Amendment 0008 7179548.pdf

PDF 937 KB Posted

Attached to
Upgrade Restrooms DLA Multiple Bldgs.
Solicitation number
N400857179549
Issued by

About this file

This is Amendment #0008 to NAVFAC Specification 7179548 for Upgrade Restrooms DLA Multiple Buildings at MCAS Cherry Point, NC. The amendment provides a revised specification Section 08 71 00 Door Hardware that details requirements for locks, hinges, closers, cylinders, electric strikes, and other door hardware components.

The amendment includes detailed hardware sets for different door types, including secure interior openings, heavy duty non-rated openings, and suite/office doors. Key requirements include Best 7-pin SFIC cores with A Keyway, stainless steel finishes (BHMA 630), coordination with the Cherry Point Base Locksmith for keying, and provision of electric strikes and card readers for secure areas. The proposal due date remains January 8, 2025 at 12:00 PM local time. The amendment notes that the deadline for pre-award RFIs has passed and no further RFIs will be accepted. Contractors must acknowledge this amendment when submitting their proposals, or risk proposal rejection.

View the file

Other files

File Type Posted
Amendment 0006 7179548.pdf PDF
Amendment 0007 7179548.pdf PDF
Amendment 0005 7179548.pdf PDF
Amendment 0004 7179548.pdf PDF
Amendment 0003 7179548.pdf PDF
Amendment 0002 7179548.pdf PDF
Amendment 0001 7179548.pdf PDF
RFP 7179548.pdf PDF
7179548 DrawingsAsOne SIGNED.pdf PDF
7179548 SpecsAsOne SIGNED.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NAVFAC

SPECIFICATION

7179548 Upgrade Restrooms DLA Multiple Bldgs.

MCAS Cherry Point, NC

AMENDMENT #0008

IMPORTANT

This amendment should be acknowledged when your proposal is submitted. Failure to acknowledge the amendment may constitute grounds for rejection of the proposal.

If your proposal has been submitted prior to the receipt of this amendment, acknowledgement should be made by telegram, which should state whether the price contained in your proposal is to remain unchanged, is to be decreased by an amount, or is to be increased by an amount. The acknowledgement must be received prior to proposal opening time.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES

1 2

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

0008 01/03/2025 7179548

6. ISSUED BY Code N40085 7. ADMINISTERED BY (If other than item 6.) Code

CG MCAS Cherry Point

FACILITIES, ROICC

B-87, 748 Roosevelt Blvd.

PSC BOX 8006

CHERRY POINT, NC 28533

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF SOLICITATION

Upgrade Restrooms DLA Multiple Bldgs.

9B. DATED (SEE ITEM 11)

AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL 10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended is not extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (if required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER: (specify type of modification and authority)

E. IMPORTANT: Contractor is not is required to sign this document and return original to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

7179548 Upgrade Restrooms DLA Multiple Bldgs., Marine Corps Air Station Cherry Point, NC

Amendment 0008 is being issued to answer pre-award RFI’s.

The deadline to submit pre-award RFI’s has passed. No further RFI’s will be accepted.

The proposal due date of 08 January 2025 at 12:00 PM local time REMAINS unchanged.

See Attached.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR (Same as Item 8) 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED

BY

(Signature of person authorized to sign) (Signature of Contracting Officer)

NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV.1-83) 0224-3(10-90)

PREVIOUS EDITION UNUSABLE Prescribed by GSA

Amendment 0008 7179548 Upgrade Restrooms DLA Multiple Bldgs.

RFI Responses:

1. Could the government please provide the details for the hardware sets that are indicated on the door schedule that are to appear in 08710? There are no Specifications available for hardware.

Response:

See revised specification 08 71 00 for hardware sets. Submit proposals in accordance with RFP, Specifications, Drawings and all amendments.

Subj: AMENDMENT TO WO 7179548, Upgrade Restrooms DLA Dist Multiple Buildings, MCAS CHERRY POINT NC

CONTINUATION SHEET

PROJECT TABLE OF CONTENTS

SECTION 08 71 00 DOOR HARDWARE is deleted and 08 71 00 DOOR HARDWARE, dated 6 DEC 2024, as shown in the footer, is added to the Project Table of Contents and accompanies this Amendment.

Upgrade Restrooms, DLA Distribution, Multiple Buildings WO# 7179548 MCAS Cherry Point, NC

SECTION 08 71 00

DOOR HARDWARE

02/16, CHG 4: 02/22

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

ANSI/BHMA A156.1 (2021) Butts and Hinges

ANSI/BHMA A156.2 (2017) Bored and Preassembled Locks and Latches

ANSI/BHMA A156.3 (2020) Exit Devices

ANSI/BHMA A156.4 (2013) Door Controls - Closers

ANSI/BHMA A156.6 (2021) Architectural Door Trim

ANSI/BHMA A156.7 (2016) Template Hinge Dimensions

ANSI/BHMA A156.13 (2017) Mortise Locks & Latches Series 1000

ANSI/BHMA A156.16 (2018) Auxiliary Hardware

ANSI/BHMA A156.18 (2020) Materials and Finishes

ANSI/BHMA A156.25 (2013) Electrified Locking Devices

ANSI/BHMA A156.31 (2013) Electric Strikes and Frame Mounted Actuators

ANSI/BHMA A156.36 (2010) Auxiliary Locks

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2023) National Electrical Code

