This document is a specification section outlining requirements for automatic door operators for a VA construction project. It specifies low energy electrohydraulic door operators capable of operating interior or exterior doors up to 200 pounds and 48 inches wide, within temperature ranges of -22 to 122 degrees Fahrenheit. It requires ANSI and NFPA compliance and lists related specification sections. Product data, shop drawings, warranties, and maintenance are to be submitted, along with field quality control and adjustment. Approved operators include models from Dorma, LCN, Norton, and Stanley. Touchless wall switches and key switches are specified as activation devices. Installation must comply with ANSI standards and coordinate with electrical and access control systems. The certified installer must provide training, and labels with door information QR codes are required.

View the file

Other files

File Type Posted
36C25922R0012 0008.docx DOCX document
36C25922R0012 0008.docx DOCX document
36C25922R0012 0007.docx DOCX document
36C25922R0012 0006.docx DOCX document
36C25922R0012 0005.docx DOCX document
Product Data Sheets.pdf PDF
SECTION 03 30 00 Cast in Place Concrete.docx DOCX document
013216.15 PROJECT SCHEDULES.pdf PDF
080671_Door_Hardware_Schedule_2022-01-21.pdf PDF
VA02821319-Floor tile and Mastic OK VA(rev).docx DOCX document
09 68 00 CARPETING .pdf PDF
OKC PACT Renovation AE601.pdf PDF
105126.18 Solid Plastic Lockers (3).pdf PDF
Hollow Metal Doors and Frames.pdf PDF
36C25922R0012 0004.docx DOCX document
OKC PACT Renovation Updated Drawings Final.pdf PDF
092400 PORTLAND CEMENT PLASTER.pdf PDF
Asbestos Building 1 Inventory.xlsx XLSX spreadsheet
2020-0647.20 F1 ACM 1-20-2022.pdf PDF
122400 Window Shades.pdf PDF
275223 - Nurse Call Systems.pdf PDF
14 92 00 PNEUMATIC TUBE SYSTEM.pdf PDF
Integrated Access Control Hardware Devices.pdf PDF
092513.13 ACRYLIC PLASTER FINISH.pdf PDF
087100_Door_Hardware.pdf PDF
090600-SCHEDULE OF FINISHES (1).pdf PDF
36C25922R0012 0003.docx DOCX document
Pre-Bid Site Walk Attendance sheet.pdf PDF
36C25922R0012 0002.docx DOCX document
36C25922R0012 0001.docx DOCX document
36C25922R0012_1.docx DOCX document
3 10 2021 Past Performance Questionnaire.docx DOCX document
OKC B-Mod Drawings.pdf PDF
OKC B-Mod Specifications.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OKC Renovate B Mod for PACT Project Number 635-19-101

RFI #1 1.24.22

01-01-21

AUTOMATIC DOOR OPERATORS 087113 - 1

SECTION 087113 - AUTOMATIC DOOR OPERATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Low energy automatic door operators for swinging doors.

B. Related Sections:

1. Division 01 Section "General Conditions".

2. Division 01 Section "Cash Allowances".

3. Division 01 Section "Product Allowances".

4. Division 01 Section "Closeout Procedures".

5. Division 08 Section “Door Schedule”.

6. Division 08 Section “Hollow Metal Doors and Frames”.

7. Division 08 Section “Flush Wood Doors”.

8. Division 08 Section “Door Hardware”.

9. Division 08 Section “Access Control Hardware”.

10. Division 26 Section “Electrical”.

A. Codes and Standards: Comply with the version year adopted by the Authority Having Jurisdiction.

1. ANSI A117.1 - Accessible and Usable Buildings and Facilities.

2. ANSI/BHMA A156.4 - Door Controls, Door Closers.

3. ANSI/BHMA A156.19 - Power Assist and Low-Energy Power Operated Doors.

4. ICC/IBC - International Building Code.

5. NFPA 70 - National Electrical Code.

6. NFPA 80 - Fire Doors and Windows.

7. NFPA 101 - Life Safety Code.

8. NFPA 105 - Installation of Smoke Door Assemblies.

9. UL/ULC and CSA C22.2 – Standards for Automatic Door Operators Used on Fire and

Smoke Barrier Doors and Systems of Doors.

10. UL 325 - Door, Drapery, Gate, Louver, and Window Operators and Systems.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 2

11. State Building Codes, Local Amendments.

1.3 PERFORMANCE REQUIREMENTS

A. Automatic door operators to be used on interior or exterior doors; up to 200 pounds (91 kg) weight and maximum door width of 48" (1219 mm).

