OKC PACT Renovation Updated Drawings Final.pdf

PDF 12 MB Posted

Attached to
Z2DA--635-19-101 Renovate B-Mod Construction (plus up) (VA-22-00016600)
Solicitation number
36C25922R0012
Issued by

About this file

This file relates to a federal contract solicitation for renovations at the Oklahoma City VA Medical Center.

The solicitation number is 36C25922R0012 and seeks proposals to renovate B-Mod construction at the Oklahoma City VA Medical Center located in Oklahoma City, Oklahoma. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19. Proposals are due by April 23, 2022 and the contract is expected to be awarded by June 2022. The solicitation seeks general construction services to renovate patient rooms and associated spaces at the medical center for an estimated price of $5-10 million. The contract will have a one year base period of performance with two one-year option periods. The acquisition is unrestricted and open to small businesses.

View the file

Other files

File Type Posted
36C25922R0012 0008.docx DOCX document
36C25922R0012 0008.docx DOCX document
36C25922R0012 0007.docx DOCX document
36C25922R0012 0006.docx DOCX document
36C25922R0012 0005.docx DOCX document
Product Data Sheets.pdf PDF
SECTION 03 30 00 Cast in Place Concrete.docx DOCX document
013216.15 PROJECT SCHEDULES.pdf PDF
080671_Door_Hardware_Schedule_2022-01-21.pdf PDF
VA02821319-Floor tile and Mastic OK VA(rev).docx DOCX document
09 68 00 CARPETING .pdf PDF
OKC PACT Renovation AE601.pdf PDF
105126.18 Solid Plastic Lockers (3).pdf PDF
Hollow Metal Doors and Frames.pdf PDF
087113_Automatic_Door_Operators.pdf PDF
36C25922R0012 0004.docx DOCX document
092400 PORTLAND CEMENT PLASTER.pdf PDF
Asbestos Building 1 Inventory.xlsx XLSX spreadsheet
2020-0647.20 F1 ACM 1-20-2022.pdf PDF
122400 Window Shades.pdf PDF
275223 - Nurse Call Systems.pdf PDF
14 92 00 PNEUMATIC TUBE SYSTEM.pdf PDF
Integrated Access Control Hardware Devices.pdf PDF
092513.13 ACRYLIC PLASTER FINISH.pdf PDF
087100_Door_Hardware.pdf PDF
090600-SCHEDULE OF FINISHES (1).pdf PDF
36C25922R0012 0003.docx DOCX document
Pre-Bid Site Walk Attendance sheet.pdf PDF
36C25922R0012 0002.docx DOCX document
36C25922R0012 0001.docx DOCX document
36C25922R0012_1.docx DOCX document
3 10 2021 Past Performance Questionnaire.docx DOCX document
OKC B-Mod Drawings.pdf PDF
OKC B-Mod Specifications.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING LIST

1i

0 GRID / COLUMN LINE DESIGNATOR

EQUIPMENT NUMBER

DOOR NUMBER

Ga5xFB1

WALL TYPE

WINDOW TYPE

ROOM NAME

101 ROOM NAME / NUMBER

REVISION TAG

PLAN NORTH

NORTH ARROW WITH TRUE

NORTH INDICATION

EGRESS ROUTE ID AND

SECTION LENGTH

ROOM

ROOM OCCUPANCY

150 SF

EGRESS : EGRESS ID

Egress Length

ROOM OCCUPANCY & AREA

ELEVATION NUMBER

SECTION

INTERIOR ELEVATION

ENLARGEMENT,

DETAIL

SPOT ELEVATION

Name Elevation FLOOR LEVEL &

NAME

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

SHEET KEYNOTE

A101

SIM

EXTERIOR ELEVATION

A-101

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

INDEX OF DRAWINGS

01-A101

DISCIPLINE:

G - GENERAL

A - ARCHITECTURE

F - FIRE PROTECTION

P - PLUMBING

M - MECHANICAL

E - ELECTRICAL

SHEET TYPE

DESIGNATOR

VICINITY MAP

PROJECT TEAM

BUILDING SUMMARY

PROJECT INFORMATION

THE SCOPE OF THIS PROJECT IS TO DEVELOP FULL DESIGN-BID-BUILD PACKAGE TO DEMOLISH AND RENOVATE APPROXIMATELY 6,330 SQ. FT. OF EXISTING CLINICAL SPACE WITHIN BUILDING 1, GROUND LEVEL, AT THE OKCVA MEDICAL CENTER INCORPORATING THE MOST CURRENT VERSION OF THE VA’S PACT SPACE MODULE DESIGN GUIDE AND INDUSTRY

BEST PRACTICES.

ANNOTATION DRAWING SYMBOLSGENERAL NOTES

PROJECT NAME:

PROJECT NUMBER:

PROJECT LOCATION:

BUILDING NUMBER

1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW

ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.

2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE

SUBMITTING COST QUOTATIONS FOR WORK.

3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE

PROVIDED PRIOR TO CONTINUING WITH WORK.

4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT

5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION.

THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.

6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE

CONTRACTOR'S EXPENSE.

7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.

8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH

RESPECT TO DELIVERY DATE, QUALITY, OR COST.

9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S

MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.

10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL

EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.

11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA

REGULATIONS DURING CONSTRUCTION.

12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.

A101

A101

SCOPE OF WORK SUMMARY:

SHEET NUMBER

WITHIN SERIES

REMODEL B MOD OKLAHOMA VAMC

635-19-101

OKLAHOMA CITY DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER

921 N.E. 13TH STREET

OKLAHOMA CITY, OK 73104

INFECTION CONTROL NOTES:

Infection Control Risk Assessment: Type C Patient Risk Group: High Risk - Laboratories (specimen) High Risk Group/Type C= Construction Project Type III/IV Infection Control approval will be required when the construction activity and risk levl indicate Class III/IV.

During Construction Project/Class III:

1. Remove or Isolate HVAC system in area where work is being done to prevent contamination of duct system.

2. Complete all critical barriers i.e. sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with HEPA vacuum for vacuuming prior to exit) before construction begins.

3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.

4. Contain construction waste before transport in tightly covered containers.

5. Cover transport receptacles or carts. Tape covering unless solid lid.

Upon Completion of Project:

1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety Department and Infection Control Department and thoroughly cleaned by the owner’s Environmental Services Department.

2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.

3. Vacuum work area with HEPA filtered vacuums.

4. Wet mop area with disinfectant.

5. Remove isolation of HVAC system in areas where work is being performed.

Romanyk Consulting Focusing on what matters

0' 1'

6" 3"

1'

Gr ap hi c S ca le

: 1 /2"

1'-

0"

0' 4"

8" 1'

2'

Gr ap hi c S ca le

: 3 /32

1'

-0

0'

8' Gr ap hi c S ca le : 1

/16

1' -0

0' 8'

4' Gr ap hi c S ca le

: 1 /8"

1'-

0"

0' 2'

1' 4'

Gr ap hi c S ca le

: 1 /4"

1'-

0"

0' 2'

1' 4'

Gr ap hi c S ca le

: 3 /8"

1'-

0"

0' 2'

4' 1' Gr ap hi c S ca le : 1

/2"

1'- 0"

0' 1'

2' 6"

Gr ap hi c S ca le

: 3 /4"

1'-

0"

0' 1'

2' 6"

Gr ap hi c S ca le

: 1

1' -0

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

8910 7 6 5 4 3 2 1

U.S. Department of Veterans Affairs

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management FULLY SPRINKLERED

BI

M

VI

SN

- O kl ah om a

C ity

P

AC

T R en ov at io n/ O kl ah om a

C ity

P

AC

T R en ov at io n.

rv t 1/

/2

:5

4:

A M

PROJECT NUMBER - 635-19-101

REMODEL B MOD OKLAHOMA VAMC - OKLAHOMA CITY, OK

100% CONTRACT DOCUMENTS

SEPTEMBER 24, 2021 (RFI #1 - 1.24.22)

BW LJ

635-19-101

GI100635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021 (RFI

#1 - 1.24.22)

01-

SHEET INDEX & GENERAL INFORMATION 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

SHEET # SHEET TITLE

PLUMBING

P-001 PLUMBING SYMBOLS, NOTES, AND ABBREVIATIONS

PD100 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DWV DEMOLITION

PD101 PARTIAL GROUND FLOOR PLAN - PLUMBING DWV DEMOLITION

PD201 PARTIAL GROUND FLOOR PLAN - PLUMBING DISTRIBUTION DEMOLITION

PP100 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DWV

PP101 PARTIAL GROUND FLOOR PLAN - PLUMBING DWV

PP200 PARTIAL BASEMENT FLOOR PLAN - PLUMBING DISTRIBUTION

PP201 PARTIAL GROUND FLOOR PLAN - PLUMBING DISTRIBUTION

PP300 PLUMBING RISER DIAGRAM - DWV

PP301 PLUMBING RISER DIAGRAM - PLUMBING DISTRIBUTION

P-400 PLUMBING DETAILS & SCHEDULES

MECHANICAL

M-001 MECHANICAL SYMBOLS, NOTES, AND ABBREVIATIONS

MD101 PARTIAL GROUND FLOOR PLAN - HVAC DEMOLITION

MD102 PARTIAL LEVEL 03 FLOOR PLAN - HVAC DEMOLITION

MD201 PARTIAL GROUND FLOOR PLAN - PIPING DEMOLITION

MH101 PARTIAL GROUND FLOOR PLAN - HVAC

MH102 PARTIAL LEVEL 03 FLOOR PLAN - HVAC

MH200 MECHANICAL HVAC DETAILS

MH300 MECHANICAL HVAC SCHEDULES

MH301 MECHANICAL HVAC SCHEDULES

MI101 PARTIAL GROUND FLOOR PLAN - MECHANICAL INSTRUMENTATION

MI301 MECHANICAL INSTRUMENTATION - SEQUENCES OIT TR UNIT

MI302 MECHANICAL INSTRUMENTATION - SEQUENCES VAV - HW REHEAT

MI303 MECHANICAL INSTRUMENTATION - SEQUENCES EXHAUST FAN - ON/OFF

MP102 PARTIAL LEVEL 03 FLOOR PLAN - PIPING

MP101 PARTIAL GROUND FLOOR PLAN - PIPING

MP200 MECHANICAL PIPING DETAILS

MPT101 PARTIAL GROUND LEVEL FLOOR PLAN - PNEUMATIC TUBING SYSTEMS

ELECTRICAL

E-001 ELECTRICAL SYMBOLS, NOTES, AND ABBREVIATIONS

ED101 PARTIAL GROUND FLOOR PLAN - ELECTRICAL DEMOLITION

EL101 PARTIAL GROUND FLOOR PLAN - LIGHTING

EP100 BASEMENT LEVEL FLOOR PLAN - CONDUIT ROUTING

EP101 PARTIAL GROUND FLOOR PLAN - POWER

EP102 GROUND FLOOR PLAN - CONDUIT ROUTING

EP103 PARTIAL LEVEL 3 FLOOR PLAN - MECHANICAL POWER

EP104 PARTIAL LEVEL 09 FLOOR PLAN - ELECTRICAL

ES101 PARTIAL GROUND FLOOR PLAN - TECHNOLOGY SYSTEMS

E-400 ENLARGED PLANS - ELECTRICAL

E-500 ELECTRICAL DETAILS

E-700 ELECTRICAL SCHEDULES

SHEET # SHEET TITLE

GENERAL

GI100 SHEET INDEX & GENERAL INFORMATION

GI101 ABBREVIATIONS & SYMBOLS

GI102 ADA INFORMATION

GI103 BUILDING CODE DATA

GI104 LIFE SAFETY PLAN

GI105 GROUND FLOOR PHASING PLAN

HAZARDOUS MATERIALS

HA101 ASBESTOS ABATEMENT PLAN

ARCHITECTURAL

AD100 PARTIAL GROUND FLOOR - DEMOLITION PLAN

AD101 REFLECTED CEILING PLAN DEMOLITION PLAN

AD102 BASEMENT DEMO REFLECTED CEILING PLAN

AE101 OVERALL GROUND FLOOR

AE102 PARTIAL GROUND FLOOR - ENLARGED FLOOR PLAN

AE103 DIMENSION PLAN

AE104 REFLECTED CEILING PLAN

AE401 ENLARGED TOILET PLANS AND ELEVATIONS

AE402 ENLARGED TOILET PLANS AND ELEVATIONS

AE403 ENLARGED PLANS & ELEVATIONS

AE404 ENLARGED PLANS

AE405 INTERIOR ELEVATIONS

AE500 WALL TYPES

AE501 ACCESSIBLE DETAILS

AE502 INTERIOR DETAILS

AE503 METAL STUD DETAILS

AE504 CEILING DETAILS SUSPENDED GYPSUM

AE601 DOOR & WINDOW SCHEDULES

AE701 CASEWORK SECTIONS AND DETAILS

AE702 CASEWORK SECTIONS AND DETAILS

AF101 GROUND FLOOR FINISH PLAN AND SCHEDULE

AW101 GROUND FLOOR SIGNAGE PLAN

AW102 SIGNAGE PLAN DETAILS

AW103 SIGNAGE PLAN DETAILS

QH101 PARTIAL GROUND FLOOR - EQUIPMENT PLAN

SPRINKLER

FS001 SPRINKLER SYMBOLS, NOTES, DETAILS, AND ABBREVIATIONS

FD101 PARTIAL GROUND FLOOR PLAN - SPRINKLER DEMOLITION

FS101 PARTIAL GROUND FLOOR PLAN - SPRINKLER

OWNER:

Oklahoma City VA Health Care System 921 NE 13th Street Oklahoma City, OK 73104

John Wilson John.Wilson3@va.gov

405-456-3922 520-400-1202 cell

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

PROJECT ARCHITECT:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Barrett Webb Barrett.Webb@RomaynkConsulting.com

855-424-3838 x318 512-413-6963 cell

HAZARDOUS MATERIALS:

SCI Engineering 130 Point West Blvd.

St. Charles MO 63301

Glen Grissom, Project Scientist @sciengineering.com

636-949-8200

ELECTRICAL ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Jonathan Foster, PE, LEED AP Jonathan.Foster@RomanykConsulting.com

855.424.3838 x307

501.428.4167 cell

MECHANICAL ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cell

PLUMBING ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cell

FIRE PROTECTION ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Scott Thraen, PE Scott.Thraen@RomanykConsulting.com

855.424.3838 x312

402.981.8882 cell

Revisions: Date:

RFI #1 1.24.22

KEY NOTES

DN

UP

GENERAL NOTES

LEGEND

ELIGIBILITY

GF103cLOW VISION

GF104

ELIGIBILITY

GF103aELIGIBILITY

GF103b

ELIGIBILITY

GF123

ELIGIBILITY

GF105

MAS SUPPLY

GF106

MY HEALTHY VET

GF107

SOCIAL WORKER

GF108

PSYCHOLOGIST

GF109

CLEAN SUPPLY

GF110

MED ROOM

GF111

EXAM

GF112

EXAM

GF113

EXAM

GF114

EXAM

GF115 VA EXPRESS

GF116

VA EXPRESS

GF117

CLEAN LINEN

GF118

SOILED LINEN

GF118b

OX STORAGE

GF118a

TELEHEALTH

GF119

RESEARCH

GF120

FOOD/ NUTRITION

GF121

FOOD/ NUTRITION

GF122

TOILET

GF124a

OFFICE

GF124bOFFICE

GF124c

EXAM

GF124d

STORAGE

GF124e

EXAM

GF124f

WAITING TELERETINAL

GF124g

OFFICE

GF125

CORR.