STEEL DOOR INSTITUTE (SDI/DOOR)

SDI/DOOR A250.8 (2017) Specifications for Standard Steel Doors and Frames

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

SECTION 08 71 00 Page 1

REVISED 06 DEC 2024

1.2 SUBMITTALS

Government approval is required for submittals. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Manufacturer's Detail Drawings

Verification of Existing Conditions

Hardware Schedule

Keying System

SD-03 Product Data

Hardware Items

SD-08 Manufacturer's Instructions

Installation

SD-10 Operation and Maintenance Data

Hardware Schedule Items, Data Package 1

SD-11 Closeout Submittals

Key Bitting

1.3 SHOP DRAWINGS

Submit manufacturer's detail drawings indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware. Base shop drawings on verified field measurements and include verification of existing conditions.

1.4 PRODUCT DATA

Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.

1.5 HARDWARE SCHEDULE

Provide Hardware Item List and Hardware Schedule containing the following information, and additional information as needed to identify the complete make up of each hardware set and its application to each opening:

1.5.1 Hardware Item List:

a. Hardware Type

b. Item Number

c. Quantity

SECTION 08 71 00 Page 2

d. Size(s)

e. Reference Publication / Type Number

f. Manufacturer's Name / Catalog Number

g. Key Control Symbols

h. UL Mark (If fire rated and listed)

i. BHMA Finish(es)

j. Remarks

1.5.2 Hardware Schedule

a. Hardware Set Number

b. Opening Number(s)

c. Opening Description (single/double leaf, hand, size, door/frame material)

d. Fire Rating

e. Sound Rating

f. Hardware Items

g. Quantity

h. Size

i. BHMA Finish

j. Remarks

In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.

1.6 KEY BITTING CHART REQUIREMENTS

1.6.1 Requirements

Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:

a. Complete listing of all keys (e.g. AA1 and AA2).

b. Complete listing of all key cuts (AA1-123456, AA2-123458).

c. Tabulation showing which key fits which door.

d. Copy of floor plan showing doors and door numbers.

e. Listing of 20 percent more key cuts than are presently required in each master system.

SECTION 08 71 00 Page 3

1.7 QUALITY ASSURANCE

1.7.1 Hardware Manufacturers and Modifications

Provide, as far as feasible, locks, hinges and closers of one lock, hinge or closer manufacturer's make. Modify hardware as necessary to provide features indicated or specified.

1.7.2 Key Shop Drawings Coordination Meeting

Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith must meet to discuss and coordinate key requirements for the facility.

Coordinate with the Cherry Point Base Locksmith to resolve keying, procurement, shipping and installation procedures. Confirm hardware set components and functions. Provide SFIC Series 7 pin, A Keyway as manufactured by Best, www.bestaccess.com.

1.8 DELIVERY, STORAGE, AND HANDLING

Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule.

Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail.

PART 2 PRODUCTS

2.1 TEMPLATE HARDWARE

Hardware applied to doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.

2.2 HARDWARE ITEMS

Clearly and permanently mark with the manufacturer's name or trademark, hinges, locks, latches, exit devices and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover.

2.2.1 Hinges

Provide in accordance with ANSI/BHMA A156.1 . Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel for doors where indicated so that pins are non-removable when door is closed. Other anti-friction bearing hinges may be provided in lieu of ball bearing hinges.

2.2.2 Locks and Latches

b. In non-air-conditioned interior environments or humid interior environments, provide interior locksets on the same Marine Grade I, fully non-ferrous as exterior locksets.

SECTION 08 71 00 Page 4

2.2.2.1 Bored Locks and Latches

Provide in accordance with ANSI/BHMA A156.2 , Series 4000, Grade 1.

2.2.2.2 Auxiliary Locks

Provide in accordance with ANSI/BHMA A156.36 , Grade 1.

2.2.3 Exit Devices

Provide in accordance with ANSI/BHMA A156.3 , Grade 1. Provide adjustable strikes for rim type and vertical rod devices. Provide open back strikes for pairs of doors with mortise and vertical rod devices.

Use stainless steel finishes. Also include stainless steel fasteners and screws.

2.2.4 Cylinders and Cores

Provide cylinders and cores for new locks, including locks provided under other sections of this specification. Provide cylinders and cores with seven pin tumblers. Provide cylinders from the products of one manufacturer, and provide cores from the products of one manufacturer.

Rim cylinders, mortise cylinders, and levers of bored locksets have interchangeable cores which are removable by special control keys. Stamp each interchangeable core with a key control symbol in a concealed place on the core.

2.2.5 Electrified Hardware

Comply with the requirements of NFPA 70 for wiring of electrified hardware.

2.2.5.1 Electric Strikes and Frame Mounted Actuators

Provide in accordance with ANSI/BHMA A156.31 , Grade 1. Provide electric strikes and actuators as required to meet operational requirements.

Provide electric strikes that remain secure during power failure. Provide a separate power supply for electric strikes, other locking devices and ancillary parts. Provide strikes and actuators with a minimum opening force of 2300 pounds.

