This is an Installation Instructions manual for FB4C and FY5B Puron fan coil units designed for residential and manufactured housing applications with cooling capacities from 18,000 to 60,000 Btuh. The manual provides comprehensive guidance for qualified installers on proper installation, configuration, and maintenance of these HVAC components.
The FB4C model features a refrigerant piston metering device (sizes 018-048) and thermostatic expansion valve (TXV) for the 060 size, paired with an X13 electronically commutated motor for efficiency. The FY5B uses piston metering devices (sizes 018-048) with 2-speed permanent split capacitor (PSC) motors, plus TXV with 3-speed PSC motor for the 060 size. Both units support upflow, downflow (with conversion kits), and horizontal installations. Factory-authorized field-installed electric heater packages are available in 5-30kW sizes. Critical installation procedures include mounting the unit with proper clearances (21-24 inches front service clearance depending on size), connecting supply air ducts to 3/4-inch flanges with flexible connectors, making refrigerant tubing connections using sweat joints and brazing to 500 microns vacuum specification, and installing primary and secondary condensate drain lines with properly-sized traps minimum 2 inches below connections. Electrical connections require separate branch circuits with field-supplied disconnect switches, 24V low-voltage wiring per NEC Class 1 standards using 18 AWG wire (or 16 AWG if exceeding 100 feet), and transformer configuration for 208V or 230V operation. Motor speed selection varies by model: FB4C uses speed taps 1-5 at the motor with 90-second blower delay pre-programmed on taps 1-3, while FY5B uses relay terminal SPT selection with low and high speed options (medium for 060 size). The manual includes detailed airflow performance tables for various static pressures and configurations, safety warnings regarding electrical hazards and proper refrigerant handling for Puron (R-410A), and maintenance requirements emphasizing monthly filter replacement or cleaning.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FB4C
FY5B
Installation Instructions
FAN COIL UNITS
FOR PURONr REFRIGERANT
SIZES 018 TO 060
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1
INTRODUCTION 1
HEATER PACKAGES 2
INSTALLATION 2
Step 1 — Check Equipment 2
Step 2 — Mount Unit 2
Step 3 — Air Ducts 4
Step 4 — Electrical Connections 4
Step 5 — Refrigerant Tubing Connection and Evacuation 7. .
Step 6 — Refrigerant Flow--Control Device 7
Step 7 — Condensate Drains 8
Step 8 — Accessories 9
Step 9 — Sequence of Operation 10
START--UP PROCEDURES 10
CARE AND MAINTENANCE 10
AIRFLOW PERFORMANCE TABLES 11
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol .
When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to unit. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Lock out and tag switch with a suitable warning label.
! WARNING
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
CAUTION!
INTRODUCTION
Models FB4C and FY5B are Puron Fan Coils designed for installation flexibility. These units are designed to meet the low air leak requirements currently in effect.
FB4C uses a refrigerant piston metering device (018 thru 048) and TXV (060) with an X13 integral electronically commutated motor for efficiency. These units have be designed for upflow, downflow (kit required), and horizontal orientations, including manufactured and mobile home applications.
FY5B uses a refrigerant piston metering device (018 thru 048) with 2--speed PSC (permanent split capacitor) motors and TXV with 3--speed PSC motor for the 060 size, These units can be used for upflow or downflow (kit required) orientations, including manufactured and mobile homes applications.
These units require a field supplied air filter, and are designed specifically for Puron refrigerant air conditioners and heat pumps as shipped. These units are available for systems of 18,000 through 60,000 Btuh nominal cooling capacity. Factory--authorized, field --installed electric heater packages are available in sizes 5 through 30kW. See Product Data literature for all available accessory kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package. For units not equipped with factory--installed heat, a factory--approved, field--installed, UL listed heater package is available from your equipment supplier. See unit rating plate for a list of factory--approved heaters. Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty. If fan coil contains a factory--installed heater package, minimum circuit ampacity (MCA) and maximum fuse/breaker may be different than units with a same size field--installed accessory heater. The differences is not an error and is due to calculation difference per UL guidelines.
INSTALLATION
Step 1 — Check Equipment Unpack unit and move to final location. Remove carton taking care not to damage unit. Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete.
Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
Step 2 — Mount Unit Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require a field--supplied secondary condensate pan to be installed under the entire unit.
Some localities may allow as an alternative, the running of a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
A. Upflow Installation If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4--in (3 to 6 mm) thick fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions. (See Fig. 1.) A field--supplied bottom closure is required.