CGF 6

ADMIN. OFFICE B MODULE

GF124

MAS SUPPLY

GF124h

WAITING ROOM B MODULE

GF103

MAS

GF103d

PHARMACY DISPENSARY

GF102

CORR.

CGF 5

CORR.

CGF 7

EXAM

GF129

MALE TOILET

GF130 FEMALE TOILET

GF131

EXAM

GF132

EXAM

GF133

EXAM

GF134 STORAGE

GF135

HAC

GF136

EXAM

GF126

1 2 3 4 5 6 7

H

I

J

K

1 2 3

77777

TYP. IN ALL

DEMO AREAS

GRAY AREA NOT IN PROJECT SCOPE

5 5 5 5

5 5 5 5

Generic - 12"

1. REFER TO ENLARGED FLOOR PLANS, ELEVATIONS AND DETAILS

ON OTHER DRAWING SHEETS FOR ADDITIONAL DETAILS OF NEW

WORK.

2. REFER TO SHEET SERIES FP, P, M, E AND T FOR ADDITIONAL

DETAIL OF DEMOLITION AND NEW WORK RELATED TO THOSE

DISCIPLINES.

3. REPAIR ALL WALL CONDITIONS THAT ARE IMPACTED BY

DEMOLITION WITH 5/8" GYPSUM BOARD AND COLD FORMED METAL

FRAMING. MATCH EXISTING DEPTH AND WALL FINISH.

PROVIDE/INSTALL ALL COMPONENTS AS PREVIOUSLY INDICATED

TO ACHIEVE A FLUSH CONSISTENT AESTHETIC/FINISH.

4. ALL COMPONENTS INDICATED TO BE REMOVED AND SALVAGED

SHALL BE LABELED AND RETURNED TO THE OWNER. COORDINATE

WITH COR FOR LOCATIONS.

5. ALL COMPONENTS INDICATED TO BE REMOVED AND DEMOLISHED

SHALL BE DISPOSED OFF-SITE DAILY.

6. DEMOLITION PLAN DIMENSIONS SHALL BE FROM EXISTING FACE

OF FINISHED WALL PARTITION UNLESS NOTED OTHERWISE. ALL

DIMENSIONS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED

PRIOR TO BEGINNING DEMOLITION

7. ALL DEMOLITION SCOPE OF WORK INDICATED ON THESE

DRAWINGS SHALL BE COORDINATED WITH THE OTHER

CONSULTANT/DISCIPLINE DRAWINGS AS WELL REFER TO THEIR

DRAWINGS FOR ADDITIONAL DETAILS.

8. DEMOLITION SHALL BE TO THE MAXIMUM EXTENT POSSIBLE IN

ORDER TO COMPLETE THE SCOPE OF WORK. ADVISE THE COTR

OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE

AFFECTED DEMOLITION CONDITIONS.

9. THE GENERAL CONTRACTOR (GC) SHALL BE RESPONSIBLE FOR

TAKING ADEQUATE PRECAUTIONS TO PROTECT BUILDING

OCCUPANTS, MATERIALS, AND EXISTING FINISHES THROUGHOUT

ALL PHASES OF CONSTRUCTION. ANY DAMAGE TO THE EXISTING

COMPONENTS, WHICH HAVE NOT BEEN IDENTIFIED FOR REMOVAL,

DEMOLITION, SHALL BE RESTORED TO THE ORIGINAL CONDITION

AT THE GENERAL CONTRACTORS EXPENSE

10. GENERAL CONTRACTOR (GC) IS RESPONSIBLE FOR KEEPING A

CLEAN AND SAFE ENVIRONMENT THROUGHOUT CONSTRUCTION

11. GENERAL CONTRACTOR (GC) SHALL COMPLY WITH VA'S ICRA

REQUIREMENTS. COORDINATE WITH COTR PRIOR TO

COMMENCING ANY DEMOLITION ACTIVITIES.

12. ALL WALL PARTITIONS SHALL BE FULLY REMOVED FROM FLOOR

TO DECK.

13. ALL CABLING SHALL BE REMOVED BACK TO POINT OF ORIGIN

WHICH MAY REQUIRE WORK OUTSIDE THIS FOOTPRINT.

14. AFTER DEMO, GENERAL CONTRACTOR WILL FIELD VERIFY

MEASUREMENTS AND CONDITIONS PRIOR TO BEGINNING NEW

CONSTRUCTION.

15. GENERAL CONTRACTOR (GC) SHALL PROVIDE DETAILED

CONSTRUCTION PLAN WHICH CLEARLY SHOWS HOW ACCESS

TO/FROM OCCUPIED AREAS IS MAINTAINED DURING

CONSTRUCTION.

16. WORK SHALL OCCUR DURING NIGHTS, WEEKENDS AND AS

COORDINATED WITH COTR AT LEAST 14 CALENDAR DAYS PRIOR

TO BEGINNING CONSTRUCTION.

NO SCOPE OF WORK ASSOCIATED WITH

THIS OCCUPIED AREA

SCOPE OF WORK AREA AS DESIGNATED/NOTED

WITH BLACK BORDER

EXISTING WALL AND ASSOCIATED COMPONENTS

SHALL BE REMOVED - REFER TO DEMOLITION

KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC

CONDITIONS.

EXISTING DOOR, FRAME, HARDWARE AND

ASSOCIATED COMPONENTS SHALL BE REMOVED

-REFER TO DEMOLITION KEYNOTES FOR

ADDITIONAL DETAILS AT SPECIFIC CONDITIONS

EXISTING WALL SHALL REMAIN

EXISTING DOOR, FRAME AND HARDWARE

SHALL REMAIN

NO. NOTE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

NORTH

KEY PLAN

NTS

NORTH

E

A

B

F

D

G

HW

C22

5 18

MOD B RENOVATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:3

:4

P

M

BW LJ

635-19-101

AD100

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

PARTIAL GROUND FLOOR - DEMOLITION PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

1/4" = 1'-0"

PARTIAL GROUND LEVEL PLAN - DEMOLITION

Note Number Note

1 REMOVE AND SALVAGE FURNITURE, EQUIPMENT AND FIXTURES SECURED TO

THE WALL. STORE AT VA DESIGNATED LOCATION.

2 REMOVE FLOOR FINISH, FLOOR COVERING, WALL BASE, WALL COVERING,

WALLS AND ASSOCIATED COMPONENTS.

3 REMOVE CEILING ASSEMBLY AND ASSOCIATED COMPONENTS.

5 DEMO EXISTING LAYER OF GYP. BD. SOUND BATT INSULATION FRAMING TO

REMAIN.

7 DEMO EXISTING DOOR AND REPLACE WITH NEW DOOR.

8 PROTECT EXISTING TILES FROM DAMAGE DURING DEMOLITION. IF DAMAGE

OCCURS, REPLACE FLOORING TO MATCH EXISTING TILE.

Revisions: Date:

RFI #1 1.24.22

GENERAL NOTES:PLAN LEGEND

KEY NOTES

BARRIER LEGEND

F E

C

FEC

F E

C

FEC

F E

C

FEC

1. CONTRACTOR TO FIELD VERIFY EXISTING

STRUCTURAL COLUMN SPACING AND OVERALL

BUILDING DIMENSIONS. CONTRACTOR TO NOTIFY

VA AND ARCHITECT IF ANY DISCREPANCIES ARE

FOUND BETWEEN FIELD DIMENSIONS AND

DRAWINGS.

2. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

3. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

4. G.C. SHALL INSTALL IN-WALL 16 GA METAL

BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS,

ETC.

5. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

6. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

7. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS AT ALL FIRE-

RATED PARTITION ASSEMBLY.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL RATED WALLS TO UNDERSIDE OF

DECK PER UL ASSEMBLY REQUIREMENTS. REFER

TO 01-AE500 FOR INTERIOR PARTITION TYPES &

DETAILS.

10. REFER TO SHEET 1-AE505 FOR RATED PARTITION

PRIORITY AND RATED PARTITION INTERSECTIONS.

11. FURNITURE AND EQUIPMENT SHOWN NIC UNLESS

OTHERWISE NOTED.

12. PROVIDE 16 GA STUDS ON WET WALLS IN

RESTROOMS AND FOR THE DRINKING FOUNTAIN

WALL. 20 GA STUDS ON ALL OTHER WALLS.

AREA WITHIN SCOPE OF WORK = 7,690 SQUARE FEET

AREA NOT IN CONTRACT

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

REFERENCE WALL TYPES SHEET FOR

CONSTRUCTION TYPE

123 SF

GF124D

EXAM/CONSULT

ROOM

125 SF

GF124E

EXAM/CONSULT

ROOM

118 SF

GF113

EXAM/CONSULT

ROOM

123 SF

GF112

EXAM/CONSULT

ROOM

136 SF

GF124B

EXAM/CONSULT

ROOM

75 SF

GF103E

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103F

BLOOD

SPECIMEN

COLLECTION

76 SF

GF103D

BLOOD

SPECIMEN

COLLECTION

75 SF

GF103C

BLOOD

SPECIMEN

COLLECTION

57 SF

GF103B

TOILET

SPECIMEN

COLLECTION

211 SF

LAB

GF103

55 SF

GF103A

TOILET

SPECIMEN

COLLECTION

75 SF

GF103K

BLOOD

SPECIMEN

COLLECTION

74 SF

GF103J

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103H

BLOOD

SPECIMEN

COLLECTION

70 SF

GF103G

BLOOD

SPECIMEN

COLLECTION

61 SF

PATIENT TLT.

GF117

64 SF

STAFF TLT.

GF116

117 SF

TELECOMMUNICATIONS ROOM

GF118

121 SF

CONSULT ROOM

GF114

717 SF

TEAM WORK AREA

GF124A

22 SF

ALCOVE RESUS

GF124L

24 SF

GF124K

ALCOVE

WHEELCHAIR

10 SF

BLOOD SPECIMEN ALCOVE

GF103I

118 SF

CONSULT ROOM

GF115

1 2 3 4 5 6 7

G

H

I

J

K

DATA ROOM ABOVE

PATIENT CORRIDOR

CGF 5

27 SF

ELECT.

GF106

GRAY AREA NOT IN

PROJECT SCOPE

EXISTING CORRIDOR

CGF 7

5' - 6"

5'

6"

73 SF

GF120

SOILED UTILITY

72 SF

GF124J

CLEAN UTILITY

109 SF

GF119

LOGISTICS

STORAGE

183 SF

GF124H

LAB 2

RECEPTION

WORKSTATIONS

845 SF

GF124

WAITING

103 SF

GF124G

COPY ROOM

51 SF

GF125

STAFF LOCKER

43 SF

GF104

ACCESSIBLE

ALCOVE

110 SF

GF124F

MED. ROOM

125 SF

GF124C

EXAM/CONSULT

ROOM

32 SF

GF124I

PATIENT

CHECK-IN

AE403 24

AE405

AE405 2

AE40519

AE405

AE405

AE405

AE403

AE40517

AE405 18

AE405 15

29 SF

GF105

HEIGHT/WEIGHT

ALCOVE

63 SF

PATIENT TLT.

GF102

CGF7A

GF117

GF124AA

GF115

GF114

GF113

GF112

GF124BA

GF106

GF124CA GF124DA GF124EA

GF124FGF124EB

GF118 GF119A GF124H GF125

GF103G

GF103H

CGF7C

GF103F

GF103E

GF103D

GF103C

GF103B

GF103K

GF103J

GF103

GF124DBGF124CB

GF124BB

GF116

GF124JB

GF124GA

GF119B

GF124JA

GF124B

GF124GB

GF120

GF124C

GF103AGF124A

GF102

307 SF

CGF 4

PATIENT

CORRIDOR

2 3 3

17 17 17

17 17

28 SF

MED. EQUIP. ALCOVE

CGF 8

41 SF

MED. EQUIP. ALCOVE

CGF

1'

6"

AE405 20

25252525252525

AE40521

AE405

AE601

GF124

1 1 1 1 1 1 1

2626262626262626

28 28

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

NORTH

KEY PLAN

NTS

NORTH

E

A

B

F

D

G

HW

C22

5 18

MOD B RENOVATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:3

:5

P

M

BW LJ

635-19-101

AE102

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

PARTIAL GROUND FLOOR - ENLARGED FLOOR

PLAN

100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

Note Number Note

1 NEW PASS THROUGH

CORNER GUARD WALL PROTECTION (FULL HEIGHT) TYP. ALL CORRIDOR

CORNER. REFER TO SPECS FOR DETAIL.

HANDRAIL AND BUMPER GUARD WALL PROTECTION ALONG LENGTH OF

WALL - REFER TO DIMENSION PLAN AND SPECS FOR DETAILS. TOP OF

HANDRAIL TO BE 34" A.F.F.

EXISTING WALL PARTITION AND DOOR ASSEMBLY SHALL REMAIN AS IS.

EXISTING WALL AND DOOR COMPONENTS SHALL BE USED AS THE

TEMPORARY BARRIER BETWEEN OCCUPIED AND NON-OCCUPIED SPACE.

PROVIDE A TEMPORARY CONSTRUCTION BARRIER BETWEEN OCCUPIED

AND NON-OCCUPIED SPACE. FREE EGRESS TO THE STAIR ENCLOSURE IS

REQUIRED DURING CONSTRUCTION.

8 PATCH, CLEAN, AND REPAIR WALLS AFTER DEMO. TYPICAL IN ALL AREAS.

PATCH, CLEAN, AND REPAIR FLOORS WHERE NEEDED AFTER DEMO. LEVEL

FLOORS WHERE NEEDED. TYPICAL IN ALL AREAS.

PAINT NEW WALLS. SEE FINISH MATERIAL SCHEDULE FOR DETAILS.

TYPICAL IN ALL AREAS.

PATCH, CLINSTALL NEW CEILING GRID AND CEILING TILES. SEE

REFLECTED CEILING PLAN FOR DETAILS. TYPICAL IN ALL AREAS.EAN, AND

REPAIR FLOORS WHERE NEEDED AFTER DEMO. LEVEL FLOORS WHERE

NEEDED. TYPICAL IN ALL AREAS.

PAINT EXISTING WALLS TO MATCH NEW WALL PAINT. SEE FINISH MATERIAL

SCHEDULE FOR DETAILS.

14 EXISTING DOOR TO REMAIN.

16 INSTALL NEW SOLID SURFACE (SS-1) TRANSACTION COUNTERTOP.

17 INSTALL NEW SOLID SURFACE (SS-1) ACCESSIBLE COUNTERTOP.

21 DRINKING FOUNTAIN WITH BOTTLE FILLER.

22 NEW PNEUMATIC TUBE TO CONNECT TO EXISTING SYSTEM

23 CONTROLLED ACCESS - REFER TO DOOR SCHEDULE

24 WATER SHUTOFF VALVE. REFER TO PLUMBING DRAWINGS

25 INSTALL NEW GYPSUM.

CONTRACTOR TO PROVIDE AND INSTALL NEW BLINDS AT WINDOW. SEE

SPEC SECTION 12 24 00 WINDOW SHADES.

