1. DRAWINGS, SPECIFICATIONS, ADDENDUMS, SKETCHES AND OTHER DOCUMENTATION COMPRISE THE PROJECT CONTRACT

DOCUMENTS AND SHALL BE USED IN COMBINATION. PROVIDE A FULLY FUNCTIONAL SECURITY SYSTEM PER THE DRAWINGS AND

SPECIFICATIONS.

2. THE DRAWINGS INDICATE THE GENERAL PROPOSED LOCATION OF EQUIPMENT, CABLE PATHWAYS AND OUTLETS. LOCATION OF

EQUIPMENT AND OUTLETS AND OTHER SUPPORTING ITEMS TO BE COORDINATED WITH ALL OTHER EXISTING UTILITIES AND TRADES.

3. DO NOT REUSE EXISTING MOTION DETECTORS, DOOR POSITION SWITCHES, CABLING, OBSOLETE EQUIPMENT, NON FUNCTIONING, OR

ANTIQUATED EQUIPMENT. COORDINATE NEW LOCATION OF REUSED EQUIPMENT WITH CONSTRUCTION DOCUMENTS AND CO.

4. THE TERM "CONTRACTOR" MEANS THE PRIME CONTRACTOR RESPONSIBLE FOR ALL WORK DEFINED IN THE DRAWINGS AND

SPECIFICATIONS.

5. THE TERM "PROVIDE" MEANS FURNISH NEW AND INSTALL, COMPLETE AND READY FOR USE.

6. THE TERM "DEMOLITION" MEANS DISCONNECT AND REMOVED BACK TO SOURCE. STOP REMOVAL WHERE WHERE DAMAGE WOULD

OCCUR IF FURTHER REMOVAL OCCURRED. CUT CONDUIT OFF AND REMOVE ALL WIRE CONDUCTORS UNDER THESE CONDITIONS.

7. COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO COMMENCING WORK. ANY CONFLICT BETWEEN DRAWINGS AND

SPECIFICATIONS SHALL BE BROUGHT TO THE CO'S ATTENTION IMMEDIATELY. DO NOT PROCEED WITH ANY WORK EXCEPT AT RISK

UNTIL CLARIFICATION OF CONFLICTS ARE ISSUED BY THE CONTRACTING OFFICER.

8. FIELD VERIFY AND COORDINATE ALL DEVICE LOCATIONS AND POWER REQUIREMENTS. WHERE CONFLICTS OCCUR, COORDINATE

AND VERIFY FINAL LOCATIONS WITH THE CONTRACTING OFFICER PRIOR TO INSTALLATION.

9. PROVIDE COORDINATION AND VERIFICATION OF ALL CONDITIONS INCLUDING EQUIPMENT AND DEVICES INSTALLED BY OTHER

TRADES, THE WORK OF THE CONTRACTOR AND SUBCONTRACTORS.

10. DETAIL REFERENCES ARE NOT NECESSARILY NUMBERED INCREMENTALLY. A GAP IN NUMBERING DOES NOT INDICATE MISSING

INFORMATION. DETAIL NAMES AND NUMBERS ARE SPECIFIC TO THIS DESIGN PACKAGE AND DO NOT CORRESPOND TO OTHER

PUBLISHED DOCUMENTS.

11. PROVIDE TAMPER SWITCHES FOR ALL ACTIVE EQUIPMENT ENCLOSURES INCLUDE: IDS PANELS, IDS EXPANSION ENCLOSURES, ACCESS CONTROL PANELS, AND READER MODULES.

AFF

AV

BCT

C

CAT

CATV

CM

CO

CT

EF

EMI

EMT

ER

EXT

FO

IMT

IN

ITS

LAN

MAX

MIN

MISC

MM

MTD

NTS

NVR

OC

OPE

OSP

PIR

PC

POTS

PP

PR

PTZ

REX

RM

RMU

SC

SM

SP

STP

TBB

TBD

TE

TGB

TMGB

TR

TYP

UNO

UON

UPS

UTP

VAC

VDC

VLAN

VP

WAO

WM

WP

WPE

ABOVE FINISHED FLOOR

AUDIO VISUAL

BONDING CONDUCTOR FOR TELECOMMUNICATIONS

CONDUIT

CATEGORY

COMMUNITY ANTENNA TELEVISION

CEILING MOUNTED

CONTRACTING OFFICER

CABLE TRAY

ENTRANCE FACILITY

ELECTROMAGNETIC INTERFERENCE

ELECTRICAL METALLIC TUBING

EQUIPMENT ROOM

EXTERIOR

FIBER OPTIC

INTERMEDIATE METALLIC TUBING

INTERIOR

INFORMATION TECHNOLOGY SYSTEMS

LOCAL AREA NETWORK

MAXIMUM

MINIMUM

MISCELLANEOUS

MULTIMODE

MOUNTED

NOT TO SCALE

NETWORK VIDEO RECORDER

ON CENTER

OWNER PROVIDED EQUIPMENT

OUTSIDE PLANT

PASSIVE INFRARED

PERSONAL COMPUTER

PLAIN OLD TELEPHONE SERVICE

PATCH PANEL

PAIR

PAN-TILT-ZOOM CAMERA

REQUEST TO EXIT

ROOM

RACK MOUNTING UNIT (1.75")