1. Auto door operator capable of operating within temperature ranges of -22°F (-30°C) and 122°F (50°C).

1.4 SUBMITTALS

A. Product Data: Manufacturer's product data sheets including installation details, material descriptions, dimensions of individual components and profiles, and finishes for automatic door operators, including activation devices. Include operating characteristics, electrical characteristics, and furnished accessories.

B. Shop Drawings: Include details and attachments to other work.

1. Include locations and elevations of each unique entrance showing activation devices.

2. Indicate required clearances, components, and location and size of field connections.

3. Wiring Diagrams: For power, signal, and activation wiring.

C. Qualification Data: Provide copy of manufacturer's official certification or accreditation document indicating proof of status as a qualified and authorized installer of automatic door operators and accessories.

D. Operating and Maintenance Manuals: Provide manufacturer's operating and maintenance manual for each item comprising the automatic door operator installation in quantity as required in Division 01, Closeout Submittals. The manual to include the name, address, and contact information of the manufacturer and Installer providing the operators and installation.

The final copies delivered after completion of the installation test to include "as built" modifications made during installation, checkout, and acceptance.

E. Warranties and Maintenance: Special warranties and maintenance agreements specified in this Section.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation and maintenance of units required for this Project.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 3

B. Certified Installer Qualifications: Locally certified ASSA ABLOY Power Operator Preferred Installer required for the installation and maintenance of the automatic door operator units and accessories indicated for the Project.

C. Source Limitations: Obtain automatic door operators, including activation devices, from single source, qualified supplier unless otherwise indicated.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a testing agency, and marked for intended location and application.

E. Exit Door Requirements: Comply with requirements of authorities having jurisdiction for doors with automatic door operators serving as a component of a required means of egress.

F. Fire Rated Door Assemblies: Provide operators for fire rated door assemblies that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction for use on types and sizes of labeled fire doors required.

G. Pre-Submittal Conference: Conduct coordination conference in compliance with requirements in Division 01 Section "Project Meetings" with attendance by representatives of Supplier, Installer, and Contractor to review proper methods and the procedures for receiving, handling, and installing automatic door operators.

1. Prior to installation of automatic door operators, arrange for certified Installer's representative to conduct a project specific meeting to review the installation and maintenance of their respective products. Project meeting to be attended by representatives of related trades furnishing and installing the aluminum, hollow metal and wood doors sections.

2. Review and finalize construction schedule and verify availability of materials.

1.6 COORDINATION

A. Electrical Systems Coordination: Coordinate the layout and installation of scheduled automatic door operators and related activation devices, with required connections to source power junction boxes, remote power supplies, access control equipment, detection and monitoring hardware, and fire alarm system.

B. Templates: Obtain and distribute to the parties involved, templates for doors, frames, operators, and other work specified to be factory prepared and reinforced for installing automatic door operators. Check Shop Drawings of other work to confirm that adequate provisions are made for locating and installing automatic door operators to comply with indicated requirements.

C. Door and Frame Preparation: Related Division 08 Sections (Steel, Aluminum and Wood) doors and corresponding frames are to be prepared, reinforced and pre-wired (if applicable) to

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 4

receive the installation of the specified automatic door operators without additional in-field modifications.

1.7 WARRANTY

A. General Warranty: Reference Division 01, General Requirements. Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

B. Special Warranty: Written warranty, executed by manufacturer, agreeing to repair or replace components of automatic door operators that fail in materials or workmanship within specified warranty period after final acceptance by Owner. Failures include, but are not limited to, the following:

1. Faulty or sporadic operation of automatic door operator, including activation and safety devices.

2. Deterioration of metals, metal finishes, and other materials beyond normal weathering or use.

C. Special Warranty Period: Two years from date of Substantial Completion.

D. Provide extended warranty from defects in material or workmanship under normal use for a period of 3 years from the date of substantial completion for units installed by a certified ASSA ABLOY Power Operator Preferred Installer in accordance with the manufacturer's written warranty certificate.

1.8 MAINTENANCE SERVICE

A. Maintenance Service: Beginning at Substantial Completion, and running concurrent with the specified warranty period, provide continuous (6) months full maintenance by skilled employees of automatic door operator Installer. Include planned and preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper door operation. Provide parts and supplies the same as those used in the manufacture and installation of original equipment.

B. Extended Maintenance Support and Service Agreement: Submit for Owner’s consideration an optional extended Service Agreement for the installed automatic door operator system. The extended Service Agreement is considered elective and is without manufacturer's requirement stipulating mandatory coverage for owner and/or vendor system support.