A COIL
UNITS
POWER ENTRY
OPTIONS
LOW VOLT
ENTRY
OPTIONS
FIELD MODIFIED
SIDE RETURN
LOCATION FOR
SLOPE COIL
UNITS ONLY
FIELD SUPPLIED
RETURN PLENUM
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
UNIT
024 - 030
A 12" (305 mm) 17" (432 mm)
A
1.5" (38 mm)
2.5" (64 mm)
19" (483 mm)
FIELD SUPPLIED
SUPPLY DUCT
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
036 19" (483 mm)
018 - 048 21" (533 mm) FRONT SERVICE 060 - 060 24" (610mm) CLEARANCE
A07565
Fig. 1 -- Slope Coil Unit in Upflow Application
B. Downflow Installation In this application, field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit.
Use fireproof resilient gasket, 1/8 to 1/4--in (3 to 6 mm) thick, between duct, unit, and floor.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A--coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow.
During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
CAUTION!
NOTE: To convert units for downflow applications, refer to Installation Instructions supplied with kit for proper installation.
For slope fan coils, use kit Part No. KFADC0201SLP. For A--coils, use kit Part No. KFADC0401ACL. Use fireproof resilient gasket, 1/8 to 1/4--in (3 to 6 mm) thick, between duct, unit, and floor.
NOTE: Gasket kit number KFAHD0101SLP is also required for all downflow applications to maintain low air leak/low sweat performance.
C. Horizontal Installation (FB4C only) Units must not be installed with access panels facing up or down.
All other units are factory built for horizontal left installation. (See Fig. 2 and 3.) When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps. (See Fig. 2.)
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
For optimum condensate drainage performance in horizontal installations, unit should be leveled along its length and width.
CAUTION!
For horizontal applications having high return static and humid return air, the Water Management Kit, KFAHC0125AAA, may need to be used to assist in water management.
UNIT
FIELD
SUPPLIED
HANGING
STRAPS
LOW VOLT
ENTRY
OPTIONS
POWER
ENTRY OPTIONS
SECONDARY
DRAIN
018-048 21" (533 mm) 060-060 24" (610 mm)
FRONT SERVICE
CLEARANCE
(FULL FACE
OF UNIT)
SECONDARY
DRAIN
A-COIL
HORIZONTAL LEFT
PRIMARY
DRAIN
PRIMARY
DRAIN
1.75" (44 mm)
FILTER ACCESS
CLEARANCE
A07566
Fig. 2 -- Slope Coil Unit in Horizontal Left Application (FB4C only)
FB
4C /F Y5 B
A
B C
FACT OR Y SHIPPED
HORIZONTAL LEFT
APPLICATION
AIR SEAL
ASSEMBLY
HORIZONTAL
DRAIN PAN
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
HORIZONTAL LEFT
PRIMARY DRAIN
HORIZONTAL LEFT
COI L
SUPPORT
RAIL
COIL
BRACKET
DRAIN PA N
SUPPORT
BRACKET
COIL
BRACKET
A00072
Fig. 3 -- A--Coil in Horizontal Left Application (Factory Ready FB4C only)
NOTE: Modular units can be disassembled and components moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites. (See Fig. 4.)
2 SCREWS
2 SCREWS
REAR CORNER
BRACKET
BLOWER BOX
COIL BOX
2 SCREWS
A95293
Fig. 4 -- Removal of Brackets on Modular Units Horizontal Right Conversion of Units With Slope Coils (FB4C only)
NOTE: Gasket kit number KFAHD0101SLP is required for horizontal slope coil conversion to maintain low air leak/low sweat performance.
1. Remove blower and coil access panel and fitting panel. (See Fig. 5.)
2. Remove coil mounting screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down. (See Fig. 5.)
5. Attach coil to casing flange using coil mounting screw pre-viously removed.
6. Make sure the pan cap in the fitting door is properly seated on the fitting door to retain the low air leak rating of the unit.
7. Add gaskets from kit KFAHD per kit instructions.
8. Align holes with tubing connections and condensate pan connections, and reinstall access panels and fitting panel.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install after brazing.
