This document provides details for a federal solicitation to renovate a B-Mod construction project for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19. Solicitation number 36C25922R0012 seeks proposals to complete Z2DA--635-19-101 Renovate B-Mod Construction (plus up) for VA-22-00016600. Interested parties should review attachment 4.23 for additional requirements. Proposals are due by the date specified in the solicitation to upgrade and expand modular buildings for a Veterans Affairs medical facility.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
PLAN NORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
INDEX OF DRAWINGS
01-A101
DISCIPLINE:
G - GENERAL
A - ARCHITECTURE
F - FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
SHEET TYPE
DESIGNATOR
VICINITY MAP
PROJECT TEAM
BUILDING SUMMARY
PROJECT INFORMATION
THE SCOPE OF THIS PROJECT IS TO DEVELOP FULL DESIGN-BID-BUILD PACKAGE TO DEMOLISH AND RENOVATE APPROXIMATELY 6,330 SQ. FT. OF EXISTING CLINICAL SPACE WITHIN BUILDING 1, GROUND LEVEL, AT THE OKCVA MEDICAL CENTER INCORPORATING THE MOST CURRENT VERSION OF THE VA’S PACT SPACE MODULE DESIGN GUIDE AND INDUSTRY
BEST PRACTICES.
ANNOTATION DRAWING SYMBOLSGENERAL NOTES
PROJECT NAME:
PROJECT NUMBER:
PROJECT LOCATION:
BUILDING NUMBER
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW
ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE
SUBMITTING COST QUOTATIONS FOR WORK.
3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE
PROVIDED PRIOR TO CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION.
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE
CONTRACTOR'S EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH
RESPECT TO DELIVERY DATE, QUALITY, OR COST.
9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S
MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.
10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL
EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA
REGULATIONS DURING CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.
A101
A101
SCOPE OF WORK SUMMARY:
SHEET NUMBER
WITHIN SERIES
REMODEL B MOD OKLAHOMA VAMC
635-19-101
OKLAHOMA CITY DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
921 N.E. 13TH STREET
OKLAHOMA CITY, OK 73104
Romanyk Consulting Focusing on what matters
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
8910 7 6 5 4 3 2 1
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:4
:4
P
M
PROJECT NUMBER - 635-19-101
REMODEL B MOD OKLAHOMA VAMC - OKLAHOMA CITY, OK
100% CONTRACT DOCUMENTS
SEPTEMBER 24, 2021
BW LJ
635-19-101
GI100
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
SHEET INDEX & GENERAL INFORMATION 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
- OKLAHOMA CITY, OK
SHEET # SHEET TITLE
PLUMBING
P-001 PLUMBING SYMBOLS, NOTES, AND ABBREVIATIONS
PD100 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DWV DEMOLITION
PD101 PARTIAL GROUND FLOOR PLAN - PLUMBING DWV DEMOLITION
PD201 PARTIAL GROUND FLOOR PLAN - PLUMBING DISTRIBUTION DEMOLITION
PP100 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DWV
PP101 PARTIAL GROUND FLOOR PLAN - PLUMBING DWV
PP200 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DISTRIBUTION
PP201 PARTIAL GROUND FLOOR PLAN - PLUMBING DISTRIBUTION
PP300 PLUMBING RISER DIAGRAM - DWV
PP301 PLUMBING RISER DIAGRAM - PLUMBING DISTRIBUTION
P-400 PLUMBING DETAILS & SCHEDULES
MECHANICAL
M-001 MECHANICAL SYMBOLS, NOTES, AND ABBREVIATIONS
MD101 PARTIAL GROUND FLOOR PLAN - HVAC DEMOLITION
MD102 PARTIAL LEVEL 03 FLOOR PLAN - HVAC DEMOLITION
MD201 PARTIAL GROUND FLOOR PLAN - PIPING DEMOLITION
MH101 PARTIAL GROUND FLOOR PLAN - HVAC
MH102 PARTIAL LEVEL 03 FLOOR PLAN - HVAC
MH200 MECHANICAL HVAC DETAILS
MH300 MECHANICAL HVAC SCHEDULES
MH301 MECHANICAL HVAC SCHEDULES
MI101 PARTIAL GROUND FLOOR PLAN - MECHANICAL INSTRUMENTATION
MI301 MECHANICAL INSTRUMENTATION - SEQUENCES OIT TR UNIT
MI302 MECHANICAL INSTRUMENTATION - SEQUENCES VAV - HW REHEAT
MI303 MECHANICAL INSTRUMENTATION - SEQUENCES EXHAUST FAN - ON/OFF
MP102 PARTIAL LEVEL 03 FLOOR PLAN - PIPING
MP101 PARTIAL GROUND FLOOR PLAN - PIPING
MP200 MECHANICAL PIPING DETAILS
ELECTRICAL
E-001 ELECTRICAL SYMBOLS, NOTES, AND ABBREVIATIONS
ED101 PARTIAL GROUND FLOOR PLAN - ELECTRICAL DEMOLITION
EL101 PARTIAL GROUND FLOOR PLAN - LIGHTING
EP100 BASEMENT LEVEL FLOOR PLAN - CONDUIT ROUTING
EP101 PARTIAL GROUND FLOOR PLAN - POWER
EP102 GROUND FLOOR PLAN - CONDUIT ROUTING
EP103 PARTIAL LEVEL 3 FLOOR PLAN - MECHANICAL POWER
EP104 PARTIAL LEVEL 09 FLOOR PLAN - ELECTRICAL
ES101 PARTIAL GROUND FLOOR PLAN - TECHNOLOGY SYSTEMS
E-400 ENLARGED PLANS - ELECTRICAL
E-500 ELECTRICAL DETAILS
E-700 ELECTRICAL SCHEDULES
SHEET # SHEET TITLE
GENERAL
GI100 SHEET INDEX & GENERAL INFORMATION
GI101 ABBREVIATIONS & SYMBOLS
GI102 ADA INFORMATION
GI103 BUILDING CODE DATA
GI104 LIFE SAFETY PLAN
GI105 GROUND FLOOR PHASING PLAN
HAZARDOUS MATERIALS
HA101 ASBESTOS ABATEMENT PLAN
ARCHITECTURAL
AD100 PARTIAL GROUND FLOOR - DEMOLITION PLAN
AD101 REFLECTED CEILING PLAN DEMOLITION PLAN
AD102 BASEMENT DEMO REFLECTED CEILING PLAN
AE101 OVERALL GROUND FLOOR
AE102 PARTIAL GROUND FLOOR - ENLARGED FLOOR PLAN
AE103 DIMENSION PLAN
AE104 REFLECTED CEILING PLAN
AE401 ENLARGED TOILET PLANS AND ELEVATIONS
AE402 ENLARGED TOILET PLANS AND ELEVATIONS
AE403 ENLARGED PLANS & ELEVATIONS
AE404 ENLARGED PLANS
AE405 INTERIOR ELEVATIONS
AE500 WALL TYPES
AE501 ACCESSIBLE DETAILS
AE502 INTERIOR DETAILS
AE503 METAL STUD DETAILS
AE504 CEILING DETAILS SUSPENDED GYPSUM
AE601 DOOR & WINDOW SCHEDULES
AE701 CASEWORK SECTIONS AND DETAILS
AE702 CASEWORK SECTIONS AND DETAILS
AF101 GROUND FLOOR FINISH PLAN AND SCHEDULE
AW101 GROUND FLOOR SIGNAGE PLAN
AW102 SIGNAGE PLAN DETAILS
AW103 SIGNAGE PLAN DETAILS
QH101 PARTIAL GROUND FLOOR - EQUIPMENT PLAN
SPRINKLER
FS001 SPRINKLER SYMBOLS, NOTES, DETAILS, AND ABBREVIATIONS
FD101 PARTIAL GROUND FLOOR PLAN - SPRINKLER DEMOLITION
FS101 PARTIAL GROUND FLOOR PLAN - SPRINKLER
OWNER:
Oklahoma City VA Health Care System 921 NE 13th Street Oklahoma City, OK 73104
John Wilson John.Wilson3@va.gov
405-456-3922 520-400-1202 cell
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
PROJECT ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Barrett Webb Barrett.Webb@RomaynkConsulting.com
855-424-3838 x318 512-413-6963 cell
HAZARDOUS MATERIALS:
SCI Engineering 130 Point West Blvd.