1. A published copy of this agreement to be included with the submittal package

2. Support for the installed automatic door operator system is provided through the vendor under a specified, limited 24 hour support program.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 5

3. Automatic door operators and components are to be available on a one-day turn around time frame from the vendor.

PART 2 - PRODUCTS

2.1 ELECTROHYDRAULIC DOOR OPERATORS

A. General: Provide low energy operators of size recommended by manufacturer for door size, weight, and movement; for condition of exposure; and for compliance with UL 325. Coordinate operator mechanisms with door operation, hinges, and activation devices.

1. Fire-Rated Doors: Provide door operators for fire-rated door assemblies that comply with NFPA 80 for fire-rated door components and are listed and labeled by a qualified testing agency.

B. Standard: Certified ANSI/BHMA A156.19.

C. Performance Requirements:

1. Opening Force if Power Fails: Not more than 15 lbf required to release a latch if provided, not more than 30 lbf required to manually set door in motion, and not more than 15 lbf required to fully open door.

2. Entrapment Protection: Not more than 15 lbf required to prevent stopped door from closing or opening.

D. Configuration: Surface mounted or in-ground as required. Door operators to control single swinging and pair of swinging doors.

E. Operation: Power opening and spring closing operation capable of meeting ANSI A117.1 accessibility guideline. Provide time delay for door to remain open before initiating closing cycle as required by ANSI/BHMA A156.19. When not in automatic mode, door operator to function as manual door closer with fully adjustable opening and closing forces, with or without electrical power.

F. Features: Operator units to have full feature adjustments for door opening and closing force and speed, backcheck, motor assist acceleration from 0 to 30 seconds, time delay, vestibule interface delay, obstruction recycle, and hold open time from 0 up to 30 seconds.

G. Provide outputs and relays on board the operator to allow for coordination of exit device latch retraction, electric strikes, magnetic locks, card readers, safety and motion sensors and specified auxiliary contacts.

H. Brackets and Reinforcements: Manufacturer's standard, fabricated from aluminum with nonferrous shims for aligning system components.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 6

I. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Dorma Products (DO) - ED800 Series.

2. LCN Closers (LC) - 4640 Series.

3. Norton Door Controls (NO) - 6000 Series.

4. Stanley Security Solutions (ST) – D-4990 Series.

2.2 ACTIVATION DEVICES

A. General: Provide activation devices in accordance with ANSI/BHMA A156.19 standard, for condition of exposure indicated and for long term, maintenance free operation under normal traffic load operation. Coordinate activation control with electrified hardware and access control interfaces. Activation switches are standard SPST, with optional DPDT availability.

B. Touch Less Wall Switch: Momentary contact door control switch with movement required activation. Single or double gang box junction box mounting.

1. Doppler radar sensor.

2. Mounting Location: As indicated on Drawings.

3. Manufacturers:

a. BEA Sensors (BS) – MS Series.

b. LCN Closers (LC) – 813 Series.

c. Norton Door Controls (NO) – 700 Series.

d. Securitron (SU) – WSS Series.

C. Key Switch: Key controlled actuator device enclosed in single or double gang junction box.

1. Faceplate Material: Stainless steel.

2. Functions: On-off, maintained contact.

3. Two-way Mounting: Recess or surface mounting as indicated on Drawings.

4. Manufacturers:

a. Alarm Controls (AK) – MCK Series.

b. Securitron (SU) – MKA Series.

c. Wikk Industries (WI) – KS Series.

2.3 ACCESSORIES

A. Signage: As required by cited ANSI/BHMA A156.19 standard for the type of operator.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 7

2.4 FINISHES

A. Standard: Designations used to indicate hardware finishes complying with ANSI/BHMA A156.18, including coordination with traditional U.S. finishes indicated by certain manufacturers for their products.

B. Provide quality of finish, including thickness of plating or coating (if any), composition, hardness, and other qualities complying with manufacturer's standards, but in no case less than specified by referenced standards for the applicable units of hardware. Units will be sprayed with a combination of waterborne acrylic and polyester powder coat.

C. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

2.5 OPENING LABELS

A. Provide 1"W x 2"H gloss polyester label imprinted with door mark and QR-type code readable via IR and visible light scan. QR code links to a security credential protected site displaying the installed door opening information. Label constructed with a high-performance, permanent acrylic adhesive resistant to chemicals, smear and scratch, and repeated freeze and thaw cycles. Face stock of label to be white or clear coated, 2.0 mil thickness with tensile strength meeting or exceeding 18,000 psi.