COIL MOUNTING
SCREW
BLOWER
ASSEMBLY
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
PRIMARY DRAINDRAINPAN
SLOPE COIL
SKI
COIL
SUPPORT
RAIL
A03001
Fig. 5 -- Conversion for Horizontal Right Applications Using a Slope Coil (FB4C only)
Horizontal Right Conversion of Units With A--Coils
1. Remove blower and coil access panels. (See Fig. 6.)
COIL
SUPPORT
RAIL
COIL
BRACKET
DRAIN PAN
SUPPORT
BRACKET
COIL
SUPPORT
RAIL
COIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIMARY DRAIN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
REFRIGERANT
CONNECTIONS
AIR SEAL
ASSEMBLY
A
B C
HORIZONTAL
RIGHT
APPLICATION
A00071
Fig. 6 -- Conversion for Horizontal Right Applications Using A--Coil (FB4C only)
2. Remove metal clip securing fitting panel to condensate pan.
Remove fitting panel.
3. Remove 2 snap--in clips securing A--coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil sup-port rail on left side of unit and reinstall on coil support rail on right side of unit. (See Fig. 7.)
DRAIN PAN DRAIN PAN
SUPPORT BRACKETSUPPORT BRACKET
A07571
Fig. 7 -- Drain Pan Support Bracket
6. Convert air--seal assembly for horizontal right.
a. Remove air--seal assembly from coil by removing 4 screws. (See Fig. 6.)
b. Remove air splitter (B) from coil seal assembly by re-moving 3 screws. (See Fig. 3--factory shipped inset.)
FB
4C /F
c. Remove filter plate (A) and install air splitter (B) in place of filter plate.
d. Install filter plate (A) as shown in horizontal right ap-plication.
e. Remove condensate troughs (C) and install on opposite tube sheets.
f. Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails.
9. Reinstall 2 snap--in clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure horizontal pan.
10. Remove two oval fitting caps from the left side of the coil door and fitting panel.
11. Remove insulation knockouts on right side of coil access panel.
12. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
13. Install condensate pan fitting caps (from item 10) in the right side of the coil door making sure that the cap snaps and seats cleanly on the back side of the coil door. Make sure no insulation interferes with seating of the cap.
14. Reinstall access fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to re-install metal clip between fitting panel and vertical condens-ate pan.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
D. Manufactured and Mobile Home Housing Applications
1. Fan coil unit must be secured to the structure using field--supplied hardware.
2. Allow a minimum of 24--in (610 mm) clearance from access panels.
3. Recommended method of securing for typical applications:
a. If fan coil is away from wall, attach pipe strap to top of fan coil using no. 10 self--tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16--in. lag screws. Typical both sides of fan coil.
DOWN FLOW
BASE KIT (KFACB)
UNIT AGAINST WALL
.125" (3mm)
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
(TYPICAL BOTH SIDES)
OR
SECURE UNIT TO FLOOR
ANGLE BRACKET OR PIPE STRAP
4” (102mm) MAX
4” (102mm) MAX
A07567
Fig. 8 -- A--Coil
b. If fan coil is against wall, secure fan coil to wall stud using 1/8--in (3 mm) thick right--angle brackets. Attach brackets to fan coil using no. 10 self--tapping screws and to wall stud using 5/16--in. lag screws. (See Fig. 8.)
Step 3 — Air Ducts Connect supply--air duct over the outside of 3/4--in (19 mm) flanges provided on supply--air opening. Secure duct to flange, using proper fasteners for type of duct used, and seal duct--to--unit joint. If return--air flanges are required, install factory--authorized accessory kit.
Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat--resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.
Units equipped with 20--30kW electric heaters require a 1--in (25
mm) clearance to combustible materials for the first 36--in (914
mm) of supply duct.
Ductwork Acoustical Treatment
Metal duct systems that do not have a 90_ elbow and 10--ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts.
Step 4 — Electrical Connections FY5B units from the factory utilize a printed--circuit board (PCB) which has a low voltage circuit protective fuse (5 amp), fan motor speed tap selection terminal (SPT), and time delay relay (TDR) jumper. To disable the TDR feature, sever the jumper wire JW1.
(See Fig. 9.)
FB4C units from the factory protect the low voltage circuit with a 3 amp automotive type fuse in--line on the wire harness and Does Not contain a circuit board. Motor speeds and time delay function are built into the motor (see section E for clarification).
When a factory--approved accessory control package has been installed, check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation. If a different control package is required, see unit rating plate.
