIDE

TEE

FOR VALVE OR

OTHER FITTING

10 5 2

DIMENSIONS SHOWN IN SCHEDULE ARE MINIMUM REQUIRED. IF MANUFACTURER

OF FURNISHED WATER FLOW MEASURING DEVICE RECOMMENDS A GREATER

DIMENSION, USE THEIR RECOMMENDATION.

INSTALL THE WATER FLOW MEASURING DEVICE SO THE ARROW IS IN THE

SAME DIRECTION AS THE FLOW.

NOTES:

THE WATER FLOW MEASURING DEVICE MAY BE INSTALLED IN EITHER HORIZONTAL

OR VERTICAL PIPE. UNITS REQUIRING REMOTE METERS SHALL HAVE THE METER

CONNECTIONS LOCATED ON OR NEAR THE SIDE WHEN INSTALLED IN HORIZONTAL

PIPE. SEE SECTION "A-A". THE METER CONNECTIONS CAN BE INSTALLED IN

ANY POSITION WHEN INSTALLED IN VERTICAL PIPE.

1.

2.

3.

WATER FLOW MEASURING

DEVICE INSTALLATION DETAIL

D

PIPE HANGERSF

AT AIR HANDLER / COIL

TYPICAL AHU

CONNECTIONS TO STEAM COIL

AIR RELIEF LINE

6" MIN.

STEAM CONTROL

VALVE

STEAM SUPPLY

BY-PASS (2 SIZES

SMALLER THAN

MAIN LINE)

COMPLETE DRIP

COND. RETURN

F&T TRAP; DETAIL F7/MQ004

DIRT POCKET FULL

SIZE OF COIL TRAPPING

FULL SIZE

NOTE:

(FULL SIZE)

DIRT POCKET

6" MIN.

STEAM MAIN

BASE OF RISER DRIPS SIMILAR TO ABOVE

OF TRAP

FULL SIZE

5LB. DROP UNLESS OTHERWISE

BUCKET TRAP CAP 200LBS/HR @

INDICATED; DETAIL B6/MQ004

DRIP RETURN MAIN

STEAM MAIN DRIP CONNECTION

END OF H.P. OR M.P.

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

PROVIDE HOSE CAP NUTELEVATION

WELDED PIPING

ELEVATION

THREADED PIPING

NOTES:

DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.

2.

VALVE CONNECTION

TYPICAL DRAIN

REDUCER

CIRCULATING WATER

PIPING

TYPICAL AIR VENT

ELEVATION

IF AUTOMATIC AIR VENTS ARE USED,

PIPE DISCHARGE TO DRAIN.

VENT ALL HIGH POINTS AS INDICATED ABOVE.

2.

NOTES:

1.

WHERE SCALE POCKETS ARE SHOWN ON PIPE

RISER DIAGRAMS AND/OR PLANS, LOCATE

DRAIN AT BOTTOM OF SCALE POCKET.

AIR VENT

VAC

BREAKER

1/4" COPPER TUBING

3/8" GATE VALVE

3/8" 4" NIPPLE

ADAPTER TO 3/4" THREAD

3/4" GATE VALVE

A

B

D

F

A

STEAM COIL

NOTE: FOR VERTICAL

COIL STEAM COMES

INTO TOP AND

CONDENSATE OUT

BOTTOM

B

ASSEMBLY INVERTED BUCKET STEAM TRAP

ASSEMBLY FLOAT AND THERMOSTATIC STEAM TRAP

THERMOSTATIC STEAM TRAP ASSEMBLY

AND BYPASS STEAM COIL DETAIL

INTEGRAL FACE

F

B

F

D

1" GREATER THAN

1/2 OF FAN STATIC

PRESSURE

COOLING COIL CONDENSATE DRAIN

PIPE SIZE PER

MANUFACTURER. PITCH

DOWN 1/8" PER FOOT TO

FLOOR DRAIN.

RUN FULL SIZE

OF DRAIN PAN

OUTLET TO AND

INCLUDING TEE

1" GREATER THAN

FAN STATIC

PRESSURE

PIPE RUN FOR

BOTTOM DRAIN

CONFIGURATION

CLEAN OUT

PLUG

COOLING COIL

DRAIN PAN

D

NOTE: PIPING SHALL

BE COPPER AND A

MINIMUM OF 1-1/4"Ø.

