About this file
This statement of work outlines analytical services and reporting requirements for laboratory testing of stormwater, wastewater, drinking water, and hazardous waste profiling at the Marine Corps Mountain Warfare Training Center in Bridgeport, California. Required services include sampling, field testing, laboratory analysis, data reporting, and courier transportation of samples from the base to the contractor's facility. Specific testing requirements are defined for stormwater outfalls, drinking water distribution and wells, wastewater influent and effluent, sludge, and groundwater monitoring wells. Deliverables include regular reporting to state regulators and the base environmental office. The period of performance is one year from contract award with an option to extend up to six additional months.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1604000 C Wastewater rFa.docx | DOCX document | |
| J-1502000-17 Roll Up Door Invetory.pdf | ||
| 1502000 J Facility Investment rFa.docx | DOCX document | |
| 1503060 J Pavement Clearance rFa.docx | DOCX document | |
| Amendment 05.pdf | ||
| Amendment 03.pdf | ||
| 1503050 C Grounds Maintenance and Landscaping rFa.docx | DOCX document | |
| Attachment J-0200000-10 UnPopulated ELINS MCMWTC Bridgeport BOS rFj 03.28.23.xlsx | XLSX spreadsheet | |
| Amendment 04.pdf | ||
| 1502000 C Facility Investment rFb.docx | DOCX document | |
| 1606000 J Water rFb.docx | DOCX document | |
| 1503060 C Pavement Clearance rF.docx | DOCX document | |
| Amendment 02.pdf | ||
| 0200000 C Management and Administration rF.pdf | ||
| 1503030-04 J ISWM rF.xlsx | XLSX spreadsheet | |
| 1606000 F Water rF.pdf | ||
| 1503020 J Pest Control rF.pdf | ||
| 1604000 C Wastewater rF.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WASTEWATER SECTION J - 1604000
DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
TABLE OF CONTENTS
| ATTACHMENT NUMBER |
| ATTACHMENT TITLE |
| J-1604000-01 |
| Definitions and Acronyms |
| J-1604000-02 |
| References and Technical Documents |
| J-1604000-03 |
| Historical Critical Spare Parts Inventory |
| J-1604000-04 |
| Waste Water Sampling and Testing Requirements |
ATTACHMENT J-1604000-01
WASTEWATER
DEFINITIONS AND ACRONYMS
DEFINITIONS
| Equipment, Collateral |
| Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project. |
| Equipment, Installed |
| Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial. |
| Equipment, Personal Property |
| Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed. |
| Facilities Life Cycle |
| A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal. |
| Facilities Maintenance Management |
| The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.” |
| Integrated Maintenance Plan |
| IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness. |
| Life-Cycle Costs |
| A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life. |
| Repair |
| Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition. |
| Replacement |
| Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance. |
| Restoration |
| Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes. |
| Sustainment |
| Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities. |
| SCADA |
| A version of telemetry commonly used in wide-area industrial applications, such as electrical power generation and distribution and water distribution, which includes supervisory control of remote stations as well as data acquisition from those stations over a bidirectional communications link. |
| ACRONYM |
| TITLE |
| ANSI |
| American National Standards Institute |
| ASHRAE |
| American Society of Heating, Refrigerating and Air-Conditioning Engineers |
| ASME |
| American Society of Mechanical Engineers |
| MACP |
| Manhole Assessment and Certification Program |
| NASSCO |
| National Association of Sewer Service Companies |
| NPDES |
| National Pollutant Discharge Elimination System |
| PACP |
| Pipeline Assessment and Certification Program |
| SCADA |
| Supervisory Control and Data Acquisition |
| SRM |
| Sustainment, Restoration and Modernization |
| UFC |
| Unified Facilities Criteria |
| WEF |
| Water Environmental Federation |
| WWTP |
| Wastewater Treatment Plant |
ATTACHMENT 1604000-02
REFERENCES AND TECHNICAL DOCUMENTS
| REFERENCE |
| TITLE |
| EI 11C201 |
| Wastewater Collection and Pumping |
| MO-209 |
| Engineering Criteria |
| MIL-HDBK-1005/9 |
| Industrial and Oily Wastewater Control |
| UFC 3-240-02N |
| Wastewater Treatment Systems |
| UFC 3-240-04A |
| Wastewater Collection |
| UFC 3-240-07FA |
| Sanitary and Industrial Wastewater Collection: Gravity Sewers and Appurtenances |
| UFC 3-240-09FA |
| Domestic Wastewater Treatment |
| UFC 4-832-01N |
| Design: Industrial and Oily Wastewater Control |
Non-Government Publications.
National Association of Sewer Service Companies, (NASSCO)
11521 Cronridge Drive, Suite J, Ownings, MD 21117
American National Standards Institute, Inc. (ANSI)
11 West 42nd Street, New York, NY 10036
ATTACHMENT J-1604000-03
HISTORICAL CRITICAL SPARE PARTS INVENTORY
The Contractor shall develop a critical spare parts inventory for submittal to the KO/COR, per section F.
ATTACHMENT J-1604000-04
WASTEWATER SAMPLING AND TESTING REQUIREMENTS
Referring to J-1604000-05 for waste water sampling and testing requirements.
ATTACHMENT J-1604000-05
ENVIRONMENTAL STORM WATER, DRINKING WATER, WASTE WATER, AND HAZARDOUS WASTE PROFILING SAMPLING AND TESTING BRIDGEPORT, CA
SECTION 1.0 - GENERAL
This Performance Work Statement (PWS) solicits services for performing laboratory testing of storm water, drinking water and waste water program requirements for water, soils, sludge and solid materials, at Marine Corps Mountain Warfare Training Center (MCMWTC), Bridgeport, CA, and shall be performed as outlined below. All work for the MCMWTC Bridgeport water program shall be completed in accordance with the most current regulations in California Code of Regulations Title 22 and updated approved revised state issued permits (i.e., Safe Drinking Water Act [SDWA], Clean Water Act [SWA] permits, National Pollutant Discharge Elimination System [NPDES] permits). All work must be performed following applicable and appropriate Department of Defense (DOD) guidance and policy and consider all site documentation and reports to date.
Under this PWS, the following services are required:
· Laboratory testing of storm water, drinking water, waste water, hazardous waste profiling and environmental media related to the MCMWTC Bridgeport water program
· Hardcopy and electronic data (PDF/NECARS) reporting deliverables
1.1 PRIMARY OBJECTIVE
The primary objective of this project is to provide laboratory testing of storm water, drinking water, and waste water program requirements at MCMWTC Bridgeport. The project scope shall include all of the necessary labor and equipment associated with meeting the objective.
The contractor shall obtain final approval of the work required by NAVFAC SW upon completion of these performance objectives as specified in Section 7: PERFORMANCE MEASUREMENT AND PAYMENT SUMMARY AND OFFER SCHEDULE.