C P
C -E
V
-0
LR40061
H S
C I
A
M P
C T G R
S P
T
K
U
R7 R9 R10
C8
C7
R2 R3 C3 R6
R11
C4
C6
C5 R8
R5 R4
Q1
C1C2
F1
JW
R1 Z1
D2
D1
NO
NC
FA
N
R E
LA
Y
C
C
A03010
Fig. 9 -- Fan Coil Printed Circuit Board for FY5B Model
FB
4C /F
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If a disconnect switch is to be mounted on unit, select a location where drill or fastener will not contact electrical or refrigerant components.
CAUTION!
Before proceeding with electrical connections, make certain that supply voltage, frequency, phase, and ampacity are as specified on the unit rating plate. See unit wiring label for proper field high--and low--voltage wiring. Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply. Use copper wire only.
The unit must have a separate branch electric circuit with a field--supplied disconnect switch located within sight from, and readily accessible from, the unit.
On units with a factory--installed disconnect with pull--out removed, service and maintenance can be safely performed on only the load side of the control package.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Field wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull--out is removed.
Service and maintenance to incoming wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off.
! WARNING
A. Line Voltage Connections If unit will contain accessory electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation Instructions.)
For units without electric heater:
1. Connect 208/230v power leads from field disconnect to yel-low and black stripped leads.
2. Connect ground wire to unit ground lug.
NOTE: Units installed without electric heat should have a field--supplied sheet metal block--off plate covering the heater opening. This will reduce air leakage and formation of exterior condensation.
B. 24--v Control System Connection To Unit
Wire low voltage in accordance with wiring label on the blower.
(See Fig. 10 through 15.) Use no. 18 AWG color--coded, insulated (35_C minimum) wire to make the low--voltage connections between the thermostat, the unit, and the outdoor equipment. If the thermostat is located more than 100--ft (30 m) from the unit (as measured along the low--voltage wire), use no. 16 AWG color--coded, insulated (35_C minimum) wire. All wiring must be NEC Class 1 and must be separated from incoming power leads.
R
G
W
Y
THERMOSTAT
RED
GRY
WHT
BLU
VIO
BRN
WHT
R
G
W2
W3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
A94058
Fig. 10 -- Wiring Layout Air Conditioning Unit (Cooling Only)
R
G
W
Y
THERMOSTAT
R
G
W2
W3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
RED
GRY
WHT
WHT
BLU
VIO
BRN
A94059
Fig. 11 -- Wiring Layout Air Conditioning Unit (Cooling and 1--Stage Heat)
R
G
C
E
L
O
Y
THERMOSTAT
R R
C
O
Y
G
C
W2
W2
W2 W3
E
FAN COIL
(CONTROL) HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
BLU
VIO
A94060
Fig. 12 -- Wiring Layout Heat Pump Unit (Cooling and 2--Stage Heat with
No Outdoor Thermostat)
FB
4C /F
R
G
C
E
L
O
Y
THERMOSTAT
R R
C
O
Y
G
C
W2
W2
W2
W3
E
ODTS
FAN COIL
(CONTROL) HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
VIO
BLU
A94061
Fig. 13 -- Wiring Layout Heat Pump Unit (Cooling and 2--Stage Heat with
1 Outdoor Thermostat)
R
G
C
L
E
O
C 1 4 7 C 9 6 3
Y
THERMOSTAT
R R
C
O
Y
G
C
W2 W2
W2
W3
E
FAN COIL
(CONTROL)
EMERGENCY HEAT RELAY
HEAT PUMP
(CONTROL)
ODTS1
ODTS2
RED
GRY
BRN
WHT
BLU
VIO
A94062
Fig. 14 -- Wiring Layout Heat Pump Unit (Cooling and 2--Stage Heat with 2 Outdoor Thermostats)
R
E
W2
R
C
THERMOSTAT FAN COIL
(CONTROL)
HEAT PUMP
(CONTROL)
G
C
W2
E
L
G
C
R
O
Y
ODTS
O
Y
W3
W2
A03088
Fig. 15 -- Wiring Layout Heat Pump Unit (Cooling and 2--Stage Heat for Manufactured Housing)
Refer to outdoor unit wiring instructions for any additional wiring procedure recommendations.
Transformer Information
Transformer is factory--wired for 230v operation. For 208v applications, disconnect the black wire from the 230v terminal on transformer and connect it to the 208v terminal. (See Fig. 16.)