St. Charles MO 63301
Glen Grissom, Project Scientist @sciengineering.com
636-949-8200
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Jonathan Foster, PE, LEED AP Jonathan.Foster@RomanykConsulting.com
855.424.3838 x307
501.428.4167 cell
MECHANICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
PLUMBING ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
FIRE PROTECTION ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Scott Thraen, PE Scott.Thraen@RomanykConsulting.com
855.424.3838 x312
402.981.8882 cell
Revisions: Date:
ACCESSIBLE SIGNAGE REQS
LETTER AND NUMBER HEIGHTS
TOILET ACCESSORY LEGEND
NOTES
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
PLAN NORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
A101
A101
ANNOTATION DRAWING SYMBOLS
INDEX OF DRAWINGS
202-A101
DISCIPLINE:
G - GENERAL
A - ARCHITECTURE
I - INTERIORS
F- FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T - TELECOM
V - VENTILATION
SHEET TYPE
DESIGNATOR
BUILDING NUMBER
SHEET NUMBER
WITHIN SERIES
ARCHITECTURAL SYMBOLS
LEGEND
CONCRETE/ PRECAST
CONCRETE
SOIL
SAND, EIFS FINISH COAT,
OR CEMENT PLASTER
BRICK
CMU
STONE
FIBERGLASS BATT
INSULATION
EXPANDED POLYSTYRENE
RIGID INSULATION
EXTRUDED POLYSTYRENE
RIGID INSULATION
POLYISOCYANURATE RIGID
INSULATION
GYPSUM BOARD
EXTERIOR GYPSUM
SHEATHING
EXTERIOR CEMENT
BOARD
COATED GLASS MAT
WATER RESISTANT
GYP BD
PLYWOOD
COVER BOARD
MATERIALS
CEILING SYMBOLS
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
24" X 24" ACOUSTICAL CEILING
PANEL AND GRID
GYPSUM BOARD CEILING OR
SOFFIT
2' x 2' LED FLUORESCENT
FIXTURE - EMERGENCY NIGHT
LIGHT
RECESSED CAN DOWNLIGHT
CEILING ELEVATION A.F.F.X'-X"
EXIT SIGN
LED LIGHT
1' x 4' LED FLUORESCENT
FIXTURE
2' x 4' LED FLUORESCENT
FIXTURE
INDUSTRIAL LUMINAIRE
EMERGENCY LIGHT
2' x 2' LED FLUORESCENT
FIXTURE
OC
NURSE CALL DOME LIGHT WALL
MOUNTED
A
FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE-CEILING
MOUNTED.
CAM
LS
OCCUPANCY SENSOR
A1 A3
DAYLIGHT LEVEL SENSOR
CLOSED CIRCUIT CAMERA (CCTV)
CEILING MOUNTED
N
S SPEAKER
CLOSED CIRCUIT CAMERA (CCTV)CAM
VC VACANCY SENSOR
WAP CEILING INFORMATION OUTLET
FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1
WALL CONTROL STATIONSW
NURSE CALL STATIONN
SMOKE,FIRE/SMOKE
DAMPER CONTROLLER
ARD
FIRE ALARM MANUAL PULL
STATION
F
FIRE ALARM SMOKE,
SMOKE DAMPER
SD
SD FIRE ALARM DUCT SMOKE
DETECTOR
D DIMMER LED
A FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE- WALL
MOUNTED.
A1 A3
S SWITCH
{LD}
{LS}
LIGHT DIMMER
LIGHT SENSOR
ARCHITECTURAL DRAWING ABBREVIATIONS
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALG ALUMINUM AND GLASS
AL ALUMINUM
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ELEV EQ ELEVATOR EQUIPMENT
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED INSTALLED BY GOVERNMENT
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GSF GROSS SQUARE FEET
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HAC HOUSE AID KEEPING CLOSET
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
ISO ISOLATION
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL FLASH SHEET METAL (FLASHING)
SHTHG SHEATHING
SHWR SHOWER
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
SEE OTHER DISCIPLINES FOR
ADDITIONAL ABREVIATIONS
NOTE: NOT ALL MAY BE USED
ARCHITECTURAL SYMBOLS
CHARACTER PROPORTIONS:
LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH-TO-HEIGHT RATIO
BETWEEN 3:5 AND 1:1 AND A STROKE-WIDTH-TO-HEIGHT RATIO BETWEEN 1:5 AND
1:10, UTILIZING AN UPPER CASE 'X' FOR MEASUREMENT.
CHARACTER HEIGHT:
SEE LETTER AND NUMBER HEIGHT CHART BELOW
*EXCEPTION: CHARACTER HEIGHT SHALL BE 5/8" HIGH MINIMUM FOR BUILDING
DIRECTORIES.
PICTOGRAMS:
WHERE PICTOGRAMS ARE REQUIRED, THEY SHALL HAVE A 6" MINIMUM SIZE
MEASURED AT THE BORDER. WHERE TEXT DESCRIPTORS FOR PICTOGRAMS ARE
REQUIRED, THEY SHALL COMPLY WITH THE TACTILE CHARACTER PROVISIONS OF
RAISED CHARACTERS AND SYMBOLS, BRAILLE, AND LOCATION OF TACTILE
SIGNAGE PORTIONS BELOW.
FINISH AND CONTRAST:
THE CHARACTERS, SYMBOLS AND BACKGROUND OF SIGNS SHALL BE EGGSHELL,
MATTE, OR OTHER NON-GLARE FINISH. CHARACTERS AND BRAILLE, AND LOCATION
OF TACTILE SIGNAGE PORTIONS BELOW. LIGHT BACKGROUND.