1.2 BACKGROUND
The contractor shall provide laboratory services and associated reporting requirements to support environmental decision making, promote the wise use of environmental resources, and determine compliance with environmental regulations and permits. The MCMWTC Bridgeport water program requires ongoing environmental laboratory services to comply with the most current regulations in California Code of Regulations Title 22 and updated approved revised state issued permits (i.e., SDWA, CWA permits). Therefore, it is critical that monitoring, trend analysis and data gathering are conducted to maintain the drinking water program to include appropriate notification of any result above maximum contaminant levels (MCLs), public health goal (PHG), or bacteriological exceedance on drinking water. The notification shall be made in accordance with regulatory requirements. The contractor shall perform all work neatly, accurately, correctly and conform to the respective specifications, standards, requirements, permits and in accordance to appropriate codes and practices to include all Federal, State, local government and MCMWTC Bridgeport base regulations, laws and permits.
ATTACHMENT J-1606000-07
(CONTINUED)
SECTION 2.0 – WORK ELEMENTS
The contractor shall furnish all labor, management, supervision, tools, material, and equipment necessary to perform all work in accordance with the PWS. The contractor shall conduct all work in accordance with all pertinent state, local and federal regulations and approved work plans.
The contractor’s work areas and activities at the site shall be subject to inspection without announcement by the Navy/Marine Corps and their representatives.
The estimate should include the following work elements:
· WORK ELEMENT 1: Project Management
· WORK ELEMENT 2: Lab Testing and Reporting
2.1 WORK ELEMENT 1 – PROJECT MANAGEMENT
The contractor shall provide project management in support of this CTO in consultation with the Contracting Officer’s Representative (COR). The contractor is expected to provide efficient project management (i.e. supervision of personnel, subcontractor procurement and management, field visits by various specialists, preparation and maintenance of project schedules, budgets and files, progress reports and billing, and overall base-wide technical coordination) in order to minimize costs to the Navy. Furthermore, project management will be in accordance with Sections A thru J of the basic contract. The contractor shall provide all labor, approved material, equipment, supplies and supervision, necessary to perform the Sampling, Field Testing and Laboratory Services.
The contractor shall consult with the COR before altering/modifying any existing approved Environmental Laboratory Services contract documents. The documents, which include Standard Operating Procedures (SOPs) and/or Safety Plans, must be consistent with NAVFAC policy and with MCMWTC Bridgeport program requirements. The most current update of the SOP will be followed. The contractor shall coordinate meetings with the COR and take meeting minutes. Draft minutes are due to the COR within two (2) working days after the meeting/teleconference concludes. Once the minutes are approved by the COR, the contractor shall distribute the COR-approved minutes to all attendees within one (1) workday.
2.2 WORK ELEMENT 2 –LAB TESTING AND REPORTING
The contractor shall provide all labor, management, supervision, tools, material, and equipment required to perform field and laboratory testing, and reporting services in accordance with the basic contract requirements per Section C
– Descriptions and Specifications, Annex 0100000, Annex 0200000, Annex 1502000, Annex 1604000, and Annex 1606000. The contractor shall execute the work under the specifications of the basic contract to meet the customer requirements which include responding to sampling requests and timely completion and delivery of lab reports.
The contractor shall provide analyses as requested in this PWS and shall provide sampling kits and courier service from MCMWTC during working hours to the laboratory. All samples will be collected by MCMWTC environmental personnel. The work shall include procurement of subcontractors, equipment and supplies as necessary. Re-sampling and associated analyses shall occasionally be required on an emergency basis.
The contractor shall provide courier services to pick-up regularly scheduled sampling. Emergency sampling pick-up shall be coordinated with the COR and MCMWTC Environmental Office to determine
ATTACHMENT J-1606000-07
WATER
WATER SAMPLING REQUIREMENTS (CONTINUED)
fastest delivery of samples to the lab. Reports of analytical results for all media must include the cited regulatory levels and flag any results exceeding regulatory levels, permit levels, MCLs, or PGHs.
Per permit requirements, annual drinking water results shall be submitted to California Department of Health Services (CA DHS) electronically from the laboratory though EDT using Primary Station Codes (PS Codes). The results of the drinking water monitoring shall be reported to CA DHS by the sixth day of the following month. A hard copy of this report shall be provided to the MCMWTC Environmental Office with emails in pdf format sent to the Chief Plant Operator, the Environmental Manager, and the Water Quality Manager. The actual analytical results shall also be available electronically in a data base spreadsheet that is up-loadable using an Excel compatible program. The results, QA/OC, chain-of-custody, etc. shall be provided to the Environmental Office in .pdf format.
Sampling requirements for MCMWTC Storm Water/NPDES requires at least two (2) storm events per year must be sampled. There are five (5) outfalls to be sampled for which the contractor shall provide sampling kits to the Environmental Office. The contractor shall provide a minimum of 2 sampling kits per outfall annually with 5 total kits being provided to the Environmental Office upon contract award. Sampling kits for the second storm water sampling event shall be provided as requested by the Environmental Office following the first event sampled.
Sampling Kits shall include sample bottles with preservative (as appropriate), labels, blue ice and cooler for shipping and to keep samples at the required temperature.
| ELIN |
| DESCRIPTION |
| MINIMUM FREQUENCY |
| ESTIMATED QUANTITY |
Storm Water Outfalls 1-5
| G00604 |
| pH |
| Two events |
| 10 |
| G00803EM |
| Total Suspended Solids |
| Two events |
| 10 |
| G00803AX |
| Conductivity (Specific Conductance) |
| Two events |
| 10 |
| G00803EG |
| Total Organic Carbon (TOC) |
| Two events |
| 10 |
| G00803CH |
| Oil and Grease |
| Two events |
| 10 |
| G00803AJ |
| Biochemical Oxygen Demand (BOD) |
| Two events |
| 10 |
| G00803AQ |
| Chemical Oxygen Demand (COD) |
| Two events |
| 10 |
| G00803AF |
| Ammonia as Nitrogen |
| Two events |
| 10 |
| G00803DJ |
| Silica |
| Two events – Outfall 3 only |
| 2 |
| G014 |
| Courier Service (Sample Pick-Up) |
| Two events |
| 2 |
Sampling requirements for MCMWTC Hazardous waste testing shall be ordered by the Environmental Office using generator knowledge of waste streams to determine required analyses that will be ordered at a unit price. Hazardous waste profiling and supporting analytical testing are required on a regular basis (semi-annual to annual). Sampling requirements for MCMWTC Waste Water sludge shall be tested for Type 3 Municipal Landfill acceptance criteria. The contractor shall provide these analyses of existing waste streams to ensure waste profiles are correct. The contractor shall provide sampling kits appropriate to tests requested by the MCMWTC Environmental Office.