C
BRN
RED
YEL
BLK
SECONDARY
PRIMARY
A05182
Fig. 16 -- Transformer Connections Heater Staging
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If W2, W3, and E on any 3 stage heater (18, 20, 24, or 30kW) are individually connected as with outdoor thermostats or any other situation, emergency heat relay must be used. This relay is in kit Part No. KHOT0201SEC and is normally used with kit Part No. KHAOT0301FST for 2 outdoor thermostat systems.
CAUTION!
The controls are factory circuited for single--stage operation. For 2--stage operation, use outdoor thermostat kit Part No.
KHAOT0301FST, and for 3--stage use both kits Part No.
KHAOT0201SEC and KHAOT0301FST.
When 2 stages are desired, cut W3 at the W2 wire nut, strip and reconnect per the thermostat kit instruction. (See Fig. 14.) When 3 stages are desired, cut the W2 wire nut off and discard. Strip W2, W3, and E and reconnect per thermostat kit instructions. (See Fig.
14.)
NOTE: When 3 stages are used or anytime the E terminal is not tied to W2, the emergency heat relay, part of outdoor kit Part No.
KHAOT0201SEC must be used.
C. Manufactured Housing In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40_F (4_C), except for a heat pump defrost cycle. Refer to Fig. 15 for typical low voltage wiring with outdoor thermostat.
FB
4C /F
D. Ground Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur.
The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used.
! WARNING
NOTE: Use UL--listed conduit and conduit connector for connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs provided in control box.
E. Minimum CFM and Motor Speed Selection Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated.
FY5B fan speed selection is done at the fan relay printed--circuit board. To change motor speeds, disconnect fan lead used on relay terminal (SPT) and replace with motor speed tap desired. (See Fig.
17.) Save insulating cap and place on motor lead removed from relay.
NOTE: In low static applications, lower motor speed tap should be used to reduce possibility of water being blown off coil.
FY5B have 2 motor speed taps. Low speed (red) and high speed (black). The 060 size only will have a Medium speed (blue).
See Table 2 -- FY5B Airflow Performance (CFM), for each setting.
INSULATING CAP (2)
MOTOR SPEED
TAP LEADS
COMMON YELLOW
FAN DECK
WRAPPER
SPEED TAP
TERMINAL
PCB
FAN RELAY
SINGLE SPADE
A97529
Fig. 17 -- Fan Coil Relay and Speed Tap Terminal for FY5B Models
The fan speed selection on the FB4C models is done at the motor.
Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated. To change motor speeds disconnect the BLUE fan lead from terminal #2 (factory default position) and move to desired speed--tap; 1, 2, 3, or 5.
Speed--taps 1, 2, and 3 have a 90 second blower time delay pre--programmed into the motor. Speed tap 4 is used for electric heat only (with 0 second blower time delay) and the WHITE wire must remain on tap 4. Speed--tap 5 is used for high static applications, but has a 0 second blower time delay pre--programmed into the motor (see Table 1 -- FB4C Airflow Performance (CFM), for each tap setting. Also, see Fig. 18 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should be used to reduce possibility of water being blown off coil.
1 2 3 4 5
A09390
Fig. 18 -- Motor Speed Selection
Step 5 — Refrigerant Tubing Connection and Evacuation Use accessory tubing package or field--supplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow--control device. ALWAYS evacuate the coil and field--supplied tubing to 500 microns before opening outdoor unit service valves.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent damage to the unit surface and condensate pan fitting caps.
CAUTION!
Units have sweat suction and liquid tube connections. Make suction tube connection first.
1. Cut tubing to correct length.
2. Insert tube into sweat connection on unit until it bottoms.
3. Braze connection using silver bearing or non--silver bearing brazing materials. Do not use solder (materials which melt below 800_F / 427_C). Consult local code requirements.
4. Evacuate coil and tubing system to 500 microns using deep vacuum method.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to piston assembly or TXV and factory--made joints.
CAUTION!
Step 6 — Refrigerant Flow--Control Device FB4C and FY5B units contain a factory installed piston with Teflon ring for sizes 018 thru 048 only. The 060 size unit comes equipped with a Puron refrigerant TXV. If a piston replacement is
FB
4C /F required, check piston size shown on indoor unit rating plate to see if it matches required piston shown on outdoor unit rating plate. If it does not match, replace indoor piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor coil combination (See Fig. 19). When changing piston, use a back--up wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ft--lbs.
NOTE: The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Always use outdoor units designed to match indoor fan coil applications.