NO SCALE

NOTE: FOR

EQUIPMENT WITH

MULTIPLE COIL

SLABS, EACH COIL

SHALL BE PIPED ASH

SHOWN ABOVE

WATER COILS - PIPING CONNECTIONS

C

3 NO SCALE

ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER

VERTICAL

2 1/2" [65mm] DIA.

ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER

HORIZONTAL

2 1/2" [65mm] DIA.

INSTALLATION OF THERMOMETER

WELLS

STEAM HUMIDIFIER -

DU

CT

H

EI

GH

T

H

1/

H 1/

H

1/

H

STEAM

CONDENSATE

RETURN

TEMPERATURE SWITCH

SCALE POCKET

HUMIDIFIER

CONTROL VALVE

TO HUMIDISTAT

MANIFOLD PIPE ADAPTERS

STEAM SUPPLY

ON-OFF CONTROL VALVE DUCT CROSS SECTION

6" M

IN

PIPING CONNECTIONS (MULTIPLE DISPERSION TUBES)

INVERTED

BUCKET TRAP

ASSEMBLY

SEE

MANUFACTURER'S

PIPING

RECOMMENDATIONS

FOR FINAL LAYOUT

F

1 NO SCALE

[1 m m

PRESSURE TRANSMITTER INSTALLATIONA

ULTRA SONIC

METER;

TYPICAL

PIPE

ON HORIZONTAL PIPE, SENSOR NOT ALLOWED TO BE

MOUNTED ON TOP OF THE PIPE. USE THE 2:00, 4:00, 8:00, OR

10:00 POSITIONS

OR ELBOW

2"

2"

STEAM TRAP ASSEMBLY

STEAM LINE DRIP POCKET

LAST

CONNECTION ON

LINE

MECHANICAL DETAILS,

WATER SIDE

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-003

23 & 25

13 36

DUCT CONNECTIONS - AIR TERMINAL UNITS

SECURING HANGER RODS IN CONCRETEA

SEISMIC BRACING FOR EQUIPMENT

F1 SUPPORT/ANCHOR FOR PIPE RISERS

F3 SUPPORT ANCHOR AT WALL

F5 SMALL PIPE ANCHOR 11

2"- 4"

PIPE/DUCT PENETRATION OF SMOKE BARRIERS

NO SCALE

1" 1"

6" 6"

6"

6"

6"

6"

F7

B1 B5

WALL

PRESSURE PLATE

BOLT

BASIS OF DESIGN: LINK SEAL

ELASTOMERIC SEAL ELEMENT

LS MODEL (C, L, S-316, O, OS-316, T)

LS Model Seal Element Bolts/Nuts Pressure Plate C EPDM (Black) Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer L EPDM (Blue) Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer O Nitrile Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer T Silicone Zinc Dichromate/Organic Coated Carbon Steel Bolt Steel Zinc Dichromate (C,L,O)+S-316 (see model options) 316 Stainless Steel Reinforced Nylon Polymer

Sleeve Model Description Material CS Century-Line Sleeve HDPE WS Steel Wall Sleeve Steel

CAST / CORE DRILLED HOLE

D5 WALL PENETRATION DETAIL

PMP

VENTED RECEIVER

PUMP

EXHAUST

INLET

CHECK

VALVE

SYSTEM

BACK

PRESSURE

CONDENSATE RETURN LINE

PRESSURE

____ PSI

OUTLET

CHECK

VALVE

MOTIVE STEAM OR

GAS PRESSURE

(AVAILABLE)

CONDENSATE LOAD:

4" INTERIOR CONCRETE PAD

FINISHED FLOOR

VENT; SEE PLAN FOR LOCATION

AND PIPE DISCHARGE.

FILLING HEAD

D3 TYPICAL CONDENSATE PUMP DETAIL

MECHANICAL CONTROLS,

BUILDING 23

CONSULTANTS: ARCHITECT/ENGINEERS:

Revisions: Date:

Drawing Title

VA Health Care System Approval:

Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

Drawing # of

Veterans Health

Administration

FCA - REPLACE MECHANICAL

EQUIPMENT IN BUILDINGS 23 & 25

657-20-109JB

www.daengineering.com www.daengineering.com voice (317) 464-9090 2707 Rand Road Indianapolis, Indiana 46241 fax (317) 464-9393

Mechanical, Electrical, and Energy Engineering

DESIGN-AIRE ENGINEERING, INC. JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

07-09-2021 DEH MV

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

P R O F E S S I O N A L E N G I N E E R

PE-2021014461

HANNAH

ROSE

KIGER

S

TA

TE

OF MI SSOUR

I

00-MG-004

14 36