RAISED CHARACTERS AND SYMBOLS:
CHARACTERS AND SYMBOLS ON TACTILE SIGNS SHALL BE RAISED 1/32" MINIMUM.
RAISED CHARACTERS AND SYMBOLS SHALL BE IN UPPERCASE CHARACTERS.
RAISED CHARACTERS AND SYMBOLS SHALL BE 5/8" HIGH MINIMUM, AND 2"
MAXIMUM. RAISED CHARACTERS AND SYMBOLS SHALL BE ACCOMPANIED BY
BRAILLE IN ACCORDANCE WITH THE PROVISIONS OUTLINED BELOW.
BRAILLE:
BRAILLE SHALL BE SEPARATED 1/2" MINIMUM FROM THE CORRESPONDING RAISED
CHARACTERS OR SYMBOLS. BRAILLE PROVIDED IN ACCORDANCE WITH THE
REQUIREMENTS FOR ELEVATOR CONTROLS SHALL BE PLACED 3/16" MINIMUM BELOW
THE CORRESPONDING CHARACTERS OR SYMBOLS. BRAILLE SHALL BE GRADE II AND
SHALL CONFORM TO SPECIFICATION #800, NATIONAL LIBRARY SERVICE, LIBRARY OF
CONGRESS.
LOCATION OF TACTILE SIGNAGE:
TACTILE SIGNAGE SHALL BE LOCATED ALONGSIDE THE DOOR ON THE LATCH SIDE
AND SHALL BE MOUNTED AT 60" ABOVE THE ADJACENT FINISHED FLOOR TO THE
CENTERLINE OF THE SIGN. IN LOCATIONS HAVING DOUBLE DOORS, TACTILE SIGNS
SHALL BE MOUNTED TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE THERE IS
NO WALL SPACE ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF
DOORS, SIGNS SHALL BE RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE
ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF DOORS, SIGNS SHALL
BE PLACED ON THE NEAREST ADJACENT WALL.
GENERAL NOTES:
ANY ADDITIONAL TEXT REQUIRED DUE TO LOCAL ORDINANCES (FINES FOR
PARKING IN ACCESSIBLE SPACES, ETC.) SHALL COMPLY WITH THE SIGNAGE
REQUIREMENTS ABOVE.
ALL INTERIOR SIGNAGE WITHIN THE ASC SHALL CONFORM TO THE REQUIREMENTS
OF ADA 2010 AND ANY OTHER STATE OR LOCAL APPLICABLE CODES.
HEIGHT ABOVE FLOOR/ GROUND: MIN. CHARACTER HEIGHT:
GREATER THAN 80" (6'-8") AFF 3"
GREATER THAN 60" (5'-0") AFF BUT LESS THAN 80" (6'-8") AFF 2"
GREATER THAN 48" (4'-0") AFF BUT LESS THAN 60" (5'-0") AFF 1"
A FLOOR MOUNTED TOILET (CFCI)
GB42 42" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB36 36" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB18 18" GRAB BAR (VERTICAL) (BLOX FURNISHED &
INSTALLED)
E MIRROR (BLOX FURNISHED & INSTALLED)
F TOILET PAPER DISPENSER (OFCI)
G ROBE HOOK (CFCI)
H SOAP DISPENSER (OFCI)
H PAPER TOWEL DISPENSER (OFCI)
J SANITARY NAPKIN DISPOSAL (CFCI)
O BABY CHANGING TABLE (CFCI)
P WALL MOUNTED SINK (BLOX FURNISHED &
INSTALLED)
U SURFACE MTD TOILET SEAT COVER DISPENSER
(CFCI)
1. SEE SPECIFICATIONS FOR MANUFACTURERS INFORMATION ON ALL TOILET
ACCESSORIES.
2. ALL SOAP DISPENSERS, PAPER TOWEL DISPENSERS, TOILET PAPER
DISPENSERS & HAND SANITIZER DISPENSERS TO BE OWNER FURNISHED AND
CONTRACTOR INSTALLED. LOCATIONS SHOWN FOR FACILITY.
3. FOR ALL TOILET ROOMS, REFER TO BLOX VENDOR DRAWINGS FOR PARTITION
TYPES & DETAILS AND BLOCKING REQUIREMENTS FOR TOILET ACCESSORIES.
4. ALL TOILET LOCATIONS, WHETHER NOTED OR NOT, SHALL BE PROVIDED WITH
THE FOLLOWING UNLESS OTHERWISE NOTED:
a) ONE MIRROR
b) ONE TOILET PAPER DISPENSER
c) ONE ROBE HOOK - MOUNTED BEHIND STALL DOORS.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:3
P
M
BW LJ
635-19-101
GI101
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
ABBREVIATIONS & SYMBOLS 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
- OKLAHOMA CITY, OK
ACCESSIBLE SIGNAGE REQS
LETTER AND NUMBER HEIGHTS
TOILET ACCESSORY LEGEND
NOTES
A D
A
T O
H A
N D
L E
MIRROR SOAP DISPENSER PAPER
TOWEL
DISPENSER
TOILET PAPER
DISPENSER
TOILET
PAPER
HOLDER
SANITARY
NAPKIN
DISPOSAL
MIN
1' - 3"
LAVATORY
M
IN
INSULATE EXPOSED
PIPING WITH WHITE
PLASTIC PRE-FITTED
INSULATION
M A
X
MEASURE
TO BOTTOM
OF REFLECTIVE
SURFACE
D
IS
P E
N S
E R
M A
X O
P E
R A
B L E
D
IS
P E
N S
E R
M
A X
T O
O P
E R
A B
L E
M A
X
M
IN
M
IN
FIRE
EXTINGUISHERS
AND CABINETS
7-PEG
COAT RACK
2' - 0"
"MIN
8"
MIN
11"
KNEE AND TOE
CLEARANCES
E
E
SEALANT
PROVIDE ADA
COMPLIANT FAUCET
WITH WRIST BLADE
CONTROLS
M A
X
5" MAX 15" MAX
ACCESS HGT. D.F.
SPOUT LOCATION
M
IN
SPOUT
HEIGHT
STANDING AND
ACCESSIBLE DRINKING
FOUNTAINS
FRONT SIDE
PLAN
ALUM. SEMI-RECESSED CAB.
W/ FULL CLEAR ACRYLIC DOOR
10 LBS
ABC TYPE
BABY CHANGING
TABLE
M A
X
/2
ROBE
HOOK
M A
X
"FIRE EXTINGUISHER" IN
RED LETTERS
G
F
F
(ALT)H
J
C
N O O
P
P
M
IN9
MIN
11"
M
IN
8"
25" MAX
30x48
CLEAR
SPACE
U
M A
X
TOILET
SEAT COVER
DISPENSER
SIGNAGE
(12" BELOW CEILING)
2"
HANDRAIL
PER NFPA 10
PTD (OF/OI)
PUBLIC TLTS
ONLY
SEMI-
RECESSED
WASTE RECP.