27 CONTRACTOR TO INSTALL NEW RECESSED FIRE EXTINGUISHER CABINET.

PROTECT EXISTING TILES FROM DAMAGE. IF DAMAGE OCCURS, REPLACE

FLOORING TO MATCH EXISTING TILE.

1/4" = 1'-0"

PARTIAL GROUND LEVEL - ENLARGED PLAN

Revisions: Date:

RFI #1 1.24.22

GENERAL NOTES:

PLAN LEGEND

BARRIER LEGEND

1 2 3 4 5 6 7

H

I

J

K

123 SF

GF124D

EXAM/CONSULT

ROOM

125 SF

GF124E

EXAM/CONSULT

ROOM

118 SF

GF113

EXAM/CONSULT

ROOM

123 SF

GF112

EXAM/CONSULT

ROOM

136 SF

GF124B

EXAM/CONSULT

ROOM

29 SF

GF105

HEIGHT/WEIGHT

ALCOVE

75 SF

GF103E

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103F

BLOOD

SPECIMEN

COLLECTION

76 SF

GF103D

BLOOD

SPECIMEN

COLLECTION

75 SF

GF103C

BLOOD

SPECIMEN

COLLECTION

57 SF

GF103B

TOILET

SPECIMEN

COLLECTION

211 SF

LAB

GF103

55 SF

GF103A

TOILET

SPECIMEN

COLLECTION

75 SF

GF103K

BLOOD

SPECIMEN

COLLECTION

74 SF

GF103J

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103H

BLOOD

SPECIMEN

COLLECTION

70 SF

GF103G

BLOOD

SPECIMEN

COLLECTION

61 SF

PATIENT TLT.

GF117

51 SF

STAFF LOCKER

GF12564 SF

STAFF TLT.

GF116

183 SF

GF124H

LAB 2

RECEPTION

WORKSTATIONS

72 SF

CLEAN UTILITY

GF124J

109 SF

GF119

LOGISTICS

STORAGE

117 SF

TELECOMMUNICATIONS ROOM

GF118

32 SF

PATIENT CHECK-IN

GF124I

845 SF

WAITING

GF124

125 SF

GF124C

EXAM/CONSULT

ROOM

121 SF

CONSULT ROOM

GF114

717 SF

TEAM WORK AREA

GF124A

22 SF

ALCOVE RESUS

GF124L

24 SF

ALCOVE WHEELCHAIR

GF124K

10 SF

BLOOD SPECIMEN ALCOVE

GF103I

118 SF

CONSULT ROOM

GF115

DATA ROOM ABOVE

PATIENT CORRIDOR

CGF 5

27 SF

ELECT.

GF106

110 SF

GF124F

MED. ROOM

AE401

AE402

AE402

GRAY AREA NOT IN

PROJECT SCOPE

/1

/1

/8

/8

12' - 10 7/8" 6' - 4 7/8" 10' - 4 7/8"

/8

/8

/8

/8

/1

10' - 0" 15' - 9 7/8"

/1

/2

/2

/1

/2

/8

/1

7' - 9 1/16" 2' - 7 13/16"

/8

/1

/4

/1

1' - 5 9/16" 6' - 4 7/8" 13' - 2 1/4" 10' - 4 7/8" 10' - 4 7/8" 9' - 8 7/8"

10' - 4 7/8" 10' - 5 1/2" 7' - 0" 9' - 10 13/16" 5' - 2" 7' - 10 5/8" 14' - 0 3/8"

EXISTING CORRIDOR

CGF 7

PATIENT CORRIDOR

CGF 4

63 SF

PATIENT TLT.

GF102

43 SF

GF104

ACCESSIBLE

ALCOVE

103 SF

COPY ROOM

GF124G

73 SF

SOILED UTILITY

GF120

33' - 11 13/16"

/1

/8

/1

/8

4' - 3 3/8" 7' - 9 5/8" 7' - 0 13/16" 6' - 9 7/16" 6' - 10 5/8" 19' - 2 7/8"

CLEAR

6' - 0"

CLEAR

6' - 0"

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

E00

P02

P02

P02

P02

P02

P02

P02

R02

P01

P01

P01

P04

P04

P02

P02

P05

P04

R02

R02

P01

P01

P02

P01

P02 P02

P01

P01

P02

P02

P02

P06

R01

R01

P02

P02

P02

P02

P02

P02 P04

P02

P01

P04

P01

P01

P01

P01

P01

P01

P01

P01

P01

P01

P01

P02

P02

P02

P01

E00

E00 P01

P01

P01

P01

P01

P01

P01

P01

P05

P01

P01

P01

P01 P05

P01

P01

P01

P04

P01

P01

P01

P01

P01

P01

P01

P01

P04

P04

E00

R02

P05

P06

P02

P05

P04

R02

E00

P04

P01

R02

P02

P02

P01

R01

P03

P02

P09

P05

P01

P07

R02

P06

P03

R02

P04

P04

P04 P05

P05

P04

P09

P06

P01

P01

P01

P04

P04

P04

P04

P06

P02

P04

P06

P03

P03

P03

P06

P04

P06

P04

P04

P03

P03

R03

P05

P09

P03

P07

P06

R02

P04

R02

R02

R02

P04

P02

P02

P01

P04

P01

P01

9' - 10 3/4"

GF115

GF114

GF113

GF112

GF124AA

GF117

GF118 GF119A GF124H GF125

GF103G

GF103H

CGF7C

GF103F

GF103E

GF103D

GF103C

GF103B

GF103K

GF103J

GF103

GF124CA GF124EAGF124DA

CGF7A

GF124EBGF124DBGF124CB

GF124BA

GF124BB

GF116

GF124JB

GF124GA

GF119B

GF124JA

GF124B

GF106

GF124F

GF124GB

GF120

GF124C

GF103AGF124A

GF102

AE702

Sim

AE702

Sim

AE701

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE702

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE701

Sim

AE404

AE404

AE404

AE404

AE404

AE404

/1

"1

3' - 0 1/4"

/4

1. CONTRACTOR TO FIELD VERIFY EXISTING

STRUCTURAL COLUMN SPACING AND OVERALL

BUILDING DIMENSIONS. CONTRACTOR TO NOTIFY

VA AND ARCHITECT IF ANY DISCREPANCIES ARE

FOUND BETWEEN FIELD DIMENSIONS AND

DRAWINGS.

2. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

3. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

4. G.C. SHALL INSTALL IN-WALL 16 GA METAL

BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS,

ETC.

5. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

6. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

7. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS AT ALL FIRE-

RATED PARTITION ASSEMBLY.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL RATED WALLS TO UNDERSIDE OF

DECK PER UL ASSEMBLY REQUIREMENTS. REFER

TO 01-AE500 FOR INTERIOR PARTITION TYPES &

DETAILS.

10. REFER TO SHEET 1-AE505 FOR RATED PARTITION

PRIORITY AND RATED PARTITION INTERSECTIONS.

11. FURNITURE AND EQUIPMENT SHOWN NIC UNLESS

OTHERWISE NOTED.

12. PROVIDE 16 GA STUDS ON WET WALLS IN

RESTROOMS AND FOR THE DRINKING FOUNTAIN

WALL. 20 GA STUDS ON ALL OTHER WALLS.