TEFLON SEAL
BRASS
HEX NUT
STRAINER
PISTON
RETAINER
BRASS
HEX BODY
DISTRIBUTOR
PISTON
FLOW IN
COOLING
TEFLON RING
A09677
Fig. 19 -- Refrigerant Flow -- Control Device
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If using a TXV in conjunction with a single--phase reciprocating compressor, a compressor start capacitor and relay are required. Consult outdoor unit pre--sale literature for start assist kit part number.
CAUTION!
Step 7 — Condensate Drains To connect drains, the cap openings must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the disk. Clean the edge of the opening if necessary and install the condensate line. Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A--coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
CAUTION!
Units are equipped with primary and secondary 3/4--in. FPT drain connections. For proper condensate line installations see Fig. 1, 2, 3, 5 and 6. To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly--sized condensate traps.
(See Fig. 20 and 21.) Factory--approved condensate traps are available. It is recommended that PVC fittings be used on the plastic condensate pan. Finger--tighten plus 1--1/2 turns. Do not over--tighten. Use pipe dope.
2” MIN
(51 mm)
UNIT
2” MIN
(51 mm)
A03002
Fig. 20 -- Recommended Condensate Trap
FILTER
ACCESS
PANEL
SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)
PRIMARY TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF
SUFFICIENT DEPTH.
STANDARD P-TRAPS ARE
NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED
CONDENSATE TRAP)
A03003
Fig. 21 -- Condensate Trap and Unit
FB
4C /F
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Shallow running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 22.)
CAUTION!
DO NOT USE SHALLOW RUNNING TRAPS!
A03013
Fig. 22 -- Insufficient Condensate Trap NOTE: When connecting condensate drain lines, avoid blocking filter access panel, thus preventing filter removal. After connection, prime both primary and secondary condensate traps.
NOTE: If unit is located in or above a living space where damage may result from condensate overflow, a field--supplied, external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan. Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4--in (19 mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing or water damage will occur.
Install traps in the condensate lines as close to the coil as possible.
(See Fig. 21.) Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area. Condensate drain lines should be pitched downward at a minimum slope of 1--in (25 mm) for every 10--ft (3 m) of length. Consult local codes for additional restrictions or precautions.
Step 8 — Accessories A. Electronic Air Cleaner The Electronic Air Cleaner may be connected to fan coil as shown in Fig. 23. This method requires a field supplied transformer. See Electronic Air Cleaner literature for kit requirements.
RFAN RELAY
NO230VAC
COM
NC
NONCSPTWIRE
NUT
TO
BLOWER
MOTOR
CONVERSION KIT
TRANSFORMER
FROM MOLEX
PLUG AND
TRANSFORMER
(IN UNIT)
TO EAC
208/230VAC COM
24VAC
COM 208/
COM
CONTROL BOARD
G T C C C
A03011
Fig. 23 -- Wiring Layout of Electronic Air Cleaner to Fan Coil for FY5B Models Only
FB
4C /F
B. Humidifier Connect humidifier and humidistat to fan coil unit as shown in Fig.
24 and Fig. 25. The cooling lockout relay is optional.
R
G
C
E
L
O
Y
THERMOSTAT
R R
C
O
Y
G
C
W2
W2
W2 W3
E
FAN COIL
(CONTROL) HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
WHT BLU
VIO
HUMIDISTAT
RELAYFAN HUMIDIFIER
115V M
A95294
Fig. 24 -- Wiring Layout of Humidifier to Heat Pump
R
G
W
Y
THERMOSTAT
R
G
W2
W3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
HUMIDISTAT
FAN HUMIDIFIER
115V
RED
GRY
WHT
WHT
BLU
VIO
BRN
M
A95295
Fig. 25 -- Wiring Layout of Humidifier to Fan Coil With Electric Heat
Step 9 — Sequence of Operation A. Continuous Fan Thermostat closes R to G. G energizes fan relay on PCB which completes circuit to indoor blower motor. When G is de--energized, there is a 90--sec delay before relay opens.
B. Cooling Mode Thermostat energizes R to G, R to Y, and R to O (heat pump only).
G energizes fan relay on PCB which completes circuit to indoor blower motor. When G is de--energized, there is a 90--sec delay before fan relay opens.
C. Heat Pump Heating with Auxiliary Electric Heat Thermostat energizes R to G, R to Y, and R to W. G energizes fan relay on PCB which completes circuit to indoor blower motor. W energizes electric heat relay(s) which completes circuit to heater element(s). When W is de--energized, electric heat relay(s) open, turning off heater elements. When G is de--energized there is a 90--sec delay before fan relay opens.