SURFACE CEILING

SINGLEMODE

SERVICE PROVIDER

SHIELDED TWISTED PAIR

TELECOMMUNICATIONS BONDING BACKBONE

TO BE DETERMINED

TELECOMMUNICATION ENCLOSURE

TELECOMMUNICATIONS GROUNDING BUSBAR

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TELECOMMUNICATIONS ROOM

TYPICAL

UNLESS NOTED OTHERWISE

UNLESS OTHERWISE NOTED

UNINTERRUPTED POWER SUPPLY

UNSHIELDED TWISTED PAIR

VOLTS ALTERNATING CURRENT

VOLTS DIRECT CURRENT

VIRTUAL LOCAL AREA NETWORK

VANDAL PROOF

WORK AREA OUTLET

WALL MOUNTED

WEATHERPROOF

WEATHERPROOF ENCLOSURE

LINE TYPE - EXISTING FOR DEMOLITION

LINE TYPE - NEW DEVICE

LINE TYPE - PRESSURE MAT BOUNDARY

DOOR POSITION SWITCH; WIDE GAP

DOOR POSITION SWITCH; SURFACE MOUNT

MOTION DETECTOR; CEILING MOUNT

MOTION DETECTOR; WALL MOUNT

GLASS BREAK SENSOR

ARM/DISARM KEYPAD

FIXED MINI DOME CAMERA

4 LENS CAMERA

TELEPHONE DROP (EXISTING TO REMAIN)

PRESSURE MAT

INTRUSION DETECTION SYSTEM PANEL

NETWORK VIDEO RECORDER

POE NETWORK SWITCH; X DENOTES NUMBER OF PORTS

POWER OVER ETHERNET INJECTOR

CELLULAR COMMUNICATOR

CELLULAR ANTENNA

UNINTERRUPTED POWER SUPPLY

WORK STATION, RACK MOUNT

120VAC CIRCUIT - COORDINATE WITH DIVISION 26

REQUIREMENTS

12VDC POWER SUPPLY

KEY NOTE INDICATOR

DETAIL NUMBER

DETAIL IDENTIFICATION BUBBLE

SHEET DETAIL IS SHOWN ON

SHEET DETAIL IS TAKEN FROM

ELEVATION NUMBER

ELEVATION IDENTIFICATION BUBBLE

SHEET ELEVATION IS SHOWN ON

SHEET ELEVATION IS TAKEN FROM

1. UTP CAT6 CABLE PROVIDED FOR ALL ETHERNET CONNECTIONS.

2. GROUND LOOPS ARE NOT PERMITTED. GROUND SHIELD DRAIN WIRES SHALL TERMINATE TO VERIFIED EARTH GROUND TERMINAL

LUGS AT THE CONTROL CABINET OR ORIGINATING EQUIPMENT. INSULATE SHIELDS AND DRAIN WIRES AT THE DEVICE OR REMOTE

TERMINATION POINT USING UL APPROVED INSULATORS. THE USE OF AC POWER NEUTRAL CONDUCTORS FOR GROUND

CONNECTIONS IS UNACCEPTABLE.

3. PROVIDE UNSHIELDED TWISTED PAIR CABLE ASSEMBLIES FOR ALL DC LOW VOLTAGE POWER DISTRIBUTION AND CONTROL

CIRCUITS.

4. PROVIDE SHIELDED TWISTED PAIR CABLE ASSEMBLIES FOR ALL AC LOW VOLTAGE POWER DISTRIBUTION.

5. WIRE AND CABLE SPLICES ARE NOT PERMITTED.

6. CONCEAL CABLING TO THE EXTENT POSSIBLE. WHERE CABLING CANNOT BE CONCEALED PROVIDE MOLD AND PAINT TO MATCH

WALL OR CEILING. OBTAIN APPROVAL FROM THE CONTRACTING OFFICER PRIOR TO INSTALLATION.

1. PROVIDE CONDUITS AND RACEWAYS FOR A COMPLETE INSTALLATION..

2. REGARDLESS OF NEC OR LOCAL CODES AND ORDINANCES, PROVIDE CONDUIT AND RACEWAY SIZED FOR A MAXIMUM FILL OF 40%.

3. REGARDLESS OF NEC OR LOCAL CODES AND CONDUIT FILL REQUIREMENTS, CONDUIT SHALL BE 3/4" MINIMUM DIAMETER.

4. PROVIDE COMPRESSION TYPE CONDUIT FITTINGS. SET SCREW TYPE FITTINGS ARE NOT ACCEPTABLE.

5. PROVIDE CO APPROVED SECURITY SCREWS AND FASTENERS FOR ALL SECURITY JUNCTION BOXES AND SCREW COVER

ENCLOSURES.