Provide facility interface devices that use direct current (dc) power to energize the solenoids. Provide electric strikes and actuators that incorporate end-of-line resistors to facilitate line supervision by the system. If not incorporated into the electric strike or local controller, provide metal oxide resistors (MOVs) to protect the controller from reverse current surges.

2.2.5.1.1 Solenoid

Provide actuating solenoid for strikes and actuators that are rated for continuous duty, cannot dissipate more than 12 Watts and must operate on 12 or 24 Volts dc. Inrush current cannot exceed 1 ampere and the holding current cannot be greater than 500 milliamperes. Actuating solenoid must move from fully secure to fully open positions in less than 500 milliseconds.

SECTION 08 71 00 Page 5

2.2.5.1.2 Signal Switches

Provide strikes and actuators with signal switches to indicate to the system when the bolt is not engaged or the strike mechanism is unlocked.

Signal switches must report a forced entry to the system.

2.2.5.1.3 Coordination

Provide electric strikes and actuators of a size, weight and profile compatible with each specified door frame. Field verify installation clearances prior to procurement.

2.2.5.1.4 Mounting Method

Provide electric strikes and actuators suitable for use with single and double doors, with mortise or rim type hardware specified, and for right or left hand mounting as specified. In double door installations, locate the lock in the active leaf and monitor the fixed leaf.

2.2.5.2 Electrified Exit Devices

Provide in accordance with ANSI/BHMA A156.25 , Grade 1. Provide electrified exit devices that remain secure during power failure. Provide facility interface devices that use dc power to energize solenoids.

Provide solenoids, resisters, and signal switches in accordance with paragraph ELECTRIC STRIKES AND FRAME MOUNTED ACTUATORS.

2.2.5.2.1 Power Transfer Hinges

Provide power transfer hinges with each electrified lock that route power and monitoring signals from the exit device to the door frame. Coordinate power transfer hinges with door frames.

2.2.5.3 Card Readers and Keypad Access Control Hardware

GFGI.

2.2.6 Keying System

Provide an extension of the existing keying system. Existing locks were manufactured by Best, www.bestaccess.com and have interchangeable cores.

Provide construction interchangeable cores.

2.2.7 Lock Trim

Provide cast, forged, or heavy wrought construction and commercial plain design for lock trim.

2.2.7.1 Lever Handles

Provide lever handles. Provide in accordance with ANSI/BHMA A156.2 for bored locks and lever handles for exit devices. Provide lever handle locks with a breakaway feature (such as a weakened spindle or a shear key) to prevent irreparable damage to the lock when force in excess of that specified in ANSI/BHMA A156.13 is applied to the lever handle. Provide lever handles return to within 1/2 inch of the door face.

SECTION 08 71 00 Page 6

2.2.8 Keys

Furnish one file key, one duplicate key, and one working key for each key change. Furnish one additional working key for each lock of each keyed-alike group. Furnish a quantity of key blanks equal to 20 percent of the total number of file keys. Stamp each key with appropriate key control symbol and "U.S. property - do not duplicate." Do not place room number on keys.

2.2.9 Closers

Provide in accordance with ANSI/BHMA A156.4 , Series C02000, Grade 1, with PT 4C. Provide with brackets, arms, mounting devices, fasteners, full metal covers. Size closers in accordance with manufacturer's printed recommendations, or provide multi-size closers, Sizes 1 through 6, and list sizes in the Hardware Schedule. Provide manufacturer's 10 year warranty.

On interior doors use closers of 302 or 304 stainless steel or non-ferrous materials. On surface-mounted closers use or apply rust inhibiting finish on all ferrous parts. Also apply this finish on concealed closers.

2.2.9.1 Identification Marking

Engrave each closer with manufacturer's name or trademark, date of manufacture, and manufacturer's size designation in locations that will be visible after installation.

2.2.10 Door Protection Plates

Provide in accordance with ANSI/BHMA A156.6 .

2.2.10.1 Sizes of Mop and Kick Plates

2 inch less than door width for single doors; 1 inch less than door width for pairs of doors. Provide 8 inch kick plates for flush doors. Provide 4 inch mop plates.

2.2.11 Door Stops and Silencers

Provide in accordance with ANSI/BHMA A156.16 . Silencers Type L03011.

Provide three silencers for each single door, two for each pair.

2.2.12 Auxiliary Hardware (Other than locks)

Provide in accordance with ANSI/BHMA A156.16 , Grade 1.

2.2.13 Special Tools

Provide special tools, such as spanner and socket wrenches and dogging keys, as required to service and adjust hardware items.

2.3 FASTENERS

Provide fasteners of type, quality, size, and quantity appropriate to the specific application. Fastener finish to match hardware. Provide stainless steel or nonferrous metal fasteners in locations exposed to weather. Verify metals in contact with one another are compatible and will avoid galvanic corrosion when exposed to weather.

SECTION 08 71 00 Page 7

2.4 FINISHES

Provide in accordance with ANSI/BHMA A156.18 . Provide hardware in BHMA 630 finish (satin stainless steel), unless specified otherwise. Provide items not manufactured in stainless steel in BHMA 626 finish (satin chromium plated) over brass or bronze. Provide hinges in stainless steel with BHMA 630 finish. Furnish exit devices in BHMA 630 finish. Match exposed parts of concealed closers to lock and door trim. Match hardware finish for aluminum doors to the doors.