D. Electric Heat or Emergency Heat Mode Thermostat closes R to W. W energizes electric heat relay(s) which completes circuit to heater element(s). Blower motor is energized through normally closed contacts on fan relay. When W is de--energized, electric heat relay(s) opens.
START--UP PROCEDURES
Refer to outdoor unit Installation Instructions for system start--up instructions and refrigerant charging method details.
UNIT COMPONENT HAZARD
Failure to follow this caution may result in product damage.
Never operate unit without a filter. Damage to blower motor or coil may result. Factory authorized filter kits must be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a field--supplied filter must be installed in the return duct system.
CAUTION!
CARE AND MAINTENANCE
To continue high performance and minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to the proper frequency of maintenance contract.
The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these, contact your dealer for maintenance. The only consumer service recommended or required is filter replacement or cleaning on a monthly basis.
FB
4C /F
AIRFLOW PERFORMANCE TABLES
Table 1 – FB4C Airflow Performance (CFM)
MODEL & SIZE BLOWER SPEED 0.10 0.20 0.30 0.40 0.50 0.60
FB4C 018
Tap 5 767 739 702 669 620 565 Tap 4 614 569 534 486 436 398 Tap 3 701 660 616 581 537 499 Tap 2 614 569 534 486 436 398 Tap 1 614 569 534 486 436 398
FB4C 024
Tap 5 969 936 892 835 763 676 Tap 4 826 795 766 743 706 660 Tap 3 826 795 766 743 706 660 Tap 2 701 660 616 581 537 499 Tap 1 617 592 552 507 472 420
FB4C 030
Tap 5 1108 1090 1065 1034 1009 974 Tap 4 1026 1000 969 938 899 865 Tap 3 1026 1000 969 938 899 865 Tap 2 909 873 842 799 762 724 Tap 1 825 795 757 722 674 634
FB4C 036
Tap 5 1301 1276 1245 1218 1176 1121 Tap 4 1227 1191 1169 1143 1105 1074 Tap 3 1227 1191 1169 1143 1105 1074 Tap 2 1087 1062 1030 1001 966 930 Tap 1 1026 1000 969 938 899 865
FB4C 042
Tap 5 1560 1544 1507 1464 1424 1358 Tap 4 1419 1397 1358 1320 1279 1239 Tap 3 1419 1397 1358 1320 1279 1239 Tap 2 1249 1220 1184 1142 1093 1052 Tap 1 1242 1205 1158 1110 1069 1026
FB4C 048
Tap 5 1743 1712 1679 1642 1610 1574 Tap 4 1669 1634 1599 1564 1531 1499 Tap 3 1669 1634 1599 1564 1531 1499 Tap 2 1452 1413 1377 1339 1308 1271 Tap 1 1300 1256 1221 1182 1142 1101
FB4C 060
Tap 5 1897 1867 1836 1808 1774 1736 Tap 4 1817 1785 1757 1724 1693 1655 Tap 3 1817 1785 1757 1724 1693 1655 Tap 2 1657 1621 1589 1557 1518 1474 Tap 1 1443 1412 1377 1332 1286 1243
Table 2 – FY5B Airflow Performance (CFM)
MODEL &
SIZE
BLOWER
SPEED
0.10 0.20 0.30 0.40 0.50 0.60 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V
FY5B 018
High 742 825 707 768 642 714 568 648 466 526 403 434 Low 541 608 480 564 417 511 357 431 299 363 n/a 304
FY5B 024
High 1041 1112 969 1030 888 936 774 791 573 654 341 438 Low 874 1014 838 953 781 868 684 740 506 573 341 418
FY5B 030
High 1256 1327 1186 1242 1071 1132 952 1005 704 791 459 482 Low 965 1117 949 1074 916 1019 805 902 575 637 396 447
FY5B 036
High 1306 1490 1264 1418 1207 1338 1135 1241 1043 1127 842 937 Low 1164 1335 1144 1290 1108 1226 1052 1148 970 1048 697 855
FY5B 042
High 1723 1768 1639 1681 1544 1576 1435 1465 1309 1340 1144 1182 Low 1387 1543 1358 1488 1311 1410 1237 1315 1137 1200 997 1047
FY5B 048
High 1902 1941 1803 1867 1706 1767 1593 1648 1472 1512 1303 1371 Low 1671 1777 1630 1711 1563 1630 1479 1528 1370 1412 1218 1266
FY5B 060
High 2064 2128 1989 2050 1906 1965 1819 1875 1725 1778 1624 1674 Medium 1812 1959 1756 1898 1692 1829 1619 1750 1538 1663 1449 1566 Low 1556 1748 1521 1709 1477 1659 1422 1598 1357 1525 1283 1442
--- Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factory--approved filter and electric heater (2 element heater sizes 018 through 036, 3 element heater sizes 042 through 060). For FB4C models, airflow at 208 volts is approximately the same as 230 volts because the X13 motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 042 -- 060 sizes must have supply static greater than 0.20 in. wc.