6. PROVIDE COLOR CODING OF ALL SECURITY CONDUITS. ALL JUNCTION BOXES, DEVICE BOXES, TERMINAL CABINETS AND WIRE

TROUGH COVERS SHALL BE PAINTED. COLOR TO BE BENJAMIN MOORE #791 OR APPROVED EQUAL.

7. CONCEAL CONDUIT AND RACEWAYS TO THE EXTENT POSSIBLE. WHERE CONDUITS AND RACEWAYS CANNOT BE CONCEALED, COORDINATE WITH THE CO TO OBTAIN APPROVAL PRIOR TO INSTALLATION.

8. DO NOT COMBINE 120VAC OR ANY POWER DISTRIBUTION CIRCUIT WITH SECURITY WIRE AND CABLE.

9. PROVIDE ACCESS COVERS OR HATCHES FOR ALL SECURITY JUNCTION BOXES CONCEALED IN STRUCTURE. PROVIDE ACCESS TO

JUNCTION BOXES AND EQUIPMENT ENCLOSURES LOCATED WITHIN 10 FEET OF SECURITY DEVICES.

10. UNLESS NOTED OTHERWISE THE PROJECT ELECTRICAL CONDUIT STANDARD IS ELECTRICAL METALLIC TUBING (EMT) AND PROVIDE

THROUGHOUT THE PROJECT. REFERENCE TO CONDUIT IS EQUIVALENT TO STATING EMT. EXTERIOR CONDUIT, INCLUDING ON THE

ROOF, SHALL BE RIGID METAL CONDUIT.

11. PROVIDE CONDUIT AS UNOBTRUSIVE AS POSSIBLE, AS CLOSE AS POSSIBLE TO FLOOR/CEILING SLAB AND PARALLEL AND AT RIGHT

ANGLES TO STRUCTURAL STEEL, CONCRETE ELEMENTS, OR BUILDING. THESE DRAWINGS ARE DIAGRAMMATIC TO SHOW DESIGN

INTENT ONLY.

PARTITION TYPE (AS REQUIRED)

ES EXHIBIT

HS HOUSE

DEVICE MOUNTING LOCATION

S SURFACE

C CEILING

R RECESSED

W WALL

DEVICE TYPE CAMERA TYPES MOUNTING TYPE

WI WIRELESS EXT EXISTING P POLE MOUNT

T TRIPLE BIAS 1080 1080P RESOLUTION PP PARAPET MOUNT

W WIDE GAP 720 720P RESOLUTION WM WALL MOUNT

D DOUBLE POLE DOUBLE THROW SC CEILING MOUNT

E EMERGENCY POWER SM SURFACE MOUNT

S SINGLE POLE DOUBLE THROW ENCLOSURE TYPES

P PROXIMITY WP WEATHER PROOF

KP KEYPAD ONLY VP VANDAL PROOF

L LONG RANGE IN INTERIOR

CAMERA NUMBER (SEE BELOW)

CAMERA TYPE (SEE BELOW)

CAMERA (TYPICAL)

ENCLOSURE TYPE (SEE BELOW)

MOUNTING LOCATION (SEE BELOW)

TYPE

# OF

CONDUCTOR

DESCRIPTION

A 20AWG 6 TWISTED SHIELDED PAIR

B 22AWG 4 TWISTED PAIR

C 22AWG 2 TWISTED PAIR

E UTP 8 CAT6

D 18AWG 2 SHIELDED

X

PM

HS

ES

HS

HS

ES

ES

HS

ES

HS

ES

HS HS

HS

HSHS

HS

HS

HS

ES

ES

HS

HS

HS

HS HS

HS

HS

ES

ES

ES

ES

ES

ES

ES

ES

HS

HS

1. THERE ARE TWO SEPARATE EXISTING INTRUSION DETECTION

SYSTEMS. ONE IS KNOW AS THE "HOUSE" (HS) WHICH

SUPPORTS THE PERIMETER OF THE BUILDING AND IS DISARMED

WHEN THE FACILITY IS OPENED. THE SECOND SYSTEM, KNOWN

AS THE "EXHIBIT" (ES) SUPPORTS ALARMS FOR THE EXHIBITS

INSIDE THE FACILITY. THIS SYSTEM REMAINS ARMED DURING

OPERATION.

2. MAINTAIN EXISTING SECURITY DEVICES OPERATIONALLY AS

LONG AS POSSIBLE. COORDINATE SECURITY SYSTEM OUTAGE

TIME WITH CONTRACTING OFFICER.

3. REMOVE SECURITY EQUIPMENT, CABLING TO SOURCE, AND

COMPONENTS SCHEDULED FOR DEMOLITION IN A MANNER TO

PRESERVE THE APPEARANCE AND OPERABILITY TO THE EXTENT

POSSIBLE.

4. STOP REMOVAL WHERE DAMAGE WOULD OCCUR IF FURTHER

REMOVAL OCCURRED.

5. WHERE POSSIBLE USE PRE-EXISTING HOLES AND PATHWAYS OF

THE PREVIOUS INTRUSION DETECTION SYSTEM TO ROUTE NEW

SECURITY CABLES.

EXISTING TO REMAIN.