PART 3 EXECUTION

3.1 INSTALLATION

Provide hardware in accordance with manufacturers' printed installation instructions. Fasten hardware to wood surfaces with full-threaded wood screws or sheet metal screws. Provide machine screws set in expansion shields for fastening hardware to solid concrete and masonry surfaces.

Provide toggle bolts where required for fastening to hollow core construction. Provide through bolts where necessary for satisfactory installation.

3.2 HARDWARE LOCATIONS

Provide in accordance with SDI/DOOR A250.8 , unless indicated or specified otherwise.

a. Kick Plates: Push side of single-acting doors. Both sides of double-acting doors.

b. Mop Plates: Bottom flush with bottom of door.

3.3 FIELD QUALITY CONTROL

After installation, protect hardware from paint, stains, blemishes, and other damage until acceptance of work. Submit notice of testing 15 days before scheduled, so that testing can be witnessed by the Contracting Officer. Adjust hinges, locks, latches, bolts, holders, closers, and other items to operate properly. Demonstrate that permanent keys operate respective locks, and give keys to the Contracting Officer. Correct, repair, and finish, errors in cutting and fitting and damage to adjoining work.

3.4 HARDWARE SETS

SECTION 08 71 00 Page 8

Secure Interior Openings

Door No: 159-A1 HWS-1 Secure AC Suite w/ Remove Mullion 1 each Removable Steel Mullion, Type 22 600 Best 1 each Mortise Cylinder Housing, F25, E09251 630 Best 1 each 7 Pin SFIC, F24, E09241 630 4 each BB 4.5 x 4.5 Butt Hinge, NRP, A8111 626 2 each BB ETW 4.5 x 4.5 Butt NRP, A8112 626 2 each FMC Closer, C02231 with 630 spring stop, stop mounted slide track arm push side mount 2 each Exit Device with Pull, EDF03 630 Type 5, B x No. B x MLR Entry by ID card Entry by keyed trim under power loss Best 2 each Rim Cylinder Housing, F26 630 Best 2 each 7 Pin SFIC, F24, E09241 630 2 each Silencer, L03011 Grey 2 each Wall Stop, L02251 or 626 Floor Stop, L02161 GFGI 1 each Power Supply 2 each Balanced Magnetic Switch Black GFGI 2 each Card Reader, Wall Mounted

Note: Furnish electric metallic tubing raceway, cabling and a blank stainless steel coverplate to receive Government furnished and installed devices

Note: Coordinate with the Government to support GFGI programming

Door No. 159-A2, 159-A3 HWS-2 Secure AC Suite, Office 3 each BB 4.5 x 4.5 Butt Hinge, NRP, A8111 626 1 each FMC Closer, C02021 630 1 each Lever Storeroom, F86 630 Best 1 each 7 Pin SFIC, F24, E09241 630 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161 GFGI 1 each Power Supply 1 each Balanced Magnetic Switch Black 1 each Electric Strike 630 2 each Card Reader, Wall Mounted Black

Note: Furnish electric metallic tubing raceway, cabling and a blank stainless steel coverplate to receive Government furnished and installed devices

Note: Coordinate with the Government to support GFGI programming

Heavy Duty Non Rated Openings

Door No: 145-A1, 146-A1, 147-A1, 147-B1, 147-D1, 147-E1, 147-H1, 147-J1, 147-K1, 148-A1, 148-B1, 150-A1, 150-B1, 150-D1, 150-E1, 159-F1, 159-G1, 159-K1, 159-L1, 4246-A1 HWS-3 Gang Head 3 each BB 4.5 x 4.5 Butt Hinge, A5111 630

SECTION 08 71 00 Page 9

1 each FMC Closer, C02021 630 1 each Strike Filler Plate 600 1 each 4 x 16 Beveled Push Plate, J301 630 1 each 4 x 16 Beveled Pull Plate, J405 630 1 each 8 x 34 Beveled Kick Plate, J102 630 1 each 4 x 34 Beveled Mop Plate, J103 630 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161

Door No: 147-F1, 159-E1, 159-H1, 159-J1 HWS-4 Head, Shower 3 each BB 4.5 x 4.5 Butt Hinge, A5111 630 1 each FMC Closer, C02021 630 1 each Lever Privacy, F76 630 No Cylinder 1 each 8 x 34 Beveled Kick Plate, J102 630 1 each 4 x 34 Beveled Mop Plate, J103 630 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161

Door No: 147-C1, 150-C1 HWS-5 3070 HMF x WD Janitor 3 each BB 4.5 x 4.5 Butt Hinge, A5111 630 1 each FMC Closer, C02021 630 1 each Lever Storeroom, F86 630 Best 1 each 7 Pin SFIC, F24, E09241 630 1 each 8 x 34 Beveled Kick Plate, J102 630 1 each 4 x 34 Beveled Mop Plate, J103 630 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161 1 each Lever Door Holder, L01381 626 Note: Trim is to have an abrasive texture to indicate a potentially hazardous environment to the blind

Door No. 147-G1 HWS-6 3070 HMF x WD Lactation 3 each BB 4.5 x 4.5 Butt Hinge, A8111 626 1 each FMC Closer, C02021 630 1 each Lever Privacy, F76 630 No Cylinder 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161