1. Approved Manufacturer: Openings Studio™ Smart Tags (AA).

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine conditions, with Installer present, for compliance with requirements for installation tolerances, door and frame preparation and reinforcements, power connections, electrical systems interfaces, and other conditions affecting performance of automatic door operators.

B. Notify architect of any discrepancies or conflicts between the door schedule, door types, drawings and scheduled hardware. Proceed only after such discrepancies or conflicts have been resolved in writing.

3.2 INSTALLATION

A. General: Install complete automatic door operators according to manufacturer's written instructions and ANSI/BHMA A156;19 standard, including activation devices, control wiring, remote power units if any, connection to the building's fire alarm system, and required signage.

RFI #1 1.24.22

AUTOMATIC DOOR OPERATORS 087113 - 8

B. Power Connection: Reference Division 26 "Electrical" Sections for connection to electrical power distribution system.

C. Access Control System: Coordinate connections and operation with access control system

D. Signage: Apply signage as required by ANSI/BHMA A156.19 standard for type of door operator and direction of pedestrian travel.

3.3 FIELD QUALITY CONTROL

A. Field Inspection (Punch Report): Reference Division 01 Sections “Closeout Procedures”.

Produce project punch report for each installed door opening indicating compliance with approved submittals and verification hardware is properly installed, operating and adjusted.

Include list of items to be completed and corrected, indicating the reasons or deficiencies causing the Work to be incomplete or rejected.

1. Organization of List: Include separate Door Opening and Deficiencies and Corrective Action Lists organized by Mark, Opening Remarks and Comments, and related Opening Images and Video Recordings.

2. Submit documentation of incomplete items in the following formats:

a. PDF electronic file.

b. Electronic formatted file integrated with the Openings Studio™ door opening management software platform.

3.4 ADJUSTING

A. Comply with requirements of ANSI/BHMA A156.19 standard. Adjust automatic door operators to function smoothly, and lubricate as recommended by manufacturer.

3.5 DEMONSTRATION

A. Certified Installer's representative to provide eight (8) hours of training to Owner's maintenance personnel in the proper adjustment, operation, and maintenance of automatic door operators.