ES

ES

ES

ES

ES

1. THERE ARE TWO SEPARATE EXISTING INTRUSION DETECTION

SYSTEMS. ONE IS KNOW AS THE "HOUSE" (HS) WHICH

SUPPORTS THE PERIMETER OF THE BUILDING AND IS DISARMED

WHEN THE FACILITY IS OPENED. THE SECOND SYSTEM, KNOWN

AS THE "EXHIBIT" (ES) SUPPORTS ALARMS FOR THE EXHIBITS

INSIDE THE FACILITY. THIS SYSTEM REMAINS ARMED DURING

OPERATION.

2. MAINTAIN EXISTING SECURITY DEVICES OPERATIONALLY AS

LONG AS POSSIBLE. COORDINATE SECURITY SYSTEM OUTAGE

TIME WITH CONTRACTING OFFICER.

3. REMOVE SECURITY EQUIPMENT, CABLING TO SOURCE, AND

COMPONENTS SCHEDULED FOR DEMOLITION IN A MANNER TO

PRESERVE THE APPEARANCE AND OPERABILITY TO THE EXTENT

POSSIBLE.

4. STOP REMOVAL WHERE DAMAGE WOULD OCCUR IF FURTHER

REMOVAL OCCURRED.

5. WHERE POSSIBLE USE PRE-EXISTING HOLES AND PATHWAYS OF

THE PREVIOUS INTRUSION DETECTION SYSTEM TO ROUTE NEW

SECURITY CABLES.

HS

ES

ES

HS

ES

HS

HS

PM PM PM PM PM PM

HS ES

HS HS

HS

HS

HS

HS

HS

HS

HS

HS HS

HS

HS

ES

ES

ES

ES

ES

ES

HS

ES

HS

HSPM

PM

PM

PM

PMPMPM

PM

PM

PM

PM

PM

PM

PM

PM

PM

PM

HS

ES

1. REPLACE THE EXISTING TWO SEPARATE IDS PANELS WITH A

SINGLE, PARTITIONS SYSTEM. PROGRAM "HOUSE" (HS) AND

"EXHIBIT" (ES) ALARMS ON SEPARATE PARTITIONS.

2. PROVIDE NEW INTRUSION DETECTION DEVICES IN SAME

LOCATION AS THE EXISTING TO BE REMOVED DEVICES.

3. MOUNT DEVICES AND RUN CABLING IN A MANNER THAT THEY

FUNCTION BUT BLEND INTO THE HISTORIC ARCHITECTURE OF

THE BUILDING. THIS INCLUDES MOUNTING DEVICES IN CORNERS

OR ADJACENT TO TRIM OR MOLDING, SO THAT THEY BLEND.

WHEN REQUIRED PROVIDE NEW WIRE MOLD (PANDUIT) TO

CONCEAL CABLING.

4. PAINT ALL CABLING AND/OR WIRE MOLD TO MATCH WALL/

CEILING.

5. ROUTE CABLING FOR FIRST FLOOR DEVICES TO THE BASEMENT.

6. FINAL FIELD DEVICE LOCATIONS TO BE DETERMINED BASED ON

THE FINAL ROOM CONFIGURATION. COORDINATE SENSOR

LOCATION AND COVERAGE PATTERNS BASED ON FINAL EXHIBIT

LAYOUT AND VISITOR PATHWAYS. SOME DEVICES MAY REQUIRE

MASKING OR REPOSITIONING TO PROVIDE COVERAGE OF THE

EXHIBITS WHILE ALLOWING FOR VISITOR IMMERSIVE SPACE.

7. MOUNT ALL SECURITY DEVICES A MINIMUM OF 1'-0" FROM

SPRINKLER HEAD(S).

8. WHERE POSSIBLE USE PRE-EXISTING HOLES AND PATHWAYS OF

THE PREVIOUS INTRUSION DETECTION SYSTEM TO ROUTE NEW

SECURITY CABLES.

PROVIDE CAMERA ABOVE WINDOW. RUN WIRE DOWN NEXT TO

WINDOW FRAME TO BASEMENT.

PROVIDE CAMERA ABOVE SECURITY DEVICES.

PROVIDE CAMERA ABOVE DOOR IN WOOD CEILING.

MOUNT DEVICE ABOVE DOOR. RUN WIRE DOWN TRIM,

THROUGH FLOOR, TO BASEMENT.

PROVIDE CAMERA ABOVE ARCH. RUN WIRE DOWN SIDE OF

ARCH.

ROUTE CABLING INTO NORTH ATTIC THEN DOWN CHASE TO

BASEMENT.

PROVIDE CAMERA ABOVE DOOR. ACCESS THROUGH ATTIC

SPACE ON THE OTHER SIDE.

CHASE FROM NORTH ATTIC TO BASEMENT.

INSTALL TWO KEY PADS. ONE ARMS/DISARMS THE "HOUSE"

DEVICE, THE OTHER THE "EXHIBIT" DEVICES.

TELEPHONE LINE. EXISTING TO REMAIN.

MOUNT CAMERA BETWEEN WOODEN BEAMS, ENSURING

INTENDED FIELD OF VIEW IS VISIBLE.