Door No: 159-B1, 159-C1, 159-D1 HWS-7 Suite, Office 3 each BB 4.5 x 4.5 Butt Hinge, A8111 626 1 each Lever Entry, F82A 630 Best 1 each 7 Pin SFIC, F24, E09241 630 3 each Silencer, L03011 Grey 1 each Wall Stop, L02251 or 626 Floor Stop, L02161

-- End of Section --

SECTION 08 71 00 Page 10

21 13 13.pdf
21 13 13 - WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 Hydraulic Design
1.2.1.1 Basis for Design
1.2.2 Sprinkler Coverage
1.2.3 Qualified Fire Protection Engineer QFPE
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Preconstruction Submittals
1.4.1.1 Shop Drawing
1.4.1.2 Product Data
1.4.1.3 Operating and Maintenance O&M Instructions
1.4.2 Qualifications
1.4.2.1 Sprinkler System Designer
1.4.2.2 Sprinkler System Installer

1.4.3 Regulatory Requirements

1.5 DELIVERY, STORAGE, AND HANDLING
1.6 EXTRA MATERIALS
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.1.1 Standard Products
2.1.2 Nameplates
2.1.3 Identification and Marking
2.1.4 Pressure Ratings
2.2 ABOVEGROUND PIPING COMPONENTS
2.2.1 Steel Piping Components
2.2.1.1 Steel Pipe
2.2.1.2 Fittings
2.2.1.3 Grooved Mechanical Joints and Fittings
2.2.1.4 Flanges
2.2.2 Flexible Sprinkler Hose
2.2.3 Pipe Hangers and Supports
2.2.4 Valves
2.3 SPRINKLERS
2.3.1 Pendent Sprinkler
2.3.2 Upright Sprinkler
2.3.3 Corrosion-Resistant Sprinkler
2.4 ACCESSORIES
2.4.1 Sprinkler Cabinet
2.4.2 Pendent Sprinkler Escutcheon
2.4.3 Identification Sign
PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
3.2 INSTALLATION
3.2.1 Waste Removal
3.3 ABOVEGROUND PIPING INSTALLATION
3.3.1 Protection of Piping Against Earthquake Damage
3.3.2 Piping in Exposed Areas
3.3.3 Piping in Finished Areas
3.3.4 Pendent Sprinklers
3.3.5 Upright Sprinklers
3.3.6 Pipe Joints
3.3.7 Reducers
3.3.8 Pipe Penetrations
3.3.9 Escutcheons
3.3.10 Inspector's Test Connection
3.3.11 Drains
3.3.12 Identification Signs
3.4 PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Test Procedures
3.5.2 Pre-Government Testing
3.5.2.1 Verification of Compliant Installation
3.5.2.2 Request for Government Final Test
3.5.3 Correction of Deficiencies
3.5.4 Government Final Tests
3.6 MINIMUM SYSTEM TESTS
3.6.1 Aboveground Piping
3.6.1.1 Hydrostatic Test

3.7 SYSTEM ACCEPTANCE

22 00 00.pdf
22 00 00 - PLUMBING, GENERAL PURPOSE
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 STANDARD PRODUCTS
1.3.1 Alternative Qualifications
1.3.2 Service Support
1.3.3 Manufacturer's Nameplate
1.3.4 Modification of References
1.3.4.1 Definitions
1.3.4.2 Administrative Interpretations
1.4 DELIVERY, STORAGE, AND HANDLING
1.5 PERFORMANCE REQUIREMENTS
1.6 REGULATORY REQUIREMENTS
1.7 PROJECT/SITE CONDITIONS
1.8 INSTRUCTION TO GOVERNMENT PERSONNEL
1.9 ACCESSIBILITY OF EQUIPMENT
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Pipe Joint Materials
2.1.2 Miscellaneous Materials
2.1.3 Pipe Insulation Material
2.2 PIPE HANGERS, INSERTS, AND SUPPORTS
2.3 VALVES
2.3.1 Relief Valves
2.3.2 Thermostatic Mixing Valves
2.4 FIXTURES
2.4.1 Lavatories
2.4.2 Automatic Controls
2.4.3 Flush Valve Water Closets
2.4.4 Flush Valve Urinals
2.4.5 Wheelchair Flush Valve Type Urinals
2.4.6 Wall Hung Lavatories
2.4.7 Countertop Lavatories
2.4.8 Kitchen Sinks
2.4.9 Service Sinks
2.4.10 Drinking-Water Coolers
2.4.11 Wheelchair Drinking Water cooler
2.4.12 Precast Terrazzo Shower Floors
2.4.13 Emergency Eye and Face Wash
2.5 BACKFLOW PREVENTERS
2.6 DRAINS
2.6.1 Floor and Shower Drains
2.6.1.1 Metallic Shower Pan Drains
2.6.1.2 Drains and Backwater Valves
2.6.2 Bathtub and Shower Faucets and Drain Fittings
2.6.3 Area Drains
2.7 SHOWER PAN
2.7.1 Nonplasticized Polyvinyl Chloride PVC Shower Pan Material
2.8 TRAPS
2.9 WATER HEATERS
2.9.1 Automatic Storage Type
2.9.1.1 Electric Type