Typical hazardous waste streams analyses that are required would normally be CAM metals, TPH (gas, diesel and waste oil), Flashpoint, EPA 8260 and EPA 8270. For the purpose of selecting ELINS per characterization, below are the lab tests that may be used:
ATTACHMENT J-1606000-07
(CONTINUED)
· Used Oil: TPH Gas/ BTEX, TPH-Diesel, flashpoint, ethylene glycol, Title 22 Metals.
· Leaded Gasoline: TPH Gas / BTEX, flashpoint
· Diesel: TPH-Diesel, flashpoint
· JP-8: Fuel Fingerprint
· Contaminated Dirt with any combination of substances assuming unknown: Volatile Organics by EPA 8260, Semi-volatile Organics by EPA 8270, Title 22 Metals, PCBs, Pesticides by EPA 8081
· Bilge: Oil and Greases by EPA 1664, Title 22 Metals, pH
· Rifle Cleaning patches: Title 22 Metals, Semi-volatile Organics by EPA 8270
· Coolant: Ethylene glycol by EPA 8015 direct injection
· Cleaning Solvents: Volatile Organics by 8260
· Oil Water Separator Sludge: Oil and Greases by EPA 1664, Title 22 Metals
Sampling requirements for MCMWTC Monitoring Wells #9, #10 and #11 (groundwater) are also required on a quarterly or annual basis depending upon the analyses.
| ELIN |
| DESCRIPTION |
| MINIMUM FREQUENCY |
| ESTIMATED QUANTITY |
Groundwater Monitoring Wells #9, #10 and #11
| G00803BX |
| Nitrate |
| Quarterly for each well |
| 6 |
| G00803CD |
| Nitrogen, Kjeldahl Total (TKN) |
| Quarterly for each well |
| 6 |
| G00803AF |
| Ammonia as Nitrogen |
| Quarterly for each well |
| 6 |
| G00803AS |
| Chlorides |
| Quarterly for each well |
| 6 |
| G00803CH |
| Oil and Grease |
| Annual for each well |
| 3 |
| G00807BC |
| Volatile Organics |
| Annual for each well |
| 3 |
| G014 |
| Courier Service (Sample Pick-Up) |
| Quarterly |
| 3 |
The results shall be reported as indicated in the applicable permits and in a manner suitable to determine compliance. For example, all results must be reported to the method detection limits with estimated values provided between the method detection limits and reporting limits. Approved analytical methods from 40 CFR part 136 should be used when possible. If not possible, methods preapproved by the applicable regulatory agency as indicted by the COR will be used. Analytical methods should be selected that have minimum levels at or below the compliance limits. The reporting limits shall be at or below the compliance limits and minimum levels when possible.
All data deliverable packages shall be provided to the COR in order to meet MCMWTC water permit and regulation requirements. The contractor shall provide the monthly compilation of the data packages no later than the 6th day of the following month (i.e. the data package for September will be due no later than 6 October) on the contractor’s web portal or as directed by the COR. The contractor shall notify the COR by email that the data packages are ready to be viewed in the system. These data deliverable packages are a monthly compilation of all field test reports, laboratory tests reports and summary reports. The contractor shall provide early notification to the COR of preliminary results that may exceed permit limits so that parameter can be resampled, at the discretion of the Navy, within the same monitoring period.
Analytical data shall reference the Environmental Laboratory Services contract documents. Furthermore, a narrative summary cover page shall be included to final report deliverables discussing any anomalies experienced in the environmental sample(s). For example, if a sample was not properly preserved or holding time was not met according to EPA requirements but analysis was still performed on the sample as requested by the Government.
Additionally, analytical data should include the summary and required reports and provide electronic data deliverables as required by the MCMWTC Bridgeport water program. This includes, but is not limited to:
Chain of Custody (COC) and sample information shall be peer-reviewed and entered in the Navy Environmental Laboratory Information Management System (LIMS).
Sample and analytical data shall be uploaded to the Naval Environmental Compliance Analytical Reporting System (NECARS).
ELIN
DESCRIPTION*
| TEST METHOD |
| TA T |
| UNIT PRICE |
| EST. QTY |
EST. AMT.
| G006 |
| Field Testing* |
| G00604 |
| pH |
| SM4500-H+B |
| 10 |
| G008 |
| Laboratory Testing* |
| G00801 |
| Bacteriological and Asbestos |
| G00801AM |
| Coliform, Total/E.coli: (Presence/Absence) |
| SM 9221/9223 (P/A) |
| 10 |
| G00801AX |
| Coliform, Total/E.coli |
(Density/Enumeration)
SM 9221/9223
(MPN)
| G00803 |
| General Chemistry |
G00803AF
Ammonia as Nitrogen EPA 350.1 Rev 2 (1993)
| G00803AJ |
| Biochemical Oxygen Demand (BOD) |
| SM 5210B |
| 10 |
| G00803AQ |
| Chemical Oxygen Demand (COD) |
| EPA 410.4 |
| 10 |
| G00803AS |
| Chlorides |
| EPA 300.0 |
| 10 |
G00803AX
Conductivity (Specific Conductance)
SM2510B/EPA 9050A
| G00803BG |
| Flashpoint |
| EPA 1010A |
| 10 |
| G00803BX |
| Nitrate |
| EPA 300.0 |
| 10 |
| G00803CD |
| Nitrogen, Kjeldahl Total (TKN) |
| EPA 351.1 |
| 10 |
G00803CH
Oil and Grease
EPA 1664/EPA 9070A
| G00803CQ |
| pH |
| SM4500-H |
| 10 |
| G00803DJ |
| Silica |
| SM4500-SI-D |
| 10 |
| G00803EG |
| Total Organic Carbon (TOC) |
| EPA 9060 |
| 10 |
G00803EM
Total Suspended Solids
EPA
160.2/SM2540 D
G00803FH
Oil and Grease in soils/solids (report as HEM and SGT-HEM)
EPA
9070A/1664
Metals
G00804AD
CA Title 22 Metals List-Total [TTLC- Sb,As,Ba,Be,Cd,Cr (total),Co,Cu,Pb,Hg,Mo,Ni,Se,Ag,Tl,V ,Zn]
EPA 200.8/245.1
G00804AU
List of Individual Metals by ICP (EPA 200.8/6020): Al, Sb, As, Ba, Be, B, Cd, Ca, Cr Total, Co, Cu, Fe, Pb, Mg, Mn, Ni, K, Se, Si, Ag, Na, Tl, Ti, V, Zn [PRICE PER METAL TESTED]
EPA 200.8/6020
| G00805 |
| Radiological |
G00805AB
Gross Alpha
EPA 900.0/SM 7110B/7110C/9
| G00806 |
| Semi-Volatile Organics (SVOA) |
G00806AD
Chlorinated Pesticides EPA 608 or
EPA 8081
| G00806AJ |
| Ethylene Glycol |
| EPA 8015 Mod |
| 10 |
G00806AN
| Fuel Fingerprint of Product (reported as percentage) |
| EPA 8015B |
(carbon range to C-35)
| G00806AQ |
| Haloacetic Acids (HAA5) |
| EPA 552.2 |
| 10 |
G00806BC
Polychlorinated Biphenyls (PCBs)
EPA 8082A
(includes PCB 1262 and 1268) or EPA 608
| G00806BJ |
| Semi volatile organics 625 |
| EPA 625 |
| 10 |
| G00806BK |
| Semi volatile organics 8270C |
| EPA 8270C |
| 10 |
G00806BN
TPH-Diesel (report includes chromatograms)
EPA 8015B
(may include carbon range to C-35)
| G00807 |
| Volatile Organics (VOA) |
| G00807AC |
| BTEX |
| EPA 8021 |
| 10 |
G00807AV
TPH-GAS (report includes chromatograms)
EPA 8015B
| G00807AW |
| Trihalomethanes (THMs) |
| EPA 524.2 |
| 10 |
| G00807BC |
| Volatile Organics |
| EPA 8260B |
| 10 |
| G00808 |
| Laboratory Test Turnaround in Less Than Specified Working Days* |
| G014 |
| Courier Service (Sample Pick-Up)* |
| G016 |
| Database Development Support* |
| G017 |
| Mod/Develop SAP/SOP Support* |
*Indicates "SHORT DESCRIPTION". Additional information about this ELIN is contained in ATTACHMENT JC- 0200000-12
SECTION 3.0 – SPECIAL REQUIREMENTS/CONDITIONS
The contractor shall produce deliverables that do not require extensive revision/correction or extra effort for internal review and QA/QC. The contractor shall ensure that deliverables will not include any major technical and/or legal issues, or inconsistencies that require extensive re-write. The contractor shall correct any deficiencies identified by the Navy at no additional cost to the Government. The contractor shall respond to all comments from the environmental compliance community and regulatory agencies throughout the duration of this delivery order that address any deliverable.