ES

ES

ES

ES

ES

1. REPLACE THE EXISTING TWO SEPARATE IDS PANELS WITH A

SINGLE, PARTITIONS SYSTEM. PROGRAM "HOUSE" (HS) AND

"EXHIBIT" (ES) ALARMS ON SEPARATE PARTITIONS.

2. PROVIDE NEW INTRUSION DETECTION DEVICES IN SAME

LOCATION AS THE EXISTING TO BE REMOVED DEVICES.

3. MOUNT DEVICES AND RUN CABLING IN A MANNER THAT THEY

FUNCTION BUT BLEND INTO THE HISTORIC ARCHITECTURE OF

THE BUILDING. THIS INCLUDES MOUNTING DEVICES IN CORNERS

OR ADJACENT TO TRIM OR MOLDING, SO THAT THEY BLEND.

WHEN REQUIRED PROVIDE NEW WIRE MOLD (PANDUIT) TO

CONCEAL CABLING.

4. PAINT ALL CABLING AND/OR WIRE MOLD TO MATCH WALL/

CEILING.

5. ROUTE CABLING FOR DEVICES ON THE SECOND FLOOR INTO

MAIN ATTIC.

6. FINAL FIELD DEVICE LOCATIONS TO BE DETERMINED BASED ON

THE FINAL ROOM CONFIGURATION. COORDINATE SENSOR

LOCATION AND COVERAGE PATTERNS BASED ON FINAL EXHIBIT

LAYOUT AND VISITOR PATHWAYS. SOME DEVICES MAY REQUIRE

MASKING OR REPOSITIONING TO PROVIDE COVERAGE OF THE

EXHIBITS WHILE ALLOWING FOR VISITOR IMMERSIVE SPACE.

7. MOUNT ALL SECURITY DEVICES A MINIMUM OF 1'-0" FROM

SPRINKLER HEAD(S).

8. WHERE POSSIBLE USE PRE-EXISTING HOLES AND PATHWAYS OF

THE PREVIOUS INTRUSION DETECTION SYSTEM TO ROUTE NEW

SECURITY CABLES.

ROUTE CABLING DOWN CHASE TO NETWORK SWITCH IN

BASEMENT.

1. REPLACE THE EXISTING TWO SEPARATE IDS PANELS WITH A

SINGLE, PARTITIONS SYSTEM. PROGRAM "HOUSE" (HS) AND

"EXHIBIT" (ES) ALARMS ON SEPARATE PARTITIONS.

2. MOUNT DEVICES AND RUN CABLING IN A MANNER THAT THEY

FUNCTION BUT BLEND INTO THE HISTORIC ARCHITECTURE OF

THE BUILDING. THIS INCLUDES MOUNTING DEVICES IN

CORNERS OR ADJACENT TO TRIM OR MOLDING, SO THAT

THEY BLEND. WHEN REQUIRED PROVIDE NEW WIRE MOLD

(PANDUIT) TO CONCEAL CABLING.

3. PAINT ALL CABLING AND/OR WIRE MOLD TO MATCH WALL/

CEILING.

4. FINAL FIELD DEVICE LOCATIONS TO BE DETERMINED BASED

ON THE FINAL ROOM CONFIGURATION. COORDINATE SENSOR

LOCATION AND COVERAGE PATTERNS BASED ON FINAL

EXHIBIT LAYOUT AND VISITOR PATHWAYS. SOME DEVICES

MAY REQUIRE MASKING OR REPOSITIONING TO PROVIDE

COVERAGE OF THE EXHIBITS WHILE ALLOWING FOR VISITOR

IMMERSIVE SPACE.

5. MOUNT ALL SECURITY DEVICES A MINIMUM OF 1'-0" FROM

SPRINKLER HEAD(S).

MOUNT CELLULAR ANTENNA ON UPPER FLOOR. CONCEAL

DEVICE AND WIRES TO CELLULAR COMMUNICATOR. LOCATE

ANTENNA WHERE SYSTEM WILL RECEIVE CELLULAR SIGNAL

MOUNT SECURITY DEVICES BENEATH THE STAIR SO THEY ARE

NOT VISIBLE TO VISITORS.

LOCATE ANTENNA WHERE SYSTEM WILL RECEIVE CELLULAR

SIGNAL.

1. REPLACE THE EXISTING TWO SEPARATE IDS PANELS WITH A

SINGLE, PARTITIONS SYSTEM. PROGRAM "HOUSE" (HS) AND

"EXHIBIT" (ES) ALARMS ON SEPARATE PARTITIONS.

2. MOUNT DEVICES AND RUN CABLING IN A MANNER THAT THEY

FUNCTION BUT BLEND INTO THE HISTORIC ARCHITECTURE OF

THE BUILDING. THIS INCLUDES MOUNTING DEVICES IN

CORNERS OR ADJACENT TO TRIM OR MOLDING, SO THAT

THEY BLEND. WHEN REQUIRED PROVIDE NEW WIRE MOLD

(PANDUIT) TO CONCEAL CABLING.