2.9.2 Electric Instantaneous Water Heaters Tankless

2.10 ELECTRICAL WORK
2.11 MISCELLANEOUS PIPING ITEMS
2.11.1 Escutcheon Plates
2.11.2 Pipe Sleeves
2.11.2.1 Sleeves in Masonry and Concrete
2.11.2.2 Sleeves Not in Masonry and Concrete
2.11.3 Pipe Hangers Supports
2.11.4 Nameplates
2.11.5 Labels
PART 3 EXECUTION
3.1 GENERAL INSTALLATION REQUIREMENTS
3.1.1 Water Pipe, Fittings, and Connections
3.1.1.1 Utilities
3.1.1.2 Cutting and Repairing
3.1.1.3 Protection of Fixtures, Materials, and Equipment
3.1.1.4 Mains, Branches, and Runouts
3.1.1.5 Pipe Drains
3.1.1.6 Expansion and Contraction of Piping
3.1.1.7 Thrust Restraint
3.1.1.8 Commercial-Type Water Hammer Arresters
3.1.2 Compressed Air Piping Non-Oil Free
3.1.3 Joints
3.1.3.1 Threaded
3.1.3.2 Mechanical Couplings
3.1.3.3 Unions and Flanges
3.1.3.4 Grooved Mechanical Joints
3.1.3.5 Cast Iron Soil, Waste and Vent Pipe
3.1.3.6 Copper Tube and Pipe
3.1.3.7 Plastic Pipe
3.1.3.8 Glass Pipe
3.1.3.9 Corrosive Waste Plastic Pipe
3.1.3.10 Polypropylene Pipe
3.1.3.11 Other Joint Methods
3.1.4 Dissimilar Pipe Materials
3.1.5 Pipe Sleeves and Flashing
3.1.5.1 Sleeve Requirements
3.1.5.2 Flashing Requirements
3.1.5.3 Waterproofing
3.1.5.4 Optional Counterflashing
3.1.5.5 Pipe Penetrations of Slab on Grade Floors
3.1.5.6 Pipe Penetrations
3.1.6 Fire Seal
3.1.7 Supports
3.1.7.1 General
3.1.7.2 Pipe Hangers, Inserts, and Supports
3.1.7.3 Structural Attachments

3.1.8 Pipe Cleanouts

3.2 WATER HEATERS AND HOT WATER STORAGE TANKS
3.2.1 Relief Valves
3.2.2 Heat Traps
3.2.3 Connections to Water Heaters
3.2.4 Expansion Tank
3.3 FIXTURES AND FIXTURE TRIMMINGS
3.3.1 Fixture Connections
3.3.2 Flushometer Valves
3.3.3 Height of Fixture Rims Above Floor
3.3.4 Shower Bath Outfits
3.3.5 Fixture Supports
3.3.5.1 Support for Solid Masonry Construction
3.3.5.2 Support for Concrete-Masonry Wall Construction
3.3.5.3 Support for Steel Stud Frame Partitions
3.3.6 Backflow Prevention Devices
3.3.7 Access Panels
3.3.8 Sight Drains
3.3.9 Traps
3.3.10 Shower Pans
3.3.10.1 General
3.3.10.2 Metal Shower Pans
3.3.10.3 Plasticized Chlorinated Polyethylene Shower Pans
3.3.10.4 Nonplasticized Polyvinyl Chloride PVC Shower Pans
3.4 IDENTIFICATION SYSTEMS
3.4.1 Identification Tags
3.4.2 Pipe Color Code Marking
3.4.3 Color Coding Scheme for Locating Hidden Utility Components
3.5 ESCUTCHEONS
3.6 PAINTING
3.6.1 Painting of New Equipment
3.6.1.1 Factory Painting Systems
3.6.1.2 Shop Painting Systems for Metal Surfaces
3.7 TESTS, FLUSHING AND DISINFECTION
3.7.1 Plumbing System
3.7.1.1 Shower Pans
3.7.2 Defective Work
3.7.3 System Flushing
3.7.3.1 During Flushing
3.7.3.2 After Flushing
3.7.4 Operational Test
3.7.5 Disinfection
3.8 POSTED INSTRUCTIONS
3.9 PERFORMANCE OF WATER HEATING EQUIPMENT
3.9.1 Storage Water Heaters
3.9.1.1 Electric

3.10 TABLES

28 31 60.pdf
28 31 60 - INTERIOR FIRE ALARM SYSTEM, NON-ADDRESSABLE
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED SECTIONS
1.3 SUMMARY
1.3.1 Scope
1.3.2 Qualified Fire Protection Engineer QFPE
1.4 DEFINITIONS
1.4.1 Terminal Cabinet
1.4.2 Designated Fire Protection Engineer DFPE
1.4.3 Qualified Fire Protection Engineer QFPE
1.5 SUBMITTALS
1.6 SYSTEM OPERATION
1.6.1 Alarm Initiating Devices and Notification Appliances Visual,
1.6.2 Functions and Operating Features
1.7 EXISTING EQUIPMENT
1.8 QUALITY ASSURANCE
1.8.1 Submittal Documents
1.8.1.1 Preconstruction Submittals
1.8.1.2 Shop Drawings
1.8.1.3 Nameplates
1.8.1.4 Wiring Diagrams
1.8.1.5 System Layout
1.8.1.6 Notification Appliances
1.8.1.7 Initiating Devices
1.8.1.8 Battery Power
1.8.1.9 Voltage Drop Calculations
1.8.1.10 Product Data
1.8.1.11 Operation and Maintenance O&M Instructions
1.8.1.12 As-Built Drawings
1.8.2 Qualifications
1.8.2.1 Fire Alarm System Designer
1.8.2.2 Supervisor
1.8.2.3 Technician
1.8.2.4 Installer
1.8.2.5 Test Technician
1.8.2.6 Manufacturer