The contractor shall obtain approval from the COR prior to obtaining photography records, still or motion picture and/or aerial or ground photographs, in accordance with Public Law: 18 U.S. Code 795 and applicable station regulations. The Government may provide a representative to act in an advisory capacity to prevent unauthorized disclosure of classified information.
No understanding, agreement, modification, change order, or other matter deviating from the terms of the basic contract and CTO between the Contractor and any person other than the Contracting Officer will be effective or binding upon the Government, unless formalized by proper contractual documents executed by the Contracting Officer prior to completion of the CTO. The Contracting Officer’s authorized representatives are:
(1) The Contracting Officers Representative (COR) is responsible to the Contracting Officer for monitoring performance and the technical management of the effort required under this CTO, and should be contacted regarding questions or problems of a technical nature. The COR is not authorized to make any commitments or changes that will affect price, quality, quantity, delivery, or any other term or condition of the contract.
(2) The Contract Specialist (CS) assists the Contracting Officer and should be contacted for all other contract administrative matters for this CTO.
Except for changes identified as such in writing and signed by the Contracting Officer, the Contractor shall notify the Administrative Contracting Officer in writing, within 30 calendar days from the date that the Contractor identifies any Government conduct (including actions, inactions, and written or oral communications) that the Contractor regards as a change to the contract terms and conditions.
The COR is the first and primary point of contact for ALL inquiries, questions, concerns, and issues related to the implementation of the technical requirements and specifications of this CTO. Subject Matter Experts (SMEs) are Government technical personnel providing assistance to the COR in the administration, oversight, and performance assessment of the CTO. Neither the COR, nor any other Government representative may direct any change that affects price, quality, quantity, delivery, or other terms and conditions of the basic contract or CTO.
The contractor shall not implement any change to the contract before receiving written authorization from; or a contract modification issued by the Contracting Officer.
Contractor employees performing services under this order will be controlled, directed, and supervised at all times by management personnel of the contractor. Contractor management will ensure that employees properly comply with the performance work standards outlined in the performance work statement. Contractor employees will perform their duties independent of, and without the supervision of, any Government official or other Defense Contractor. The tasks, duties, and responsibilities set forth in the task order may not be interpreted or implemented in any manner that results in any contractor employee creating or modifying Federal policy, obligating the appropriate funds of the United States Government, overseeing the work of Federal employees, providing direct personal services to any Federal employee, or otherwise violating the prohibitions set forth in Parts 7.5 and 37.1 of the Federal Acquisition Regulation (FAR). The Government will control access to the facility and will perform the inspection and acceptance of the completed work.
Public Affairs – The contractor shall not disclose any data resulting from actions in this contract to the news media or public. The contractor shall refer all press or public contacts to the COR. The contractor may not distribute reports or data to any other source, and shall follow the public affairs policies in accordance with NAVFAC Southwest instruction. The contractor shall provide copies of all correspondence to the COR.
SECTION 4.0 – GOVERNMENT FURNISHED EQUIPMENT/DATA
There is no government furnished equipment to be available at MCMWTC Bridgeport to the contractor for use under this contract. Government Furnished Property shall be in accordance with the basic contract and applicable modifications, Section J. Attachment JC-0200000-08.
SECTION 5.0 – POINTS OF CONTACT
Contracting Officer’s Representatives (COR/ACOR):
Names: Elliott Vandermaas (COR) Vincent Sandre (ACOR) Address: Marine Corps Mountain Warfare Training Center Attn: Facilities Maintenance Bridgeport, CA 93517 Phones: (760) 932-1592
(619) 453-8976 Emails: Elliott.vandermaas1@usmc.mil vinnie.sandre@usmc.mil
Contracting Officer (KO):
| Name: | Katherine Simpson |
| Address: | Naval Facilities Engineering Command Southwest Environmental Contracts Core |
1220 Pacific Highway
| San Diego, California 92132-5190 Phone: | (760) 725-9959 |
| Email: | katherine.simpson@navy.mil |
Contract Specialist (CS):
| Name: | XXXX XXXX |
| Address: | Naval Facilities Engineering Systems Command Southwest ACQ Environmental Core |
1220 Pacific Highway
| San Diego, California 92132-5190 Phone: | (619) 705-XXXX |
| Email: | xxxx.xxxx@navy.mil |
MCMWTC Environmental Manager:
| Name: | Brent Husung | |
| Address: | Marine Corps Mountain Warfare Training Center HC-83 Bridgeport, CA 93517 |
Bridgeport, CA 93517-9802
| Phone: | (760) 932-1457/(760) 219-5861 |
| Email: | martin.husung@usmc.mil |
SECTION 6.0 – DELIVERABLES
Deliverables shall be in provided accordance with the basic contract and applicable modifications, as provided in the schedule below.
| WE |
| Base / Facility |
| Deliverable Description |
| Number of Hard Copies/ CDs |
| Due/Milestone/Work Days |
Work Element 1 – Project Management
| 1 |
| MCMWTC |
Bridgeport Meetings and LIMS login Chain of Custody (COC) review.