3. PAINT ALL CABLING AND/OR WIRE MOLD TO MATCH WALL/

CEILING.

4. FINAL FIELD DEVICE LOCATIONS TO BE DETERMINED BASED

ON THE FINAL ROOM CONFIGURATION. COORDINATE SENSOR

LOCATION AND COVERAGE PATTERNS BASED ON FINAL

EXHIBIT LAYOUT AND VISITOR PATHWAYS. SOME DEVICES

MAY REQUIRE MASKING OR REPOSITIONING TO PROVIDE

COVERAGE OF THE EXHIBITS WHILE ALLOWING FOR VISITOR

IMMERSIVE SPACE.

5. MOUNT ALL SECURITY DEVICES A MINIMUM OF 1'-0" FROM

SPRINKLER HEAD(S).

MOUNT CELLULAR ANTENNA ON SECOND FLOOR. CONCEAL

DEVICE AND WIRES TO CELLULAR COMMUNICATOR. LOCATE

ANTENNA WHERE SYSTEM WILL RECEIVE CELLULAR SIGNAL.

RELOCATE TELEPHONE LINE.

1. REPLACE THE EXISTING TWO SEPARATE IDS PANELS WITH A

SINGLE, PARTITIONS SYSTEM. PROGRAM "HOUSE" (HS) AND

"EXHIBIT" (ES) ALARMS ON SEPARATE PARTITIONS.

2. MOUNT DEVICES AND RUN CABLING IN A MANNER THAT THEY

FUNCTION BUT BLEND INTO THE HISTORIC ARCHITECTURE OF

THE BUILDING. THIS INCLUDES MOUNTING DEVICES IN CORNERS

OR ADJACENT TO TRIM OR MOLDING, SO THAT THEY BLEND.

WHEN REQUIRED PROVIDE NEW WIRE MOLD (PANDUIT) TO

CONCEAL CABLING.

3. PAINT ALL CABLING AND/OR WIRE MOLD TO MATCH WALL/

CEILING.

4. FINAL FIELD DEVICE LOCATIONS TO BE DETERMINED BASED ON

THE FINAL ROOM CONFIGURATION. COORDINATE SENSOR

LOCATION AND COVERAGE PATTERNS BASED ON FINAL EXHIBIT

LAYOUT AND VISITOR PATHWAYS. SOME DEVICES MAY REQUIRE

MASKING OR REPOSITIONING TO PROVIDE COVERAGE OF THE

EXHIBITS WHILE ALLOWING FOR VISITOR IMMERSIVE SPACE.

5. MOUNT ALL SECURITY DEVICES A MINIMUM OF 1'-0" FROM

SPRINKLER HEAD(S).

DETAIL KEY NOTES:

1. RACK CABINET

2. PoE NETWORK SWITCH, 12 PORT

3. PoE NETWORK SWITCH, 24 PORT

4. NETWORK VIDEO RECORDER

5. WORK STATION

6. UNINTERRUPTED POWER SUPPLY

7. BLANK PLATE

DETAIL KEY NOTES:

1. ALARM PANEL

2. CELLULAR COMMUNICATOR

3.BATTERY

4. TAMPER DEVICE

DETAIL KEY NOTES

1. CEILING SLAB

2. CONCEALED CABLING TO

SECURITY PANEL

3. IDS KEYPAD WITH DOUBLE

GANG BACK BOX

4. SUSPENDED CEILING

DETAIL NOTES

A. DETAIL IS DIAGRAMMATIC.

B. REFER TO NOTES AND

SPECIFICATIONS FOR SECURITY

WIRING INFRASTRUCTURE

REQUIREMENTS.

3'-

1. CEILING SLAB

2. CONCEALED CABLING TO

SECURITY PANEL, CABLE

MAY ROUTE UP OR DOWN

BASED ON LOCATION

3. IDS KEYPAD

4. CEILING

DETAIL NOTES:

A. MOTION DETECTOR SHALL BE MOUNTED AT 6 TO

8 FEET ABOVE FINISHED FLOOR (H).

B. ADJUST THE MOUNTING HEIGHT, AIM AND LENS

TO ACHIEVE COVERAGE OF SECURED AREA AT

EACH LOCATION.

C. PERFORM DETECTOR TESTS PER

SPECIFICATIONS AND IN ACCORDANCE WITH

MANUFACTURERS RECOMMENDATIONS.

D. VERIFY PARTITION TYPE FOR EACH LOCATION.

CONDUIT SUPPORTING MOTION DETECTOR

SHOULD RUN IN CHASE PARTITION.

DETAIL KEY NOTES:

1. CONCEALED CABLING TO SECURITY

PANEL. CABLE MAY ROUTE UP OR

DOWN BASED ON LOCATION

2. WALL MOUNTED DETECTOR

3. WALL

DETAIL KEY NOTES:

1. HATCH

2. MAGNET WITH SPACER

3. DOOR POSITION SWITCH

4. DOOR POSITION SWITCH

CABLING TO SECURITY PANEL

DETAIL NOTES:

A. DETAIL IS DIAGRAMMATIC,

COORDINATE REQUIREMENTS

WITH DIVISION 8 CONTRACTOR.