3. Airflow above 400 cfm/ton on 048--060 size could result in condensate blowing off coil or splashing out of drain pan.
FB
4C /F
AIRFLOW PERFORMANCE TABLES (cont.)
Table 3 – FB4C Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)
UNIT SIZE
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 018 0.034 0.049 0.063 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 024 0.034 0.049 0.063 0.076 0.089 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 030 --- --- --- --- --- --- 0.049 0.059 0.070 0.080 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 036 --- --- --- --- --- --- --- --- --- --- 0.070 0.080 0.090 0.099 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 042 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.049 0.056 0.063 0.070 --- --- --- --- --- --- --- --- --- --- 048 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.063 0.070 0.076 0.083 0.090 --- --- --- --- 060 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.049 0.054 0.059 0.065 0.070
Table 4 – FY5B Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)
UNIT SIZE
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 018 0.016 0.027 0.038 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 024 0.016 0.027 0.038 0.049 0.059 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 030 --- --- --- --- --- --- 0.036 0.046 0.055 0.064 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 036 --- --- --- --- --- --- --- --- --- --- 0.055 0.064 0.073 0.081 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 042 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.049 0.056 0.063 0.070 --- --- --- --- --- --- --- --- --- --- 048 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.038 0.043 0.049 0.054 0.059 --- --- --- --- 060 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0.031 0.036 0.040 0.044 0.049
Table 5 – FB4C Electric Heater Static Pressure Drop (in. wc)
UNIT SIZE
CFM
400 600 800 1000 1200 1400 1600 1800 2000 018, 024 0.020 0.044 0.075 --- --- --- --- --- --- --- --- --- --- --- --- 030, 036 --- --- --- --- 0.048 0.072 0.100 --- --- --- --- --- --- --- ---
042, 048, 060 --- --- --- --- --- --- --- --- 0.070 0.092 0.120 0.152 --- ---
Table 6 – FY5B Electric Heater Static Pressure Drop (in. wc)
UNIT SIZE
CFM
400 600 800 1000 1200 1400 1600 1800 2000 018, 024 0.020 0.044 0.075 0.110 0.100 --- --- --- --- --- --- --- ---
030, 036, 042 --- --- --- --- 0.048 0.072 0.100 0.130 0.120 --- --- --- --- 048, 060 --- --- --- --- --- --- --- --- --- --- 0.092 0.120 0.152 0.187
Table 7 – Electric Heater Static Pressure Drop (in. wc)
FB4C, FY5B
018 --- 036
FB4C, FY5B
042 --- 060
HEATER
ELEMENTS kW
EXTERNAL STATIC
PRESSURE
CORRECTION
HEATER
ELEMENTS kW
EXTERNAL STATIC
PRESSURE
CORRECTION
0 0 +.02 0 0 +.04 1 3, 5 +.01 2 8, 10 +.02 2 8, 10 0 3 9, 15 0 3 9, 15 –.02 4 20 –.02 4 20 –.04 6 18, 24, 30 –.10
FB
4C /F
PURONR (R--410A) QUICK REFERENCE GUIDE
S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant.
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron refrigerant, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquid--line filter driers with rated working pressures less than 600 psig.
S Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours.
S Do not install a suction--line filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid--line filter drier is required on every unit.
S Do NOT use an R--22 TXV.
S If indoor unit is equipped with a R--22 TXV or piston metering device, it must be changed to a hard--shutoff Puron refrigerant
TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron refrigerant into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All indoor coils must be installed with a hard--shutoff Puron refrigerant TXV metering device.
FB
4C /F
Copyright 2010 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: IM---FB4CNF---02 Replaces: IM---FB4CNF---01
FB
4C /F