S P
O U
T H
G T
S T
A N
D
IN
G H
E
IG
H T
D .F
A C
C E
S S
H
E
IG
H T
D .F
M A
X
NOTE: PROVIDE CANE
DETECTABLE APRON AT
THE STANDING HEIGHT
UNIT
MIN
3' - 6"
MAX
1' - 0"
WATER CLOSET
SIDE WALL
1 1/4" MIN., 2" MAX DIA.
GRAB BAR WITH 1 1/2"
GAP FROM WALL
WATER CLOSET
BACK WALL
TP DISPENSER
MOUNTING AREA
1' - 6"
T .O
G
.B
/2
4' - 6" MIN
MIN
1' - 0"
MIN
2' - 0"
FLUSH CONTROLS
ON OPEN SIDE
M
IN
GB42
GB36
A
A
3' - 4"
/2
GB18
U
CENTER ON
GRAB BAR END
NOTE: GRAB BARS
SHALL BE 33" - 36" TO
TOP OF BAR
MEASURE
TO BOTTOM
OF REFLECTIVE
SURFACE
3' - 0"
6"
6"
8"
MEN WOMEN
NO SMOKING
T
O F
IN
IS
H E
D F
L O
O R
F
IN
IS
H
E D
F L O
O R
T O
T O
F
IN
IS
H
E D
F L O
O R
PROPORTIONS OF THE INTERNATIONAL
SYMBOL OF ACCESSIBILITY
INTERIOR SIGNAGE
DOOR FRAME
LATCH SIDE OF
DOOR PANEL
TO TOP OF SIGN
GENERAL NOTES:
PROVIDE INTERIOR SIGNAGE FOR EVERY DOOR/ROOM UNLESS NOTED
OTHERWISE (REFER TO FINISH DRAWINGS).
ALL FINAL ROOM NAMES SHALL BE APPROVED BY ARCHITECT/OWNER PRIOR
TO SIGN FABRIACATION.
AT LOCATIONS WHERE THERE ISN'T AVAILABLE WALL SPACE TO INSTALL THE
INTERIOR SIGNAGE AS INDICATED, OBTAIN ARCHITECT'S INSTRUCTION PRIOR
TO INSTALLATION.
AT LOCATIONS WHERE THERE ISN'T AVAILABLE WALL SPACE, BUT AVAILABLE
WINDOW SPACE, ADHERE INTERIOR SIGNAGE WITH DOUBLE SIDED TAPE TO
PROVIDE A PERMANENT INSTALLATION. PROVIDE A BLANK PANEL OF THE
SAME COLOR, SIZE, AND MATERIAL FOR THE BACK SIDE OF THE SIGN TO BE
INSTALLED ON THE GLASS.
1.
2.
3.
4.
T-SHAPED TURNING SPACE
TURNING RADIUS
ø 5
5' - 0"
2' - 0" 3' - 0"
IF DOOR HAS BOTH
A CLOSER AND LATCH
OTHERWISE THIS = 0"
LATCH APPROACH, PUSH SIDE
Y= 4'-0" MIN IF DOOR HAS
A CLOSER, OTHERWISE Y = 3'-6"
FRONT APPROACH, PUSH SIDE
Y= 4'-6" MIN. IF DOOR HAS
A CLOSER, OTHERWISE
Y = 4'-0" MIN
Y= 4'-0" MIN IF DOOR HAS
BOTH A CLOSER AND LATCH
OTHERWISE Y = 3'-6"
HINGE APPROACH, PUSH SIDE
X= 3'-0" MIN. IF Y= 5'-0"
X= 3'-6" MIN. IF Y= 4'-6"
MIN
2' - 0"
Y M
IN
MIN
1' - 6"
Y X
MIN
2' - 0" Y 1' - 0" Y
1' - 10"
LATCH APPROACH, PULL SIDE FRONT APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE
CHARACTER PROPORTIONS:
LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH-TO-HEIGHT RATIO
BETWEEN 3:5 AND 1:1 AND A STROKE-WIDTH-TO-HEIGHT RATIO BETWEEN 1:5 AND
1:10, UTILIZING AN UPPER CASE 'X' FOR MEASUREMENT.
CHARACTER HEIGHT:
SEE LETTER AND NUMBER HEIGHT CHART BELOW
*EXCEPTION: CHARACTER HEIGHT SHALL BE 5/8" HIGH MINIMUM FOR BUILDING
DIRECTORIES.
PICTOGRAMS:
WHERE PICTOGRAMS ARE REQUIRED, THEY SHALL HAVE A 6" MINIMUM SIZE
MEASURED AT THE BORDER. WHERE TEXT DESCRIPTORS FOR PICTOGRAMS ARE
REQUIRED, THEY SHALL COMPLY WITH THE TACTILE CHARACTER PROVISIONS OF
RAISED CHARACTERS AND SYMBOLS, BRAILLE, AND LOCATION OF TACTILE
SIGNAGE PORTIONS BELOW.
FINISH AND CONTRAST:
THE CHARACTERS, SYMBOLS AND BACKGROUND OF SIGNS SHALL BE EGGSHELL,
MATTE, OR OTHER NON-GLARE FINISH. CHARACTERS AND BRAILLE, AND LOCATION
OF TACTILE SIGNAGE PORTIONS BELOW. LIGHT BACKGROUND.
RAISED CHARACTERS AND SYMBOLS:
CHARACTERS AND SYMBOLS ON TACTILE SIGNS SHALL BE RAISED 1/32" MINIMUM.
RAISED CHARACTERS AND SYMBOLS SHALL BE IN UPPERCASE CHARACTERS.
RAISED CHARACTERS AND SYMBOLS SHALL BE 5/8" HIGH MINIMUM, AND 2"
MAXIMUM. RAISED CHARACTERS AND SYMBOLS SHALL BE ACCOMPANIED BY
BRAILLE IN ACCORDANCE WITH THE PROVISIONS OUTLINED BELOW.
BRAILLE:
BRAILLE SHALL BE SEPARATED 1/2" MINIMUM FROM THE CORRESPONDING RAISED
CHARACTERS OR SYMBOLS. BRAILLE PROVIDED IN ACCORDANCE WITH THE
REQUIREMENTS FOR ELEVATOR CONTROLS SHALL BE PLACED 3/16" MINIMUM BELOW
THE CORRESPONDING CHARACTERS OR SYMBOLS. BRAILLE SHALL BE GRADE II AND
SHALL CONFORM TO SPECIFICATION #800, NATIONAL LIBRARY SERVICE, LIBRARY OF
CONGRESS.