Email word document for the meeting minutes. Email PDF for the LIMS login COC review Distribution of meeting minutes within 1 working day from the COR approval of draft meeting minutes.
Corrected LIMS login within 10 days or less date of receipt of samples
Work Element 2 – Sampling, Field and Lab Testing and Reporting
| 2 |
| MCMWTC |
Bridgeport
| Laboratory analyses and reporting final results |
| Email PDF and upload final results into NECARS. |
| · Sample collection will begin 5 days from the date of award. At a minimum, samples will be collected on a bimonthly basis and in accordance with the MCMWTC water permit and regulation requirements. Extra sample collection and rush TAT may occur based on the findings and evaluation of the laboratory results. |
· Data deliverable reports will be due 10 working days from the time of sample receipt. Monthly compilation of the data packages shall be
| WE |
| Base / Facility |
| Deliverable Description |
| Number of Hard Copies/ CDs |
| Due/Milestone/Work Days |
provided no later than the 6th of the following month.
· Notify COR by email prior to courier arrival on base for sample pick-up; and upon completion of lab testing completion via email.
A narrative summary cover page shall be included to final report deliverables if anomalies regarding the environmental sample(s) has occurred. For example, if a sample was not properly preserved or holding time was not met according to EPA requirements but analysis was still performed on the sample as requested by the Government PM.
SECTION 7.0 – PERFORMANCE MEASUREMENT AND PAYMENT SUMMARY AND OFFER
The following service delivery summary includes the performance objective and performance threshold for each task in the contract. In addition, the contract will meet the performance standards listed in this contract under Section C, Annex 1800000 Spec Item 3 and 4. This performance threshold provides a vehicle to align performance with the Government standard/business objective, and provides a focus on critical success factors in meeting these objectives. The referenced sections provide further detail of the performance objective. Performance is measured according to the Performance Assessment Plan, Section J.
Work Element / Task
| Performance Standard |
| Acceptable Quality |
Level
| Assessment Method |
| Performance Payment and Incentive |
| Section 2.1 - |
| Successful |
| 100% Navy |
| Navy performance |
| Payable monthly upon |
| Work |
| coordination, project |
| Acceptance |
| evaluation. Navy receipt |
| completion and Navy |
| Element 1 - |
| management and |
| of the Contractor prepared |
| acceptance per Firm Fixed |
| Project |
| administrative support |
| minutes as required by the |
| Price unit pricing. |
| Management |
| to keep the project |
Performance Work within scope, schedule, Statement.
and budget. Invoices and status reports report provide sufficient information and submitted timely.
| Section 2.2 - |
| Laboratory analysis |
| 100% Navy |
| Navy acceptance by |
| Lump sum payable monthly |
| Work |
| meet all QA/QC |
| Acceptance |
| Contracting Officer (KO) |
| upon completion and Navy |
| Element 2- |
| criteria. In addition, |
| input and product |
| acceptance per IDIQ unit |
| Lab Testing |
| data deliverable |
| deliverable satisfaction |
| pricing. |
| and |
| packages (hardcopy and |
from COR. The due dates
| Reporting |
| EDDs) are provided in |
of the data deliverable a timely manner in packages (i.e. hardcopy accordance to the and EDDs) are reported to appropriate water the MCMWTC Bridgeport permit frequency and designated PM as stated on regulation requirements the Chain of Custody
(COC) or sooner to meet permit and regulation requirements. Sample holding times are met
100% of the time.
SECTION 8.0 – REFERENCES
Please refer to the basic contract and modifications, as necessary.
IGE for OP6 Bridgeport
Period of Performace ~October 1, 2016 thru April 30, 2017 (7 months or 2 quarterly events or 1 annual event)
| SOWNam e |
| ELIN |
| Method |
| TAT |
| ELIN |
Price Est. Qua ntity
Extended Price
DESCRIPTION
Stormwater - Outfalls 1-5
OP06-
Bridgeport
| G00803 CQ |
| SM4500-H |
| 10 |
| $ |
| 10 |
| $ |
| pH |
OP06-
Bridgeport
| G00803 EM |
| EPA 160.2/SM2540D |
| 10 |
| $ |
| 10 |
| $ |
| Total Suspended Solids |
OP06-
Bridgeport G00803
AX
SM2510B/EPA
9050A
| 10 |
| $ |
| 10 |
| $ |
| Conductivity (Specific |
Conductance)
OP06-
Bridgeport
| G00803 EG |
| EPA 9060 |
| 10 |
| $ |
| 10 |
| $ |
| Total Organic Carbon (TOC) |
OP06-
Bridgeport G00803
CH
EPA 1664/EPA
9070A
| 10 |
| $ |
| 10 |
| $ |
| Oil and Grease |
OP06-
Bridgeport
| G00803 AJ |
| SM 5210B |
| 10 |
| $ |
| 10 |
| $ |
| Biochemical Oxygen Demand (BOD) |
OP06-
Bridgeport
| G00803 AQ |
| EPA 410.4 |
| 10 |
| $ |
| 10 |
| $ |
| Chemical Oxygen Demand (COD) |
OP06-
Bridgeport G00803
AF
EPA 350.1 Rev 2 (1993)
| 10 |
| $ |
| 10 |
| $ |
| Ammonia as Nitrogen |
OP06-
Bridgeport
| G00803 DJ |
| SM4500-SI-D |
| 10 |
| $ |
| 2 |
| $ |
| Silica |
OP06-
Bridgeport G014
| $ |
| 2 |
| $ |
| Courier Service (Sample Pick- Up) |
Drinking Water (Treated Samples)
OP06-
Bridgeport
| G00801 AM |
| SM 9221/9223 (P/A) |
| 10 |
| $ |
| 14 |
| $ |
| Coliform, Total/E.coli (Presence/Absence) |
OP06-
Bridgeport
| G00804 AU |
| EPA 200.8/6020 |
| 10 |
| $ |
| 7 |
| $ |
| List of Individual Metals by ICP (EPA 200.8/6020): Al, Sb, |
As, Ba, Be, B, Cd, Ca, Cr Total, Co, Cu, Fe, Pb, Mg, Mn, Ni, K, Se, Si, Ag, Na, Tl, Ti, V, Zn [PRICE PER METAL