DETAIL NOTES:

6"

1. CONTRACTOR TO CONFIRM

RESISTOR NETWORK/VALUES

PRIOR TO START OF WORK.

2. REFER TO MANUFACTURERS

INSTRUCTIONS FOR MOUNTING

REQUIREMENTS.

DETAIL KEY NOTES:

1. DOOR CONTACT

2. CONCEALED CABLE TO

SECURITY PANEL

3. DOOR FRAME

4. DOOR

DETAIL KEY NOTES:

1. CEILING

2. CONCEALED CABLING, ROUTE UP

OR DOWN BASED ON LOCATION

3. INTERIOR DOME CAMERA

4. FINISHED FLOOR

DETAIL NOTES:

A. DETAIL IS DIAGRAMMATIC, THE CAMERA MOUNTING ASSEMBLY VARIES WITH MANUFACTURER.

B. MOUNT CAMERA ASSEMBLY AT MOST DESIRABLE HEIGHT ABOVE FINISHED FLOOR TO AVOID

OBSTRUCTIONS AND TO PROVIDE THE FIELD-OF-VIEW DESIRED.

C. ALL CAMERA ASSEMBLIES SHALL BE FIRMLY ATTACHED TO SUBSTANTIAL WALL SURFACES OR

STRUCTURAL MEMBERS.

D. COORDINATE THE CAMERA LOCATION WITH OTHER DISCIPLINES TO PROVIDE REQUIRED

VIDEO COVERAGE.

E. COORDINATE FINAL CAMERA VIEWS WITH THE CONTRACTING OFFICER.

SIDE VIEW

MI

N

9'

1ST FLOOR

2ND FLOOR

ATTIC

BASEMENT

SECURITY RACK

ROOM 005

PoE NETWORK SWITCH 1

PoE NETWORK SWITCH 2

NVR

WORK STATION

UPS

ROOM 005ARLINGTON HOUSE

2ND FLOOR

ATTIC

BASEMENT

HS: 009

HS: 001

ROOM #

HS: 001

HS: 003

ES: 003

HS: 002

ES: 002

ES: 002

HS: 116

ROOM #

HS: 117

ES: 117

ROOM #

HS: 116

ES: 117

ES: 114

HS: 114

HS: 115

HS: 111

HS: 111

HS: 116

HS: 116

ROOM #

HS: 113

HS: 113

HS: 112

HS: 112

HS: 110

ES: 109

ES: 109

ES: 110

ES: 110

HS: 101

HS: 108

ES: 101

HS: 103

HS: 103

ES: 105

ROOM #

ES: 106

ROOM #

ROOM #

ES: 202

ES: 201

ES: 202

ES: 203

ES: 206

ROOM #

ES: 207

CELLULAR COMMUNICATIONS IS THE PRIMARY, POTS LINE IS

SECONDARY.

HS: 111

ES: 107

ROOM #

ES: 301

BASEMENTROOM 003

ROOM #

2ND FLOOR

1ST FLOORROOM 103

ROOM #

1ST FLOORROOM 104

ROOM #

ROOM #

1ST FLOOR

CRAWL SPACE

ATTIC

1st FLOORROOM 101

ROOM #

ROOM 101

CELLULAR COMMUNICATIONS IS THE PRIMARY, POTS LINE IS

SECONDARY.