AREA WITHIN SCOPE OF WORK = 7,690 SQUARE FEET

AREA NOT IN CONTRACT

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

REFERENCE WALL TYPES SHEET FOR

CONSTRUCTION TYPE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

NORTH

KEY PLAN

NTS

NORTH

E

A

B

F

D

G

HW

C22

5 18

MOD B RENOVATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:2

:0

P

M

BW LJ

635-19-101

AE103

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

DIMENSION PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

1/4" = 1'-0"

PARTIAL GROUND LEVEL - DIMENSION PLAN

Revisions: Date:

RFI #1 1.24.22

GENERAL NOTES:

PLAN LEGEND

RCP LEGEND

BARRIER LEGEND

1 2 3 4 5 6 7

H

I

J

K

GRAY AREA NOT IN

PROJECT SCOPE

9' - 0"A.F.F

9' - 0"A.F.F

8' - 0"A.F.F

8' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

8' - 0"A.F.F

8' - 0"A.F.F

9' - 0"A.F.F9' - 0"A.F.F9' - 0"A.F.F9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

8' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

8' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

717 SF

TEAM WORK AREA

GF124A

109 SF

LOGISTICS STORAGE

GF119

118 SF

CONSULT ROOM

GF115

121 SF

GF114

CONSULT ROOM

118 SF

GF113

EXAM/CONSULT

ROOM

123 SF

GF112

EXAM/CONSULT

ROOM

136 SF

EXAM/CONSULT ROOM

GF124B

125 SF

EXAM/CONSULT ROOM

GF124C

123 SF

EXAM/CONSULT ROOM

GF124D

125 SF

EXAM/CONSULT ROOM

GF124E

110 SF

MED. ROOM

GF124F

803 SF

PATIENT CORRIDOR

CGF 5

29 SF

GF105

HEIGHT/WEIGHT

ALCOVE

43 SF

GF104

ACCESSIBLE

ALCOVE

63 SF

PATIENT TLT.

GF102

55 SF

GF103A

TOILET

SPECIMEN

COLLECTION

57 SF

GF103B

TOILET

SPECIMEN

COLLECTION

75 SF

GF103K

BLOOD

SPECIMEN

COLLECTION

307 SF

CGF 4

PATIENT

CORRIDOR

75 SF

GF103C

BLOOD

SPECIMEN

COLLECTION

76 SF

GF103D

BLOOD

SPECIMEN

COLLECTION

75 SF

GF103E

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103F

BLOOD

SPECIMEN

COLLECTION

211 SF

LAB

GF103

74 SF

GF103J

BLOOD

SPECIMEN

COLLECTION

73 SF

GF103H

BLOOD

SPECIMEN

COLLECTION

70 SF

GF103G

BLOOD

SPECIMEN

COLLECTION

61 SF

PATIENT TLT.

GF117

51 SF

STAFF LOCKER

GF12564 SF

STAFF TLT.

GF116

183 SF

GF124H

LAB 2

RECEPTION

WORKSTATIONS

72 SF

CLEAN UTILITY

GF124J

117 SF

TELECOMMUNICATIONS ROOM

GF118

32 SF

PATIENT CHECK-IN

GF124I

845 SF

WAITING

GF124

22 SF

ALCOVE RESUS

GF124L

24 SF

GF124K

ALCOVE

WHEELCHAIR

10 SF

BLOOD SPECIMEN ALCOVE

GF103I

920 SF

EXISTING CORRIDOR

CGF 7

EXISTING EXAM

GF129

EXISTING MALE TOILET

GF130

EXISITNG FEMALE TOILET

GF131

EXISTING EXAM

GF132

EXISTING EXAM

GF133

EXISTING EXAM

GF134 EXISTING STORAGE

GF135

EXISTING HAC

EXISTING EXAM

GF126

27 SF

ELECT.

GF106

73 SF

SOILED UTILITY

GF120

103 SF

COPY ROOM

GF124G

8' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

8' - 0"A.F.F

8' - 0"A.F.F

9' - 0"A.F.F

(OPEN CEILING)

3' - 11"

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

AE502

Sim

AE502

Sim 1

AE502

Sim1

AE502

Sim

9' - 0"A.F.F

9' - 0"A.F.F

1. CONTRACTOR TO FIELD VERIFY EXISTING

STRUCTURAL COLUMN SPACING AND OVERALL

BUILDING DIMENSIONS. CONTRACTOR TO NOTIFY

VA AND ARCHITECT IF ANY DISCREPANCIES ARE

FOUND BETWEEN FIELD DIMENSIONS AND

DRAWINGS.

2. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

3. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

4. G.C. SHALL INSTALL IN-WALL 16 GA METAL

BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS,

ETC.

5. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

6. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

7. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS AT ALL FIRE-

RATED PARTITION ASSEMBLY.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL RATED WALLS TO UNDERSIDE OF

DECK PER UL ASSEMBLY REQUIREMENTS. REFER

TO 01-AE500 FOR INTERIOR PARTITION TYPES &

DETAILS.

10. REFER TO SHEET 1-AE505 FOR RATED PARTITION

PRIORITY AND RATED PARTITION INTERSECTIONS.

11. FURNITURE AND EQUIPMENT SHOWN NIC UNLESS

OTHERWISE NOTED.

12. PROVIDE 16 GA STUDS ON WET WALLS IN

RESTROOMS AND FOR THE DRINKING FOUNTAIN

WALL. 20 GA STUDS ON ALL OTHER WALLS.

AREA WITHIN SCOPE OF WORK = 7,690 SQUARE FEET

AREA NOT IN CONTRACT

MECHANICAL SUPPLY DIFFUSER

MECHANICAL RETURN GRILLE

MECHANICAL EXHAUST GRILLE

24" X 48" ACOUSTICAL CEILING

PANEL AND GRID

24" X 24" ACOUSTICAL CEILING

PANEL AND GRID

GYPSUM BOARD CEILING OR

SOFFIT

2' x 4' FLUORESCENT FIXTURE

2' x 2' FLUORESCENT FIXTURE

1' x 4' FLUORESCENT FIXTURE

RECESSED CAN DOWNLIGHT

CEILING ELEVATTION A.F.F.

X'-X"

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

REFERENCE WALL TYPES SHEET FOR

CONSTRUCTION TYPE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

NORTH

KEY PLAN

NTS

NORTH

E

A

B

F

D

G

HW

C22

5 18

MOD B RENOVATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:2

:3

A

M

BW LJ

635-19-101

AE104

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

REFLECTED CEILING PLAN 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

1/4" = 1'-0"

GROUND LEVEL REFLECTED CEILING PLAN

Revisions: Date:

RFI #1 1.24.22

TOILET ACCESSORY SCHEDULE

SURFACE MOUNTED PAPER TOWEL DISPENSER. BY OWNER (VA) CONTRACTOR INSTALLED. MOUNT BOTTOM

OF UNIT AT 48" AFF

STAINLESS STEEL GRAB BAR. MOUNT AT 36' A.F.F. TO CENTERLINE OF BAR AS SHOWN. SIDE GRAB BAR TO EXTEND 54" (12"+42") FROM REAR WALL. REAR GRAB BAR TO BE 36" LONG. VERTICAL 18" WALL MOUNTED GRAB BAR MOUNTED 40" FROM THE BACK WALL AND 40" FROM THE FINISHED FLOOR TO BOTTOM OF GRAB BAR.

TYPICAL ALL TOILETS WITH GRAB BARS AND AS NOTED. PROVIDE SMALL CIRCULAR PIECE OF SOLID SURFACE UNDER UPPER ESCUTCHEON OF 18" GRAB BAR FOR LEVEL INSTALLATION. PROVIDE METAL STRAP BLOCKING

IN WALLS FOR GRAB BAR MOUNTING, TYP. SEE 1-AE701 FOR DETAILS

SURFACE MOUNTED, DOUBLE ROLL, TOILET PAPER HOLDER, UNCONTROLLED DELIVERY. MOUNT 1'-7" A.F.F. TO

CENTERLINE OF UNIT, 3'-0" MAX FROM WALL. BY OWNER (VA) CONTRACTOR INSTALLED.

SURFACE MOUNTED MIRROR, MOUNT 3'-4" MAX. TO BOTTOM OF MIRROR. MIRROR SIZE 30"x36" (FIELD VERIFY)- CAULK TO WALL. PROVIDE PLYWOOD BEHIND MIRROR, ABOVE TILE, IF NECESSARY FOR LEVEL INSTALLATION.