TESTED]
OP06-
G014
| $ |
| 14 |
| $ |
| Courier Service (Sample Pick- Up) |
Drinking Water (Wells 1 & 2 raw water)
OP06-
Bridgeport
| G00804 AU |
| EPA 200.8/6020 |
| 10 |
| $ |
| 14 |
| $ |
| List of Individual Metals by ICP (EPA 200.8/6020): Al, Sb, |
As, Ba, Be, B, Cd, Ca, Cr Total, Co, Cu, Fe, Pb, Mg, Mn, Ni, K, Se, Si, Ag, Na, Tl, Ti, V, Zn [PRICE PER METAL TESTED]
| OP06- |
| G00803 |
| SM4500-H |
| 10 |
| $ |
| 14 |
| $ |
| pH |
| Bridgeport |
| CQ |
OP06-
| G00801 AX |
| SM 9221/9223 (MPN) |
| 10 |
| $ |
| 4 |
| $ |
| Coliform, Total/E.coli (Density/Enumeration) |
OP06-
Bridgeport
| G00805 AB |
| EPA 900.0/SM 7110B/7110C/931 |
| 10 |
| $ |
| 4 |
| $ |
| Gross Alpha |
OP06-
Bridgeport
| G00807 AW |
| EPA 524.2 |
| 10 |
| $ |
| 2 |
| $ |
| Trihalomethanes (THMs) |
OP06-
Bridgeport
| G00806 AQ |
| EPA 552.2 |
| 10 |
| $ |
| 2 |
| $ |
| Haloacetic Acids (HAA5) |
OP06-
Bridgeport G00803
BX
| EPA 300.0 |
| 10 |
| $ |
| 2 |
| $ |
| Nitrate |
OP06-
G014
| $ |
| 7 |
| $ |
| Courier Service (Sample Pick- Up) |
Hazardous Waste Testing
OP06-
Bridgeport
| G00804 AD |
| EPA 200.8/245.1 |
| 10 |
| $ |
| 1 |
| $ |
| CA Title 22 Metals List-Total [TTLC-Sb,As,Ba,Be,Cd,Cr |
(total),Co,Cu,Pb,Hg,Mo,Ni,Se, Ag,Tl,V,Zn]
OP06-
Bridgeport
| G00807 AC |
| EPA 8021 |
| 10 |
| $ |
| 1 |
| $ |
| BTEX |
OP06-
Bridgeport
| G00807 AV |
| EPA 8015B |
| 10 |
| $ |
| 1 |
| $ |
| TPH-GAS (report includes chromatograms) |
OP06-
Bridgeport
| G00806 BN |
| EPA 8015B (may |
include carbon range to C-35)
| 10 |
| $ |
| 1 |
| $ |
| TPH-Diesel (report includes chromatograms) |
OP06-
Bridgeport
| G00806 AN |
| EPA 8015B |
(carbon range to C-35)
| 10 |
| $ |
| 1 |
| $ |
| Fuel Fingerprint of Product (reported as percentage) |
OP06-
Bridgeport
| G00803 BG |
| EPA 1010A |
| 10 |
| $ |
| 1 |
| $ |
| Flashpoint |
OP06-
Bridgeport G00807
BC
| EPA 8260B |
| 10 |
| $ |
| 1 |
| $ |
| Volatile Organics |
OP06-
Bridgeport
| G00806 BK |
| EPA 8270C |
| 10 |
| $ |
| 1 |
| $ |
| Semi volatile organics 8270C |
OP06-
Bridgeport
| G00806 AJ |
| EPA 8015 Mod |
| 10 |
| $ |
| 1 |
| $ |
| Ethylene Glycol |
OP06-
Bridgeport
| G00806 BC |
| EPA 8082A |
(includes PCB 1262 and 1268) or
EPA 608
| 10 |
| $ |
| 1 |
| $ |
| Polychlorinated Biphenyls (PCBs) |
OP06-
Bridgeport
| G00806 AD |
| EPA 608 or EPA 8081 |
| 10 |
| $ |
| 1 |
| $ |
| Chlorinated Pesticides |
OP06-
Bridgeport
| G00803 FH |
| EPA 9070A/1664 |
| 10 |
| $ |
| 1 |
| $ |
| Oil and Grease in soils/solids (report as HEM and SGT-HEM) |
OP06-
Bridgeport
| G00803 CQ |
| SM4500-H |
| 10 |
| $ |
| 1 |
| $ |
| pH |
OP06-
G014
| $ |
| 1 |
| $ |
| Courier Service (Sample Pick- Up) |
Waste Water Influent
OP06-
Bridgeport
| G00803 AJ |
| SM 5210B |
| 10 |
| $ |
| 7 |
| $ |
| Biochemical Oxygen Demand (BOD) |
| OP06- |
| G014 |
| $ |
| 7 |
| $ |
| Courier Service (Sample Pick- |
Bridgeport
Up)
Waste Water Effluent
OP06-
Bridgeport
| G00803 AJ |
| SM 5210B |
| 10 |
| $ |
| 14 |
| $ |
| Biochemical Oxygen Demand (BOD) |
OP06-
Bridgeport G00803
CQ
| SM4500-H |
| 10 |
| $ |
| 14 |
| $ |
| pH |
OP06-
Bridgeport
| G00803 CD |
| EPA 351.1 |
| 10 |
| $ |
| 7 |
| $ |
| Nitrogen, Kjeldahl Total (TKN) |
OP06-
Bridgeport
| G00803 BX |
| EPA 300.0 |
| 10 |
| $ |
| 7 |
| $ |
| Nitrate |
OP06-
Bridgeport G00803
AF
EPA 350.1 Rev 2 (1993)
| 10 |
| $ |
| 7 |
| $ |
| Ammonia as Nitrogen |
OP06-
Bridgeport
| G00803 AS |
| EPA 300.0 |
| 10 |
| $ |
| 7 |
| $ |
| Chlorides |
OP06-
Bridgeport G00803
CH
EPA 1664/EPA
9070A
| 10 |
| $ |
| 1 |
| $ |
| Oil and Grease |
OP06-
Bridgeport
| G00807 BC |
| EPA 8260B |
| 10 |
| $ 1 |
| 1 |
| $ |
| Volatile Organics |
OP06-
Bridgeport
| G00806 BJ |
| EPA 625 |
| 10 |
| $ |
| 1 |
| $ |
| Semi volatile organics 625 |
OP06-
Bridgeport
| G00804 AD |
| EPA 200.8/245.1 |
| 10 |
| $ |
| 1 |
| $ |
| CA Title 22 Metals List-Total [TTLC-Sb,As,Ba,Be,Cd,Cr |
(total),Co,Cu,Pb,Hg,Mo,Ni,Se, Ag,Tl,V,Zn]
OP06-
Bridgeport G00807
AV
| EPA 8015B |
| 10 |
| $ |
| 1 |
| $ |
| TPH-GAS (report includes |
chromatograms)
OP06-
Bridgeport
| G00806 BN |
| EPA 8015B (may |
include carbon range to C-35)
| 10 |
| $ |
| 1 |
| $ |
| TPH-Diesel (report includes chromatograms) |
OP06-
Bridgeport
| G00806 AN |
| EPA 8015B |
(carbon range to C-35)
| 10 |
| $ |
| 1 |
| $ |
| Fuel Fingerprint of Product (reported as percentage) |
OP06-
G014
| $ |
| 14 |
| $ |
| Courier Service (Sample Pick- |
Up)
Waste Water Sludge - Type 3 Municipal Landfill Acceptance Criteria
OP06-
OP06-
OP06-
G014
Courier Service (Sample Pick- Up)
Monitoring Wells #9, #10, and #11 (Groundwater)
OP06-
Bridgeport
| G00803 BX |
| EPA 300.0 |
| 10 |
| $ |
| 6 |
| $ |
| Nitrate |
OP06-
Bridgeport G00803
CD
| EPA 351.1 |
| 10 |
| $ |
| 6 |
| $ |
| Nitrogen, Kjeldahl Total (TKN) |
OP06-
Bridgeport
| G00803 AF |
| EPA 350.1 Rev 2 |
(1993)
| 10 |
| $ |
| 6 |
| $ |
| Ammonia as Nitrogen |
OP06-
Bridgeport
| G00803 AS |
| EPA 300.0 |
| 10 |
| $ |
| 6 |
| $ |
| Chlorides |
OP06-
Bridgeport G00803
CH
EPA 1664/EPA
9070A
| 10 |
| $ |
| 3 |
| $ |
| Oil and Grease |
| OP06- |
| G00807 |
| EPA 8260B |
| 10 |
| $ |
| 3 |
| $ |
| Volatile Organics |
| Bridgeport |
| BC |
OP06-
G014
| $ |
| 3 |
| $ |
| Courier Service (Sample Pick- Up) |
Lump sum amount for any rush turnaround time sampling in less than specified working days
OP06-
G00808
| $ |
| Rush TAT |
| $ |
| IGE for OP6. Amount for 2276 funding doc |
| $ |
| COMMODITY COST. |
Amount for 2275 funding doc
| $ |
| Total |
ATTACHMENT J-1604000-04 DISPOSAL LOCATIONS
Explained at Award.