1.8.3 Regulatory Requirements

1.9 DELIVERY, STORAGE, AND HANDLING
1.10 MAINTENANCE
1.10.1 Spare Parts
1.10.2 Special Tools
PART 2 PRODUCTS
2.1 GENERAL PRODUCT REQUIREMENT
2.2 MATERIALS AND EQUIPMENT
2.2.1 Standard Products
2.2.2 Keys
2.3 NOTIFICATION APPLIANCES
2.3.1 Audible Notification Appliances
2.3.1.1 Horns

2.3.2 Visual Notification Appliances

2.4 ELECTRIC POWER
2.5 SECONDARY POWER SUPPLY
2.5.1 Batteries
2.5.1.1 Capacity
2.5.1.2 Battery Power Calculations

2.5.2 Battery Chargers

2.6 SURGE PROTECTIVE DEVICES
2.7 WIRING
2.7.1 Alarm Wiring
PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
3.2 INSTALLATION
3.2.1 Notification Appliances
3.2.2 Ceiling Bridges
3.3 SYSTEM FIELD WIRING
3.3.1 Wiring within Cabinets, Enclosures, and Boxes
3.3.2 Terminal Cabinets
3.3.3 Alarm Wiring
3.3.4 Back Boxes and Conduit
3.3.5 Conductor Terminations
3.4 PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Test Procedures
3.5.2 Pre-Government Testing
3.5.2.1 Verification of Compliant Installation
3.5.2.2 Request for Government Final Test
3.5.3 Correction of Deficiencies
3.5.4 Government Final Tests
3.6 MINIMUM SYSTEM TESTS
3.6.1 System Tests
3.6.2 Audibility Tests
3.7 SYSTEM ACCEPTANCE
3.8 EXTRA MATERIALS
3.8.1 Repair Service/Replacement Parts
3.8.2 Spare Parts
3.8.3 Document Storage Cabinet
28 31 70.pdf
28 31 70 - INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED SECTIONS
1.3 SUMMARY
1.3.1 Scope
1.3.2 Qualified Fire Protection Engineer QFPE
1.4 DEFINITIONS
1.4.1 Interface Device
1.4.2 Fire Alarm Control Unit FACU
1.4.3 Remote Fire Alarm Control Unit
1.4.4 Terminal Cabinet
1.4.5 Control Module and Relay Module
1.4.6 Designated Fire Protection Engineer DFPE
1.4.7 Qualified Fire Protection Engineer QFPE
1.5 SUBMITTALS
1.6 SYSTEM OPERATION
1.6.1 Alarm Initiating Devices and Notification Appliances Visual,
1.6.2 Functions and Operating Features
1.7 EXISTING EQUIPMENT
1.8 QUALITY ASSURANCE
1.8.1 Submittal Documents
1.8.1.1 Preconstruction Submittals
1.8.1.2 Shop Drawings
1.8.1.3 Nameplates
1.8.1.4 Wiring Diagrams
1.8.1.5 System Layout
1.8.1.6 Notification Appliances
1.8.1.7 Initiating Devices
1.8.1.8 Battery Power
1.8.1.9 Voltage Drop Calculations
1.8.1.10 Product Data
1.8.1.11 Operation and Maintenance O&M Instructions
1.8.1.12 As-Built Drawings
1.8.2 Qualifications
1.8.2.1 Fire Alarm System Designer
1.8.2.2 Supervisor
1.8.2.3 Technician
1.8.2.4 Installer
1.8.2.5 Test Technician
1.8.2.6 Manufacturer

1.8.3 Regulatory Requirements

1.9 DELIVERY, STORAGE, AND HANDLING
1.10 MAINTENANCE
1.10.1 Spare Parts
1.10.2 Special Tools
PART 2 PRODUCTS
2.1 GENERAL PRODUCT REQUIREMENT
2.2 MATERIALS AND EQUIPMENT
2.2.1 Standard Products
2.2.2 Keys
2.3 ISOLATION MODULES
2.4 NOTIFICATION APPLIANCES
2.4.1 Audible Notification Appliances
2.4.1.1 Horns