END OF SECTION 087113

PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Low energy automatic door operators for swinging doors.
B. Related Sections:
1. Division 01 Section "General Conditions".
2. Division 01 Section "Cash Allowances".
3. Division 01 Section "Product Allowances".
4. Division 01 Section "Closeout Procedures".
5. Division 08 Section “Door Schedule”.
6. Division 08 Section “Hollow Metal Doors and Frames”.
8. Division 08 Section “Door Hardware”.
A. Codes and Standards: Comply with the version year adopted by the Authority Having Jurisdiction.
1. ANSI A117.1 - Accessible and Usable Buildings and Facilities.
2. ANSI/BHMA A156.4 - Door Controls, Door Closers.
3. ANSI/BHMA A156.19 - Power Assist and Low-Energy Power Operated Doors.
4. ICC/IBC - International Building Code.
5. NFPA 70 - National Electrical Code.
6. NFPA 80 - Fire Doors and Windows.
7. NFPA 101 - Life Safety Code.
8. NFPA 105 - Installation of Smoke Door Assemblies.
9. UL/ULC and CSA C22.2 – Standards for Automatic Door Operators Used on Fire and Smoke Barrier Doors and Systems of Doors.
10. UL 325 - Door, Drapery, Gate, Louver, and Window Operators and Systems.
11. State Building Codes, Local Amendments.
1.3 PERFORMANCE REQUIREMENTS
A. Automatic door operators to be used on interior or exterior doors; up to 200 pounds (91 kg) weight and maximum door width of 48" (1219 mm).
1. Auto door operator capable of operating within temperature ranges of -22 F (-30 C) and 122 F (50 C).
1.4 SUBMITTALS
A. Product Data: Manufacturer's product data sheets including installation details, material descriptions, dimensions of individual components and profiles, and finishes for automatic door operators, including activation devices. Include operating cha...
B. Shop Drawings: Include details and attachments to other work.
1. Include locations and elevations of each unique entrance showing activation devices.
2. Indicate required clearances, components, and location and size of field connections.
3. Wiring Diagrams: For power, signal, and activation wiring.
C. Qualification Data: Provide copy of manufacturer's official certification or accreditation document indicating proof of status as a qualified and authorized installer of automatic door operators and accessories.
D. Operating and Maintenance Manuals: Provide manufacturer's operating and maintenance manual for each item comprising the automatic door operator installation in quantity as required in Division 01, Closeout Submittals. The manual to include the name...
E. Warranties and Maintenance: Special warranties and maintenance agreements specified in this Section.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation and maintenance of units required for this Project.
B. Certified Installer Qualifications: Locally certified ASSA ABLOY Power Operator Preferred Installer required for the installation and maintenance of the automatic door operator units and accessories indicated for the Project.
C. Source Limitations: Obtain automatic door operators, including activation devices, from single source, qualified supplier unless otherwise indicated.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a testing agency, and marked for intended location and application.
E. Exit Door Requirements: Comply with requirements of authorities having jurisdiction for doors with automatic door operators serving as a component of a required means of egress.
F. Fire Rated Door Assemblies: Provide operators for fire rated door assemblies that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction for use on types and sizes of labeled fire doors required.
G. Pre-Submittal Conference: Conduct coordination conference in compliance with requirements in Division 01 Section "Project Meetings" with attendance by representatives of Supplier, Installer, and Contractor to review proper methods and the procedure...
1. Prior to installation of automatic door operators, arrange for certified Installer's representative to conduct a project specific meeting to review the installation and maintenance of their respective products. Project meeting to be attended by rep...
2. Review and finalize construction schedule and verify availability of materials.
1.6 COORDINATION
A. Electrical Systems Coordination: Coordinate the layout and installation of scheduled automatic door operators and related activation devices, with required connections to source power junction boxes, remote power supplies, access control equipment,...
B. Templates: Obtain and distribute to the parties involved, templates for doors, frames, operators, and other work specified to be factory prepared and reinforced for installing automatic door operators. Check Shop Drawings of other work to confirm t...
C. Door and Frame Preparation: Related Division 08 Sections (Steel, Aluminum and Wood) doors and corresponding frames are to be prepared, reinforced and pre-wired (if applicable) to receive the installation of the specified automatic door operators wi...
1.7 WARRANTY
A. General Warranty: Reference Division 01, General Requirements. Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run...
B. Special Warranty: Written warranty, executed by manufacturer, agreeing to repair or replace components of automatic door operators that fail in materials or workmanship within specified warranty period after final acceptance by Owner. Failures incl...
1. Faulty or sporadic operation of automatic door operator, including activation and safety devices.
2. Deterioration of metals, metal finishes, and other materials beyond normal weathering or use.
C. Special Warranty Period: Two years from date of Substantial Completion.
D. Provide extended warranty from defects in material or workmanship under normal use for a period of 3 years from the date of substantial completion for units installed by a certified ASSA ABLOY Power Operator Preferred Installer in accordance with t...
1.8 MAINTENANCE SERVICE
A. Maintenance Service: Beginning at Substantial Completion, and running concurrent with the specified warranty period, provide continuous (6) months full maintenance by skilled employees of automatic door operator Installer. Include planned and preve...
B. Extended Maintenance Support and Service Agreement: Submit for Owner’s consideration an optional extended Service Agreement for the installed automatic door operator system. The extended Service Agreement is considered elective and is without manuf...
1. A published copy of this agreement to be included with the submittal package