SANITARY NAPKIN DISPOSAL. MOUNT AT 2'5" TO TOP OF DISPOSAL.

SURFACE MOUNTED SOAP DISPENSER BY OWNER (VA) CONTRACTOR INSTALLED.

ROBE/COAT HOOK, MOUNT AT 4'-0" A.F.F MAX

PROVIDE H/C PLUMBING PROTECTION AT ALL EXPOSED PLUMBING, TYPICAL.

SURFACE MOUNTED LIGHT FIXTURE. SEE ELECTRICAL SHEETS. MOUNT AT 80" MIN. TO BOTTOM OF FIXTURE.

BASKET, WASTEPAPER, FIRE RESISTANT

LAVATORY, VITREOUS CHINA, SLAB TYPE

NURSE CALL PULL BOX

PASS-THROUGH SPECIMEN CABINET, MOUNT 4'-0" A.F.F. TO CENTERLINE OF CABINET.

NOTE

NUMBER

JSN#

A5080

A5109

A5200

A1067

A5090

A5075

A5145

N/A

N/A

F2000

P3100

N/A

L1200

ITEM NAME ACQ/INS

C/C

C/C

C/C

C/C

C/C

V/V

C/C

C/C

C/C

V/V

C/C

C/C

C/C

ACQ/INS

FURNISHED/INSTALLED NOTE:

VV- NOT IN CONTRACT (GOVERNMENT FURNISHED, GOVERNMENT

INSTALLED.

CC- IN CONTRACT (CONTRACTOR FURNISHED, CONTRACTOR INSTALLED)

A D

A

T O

H A

N D

L E

MIRROR SOAP DISPENSER PAPER

TOWEL

DISPENSER

TOILET PAPER

DISPENSER

TOILET

PAPER

HOLDER

SANITARY

NAPKIN

DISPOSAL

MIN

1' - 3"

LAVATORY

M

IN

INSULATE EXPOSED

PIPING WITH WHITE

PLASTIC PRE-FITTED

INSULATION

M A

X

MEASURE

TO BOTTOM

OF REFLECTIVE

SURFACE

D

IS

P E

N S

E R

M A

X O

P E

R A

B L E

D

IS

P E

N S

E R

M

A X

T O

O P

E R

A B

L E

M A

X

M

IN

M

IN

FIRE

EXTINGUISHERS

AND CABINETS

7-PEG

COAT RACK

2' - 0"

"MIN

8"

MIN

11"

KNEE AND TOE

CLEARANCES

E

E

SEALANT

PROVIDE ADA

COMPLIANT FAUCET

WITH WRIST BLADE

CONTROLS

M A

X

5" MAX 15" MAX

ACCESS HGT. D.F.

SPOUT LOCATION

M

IN

SPOUT

HEIGHT

STANDING AND

ACCESSIBLE DRINKING

FOUNTAINS

FRONT SIDE

PLAN

ALUM. SEMI-RECESSED CAB.

W/ FULL CLEAR ACRYLIC DOOR

10 LBS

ABC TYPE

BABY CHANGING

TABLE

M A

X

/2

ROBE

HOOK

M A

X

"FIRE EXTINGUISHER" IN

RED LETTERS

G

F

F

(ALT)H

J

C

N O O

P

P

M

IN9

MIN

11"

M

IN

8"

25" MAX

30x48

CLEAR

SPACE

U

M A

X

TOILET

SEAT COVER

DISPENSER

SIGNAGE

(12" BELOW CEILING)

2"

HANDRAIL

PER NFPA 10

PTD (OF/OI)

PUBLIC TLTS

ONLY

SEMI-

RECESSED

WASTE RECP.

S P

O U

T H

G T

S T

A N

D

IN

G H

E

IG

H T

D .F

A C

C E

S S

H

E

IG

H T

D .F

M A

X

NOTE: PROVIDE CANE

DETECTABLE APRON AT

THE STANDING HEIGHT

UNIT

MIN

3' - 6"

MAX

1' - 0"

WATER CLOSET

SIDE WALL

1 1/4" MIN., 2" MAX DIA.

GRAB BAR WITH 1 1/2"

GAP FROM WALL

WATER CLOSET

BACK WALL

TP DISPENSER

MOUNTING AREA

1' - 6"

T .O

G

.B

/2

4' - 6" MIN

MIN

1' - 0"

MIN

2' - 0"

FLUSH CONTROLS

ON OPEN SIDE

M

IN

GB42

GB36

A

A

3' - 4"

/2

GB18

U

CENTER ON

GRAB BAR END

NOTE: GRAB BARS

SHALL BE 33" - 36" TO

TOP OF BAR

MEASURE

TO BOTTOM

OF REFLECTIVE

SURFACE

3' - 0"

HANDRAIL

BUMPER GUARD

COVE BASE

T

IL

E H

E

IG

H T

T Y

P

H

AE401

61 SF

PATIENT TLT.

GF117

AE4013

/2

1' - 9 1/8"

64 SF

STAFF TLT.

GF116

/2

R03

P05

P05

R01

P03

10' - 9 1/4"

1' - 9 1/2"

/4

1' - 4 1/2"

P06 P03

P05

P05

P03

P03

P06

P06 P09

P07

P05

P05

GF116

GF117

/2

3 5

8' - 6 1/8"

8' - 6 3/16"

/1

83 5

83 5

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:3

:5

P

M

BW LJ

635-19-101

AE401

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

ENLARGED TOILET PLANS AND ELEVATIONS 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

NTS

TOILET ACCESSORY MOUNTING HEIGHTS

1/2" = 1'-0"

STAFF TLT. GF116

1/2" = 1'-0"

ENLARGED STAFF TLT. GF116 & PATIENT TLT. GF117

1/2" = 1'-0"

STAFF TLT. GF116

1/2" = 1'-0"

PATIENT TLT. GF117

1/2" = 1'-0"

PATIENT TLT. GF117

Revisions: Date:

RFI #1 1.24.22

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

TYPE FIRE RATINGSTUD SIZE

P00 NON-RATED7/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

ONE SIDE

CEILING AS

SCHEDULED

LINE OF FLOOR

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

7/8" HAT CHANNEL

FURRING

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P01 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

TYPE FIRE RATINGSTUD SIZE

P03 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

TYPE FIRE RATINGSTUD SIZE

P02 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P04 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

TYPE FIRE RATINGSTUD SIZE

P05 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

SOUND BATT

INSULATION

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P06 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P07 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

6" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P09 NON-RATED6"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON BOTH

SIDES (LEAD LINED ON

EMG/SCI/PROCEDURE

ROOM SIDES ONLY - LEAD

SHIELDING UP TO 7'-0"

A.F.F.)

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P08 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

5/8" TYPE "X"

GYP BD ON ONE

SIDE

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PROVIDE FIRE RATED

CAULK

PROVIDE FIRE RATED

CAULK

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R02 1 HR3 5/8"

PLACEMENT

INTERIOR

STC

50 MINIMUM

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X"

GYP BD ON

BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

TYPE FIRE RATINGSTUD SIZE

R01 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R03 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X"

GYP BD ON

BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

STC

50 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

5/8" TYPE "X"

GYP BD ON ONE

SIDE

PROVIDE FIRE RATED

CAULK

PROVIDE FIRE RATED

CAULK

TYPE FIRE RATINGSTUD SIZE

R04 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

STC

50 MINIMUM

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R05 1 HR3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X" GYP BD

ON BOTH SIDES

(LEAD LINED ON

PROCEDURE ROOM

SIDE ONLY - LEAD

SHIELDING UP TO

7'-0" A.F.F.)