2.4.2 Visual Notification Appliances

2.5 SECONDARY POWER SUPPLY
2.5.1 Batteries
2.5.1.1 Capacity
2.5.1.2 Battery Power Calculations

2.5.2 Battery Chargers

2.6 SURGE PROTECTIVE DEVICES
2.7 WIRING
2.7.1 Alarm Wiring
PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
3.2 INSTALLATION
3.2.1 Notification Appliances
3.2.2 Ceiling Bridges
3.3 SYSTEM FIELD WIRING
3.3.1 Wiring within Cabinets, Enclosures, and Boxes
3.3.2 Terminal Cabinets
3.3.3 Alarm Wiring
3.3.4 Back Boxes and Conduit
3.3.5 Conductor Terminations
3.4 PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Test Procedures
3.5.2 Pre-Government Testing
3.5.2.1 Verification of Compliant Installation
3.5.2.2 Request for Government Final Test
3.5.3 Correction of Deficiencies
3.5.4 Government Final Tests
3.6 MINIMUM SYSTEM TESTS
3.6.1 System Tests
3.6.2 Audibility Tests
3.7 SYSTEM ACCEPTANCE
3.8 EXTRA MATERIALS
3.8.1 Repair Service/Replacement Parts
3.8.2 Spare Parts
3.8.3 Document Storage Cabinet
28 31 76.pdf
28 31 76 - INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM, ADDRESSABLE
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED SECTIONS
1.3 SUMMARY
1.3.1 Scope
1.3.2 Qualified Fire Protection Engineer QFPE
1.4 DEFINITIONS
1.4.1 Interface Device
1.4.2 Fire Alarm and Mass Notification Control Unit FMCU
1.4.3 Terminal Cabinet
1.4.4 Control Module and Relay Module
1.4.5 Designated Fire Protection Engineer DFPE
1.4.6 Qualified Fire Protection Engineer QFPE
1.5 SUBMITTALS
1.6 SYSTEM OPERATION
1.6.1 Alarm Initiating Devices and Notification Appliances Visual, Voice,
1.6.2 Functions and Operating Features
1.7 EXISTING EQUIPMENT
1.8 QUALITY ASSURANCE
1.8.1 Submittal Documents
1.8.1.1 Preconstruction Submittals
1.8.1.2 Shop Drawings
1.8.1.3 Nameplates
1.8.1.4 Wiring Diagrams
1.8.1.5 System Layout
1.8.1.6 Notification Appliances
1.8.1.7 Initiating Devices
1.8.1.8 Amplifiers
1.8.1.9 Battery Power
1.8.1.10 Voltage Drop Calculations
1.8.1.11 Product Data
1.8.1.12 Operation and Maintenance O&M Instructions
1.8.1.13 As-Built Drawings
1.8.2 Qualifications
1.8.2.1 Fire Alarm System Designer
1.8.2.2 Supervisor
1.8.2.3 Technician
1.8.2.4 Installer
1.8.2.5 Test Technician
1.8.2.6 Manufacturer

1.8.3 Regulatory Requirements

1.9 DELIVERY, STORAGE, AND HANDLING
1.10 MAINTENANCE
1.10.1 Spare Parts
1.10.2 Special Tools
PART 2 PRODUCTS
2.1 GENERAL PRODUCT REQUIREMENT
2.2 MATERIALS AND EQUIPMENT
2.2.1 Standard Products
2.2.2 Keys
2.3 ISOLATION MODULES
2.4 NOTIFICATION APPLIANCES
2.4.1 Audible Notification Appliances
2.4.1.1 Speakers

2.4.2 Visual Notification Appliances

2.5 SECONDARY POWER SUPPLY
2.5.1 Batteries
2.5.1.1 Capacity
2.5.1.2 Battery Power Calculations

2.5.2 Battery Chargers

2.6 SURGE PROTECTIVE DEVICES
2.7 WIRING
2.7.1 Alarm Wiring

2.8 ENVIRONMENTAL ENCLOSURES OR GUARDS

PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
3.2 INSTALLATION
3.2.1 Notification Appliances
3.2.2 Ceiling Bridges
3.3 SYSTEM FIELD WIRING
3.3.1 Wiring within Cabinets, Enclosures, and Boxes
3.3.2 Terminal Cabinets
3.3.3 Alarm Wiring
3.3.4 Back Boxes and Conduit
3.3.5 Conductor Terminations
3.4 PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Test Procedures
3.5.2 Pre-Government Testing
3.5.2.1 Verification of Compliant Installation
3.5.2.2 Request for Government Final Test
3.5.3 Correction of Deficiencies
3.5.4 Government Final Tests
3.6 MINIMUM SYSTEM TESTS
3.6.1 System Tests
3.6.2 Audibility Tests
3.6.3 Intelligibility Tests
3.7 SYSTEM ACCEPTANCE
3.8 EXTRA MATERIALS
3.8.1 Repair Service/Replacement Parts
3.8.2 Spare Parts
3.8.3 Document Storage Cabinet
12882182.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-413
12882181.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-412
12882180.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-411
12882179.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-410
12882178.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-409
12882177.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-408
12882176.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-407
12882175.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-406
12882174.pdf
Sheets and Views
2204 A-405 THRU A-413 ELEVS-A-405
12882157.pdf
Sheets and Views
2204 A-101 THRU A-111-A-103
12882155.pdf
Sheets and Views
2204 A-101 THRU A-111-A-101
12882216.pdf
Sheets and Views
P-701
12882213.pdf
Sheets and Views
P-501
12882209.pdf
Sheets and Views
P-110
12882187.pdf
Sheets and Views
F-001

File details come from the government source that posted it. Updated .