LOCATION OF TACTILE SIGNAGE:
TACTILE SIGNAGE SHALL BE LOCATED ALONGSIDE THE DOOR ON THE LATCH SIDE
AND SHALL BE MOUNTED AT 60" ABOVE THE ADJACENT FINISHED FLOOR TO THE
CENTERLINE OF THE SIGN. IN LOCATIONS HAVING DOUBLE DOORS, TACTILE SIGNS
SHALL BE MOUNTED TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE THERE IS
NO WALL SPACE ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF
DOORS, SIGNS SHALL BE RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE
ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF DOORS, SIGNS SHALL
BE PLACED ON THE NEAREST ADJACENT WALL.
GENERAL NOTES:
ANY ADDITIONAL TEXT REQUIRED DUE TO LOCAL ORDINANCES (FINES FOR
PARKING IN ACCESSIBLE SPACES, ETC.) SHALL COMPLY WITH THE SIGNAGE
REQUIREMENTS ABOVE.
ALL INTERIOR SIGNAGE WITHIN THE ASC SHALL CONFORM TO THE REQUIREMENTS
OF ADA 2010 AND ANY OTHER STATE OR LOCAL APPLICABLE CODES.
HEIGHT ABOVE FLOOR/ GROUND: MIN. CHARACTER HEIGHT:
GREATER THAN 80" (6'-8") AFF 3"
GREATER THAN 60" (5'-0") AFF BUT LESS THAN 80" (6'-8") AFF 2"
GREATER THAN 48" (4'-0") AFF BUT LESS THAN 60" (5'-0") AFF 1"
A FLOOR MOUNTED TOILET (CFCI)
GB42 42" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB36 36" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB18 18" GRAB BAR (VERTICAL) (BLOX FURNISHED &
INSTALLED)
E MIRROR (BLOX FURNISHED & INSTALLED)
F TOILET PAPER DISPENSER (OFCI)
G ROBE HOOK (CFCI)
H SOAP DISPENSER (OFCI)
H PAPER TOWEL DISPENSER (OFCI)
J SANITARY NAPKIN DISPOSAL (CFCI)
O BABY CHANGING TABLE (CFCI)
P WALL MOUNTED SINK (BLOX FURNISHED &
INSTALLED)
U SURFACE MTD TOILET SEAT COVER DISPENSER
(CFCI)
1. SEE SPECIFICATIONS FOR MANUFACTURERS INFORMATION ON ALL TOILET
ACCESSORIES.
2. ALL SOAP DISPENSERS, PAPER TOWEL DISPENSERS, TOILET PAPER
DISPENSERS & HAND SANITIZER DISPENSERS TO BE OWNER FURNISHED AND
CONTRACTOR INSTALLED. LOCATIONS SHOWN FOR FACILITY.
3. FOR ALL TOILET ROOMS, REFER TO BLOX VENDOR DRAWINGS FOR PARTITION
TYPES & DETAILS AND BLOCKING REQUIREMENTS FOR TOILET ACCESSORIES.
4. ALL TOILET LOCATIONS, WHETHER NOTED OR NOT, SHALL BE PROVIDED WITH
THE FOLLOWING UNLESS OTHERWISE NOTED:
a) ONE MIRROR
b) ONE TOILET PAPER DISPENSER
c) ONE ROBE HOOK - MOUNTED BEHIND STALL DOORS.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:5
P
M
BW LJ
635-19-101
GI102
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
ADA INFORMATION 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
NOTE: THESE DRAWINGS DO NOT
INCLUDE IBC BUILDING CODE
INFORMATION
CODE SUMMARY – BUILDING 1 GROUND FLOOR B MODULE
1. DRAWING PURPOSE : NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:
a. 2018 NFPA 101 LIFE SAFETY CODE
1. CHAPTER 4 – GENERAL
2. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS
3. CHAPTER 7 - MEANS OF EGRESS
4. CHAPTER 21 - EXISTING AMBULATORY OCCUPANCY
3. OWNER:
OKLAHOMA CITY VA HEALTH CARE SYSTEM
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
PH (405) 456-1000
4. DATE DEVELOPED: 7/29/2021
5. ARCHITECT:
ROMANYK CONSULTING
3308 PRESTON ROAD
SUITE 350-164
PLANO, TEXAS
6. ARCHITECT SEAL: SEE STAMP IN TITLEBLOCK
7. FIRE SERVICE: OKLAHOMA CITY FIRE DEPARTMENT
8. INSPECTION: TJC; CITY OF OKLAHOMA CITY
9. OCCUPANCY GROUP TYPE:
a. OCCUPANCY 1/ BUILDING 1/ GROUND FLOOR: AMBULATORY HEALTHCARE OCCUPANCY
10. CONSTRUCTION TYPE:
CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)
11. BUILDING 1 - OCCUPANCY 1 GROSS FLOOR AREAS:
GROUND FLOOR AREA ACTUAL: 63,736 SF (TOTAL FLOOR)
6,330 SF (AREA OF WORK)
12. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
AMBULATORY HEALTH CARE OCCUPANCY:
ALLOWABLE HEIGHT/ 4 OR MORE STORIES
ACTUAL HEIGHT/STORIES 10 OCCUPIABLE STORIES
13. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
CONSTRUCTION TYPE II (222)
AMBULATORY
HEALTHCARE
OCCUPANCY
BEARING WALLS:
A. EXTERIOR 2 HR
B. INTERIOR 2 HR
C. INT/EXT (ROOF ONLY) 1 HR
NON-BEARING WALLS:
A. EXTERIOR 0 HR
B. INTERIOR NON-COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS 2 HR
B. SUPPORT ROOF ONLY 1 HR
BEAMS/GIRDER/TRUSSES:
A. EXTERIOR: 2 HR
B. INTERIOR: 1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
14. ACTIVE FIRE SAFETY FEATURES:
a. AUTOMATIC SUPPRESSION SYSTEMS:
• SPRINKLER SYSTEM (FULLY SPRINKLED)
• AUTOMATIC AIR-HANDLING SHUT-DOWN
b. FIRE ALARM SYSTEM - HONEYWELL, ADDRESSABLE, AUTO DIAL-UP
c. GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR POWERED
d. EXIT LIGHTING.
e. PORTABLE EXTINGUISHERS
f. SMOKE DETECTORS WILL BE IN MECHANICAL AND ELECTRICAL ROOMS, STORAGE ROOMS, DATA ROOMS, CORRIDORS, SMOKE DOORS AND OTHER AREAS AS REQUIRED
15. WATER SUPPLY: CITY OF OKLAHOMA CITY
16. SPRINKLERS: FULLY SPRINKLERED
17. TOTAL OCCUPANTS
TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
USE (FT2 /PERSON)
AMBULATORY HEALTHCARE USE
INPATIENT TREATMENT DEPARTMENTS 240
SLEEPING DEPARTMENTS 120
AMBULATORY HEALTH CARE 150
OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)
(AREA OF WORK): 7,690/150 = 52 occupants
18. EXIT WIDTH: TABLE 7.3.3.1 CAPACITY FACTORS
EXIT WIDTH STAIRS: 52 OCCUPANTS X.3 INCHES = 15.6" (SCOPE OF WORK)
EXIT WIDTH LEVEL COMPONENTS: 52 OCCUPANTS X .2 INCHES = 10.4" (SCOPE OF WORK)
19. MEANS OF EGRESS: TWO MEANS OF EGRESS, AS A MINIMUM REQUIRED (4.5.3.1).
ACTUAL MEANS OF EGRESS (SCOPE OF WORK): 3 MEANS OF EGRESS
20. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN 32"
IN CLEAR WIDTH (7.2.1.2.3.2). DOOR OPENINGS IN PROJECT ARE 36".
21. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET.
ACTUAL PROJECT DEAD END CORRIDOR (SCOPE OF WORK) = 6 FEET.
22. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,
SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)
23. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN
44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).
ACTUAL CORRIDOR WIDTH (SCOPE OF WORK): 72 INCHES (MIN.)
24. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 6.
25. TRAVEL DISTANCE TO EXITS= THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). ACTUAL TRAVEL DISTANCE
100.5 FEET.(GROUND FLOOR)
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:0
P
M
BW LJ
635-19-101
GI103
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
BUILDING CODE DATA 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
LIFE SAFETY NOTES
FE
FEC
LIFE SAFETY LEGEND
PLAN LEGEND
1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.
2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AND IS
3. PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE DETECTION
SYSTEM.
4. WALL TYPES ARE DETAILED ON G002 AND INDICATED ON THE
DIMENSIONED FLOOR PLAN ON A102.
5. REFER TO THIS DRAWING FOR MEANS OF EGRESS
6. REFER TO THIS DRAWING FOR DOOR CAPACITIES.
7. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE
MARSHAL.
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FDC
F
L
L
D
MHO
FACP
FAAP
FIRE DEPARTMENT CONNECTION
EXIT
ILLUMINATED EXIT SIGN
FIRE ALARM - MANUAL PULL STATION
FIRE ALARM - STROBE / CHIME
FIRE ALARM - STROBE
SMOKE DETECTOR
MAGNETIC HOLD OPEN
FIRE ALARM CONTROL PANEL
FIRE ALARM ANUNCIATOR PANEL
EXTERIOR EMERGENCY LIGHTING
DD
EE
FF
GG
HH
II
JJ
K
123 SF
EXAM/CONSULT ROOM
GF124D
125 SF
EXAM/CONSULT ROOM
GF124E
118 SF
EXAM/CONSULT ROOM
GF113
123 SF
EXAM/CONSULT ROOM
GF112
136 SF
EXAM/CONSULT ROOM
GF124B
29 SF
HEIGHT/WEIGHT
ALCOVE
GF105
75 SF
BLOOD SPECIMEN
COLLECTION
GF103E
73 SF
BLOOD SPECIMEN
COLLECTION
GF103F
76 SF
BLOOD SPECIMEN
COLLECTION
GF103D
75 SF
BLOOD SPECIMEN
COLLECTION
GF103C
57 SF
TOILET SPECIMEN
COLLECTION
GF103B
211 SF
LAB
GF103
55 SF
TOILET SPECIMEN
COLLECTION
GF103A
75 SF
BLOOD SPECIMEN
COLLECTION
GF103K
74 SF
BLOOD SPECIMEN
COLLECTION
GF103J
73 SF
BLOOD SPECIMEN
COLLECTION
GF103H
70 SF
BLOOD SPECIMEN
COLLECTION
GF103G
62 SF
PATIENT TLT.
GF117
51 SF
STAFF LOCKER
GF125
64 SF
STAFF TLT.
GF116
183 SF
LAB 2 RECEPTION
WORKSTATIONS
GF124H
72 SF
CLEAN UTILITY
GF124J
111 SF
LOGISTICS STORAGE
GF119
117 SF
TELECOMMUNICATIONS
ROOM
GF118
32 SF
PATIENT CHECK-IN
GF124I
846 SF
WAITING
GF124
125 SF
EXAM/CONSULT ROOM
GF124C
121 SF
CONSULT ROOM
GF114
717 SF
TEAM WORK AREA
GF124A
22 SF
ALCOVE RESUS
GF124L
24 SF
ALCOVE WHEELCHAIR
GF124K
10 SF
BLOOD SPECIMEN
ALCOVE
GF103I
GRAY AREA NOT IN PROJECT
SCOPE
27 SF
ELECT.
GF106
118 SF
CONSULT ROOM
GF115
112 SF
MED. ROOM
GF124F
803 SF
PATIENT CORRIDOR
CGF 5
308 SF
PATIENT CORRIDOR
CGF 4
AE102
EXISTING
STAIR #7
TRAVEL DISTANCE: 65' - 0"
TRAVEL DISTANCE: 100' - 6"
63 SF
PATIENT TLT.
GF102
EXISTING BUILDING #1 - OCCUPANCY #1 - GROUND FLOOR =
63,736 SF
OCCUPANCY TYPE - AMBULATORY HEALTHCARE
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 425
FULLY SPRINKLERED
COMPLIANCE NOTE
PER 7.5.1.6
EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
PERMITTED TO BE THROUGH
ADJOINING OR INTERVENING ROOMS OR AREAS,
PROVIDED THAT SUCH ROOMS OR AREAS ARE
ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES,
AND RECEPTION ROOMS. CONSTRUCTED AS
REQUIRED FOR CORRIDORS SHALL NOT BE
CONSTRUED AS INTERVENING ROOMS.
CONTROLLED
ACCESS
TRAVEL
PATH
STARTING
LOCATION
TD = XX
TRAVEL DISTANCE
NO. OF OCC./
NO. OF EXITS
ACTUAL
EXIT
WIDTH
OCC.
LOAD
FACTOR
LIFE SAFETY SYMBOLS
10/1
2"
34"
1:50
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
NEW
PARTITION KEY
NFPA
101-2015
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
(FIRE WALL IN IBC)
2 HR 90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR 90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS (SPRINKLERED)
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
VERT. OPG. (SHAFT)
FIRE BARRIER
60 MIN
[D]
1 HR
2 HR
60 MIN
90 MIN
EXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
8.7
NFPA 6.1.14.4.1
18.1.3.5.1 19.1.3.5.1
NFPA 7.2.A.3.1 (1)
NFPA 18.1.3.8/
19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1
NFPA 19.3.1.1
NFPA 8.6.2
8.6.5
NFPA 18.3.2.1.2
NFPA 8.4.1.1
19.3.2.1
NFPA 8.4.2 (3)
18.3.2.1.3 19.3.2.1.2
NFPA 8.5.2
18.3.7.3 19.3.7.3
NFPA 8.4.2
18.2.5.7.1.4 19.2.5.7.1.1
NFPA 8.4.2
18.3.6.2 19.3.6.2
21.3.6 39.3.6
NFPA 19.3.1.1
19.2.2.7 8.6.2 8.6.5(3) & 2
NFPA 7.2.6
19.2.2.7 18.2.2.7
NFPA 221
8.2.1.3
EXIST SOL.