2. Support for the installed automatic door operator system is provided through the vendor under a specified, limited 24 hour support program.
3. Automatic door operators and components are to be available on a one-day turn around time frame from the vendor.
PART 2 - PRODUCTS
2.1 ELECTROHYDRAULIC DOOR OPERATORS
A. General: Provide low energy operators of size recommended by manufacturer for door size, weight, and movement; for condition of exposure; and for compliance with UL 325. Coordinate operator mechanisms with door operation, hinges, and activation dev...
1. Fire-Rated Doors: Provide door operators for fire-rated door assemblies that comply with NFPA 80 for fire-rated door components and are listed and labeled by a qualified testing agency.
B. Standard: Certified ANSI/BHMA A156.19.
C. Performance Requirements:
1. Opening Force if Power Fails: Not more than 15 lbf required to release a latch if provided, not more than 30 lbf required to manually set door in motion, and not more than 15 lbf required to fully open door.
2. Entrapment Protection: Not more than 15 lbf required to prevent stopped door from closing or opening.
D. Configuration: Surface mounted or in-ground as required. Door operators to control single swinging and pair of swinging doors.
E. Operation: Power opening and spring closing operation capable of meeting ANSI A117.1 accessibility guideline. Provide time delay for door to remain open before initiating closing cycle as required by ANSI/BHMA A156.19. When not in automatic mode, d...
F. Features: Operator units to have full feature adjustments for door opening and closing force and speed, backcheck, motor assist acceleration from 0 to 30 seconds, time delay, vestibule interface delay, obstruction recycle, and hold open time from 0...
G. Provide outputs and relays on board the operator to allow for coordination of exit device latch retraction, electric strikes, magnetic locks, card readers, safety and motion sensors and specified auxiliary contacts.
H. Brackets and Reinforcements: Manufacturer's standard, fabricated from aluminum with nonferrous shims for aligning system components.
I. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Dorma Products (DO) - ED800 Series.
2. LCN Closers (LC) - 4640 Series.
3. Norton Door Controls (NO) - 6000 Series.
4. Stanley Security Solutions (ST) – D-4990 Series.
2.2 ACTIVATION DEVICES
A. General: Provide activation devices in accordance with ANSI/BHMA A156.19 standard, for condition of exposure indicated and for long term, maintenance free operation under normal traffic load operation. Coordinate activation control with electrified...
B. Touch Less Wall Switch: Momentary contact door control switch with movement required activation. Single or double gang box junction box mounting.
1. Doppler radar sensor.
2. Mounting Location: As indicated on Drawings.
3. Manufacturers:
a. BEA Sensors (BS) – MS Series.
b. LCN Closers (LC) – 813 Series.
c. Norton Door Controls (NO) – 700 Series.
d. Securitron (SU) – WSS Series.
C. Key Switch: Key controlled actuator device enclosed in single or double gang junction box.
1. Faceplate Material: Stainless steel.
2. Functions: On-off, maintained contact.
3. Two-way Mounting: Recess or surface mounting as indicated on Drawings.
4. Manufacturers:
a. Alarm Controls (AK) – MCK Series.
b. Securitron (SU) – MKA Series.
c. Wikk Industries (WI) – KS Series.
2.3 ACCESSORIES
A. Signage: As required by cited ANSI/BHMA A156.19 standard for the type of operator.
2.4 FINISHES
A. Standard: Designations used to indicate hardware finishes complying with ANSI/BHMA A156.18, including coordination with traditional U.S. finishes indicated by certain manufacturers for their products.
B. Provide quality of finish, including thickness of plating or coating (if any), composition, hardness, and other qualities complying with manufacturer's standards, but in no case less than specified by referenced standards for the applicable units o...
C. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
2.5 OPENING LABELS
A. Provide 1"W x 2"H gloss polyester label imprinted with door mark and QR-type code readable via IR and visible light scan. QR code links to a security credential protected site displaying the installed door opening information. Label constructed w...
1. Approved Manufacturer: Openings Studio™ Smart Tags (AA).
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine conditions, with Installer present, for compliance with requirements for installation tolerances, door and frame preparation and reinforcements, power connections, electrical systems interfaces, and other conditions affecting performance of...
B. Notify architect of any discrepancies or conflicts between the door schedule, door types, drawings and scheduled hardware. Proceed only after such discrepancies or conflicts have been resolved in writing.
3.2 INSTALLATION
A. General: Install complete automatic door operators according to manufacturer's written instructions and ANSI/BHMA A156;19 standard, including activation devices, control wiring, remote power units if any, connection to the building's fire alarm sys...
B. Power Connection: Reference Division 26 "Electrical" Sections for connection to electrical power distribution system.
C. Access Control System: Coordinate connections and operation with access control system
D. Signage: Apply signage as required by ANSI/BHMA A156.19 standard for type of door operator and direction of pedestrian travel.
3.3 FIELD QUALITY CONTROL
A. Field Inspection (Punch Report): Reference Division 01 Sections “Closeout Procedures”. Produce project punch report for each installed door opening indicating compliance with approved submittals and verification hardware is properly installed, oper...
1. Organization of List: Include separate Door Opening and Deficiencies and Corrective Action Lists organized by Mark, Opening Remarks and Comments, and related Opening Images and Video Recordings.
2. Submit documentation of incomplete items in the following formats:
a. PDF electronic file.
b. Electronic formatted file integrated with the Openings Studio™ door opening management software platform.
3.4 ADJUSTING
A. Comply with requirements of ANSI/BHMA A156.19 standard. Adjust automatic door operators to function smoothly, and lubricate as recommended by manufacturer.
3.5 DEMONSTRATION
A. Certified Installer's representative to provide eight (8) hours of training to Owner's maintenance personnel in the proper adjustment, operation, and maintenance of automatic door operators.