Paint Booth SOW - Appendix B - Summary of Available Utilities within Hangar 253.pdf

PDF 173 KB Posted

Attached to
Paint Booth- W508S8A -20-Q-0005
Solicitation number
W508SA
Issued by

About this file

This document includes a solicitation for a paint booth and installation services. The New Hampshire Army National Guard requires a paint booth under CLIN 0001 and installation services under CLIN 0002 to meet the statement of work. Quotes are due by the date specified in the solicitation. The requirement is set aside entirely for small businesses with a size standard of 500 employees. The solicitation also specifies terms for payment, system for award management registration, applicable federal acquisition regulation provisions and clauses, and recommended site visit details.

View the file

Other files

File Type Posted
RFI Tracker Ver_4_Final_RFI_21___JULY_1_2020.pdf PDF
Paint Booth SOW - Appendix F - Hazardous Materials Building Inspection KC-46A Fuel Cell Hangar B253_JUN_26_2020.pdf PDF
52.212-3 Offeror Representations and Certifications-Commercial Items. _JUN_26_2020.pdf PDF
Paint Booth SOW - Appendix G - Asbestos Test Report_Corr Metal Siding B253_JUn_26_2020.pdf PDF
Paint Booth SOW - Appendix A - Hangar 253 Building Plans (Abridged Set for Paint Booth Installation)_v4_Addendum_JUN_26_2020.pdf PDF
Paint Booth SOW - Appendix H - Compressed Air Piping Specifications B253_JUN_26_2020.pdf PDF
Paint Booth SOW - Appendix B - Summary of Available Utilities within Hangar 253_v2_Addendum_JUN_26_2020.pdf PDF
Paint Booth Statement of Work Final_RFI Addendum_JUN_26_2020.pdf PDF
Paint Booth SOW - Appendix A1 - Hangar 253 Building Plans (Supplemental Drawings for Addendum)_JUN_26_2020.pdf PDF
RFI Tracker Ver_3_Final_Comments_JUN_26_2020.pdf PDF
Sign in Sheet_JUNE_10_2020.pdf PDF
Site Visit Info_Paint Booth_Wed_June_10_2020.docx DOCX document
Paint Booth SOW - Appendix A - Hangar 253 Building Plans (Abridged Set for Paint Booth Installation)_v3.pdf PDF
Paint Booth Statement of Work 12MAR20.pdf PDF
Paint Booth SOW - Appendix E - FP Hydraulic Calc Revisions 11.30.2018 [Submittal]_Abridged.pdf PDF
Paint Booth SOW - Appendix C - NHDES Air Permit Application.doc DOC document
Paint Booth SOW - Appendix E - FP Hydraulic Calc Revisions 11.30.2018 [Submittal].pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX B – SUMMARY OF AVAILABLE UTILITIES WITHIN HANGAR 253

Provided at Rm 129

1 ½ inch gas line @ north wall

1 inch Compressed Air/Tool Lines x 2 at east and west walls

Floor Drain located at north/center of room for potential Eye Wash/Shower

Electrical service (all located along west wall):

Panel HP-2 (200A main circuit breaker) o 15A 480/277V 3Ph/4Wire previously for Blast Booth Claim System (3HP)

(Unused) o 15A 480/277V 3Ph/4Wire previously for Blast Booth Dry Honer (2HP) (Unused)

Panel HP-4 (150A main circuit breaker) o 60A 480/277V 3Ph/4Wire previously for Despatch Oven Rm 129 (Unused) o Additional capacity available in panel

Panel LP-2 (208/120V)

Panel LP-2A (208/120V)

Fire sprinkler system w/ drain/test valve located in the southeast corner of Rm 129 (capacity calculation needed for Paint Booth requirement)

Surrounding Room Fire Suppression/Alarms – HC-2 coverage provided, 0.2GPM/SQFT

@ Design Area of 2,500SF

Provided Elsewhere in Bldg 253

Electrical capacity at Panel RDP-1 in the main electrical room of Bldg 253, depicted as Room C on drawing AE-101:

70A 480/277V 3Ph/4Wire for Blast Booth Vent (25HP) planned at Rm 120 (Circuit breaker/wiring not installed)

60A 480/277V 3Ph/4Wire for Paint Booth Make Up Air Unit (20HP) planned at Rm 120

(Circuit breaker/wiring not installed)

60A 480/277V 3Ph/4Wire for Paint Booth Exhaust Fan (20HP) planned at Rm 120

(Circuit breaker/wiring not installed)

Compressed Air-Breathing Air (closest breathing air supply is at CTK Rm 123 or at Mechanical

Mezzanine above and west of Room 129)

Domestic water supply (available above ceiling at the restrooms and Mechanical Mezzanine above and west of Room 129)