CORE WD.
NFPA 7.2.1.4.1
7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4
8.3.4.2 TBL
18.4.4.7.2.2
7.1.3.2.9 (9)
NFPA 8.3.4.2 TBL
19.3.2.1.3,5
NFPA 8.3.4.2 TBL
8.5.4 18.3.7.8
NFPA 8.3.4.2 TBL
8.3.4.2 TBL
8.3.4.2 TBL
NFPA 8.3.4.2 TBL
8.3.4.2 8.4.3 19.3.2.1.4,3,5
8.4.3
8.4.3 18.3.6.4.1 19.3.6.4.1
N/A
FIRE
90 MIN
FIRE
90 MIN
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
NFPA 90
8.3.5.7 9.2.1
NFPA 8.3.5.7
9.2.1 7.2.4.3.5
N/A
8.5.5.2 18.3.7.3(2) 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2 18.3.6.4.1
N/A
WALL
RATING
RATED UL
ASSEMBLIES
2 HR
1 HR
1 HR
NR-
RESIST
SMK
NR
NR-
RESIST
SMK
NR
8.3
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
NR
SELF OR AUTO
CLOSING
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
NFPA 90
8.3.5.7 9.2.1
AREA WITHIN SCOPE OF WORK = 7,690 SQUARE FEET
AREA NOT IN CONTRACT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:2
P
M
BW LJ
635-19-101
GI104
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
LIFE SAFETY PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
- OKLAHOMA CITY, OK
1" = 10'-0"
GROUND LEVEL - LIFE SAFETY PLAN
GENERAL NOTES
1. THE PURPOSE OF THE CONSTRUCTION PHASING
NOTES AND DRAWINGS IS TO PROVIDE THE
GENERAL CONTRACTOR (GC) WITH GUIDANCE FOR
THE CONSTRUCTION SCHEDULE.
2. THE GC SHALL COORDINATE WITH THE
CONTRACTING OFFICER REPRESENTATIVE (COR) TO
DEVELOP A CRITICAL PATH METHOD (CPM)
SCHEDULE, SEQUENCING, COMPLETION DATES FOR
RENOVATION AND NEW CONSTRUCTION FOR THE
PROJECT.
3. THE MEDICAL CENTER MUST REMAIN IN FULL
OPERATION DURING CONSTRUCTION WITH MINIMAL
INTERRUPTION DUE TO ALL CONSTRUCTION
ACTIVITIES FOR THE PROJECT, INCLUDING NOISE,
DUST, VIBRATION, ETC., CREATED BY
CONSTRUCTION ACTIVITIES RELATED TO THIS
PROJECT.
4. THE GC’S SCHEDULES SHOULD INCLUDE BUT IS NOT
LIMITED TO THE FOLLOWING:
• ALL CONSTRUCTION-ACTIVITY-RELATED ISSUES
WHICH MAY AFFECT THE CONTINUAL
OPERATIONS OF THE MEDICAL CENTER.
• SCHEDULES FOR SHUTTING DOWN EXISTING
SYSTEMS OR ACCESS FOR TIE-INS AND/OR
REPLACEMENT.
• SCHEDULES FOR AFTER-HOURS CONSTRUCTION
ACTIVITIES.
5. PROVIDE TEMPORARY CHAINLINK CONSTRUCTION
FENCING WITH GATES AND CONSTRUCTION
BARRIERS AS REQUIRED TO SEPARATE
CONSTRUCTION ACTIVITIES FROM PUBLIC AREAS
AND AREAS REQUIRING ACCESS DURING
CONSTRUCTION. FENCING AND BARRIERS SHOULD
BE RELOCATED AS REQUIRED AFTER EACH PORTION
OF WORK IS COMPLETED TO ACCOMMODATE
ACCESS TO EXISTING FACILITIES AS CONSTRUCTION
PROGRESSES.
6. IF MEDICAL CENTER ACCESS PATHWAYS IDENTIFIED
ON THE PHASING PLANS ARE REQUIRED TO BE
BLOCKED TEMPORARILY TO ACCOMMODATE
CONSTRUCTION, COORDINATE ALTERNATE
PATHWAYS WITH THE COR AND PROVIDE
TEMPORARY SIGNAGE AND TEMPORARY
PROTECTIVE BARRIERS TO CREATE ALTERNATE
PATHWAYS AS REQUIRED. VERTICAL EXPANSION OF
THE EXISTING EAST AND WEST STAIRS MAY NEED TO
OCCUR AFTER-HOURS, SO THEY REMAIN IN SERVICE
DURING CONSTRUCTION. REFER TO THE PHASING
DIAGRAMS FOR ADDITIONAL NOTES. COORDINATE
AND SCHEDULE ANY DOWNTIME FOR THESE ROUTES
WITH THE COR.
7. THE GC SHALL SEEK FINAL APPROVAL OF THE
LOCATION OF CONSTRUCTION FENCING,
TEMPORARY CONSTRUCTION AND INFECTION
CONTROL BARRIERS, CONTRACTOR SITE ACCESS
AND DEBRIS AND MATERIAL HAUL ROUTES WITH THE
COR.
8. MAINTAIN ACCESS TO ALL EXISTING BUILDINGS,
UTILITIES AND FACILITIES WITHIN THE
CONSTRUCTION LIMITS TO ACCESS EQUIPMENT AND
TO PROVIDE SERVICE OR MAINTENANCE OF
EXISTING FACILITIES AND EQUIPMENT SERVING THE
MEDICAL CENTER.
9. COORDINATE UTILITY SHUT DOWNS OR ANY
CONSTRUCTION ACTIVITIES WHICH MAY
POTENTIALLY AFFECT THE EXISTING OPERATIONS
OF THE MEDICAL CENTER WITH THE COR. MAINTAIN
UNINTERRUPTED OPERATION OF THE EXISTING
FACILITIES, AND MINIMIZE DISRUPTIONS TO THE
MEDICAL CENTER FOR ALL SWITCH-OVER OF
UTILITIES. SCHEDULE THESE EVENTS AFTER-HOURS
OR AS APPROVED BY THE COR.
10. THE GC HAS RESPONSIBILITY IN DETERMINING THE
CORRECT PHASING TO MATCH THE REQUIREMENTS
OF THE CONSTRUCTION CONTRACT AS WELL AS THE
ACTUAL LOCATIONS AND THE METHODS THROUGH
WHICH TO CONSTRUCTION THE ICRA-COMPLIANT
CONSTRUCTION BARRIERS.
11. THE GC SHALL COORDINATE WITH THE COR TO
LOCATE THE SAFETY SIGN AND CONSTRUCTION
SIGN.
12. THE GENERAL CONTRATOR SHALL PROVIDE
ISOLATION BARRIERS.COMPLETE ALL CRITICAL
BARRIERS BEFORE CONSTRUCTION WORK BEGINS.