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PLAN VIEW

TYPE FIRE RATINGSTUD SIZE

E00 NON-RATEDN/A

PLACEMENT

EXTERIOR

SECTION VIEW

LINE OF

FLOOR

EXISTING WALL

FIELD VERIFY

CONSTRUCTION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

ONE SIDE

CEILING AS

SCHEDULED

LINE OF FLOOR

6" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P10 NON-RATED6"

PLACEMENT

INTERIOR

STC

45 MINIMUM

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

O k la h o m a C it y P

A C

T R e n o v a ti o n /O k la h o m a C it y P

A C

T R e n o v a ti o n .r v t

/1

/2

:3

:4

P

M

BW LJ

635-19-101

AE500

635 - OKLAHOMA CITY, OK

SEPTEMBER 24, 2021

(RFI #1 - 1.24.22)

01-

WALL TYPES 100% CONTRACT DOCUMENTS REMODEL B MOD OKLAHOMA VAMC

- OKLAHOMA CITY, OK

Revisions: Date:

RFI #1 1.24.22

DOOR LEGEND & ABBREVIATIONS

DOOR PANEL TYPE LEGEND

AA PAIR BOTH ACTIVE

AI PAIR ACTIVE/INACTIVE

DE PAIR DOUBLE EGRESS

OC OVERHEAD COILING DOOR

SG SINGLE DOOR LEAF

SS SINGLE SLIDER

TS TELESCOPIC SLIDER

DOOR ABBREVIATIONS LEGEND

AL ALUMINUM

AP AI PHONE INTERCOM/CAMERA

CR CARD READER

CAL CARD ACCESS LOCKSET

DBL DOUBLE

EXT EXTERIOR

GL GLAZING

HM HOLLOW METAL

AL/GL ALUMINUM W/ GLASS

KP KEYPAD

CR/KP CARD READER/KEYPAD COMBO

MHO MAGNETIC HOLD-OPENS

MOT MOTION SENSOR

OPNG OPENING

PB PUSH BUTTON

PTD PAINTED

RR REMOTE RELEASE

SCWD SOLID-CORE WOOD DOOR

SMOKE SMOKE-TIGHT

THHD THRESHOLD

STL STEEL

DOOR NOTES

1. DOOR 116 MAGLOCK ACTIVATES UPON DOOR LATCHING

OR CARD READER ACTIVATION. DOOR AUTOMATICALLY

UNLOCKS UPON EITHER ACTIVATION OF THE FIRE ALARM

OR DETECTION OF WATERFLOW IN THE SPRINKLER

SYSTEM. CARD READER INSIDE THE ROOM SHALL BE

MOUNTED INSIDE THE WALL WITH A RED DOT PROVIDED

TO INDICATE SCAN AREA. DOOR SHALL BE SELF-LATCHING

APART FROM THE MAGLOCK.

2. CARD READER BOTH SIDES (IN-WALL ON ROOM SIDE)

KEYSWITCH OVERRIDE FOR CARD READER TO TURN 'ON'

AND 'OFF'.

3. CONTRACTOR SHALL FIELD VERIFY WALL THICKNESSES

FOR EACH DOOR HEAD/JAMB

4. DOORS INDICATED TO BE "LEAD-LINED" SHALL BE

MANUFACTURED WITH EQUIVALENT LEAD THICKNESS AS

THE WALL WITHIN WHICH THEY WILL BE INSTALLED.

REFER TO PHYSICIST REPORT FOR SPECIFIC SHIELDING

REQUIREMENTS.

F-1

WIDTH AS SCHEDULED2" 2"

H

EI

G H

T

AS

S C

H

ED

U

LE

D 2"

2" 2"WIDTH AS SCHEDULED

2" H

EI

G

H T

AS

S

C H

ED

U

LE

D

F-2

TYPE DTYPE CTYPE B TYPE E

FLUSH PANEL

DOORS

FLUSH PANEL

DOOR

FLUSH PANEL DOOR

W/ VISION PANEL

ALUMINUM AND GLASS

DOOR

6" 6'

6"

2'

0"

6"

4'

6"

6"

PANIC

HARDWARE

AS NOTED IN

THE

HARDWARE

SCHEDULE

HEAD/JAMB DETAIL

1 LAYER

GYPSUM

WALL BOARD

INSULATION WHERE INDICATED

GYPSUM WALL

BOARD ON METAL

STUD

METAL STUD

FRAME

SEALANT

DOOR

1/2"

DIM.

PARTITION 1/2"

D O

O R

D

IM

2"

PARTITION AS SCHED.

H.M. FRAME

CONT. SEALANT

(BOTH SIDES)

DOOR AS SCHED.

METAL STUD

TRACK - GAUGE TO

MATCH STUDS

+ 1"

PARTITION WIDTH

1/2"

DIM.

PARTITION 1/2"

D O

O R

D

IM

2"

PARTITION AS SCHED.

H.M. FRAME

CONT. SEALANT

(BOTH SIDES)

DOOR AS SCHED.

+ 1"

PARTITION WIDTH

DOUBLE METAL STUDS

AT JAMBS - TYP.

SHIM AS REQUIRED

DOOR AS SCHED.

+ 1"

PARTITION WIDTH

1/ 4"

1/8" CLEARANCE ABOVE

THRESHOLD

DOOR

THRESHOLD

DOOR FRAME BEYOND

3/ 4"

5/8" GYP. BD. OVER

MTL. STUD FRAMING

BLOCKING

EXISTING EXTERIOR WALL

EXISTING WINDOW

09 5113 METAL

CEILING TRIM

WINDOW SHADE WHERE

OCCURS.

3 5/8" MTL. STUD

OVER 5/8" GYP.

BD.

CEILING

9'-0"

NOTE: CONTRACTOR TO PROVIDE AND INSTALL BLINDS

3"

1/

8"

4 11/16" 4 5/16"

2"

9'

0"

9' - 10 7/8"

1' - 11"4' - 0 3/8"3' - 11 1/2"

8'

6"

3'

0" 6"

2 1/2" ALUMINUM

MULLIONGF124

5'

6"

WIDTH AS SCHEDULED

H

EI

G H

T

AS

S C

H

ED

U

LE

D

AE502

Sim

EXISTING ALUMINUM

STOREFRONT

EXISTING EXTERIOR WALL

5/8" GYP. BD. OVER

EXISTING 3 5/8" MTL. STUD

GYP. ALUM. REGLET

EXISTING SOLID

SURFACE WINDOW

SILL

AE-601 - DOOR SCHEDULE

LOCATION DOOR SLAB FRAME DETAILS

HARDWARE

ACCESS

CONTROL NOTES / REMARKSLevel

DOOR

NUMBER

SIZE

TYPE MATL. RATING TYPE MATL. FINISH HEAD JAMB SILLWIDTH HEIGHT THK

GROUND LEVEL

GROUND LEVEL CGF7A 3' - 6" 7' - 0" 1 3/4" C WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3H CR CONTROLLED ACCESS GROUND LEVEL CGF7C 3' - 6" 7' - 0" 1 3/4" C WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-UA-3 CR CONTROLLED ACCESS GROUND LEVEL GF102 3' - 6" 7' - 0" 1 3/4" B WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-2H GROUND LEVEL GF103 3' - 6" 7' - 0" 1 3/4" C WD 1 HOUR F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3H CR CARD READER GROUND LEVEL GF103A 3' - 6" 7' - 0" 1 3/4" B WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-2C GROUND LEVEL GF103B 3' - 6" 7' - 0" 1 3/4" B WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-2C

GROUND LEVEL GF103C 3' - 6" 7' - 0" 2" F-1 HM 2/AE601 3/AE601 4/AE601

GROUND LEVEL GF103D 3' - 6" 7' - 0" 2" F-1 HM 2/AE601 3/AE601 4/AE601

GROUND LEVEL GF103E 3' - 6" 7' - 0" 2" F-1 HM 2/AE601…