ATTACHMENT J-1604000-05 SAMPLE OF DISPOSAL TESTING REPORT
ATTACHMENT J-1604000-06 SPILL CONTAINMENT PLAN
ATTACHMENT J-1604000-07 HISTORICAL
CRITICAL SPARE PARTS.
ATTACHMENT J-1604000-08 HISTORICAL
CHEMICAL AND MATERIAL USAGE.
Refurbish Caustic Soda, Sulfuric acid and Chlorine every 40 days.
Sulfuric Acid 71 ea. (49 gallon drum) 751 pounds.
Caustic Soda/Chlorine 536 bags, of 50 pound each bags.
ATTACHMENT J-1606000-01
WATER TREATMENT PLANT AND DISTRIBUTION SYSTEM DESCRIPTION AND INVENTORY
In section 2.5 it calls for the results to be sent to CADHS. The regulator is now the State Water Resource Control Board Division of Drinking Water. The wastewater analysis all looks good. There is a lot missing on the water end. Both wells need to be sampled for the following:
Arsenic, Inorganic chemicals, General mineral, General physical, Synthetic organic compounds, Secondary/ General physical, nitrate, nitrite, perchlorate and Volatile organic compounds. Also, five sites will need to be sampled for copper and lead. I think that will cover it. Please feel free to contact me anytime, Larry. Ph. 760-932-1601, cell., 619-453-9013.
1.0 Introduction
The general scope of this statement of work consists of performing analytical services and reporting the results.
2.0 Scope
The contractor shall furnish all supervision, labor, materials, equipment, required testing, laboratory support, reports and incidentals necessary to perform laboratory analysis for storm water, wastewater, drinking water, and hazard waste profiling, to include courier services. To include appropriate notification of any result above MCL's (minimum contamination level), PHG (public health goal), or bacteriological exceedance on drinking water. The notification shall be made in accordance with regulatory requirements. The contractor shall perform all work neatly, accurately, correctly and conform to the respective specifications, standards, requirements, permits and in accordance to appropriate codes and practices to include all Federal, State, local government and MCMWTC Bridgeport base regulations, laws and permits.
2.1 Contractor shall provide analyses as requested in the following paragraphs, sampling kits and courier service from MCMWTC to Lab. The work shall include procurement of subcontractors, equipment and supplies as necessary.
2.2 Field implementation: The contractor shall provide courier services to pick-up regularly scheduled sampling. Emergency sampling pick-up shall be coordinated with Environmental Office to determine fastest delivery of samples to Lab. Reports of analytical results for all media must include the cited regulatory levels and flag any results exceeding regulatory levels, permit levels, MCL's or PGHs
2.3 The contractor shall provide sampling kits for Environmental Personnel to collect all samples. Contractor shall provide courier service to pick up samples during working hours for lab analysis. Re- sampling and associated analyses shall occasionally be required on an emergency basis.
2.4 Hazardous waste profiling and supporting analytical testing are required on a regular basis (semi annual to annual).
2.5 Per permit requirements, annual drinking water results shall be submitted to California Department of Health Services (CA DHS) electronically from the laboratory though EDT using Primary Station Codes (PSCodes). The results of the drinking water monitoring shall be reported to CA DHS by the tenth day of the following month. A hard copy of this report shall be provided to the MCMWTC Environmental Office with emails in pdf format sent to the Chief Plant Operator, the Environmental Manager, and the Water Quality Manager. The actual analytical results shall also be available electronically in a data base spreadsheet that is up-loadable using an Excel compatible program. The results, QA/OC, chain-of- custody, etc. shall be provided to the Environmental Office in .pdf format.
2.6 Sampling requirements MCMWTC storm water/NPDES Analysis Requirements: At least 2 storm events per year must be sampled. There are five outfalls to be sampled for which the contractor shall provide sampling kits to the Environmental Office. The following tests are required:
Outfalls 1,2,4 and 5
| Analyze |
| Test Method |
| pH |
| SM 4500H |
| Total suspended solids (TSS) |
| SM2540D |
| Specific conductance |
| SM251 OB |
| Total Organic Carbon (TOC) |
| EPA 415.1 |
| Oil and Grease (O & G) |
| EPA 413.1 |
| Biochemical Oxygen Demand (BOD) |
| SM5210B |
| Chemical Oxygen Demand (COD) |
| EPA 410.4 |
| Ammonia (NH3) |
| EPA 350.2 |
Misc Sampling of water and soil not mentioned above or anywhere else in the scope of work.
Outfall 3 only when discharge occurs
All of the above
| Silica |
| EPA 370.1 |
2.7 Storm water sampling kits: minimum of 2 sets per outfall annually– 5 total minimum shall be provided to the Environmental Office at the beginning of the contract. Sampling kits for the second storm water sampling event shall be provided as requested by the Environmental Office following the first event sampled. Sampling Kits shall include sample bottles with preservative as required. Labels, blue ice and cooler for shipping and to keep samples on ice.