13. MAINTAIN ALL FIRE BARRIERS AND DUST
PARTITIONS AS REQUIRED TO PROVIDE A DUST-FREE
AND CLEAN ENVIRONMENT BETWEEN RENOVATED
AREAS WITHIN THE HOSPITAL AND AREAS ADJACENT
TO RENOVATED AND NEW CONSTRUCITON.
14. MAINTAIN INSULATED AND WATERTIGHT EXTERIOR
ENCLOSURE FOR EXISTING FACILITY AT ALL TIMES.
WORK REQUIRED TO REMOVE THE EXISTING
PARAPET, ROOFING, MASONRY, ETC. TO
ACCOMMODATE THE VERTICAL EXPANSION SHALL BE
PERFORMED IN PHASES TO PROTECT THE
ENCLOSURE.
15. ISOLATE HVAC SYSTEM WHERE WORK IS
PERFORMED TO PREVENT CONTAMINATION OF DUCT
SYSTEM.
16. ALL PERSONNEL ENTERING RENOVATION AREAS
WITHIN OCCUPIED FLOORS OF THE MEDICAL CENTER
SHALL WEAR SHOE COVERS, AND THESE MUST BE
CHANGED EACH TIME THE WORKER EXITS THE
WORK AREA. PROVIDE ADHESIVE WALK-OFF MATS
AT ENTRANCES TO THESE WORK AREAS. IF THERE
IS AN ANTEROOM, A MAT SHOULD BE WITHIN THIS
AREA. REPLACE MATS DAILY OR WHEN THEY NO
LONGER ARE ABLE TO CONTAIN DUST AND DIRT.
WET MOP AND/OR VACUUM WORK AREA WITH HEPA
FILTERED VACUUM BEFORE LEAVING WORK AREAS.
CONTAIN CONSTRUCTION WASTE IN TIGHTLY
COVERED CONTAINERS BEFORE TRANSPORTING.
REMOVE HVAC ISOLATION FROM SYSTEM IN AREAS
WHERE WORK IS BEING PERFORMED. REMOVE
BARRIER MATERIALS CAREFULLY TO MINIMIZE THE
SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION. DO NOT REMOVE BARRIERS FROM
WORK AREA UNTIL COMPLETED PROJECT IS
THOROUGHLY CLEANED.
17. REFER TO SPECIFICATIONS SECTION 01 00 00
GENERAL REQUIREMENTS.
DD
EE
FF
GG
HH
II
JJ
K
123 SF
EXAM/CONSULT ROOM
GF124D
125 SF
EXAM/CONSULT ROOM
GF124E
118 SF
EXAM/CONSULT ROOM
GF113
123 SF
EXAM/CONSULT ROOM
GF112
136 SF
EXAM/CONSULT ROOM
GF124B
29 SF
HEIGHT/WEIGHT
ALCOVE
GF105
75 SF
BLOOD SPECIMEN
COLLECTION
GF103E
73 SF
BLOOD SPECIMEN
COLLECTION
GF103F
76 SF
BLOOD SPECIMEN
COLLECTION
GF103D
75 SF
BLOOD SPECIMEN
COLLECTION
GF103C
57 SF
TOILET SPECIMEN
COLLECTION
GF103B
211 SF
LAB
GF103
55 SF
TOILET SPECIMEN
COLLECTION
GF103A
75 SF
BLOOD SPECIMEN
COLLECTION
GF103K
74 SF
BLOOD SPECIMEN
COLLECTION
GF103J
73 SF
BLOOD SPECIMEN
COLLECTION
GF103H
70 SF
BLOOD SPECIMEN
COLLECTION
GF103G
62 SF
PATIENT TLT.
GF117
51 SF
STAFF LOCKER
GF125
64 SF
STAFF TLT.
GF116
183 SF
LAB 2 RECEPTION
WORKSTATIONS
GF124H
72 SF
CLEAN UTILITY
GF124J
111 SF
LOGISTICS STORAGE
GF119
117 SF
TELECOMMUNICATIONS
ROOM
GF118
32 SF
PATIENT CHECK-IN
GF124I
846 SF
WAITING
GF124
125 SF
EXAM/CONSULT ROOM
GF124C
121 SF
CONSULT ROOM
GF114
717 SF
TEAM WORK AREA
GF124A
22 SF
ALCOVE RESUS
GF124L
24 SF
ALCOVE WHEELCHAIR
GF124K
10 SF
BLOOD SPECIMEN
ALCOVE
GF103I
GRAY AREA NOT IN PROJECT
SCOPE
27 SF
ELECT.
GF106
118 SF
CONSULT ROOM
GF115
112 SF
MED. ROOM
GF124F
803 SF
PATIENT CORRIDOR
CGF 5
308 SF
PATIENT CORRIDOR
CGF 4
TRAVEL DISTANCE: 65' - 0"
TRAVEL DISTANCE: 100' - 6"
63 SF
PATIENT TLT.
GF102
CONTROLLED
ACCESS
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:4
P
M
BW LJ
635-19-101
GI105
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
GROUND FLOOR PHASING PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
- OKLAHOMA CITY, OK
1" = 10'-0"
GROUND LEVEL -PHASING PLAN
MATERIAL LEGEND
KEY NOTES
BLACK MASTIC UNDER 12" x 12" FLOOR TILE
ASSUMED RESIDUAL BLACK MASTIC UNDER CARPET &
WOOD LAMINATE
TAN DUCT MASTIC THROUGHOUT PLENUM
1 2 3 4 5 6 7
H
I
J
K
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
NORTH
KEY PLAN
NTS
NORTH
E
A
B
F
D
G
HW
C22
5 18
MOD B RENOVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
NORTH
FULLY SPRINKLERED
B
IM
/V
IS
N
O k la h o m a C it y P
A C
T R e n o v a ti o n /O k la h o m a C it y P
A C
T R e n o v a ti o n .r v t
/2
/2
:2
:0
P
M
GAG RCV
635-19-101
HA101
635 - OKLAHOMA CITY, OK
SEPTEMBER 24, 2021
01-
ASBESTOS ABATEMENT PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC
- OKLAHOMA CITY, OK
1/4" = 1'-0"
PARTIAL GROUND LEVEL PLAN - ASBESTOS ABATEMENT
Note Number Note
1 ACTUAL MATERIAL COVERS WHOLE AREA IN SMALL ISOLATED
LOCATIONS.
DN
UP
GENERAL NOTES
LEGEND
ELIGIBILITY
GF103cLOW VISION
GF104
ELIGIBILITY
GF103aELIGIBILITY
GF103b
ELIGIBILITY
GF123
ELIGIBILITY
GF105
MAS SUPPLY
GF106
MY HEALTHY VET
GF107
SOCIAL WORKER
GF108
PSYCHOLOGIST
GF109
CLEAN SUPPLY
GF110
MED ROOM
GF111
EXAM
GF11…