PoE NETWORK SWITCH SCHEDULE

SWITCH 1

SWITCH INPUT CAMERA #

1 102 2 103 3 201 4 202 5 203 6 204

CAMERA SCHEDULE - INTENDED FIELD OF VIEW

CAMERA # INTENDED FIELD OF VIEW

001 EXTERIOR DOOR

002 EXTERIOR DOOR

003 EXTERIOR DOOR

004 WINTER KITCHEN

101 ENTRANCE TO OFFICE/STUDIO

102 MORNING ROOM

103 MORNING ROOM

104 CONSERVATORY EXIT DOOR

105 STAIR DOOR AND HUNTING HALL

106 WHITE PARLOR

107 EXTERIOR DOOR

108 CENTER HALL ENTRANCE DOOR

109 FAMILY PARLOR

110 DINNING ROOM

111 INNER HALL

112 GUEST CHAMBER

113 OUT HALL EXIT DOOR

114 SCHOOL/SEWING ROOM

201 COLONEL & MRS. LEE'S CHAMBER

202 SMALL CHAMBER AND ENTRANCE DOOR

203 MULTI-LENS COVER ALL HALLWAYS

204 LEE GIRLS' CHAMBER AND ENTRANCE DOOR

SWITCH 2

SWITCH INPUT CAMERA #

1 001 2 002 3 003 4 004 5 101 6 104 7 105 8 106 9 107

10 108 11 109 12 110 13 111 14 112 15 113 16 114

X

H

XX

C

C

C

C

C

FIRE

FINISHED FLOOR

D

D D

D

D D

DD

D D

DD

M0.1 Mechanical Cover Sheet
MD.0 Mechanical Site Plan
MD.1 Demo Main House Basement
MD.2 Demo Main House First Floor
MD.3 Demo Main House Second Floor
MD.4 Demo Main House Attic
MD.5 Demo North Slave Quarters
MD.6 Demo South Slave Quarters
MD.7 Demo Comfort Station
MD.8 Demo Comfort Station
MD.9 Demo Museum
MD.10 Demo HVAC Mechanical Bunker
MD.11 Demo Piping Mechanical Bunker
M0.2 Mechanical Site Plan
M1.1 HVAC Main House Basement
M1.2 HVAC Main House First Floor
M1.3 HVAC Main House Second Floor
M1.4 HVAC Main House Attic
M1.5 HVAC North Slave Quarters
M1.6 HVAC South Slave Quarters
M1.7 HVAC Comfort Station
M1.8 HVAC Comfort Station
M1.9 Plumbing Comfort Station
M1.10 Plumbing Comfort Station
M1.11 HVAC Museum
M1.12 HVAC Mechanical Bunker
M1.13 Piping Mechanical Bunker
M2.1 Mechanical Details
M2.2 Mechanical Details
M3.1 Mechanical Schedules
M4.1 Mechanical Controls
M4.2 Mechanical Controls
M4.3 Mechanical Controls
E0.1 Electrical Legend
E0.2 Electrical Conv Abbrev
E0.3 Electrical Site Plan Demo
E0.4 Electrical Site Plan New
ED.1 Demo Main House Basement
ED.2 Demo Main House First Floor
ED.3 Demo Main House Second Floor
ED.4 Demo Main House Attic
ED.5 Demo North Slave Quarters
ED.6 Demo South Slave Quarters
ED.7 Demo Comfort Station
ED.8 Demo Museum
ED.9 Demo Mechanical Bunker
E1.1 Lighting Main House Basement
E1.2 Lighting Main House First Floor
E1.3 Lighting Main House Second Floor
E1.4 Lighting Main House Attic
E1.5 Lighting North Slave Quarters
E1.6 Lighting South Slave Quarters
E1.7 Lighting Comfort Station
E1.8 Lighting Museum
E1.9 Lighting Mechanical Bunker
E2.1 Power Main House Basement
E2.2 Power Main House First Floor
E2.3 Power Main House Second Floor
E2.4 Power Main House Attic
E2.5 Power North Slave Quarters
E2.6 Power South Slave Quarters
E2.7 Power Comfort Station
E2.8 Power Museum
E2.9 Power Mechanical Bunker
E2.10 Mech Bunker Elevation
E4.1 Electrical Part Plans
E4.2 Electrical Part Plans
E5.1 Electrical Details
E5.2 Electrical Details
E6.1 One Line Existing
E6.2 One Line New
E6.3 Electrical Grounding
E7.1 Electrical Schedules
E7.2 Electrical Schedules
E7.3 Electrical Schedules
E7.4 Electrical Schedules
E7.5 Electrical Schedules
E7.6 Electrical Schedules
E7.7 Electrical Schedules
E7.8 Electrical Schedules
E7.9 Electrical Schedules
E7.10 Electrical Schedules
E8.1 Luminaire
E8.2 Luminaire
E8.3 Luminaire
E8.4 Luminaire
E8.5 Lighting Control
E8.6 Lighting Control
E8.7 Lighting Control
ES0.1 REFERENCE PLAN
ES0.2 SITE PLAN
ES1.0 ARLINGTON HOUSE DEMOLITION
ES1.1 ARLINGTON HOUSE DEMOLITION
ES1.2 ARLINGTON HOUSE NEW WORK
ES1.3 ARLINGTON HOUSE NEW WORK
ES1.4 NORTH & SOUTH SLAVE QUARTERS HOUSE NEW WORK
ES1.5 COMFORT STATION & MECHANICAL BUNKER NEW WORK
ES1.6 MUSEUM NEW WORK
ES5.1 DETAILS
ES5.2 DETAILS
ES6.1 ONE-LINE DIAGRAMS
ES6.2 ONE-LINE DIAGRAMS
ES6.3 ONE-LINE DIAGRAMS
ES71 SCHEDULES
FA0.1 REFERENCE PLAN
FA1.0 ARLINGTON HOUSE DEMOLITION
FA1.1 ARLINGTON HOUSE DEMOLITION
FA1.2 ARLINGTON HOUSE NEW WORK
FA1.3 ARLINGTON HOUSE NEW WORK
FA1.4 NORTH SLAVE QUARTERS DEMOLITION AND NEW WORK
FA1.5 SOUTH SLAVE QUARTERS DEMOLITION AND NEW WORK
FA1.6 MUSEUM NEW WORK
FA1.7 MECHANICAL BUNKER
FA5.1 DETAILS
SP0.1 REFERENCE PLAN
SP0.2 SITE PLAN
SP1.0 NORTH SLAVE QUARTERS DEMOLITION AND NEW WORK
SP1.1 SOUTH SLAVE QUARTERS NEW WORK
SP1.2 MUSEUM NEW WORK
SP5.1 DETAILS