25R1319 Note23.pdf
PDF 407 KB Posted
- Attached to
- FY21 MCON PROJECT P-649 GUAM JOINT COMMUNICATIONS UPGRADE MARINE CORPS BASE CAMP BLAZ, GUAM
- Solicitation number
- N6274225R1319
About this file
This is Notice No. 23 containing pre-proposal questions and answers for RFP N62742-25-R-1319, issued by the Department of the Navy Naval Facilities Engineering Systems Command Pacific on February 14, 2025, regarding the FY21 MCON Project P-649 Guam Joint Communications Upgrade at Marine Corps Base Camp Blaz, Guam.
The notice addresses two technical clarifications: 1) Stainless steel doors do not require fluted ribbed patterns and can have smooth painted finish, while only exterior aluminum doors need fluted face patterns per Spec Section 08 11 16, and 2) Exterior CIP and CMU walls must be finished with EFS, while CMU screen blocks and CMU knockout walls should be painted. The document notes that these answers are for information only and the RFP remains unchanged unless amended via Standard Form 30.
View the file
Other files
Show 40 more
Latest 50 of 131 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP N62742-25-R-1319
Notice No. 23
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND PACIFIC
258 MAKALAPA DR STE 100
PEARL HARBOR HI 96860-3134
Notice No. 23 14 Feb 2025
PRE-PROPOSAL QUESTIONS & ANSWERS
RFP N62742-25-R-1319
WON 1614533, FY21 MCON PROJECT P-649 GUAM JOINT COMMUNICATIONS
UPGRADE MARINE CORPS BASE CAMP BLAZ, GUAM
NOTE: The following questions and answers are provided for INFORMATION ONLY. The RFP remains unchanged unless it is amended in writing on a Standard Form 30.
RESPONSES FOR NOTICE 23
368. Reference Notice 22-Response to #359, Amd #13 -Spec Section 08 11 13, Amd #13 Drawings A-515, A-605B, A-605C, Amd#4 Drawing A-511 (Door types) and Amd #15 Spec Section 08 11 16, Para 2.3.2.1 regarding the Fluted Aluminum doors. Response to #359-That manufacturer does not provide the fluted doors in Stainless steel finish. Although Spec Section 08 11 13 mentions the stainless steel finish, it does not address a fluted ribbed pattern. Drawing A-511 describes Type A doors as “Alum Fluted Face” and 08 11 16, Para
2.3.2.1 describes a Alum facing sheet with a fluted pattern surface. Both Amd #13 Drawing A-515 lists doors 426A and 453 (both one-hour fire-rated), Amd #13 drawing A-605B lists door B07B (45 min fire-rated) and Amd #13 drawing A-605C lists door C07B (45 min fire-rated) as being Stainless steel with a fluted surface. As mentioned in previous Notices, alum doors are not available with a fire-rating. Please clarify and provide a basis of design product for the stainless steel, fluted face doors.
ANSWER: Stainless steel doors do not need to have a fluted ribbed pattern and can be smooth painted finish. Only exterior aluminum doors need to have the fluted face pattern per Spec Section 08 11 16.
369. Detail B1/A-201E is calling out for EFS to be applied on the exterior CIP walls at the Generator Building. Detail A3/A-201E is calling out for exterior CIP walls to be painted. Please advise.
ANSWER: Exterior CIP and CMU walls shall be finished with EFS. CMU screen blocks and CMU knockout walls shall be painted.