2.8 MCMWTC Drinking Water Sampling Requirements:
2.8.1 Sampled twice per month by the Water System Operator
Drinking Water distribution system (treated water samples)
| Analyze |
| Frequency |
| Test Method |
| Total Coliform |
| Twice monthly |
| SM9223B (IDEXX |
Colilert)
| Manganese |
| Monthly |
Wells 1 & 2 (raw water samples)
| Manganese |
| Monthly for each well |
| pH |
| Monthly for each well |
| SM 4500H |
| Total Coliform |
| Quarterly for each well |
| Quant-tray (MPN) |
| Gross Alpha |
| Quarterly for each well |
| Disinfection Byproducts |
| Annual for each well |
| Haloacetic Acids |
| Annual for each well |
| Nitrates (as NO3) |
| Annual for each well |
2.8.2 Bacteriological:
2.8.2.1 Minimum of two (2) presence/absence distribution system bacti samples are required monthly. If a positive result occurs, re-sampling must take within 24 hours. E coli results are required on all positive samples.
2.8.2.2 Minimum of two (2) MPN bacti samples from the Wells are required quarterly.
2.8.3 Contractor shall provide sampling kits – minimum of (2) months worth of sampling kits sets per location shall be provided at the beginning of the contract. Sampling kits shall include sample bottles with preservatives as required, labels, blue ice and coolers for shipping and to keep samples on ice.
2.9 MCMWTC Hazardous waste testing: These tests shall be ordered by the Environmental Office using generator knowledge of waste streams to determine required analyses that will be ordered at a unit price.
2.9.1
2.9.1 Provide annual analyses of existing waste streams to ensure Base waste profiles are correct.
2.9.2 Contractor shall provide sampling kits appropriate to tests requested by Environmental Office.
2.9.3 Typical hazardous waste streams analyses that are required would normally be CAM metals, TPH (gas, diesel and waste oil), Flashpoint, EPA 8260 and EPA 8270. For purpose of providing costs these are the lab tests used for characterization:
2.9.3.1 Used Oil: TPH Gas/ BTEX, TPH-Diesel, flashpoint, ethylene glycol, Title 22 Metals.
2.9.3.2 Leaded Gasoline: TPH Gas / BTEX, flashpoint
2.9.4.1 2.9.3.3 Diesel: TPH-Diesel, flashpoint
2.9.4.2 2.9.3.4 JP-8: Fuel Fingerprint
2.9.3.5 Contaminated Dirt with any combination of substances assuming unknown:
2.9.4.5.1 Volatile Organics by EPA 8260, Semi-volatile Organics by EPA 8270, Title 22 Metals, PCBs, Pesticides by EPA 8081
2.9.4.6 Bilge: Oil and Greases by EPA 1664, Title 22 Metals, pH.
2.9.4.7 Rifle Cleaning patches: Title 22 Metals, Semi-volatile Organics by EPA 8270.
2.9.4.8 Coolant: Ethylene glycol by EPA 8015 direct injection.
2.9.4.9 Cleaning Solvents: Volatile Organics by 8260
2.9.4.10 Oil Water Separator Sludge: Oil and Greases by EPA 1664, Title 22 Metals.
2.10 MCMWTC Waste Water Sampling, testing and reporting requirements. Sampled by Wastewater Treatment Operator. Report results by email (pdf) to the Chief Operator and the Water Quality Manager by the 10th day of the month following the sampling:
2.10.1 Wastewater influent:
| Test |
| Units |
| Frequency |
| BOD5 (biochemical oxygen demand) |
| mg/l |
| Monthly |
2.10.2 Wastewater effluent:
| Test |
| Units |
| Frequency |
| BOD5 (biochemical oxygen demand) |
| mg/l |
| Twice monthly |
| pH |
| pH units |
| Twice monthly |
| Total Kjeldahl Nitrogen |
| mg/l as N |
| Monthly |
| Nitrate nitrogen |
| mg/l as N |
| Monthly |
| Ammonia nitrogen |
| mg/l as N |
| Monthly |
| Chlorides |
| mg/l |
| Monthly |
| Oil and Grease |
| mg/l |
| Annual |
| Purgeable Organics |
| µg/l |
| Annual |
| Base / Neutral Extractable Organics |
| µg/l |
| Annual |
| Acid Extractable Organics |
| µg/l |
| Annual |
| Heavy Metals |
| µg/l |
| Annual |
| Total Petroleum Hydrocarbons |
| mg/l |
| Annual |
2.10.3 Wastewater sludge:
The wastewater sludge shall be tested for a Type 3 Municipal Landfill acceptance criteria.
2.10.4 Monitoring Wells #9, #10 and #11 (groundwater):
| Test |
| Units |
| Frequency |
| Nitrate nitrogen |
| mg/l as N |
| Quarterly |
| Total Kjeldahl Nitrogen |
| mg/l as N |
| Quarterly |
| Ammonia nitrogen |
| mg/l as N |
| Quarterly |
| Chlorides |
| mg/l |
| Quarterly |
| Oil and Grease |
| mg/l |
| Annual |
| Purgeable Organics |
| µg/l |
| Annual |
3.0 Period of Performance
The period of performance is 365 days from the contract award date. The period of performance may be extended at the governments interest by no more than 6 additional months or decreased as necessary at the governments interest to facilitate MCMWTC's compliance (i.e. all reports and reporting and standard operational procedures) with regional, state and/or federal requirements for storm water, ground water, waste water and potable water monitoring, sampling and reporting.
4.0 Contract Authority:
Notwithstanding any other provision of this contract, the Contracting Officer shall be the only individual authorized to redirect the effort or otherwise amend any of the terms of this contract.
5.0 Place of Performance
The place of performance is the MCMWTC, all areas, potable water wells, storm water outfalls, monitoring wells, other areas designated for sampling and associated facilities for onsite work. Offsite work (testing) will be done at contractor’s facility.
6.0 Government Furnished Property
There is no government owned equipment to be furnished to the contractor for use under this contract.
7.0 Technical Point of Contact and Inspection and Acceptance
The Contracting Officer’s Technical Assistant under this performance based contract and the person(s) responsible for performing inspection an acceptance of the contractor’s performance at MCMWTC (i.e., destination) is/are:
Larry Robasciotti (760) 932-1601; larry.robasciotti@usmc.mil
8.0 Non Personal Services
Contractor employees performing services under this order will be controlled, directed, and supervised at all times by management personnel of the contractor. Contractor management will ensure that employees properly comply with the performance work standards outlined in the statement of work. Contractor employees will perform their duties independent of, and without the supervision of, any Government official or other Defense Contractor. The tasks, duties, and responsibilities set forth in the task order may not be interpreted or implemented in any manner that results in any contractor employee creating or modifying Federal policy, obligating the appropriate funds of the United States Government, overseeing the work of Federal employees, providing direct personal services to any Federal employee, or otherwise violating the prohibitions set forth in Parts 7.5 and 37.1 of the Federal Acquisition Regulation (FAR). The Government will control access to the facility and will perform the inspection and acceptance of the completed work.