This document is a technical drawing specification for G&W Electric Company's 3-phase junction bar cabinets, specifically two models: the PME-3-JB56666615P (5-position) and PME-3-JB666666615P (6-position). Both cabinets are pad-mounted enclosures constructed of 304 stainless steel with a padmount green finish (Munsell 7GY3.29/1.5) and designed in accordance with IEEE C37.62, C37.74, and C37.75 standards.
The cabinets feature identical electrical specifications: 15.5 kV maximum design voltage, 95 kV impulse level (BIL), 600 A continuous current (RMS symmetric), 34 kV AC 1-minute withstand (dry), and 53 kV DC 15-minute withstand. All five or six bushing positions accommodate 15.5 kV 600A deadbreak apparatus bushings per IEEE 386 Interface 11. The 5-position model weighs approximately 500 lbs in-service and 700 lbs when shipping; the 6-position model weighs approximately 550 lbs and 800 lbs respectively. Both cabinets include hinged flip-top lids with stainless steel hinges, two lifting provisions, parking stands for each bushing, grounding provisions with 1/2"-13 threaded connections, and cable training compartments with 24-inch depth. Each enclosure ships with four securing brackets for mounting to concrete pads and must be secured using user-supplied 0.625" diameter hardware. The 6-position model includes an additional ground bus bar with 18 holes and a 304/304L stainless steel mounting frame.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Th is d ra wi ng a nd t he i nf or ma ti on t he re on a re a nd r em ai n th e pr op er ty o f G &W a nd a re n ot t o be c op ie d, r ep ro du ce d or d ic lo se d to o th er s wi th ou t th e ex pr es se d wr it te n co ns en t of G
&W
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
TYP.
7.00 178[ ]
24.00 610[ ]
CABLE
COMPARTMENT
DEPTH
24.00 610[ ]
TYP.
1.69 43[ ]
TYP.
4.00 102[ ]
TYP.
18.13 461[ ]
34.00 864[ ]
TYP.
3.63 92[ ]
TYP.
1.63 41[ ]
3.00 76[ ]
MAXIMUM LID
TRAVEL
48.75 1238[ ]
COG
30.62
778[ ] COG
25.95 659[ ]
COG
23.64 600[ ]
61.89 1572[ ]
6.03 153[ ]
TYP.
4.00 102[ ]
55.89 1420[ ]
ENCLOSURE
MOUNTING
57.57 1462[ ]
1.53 39[ ]
TYP
2.19 56[ ]
4.00 102[ ]
21.75 552[ ]
4.53 115[ ]
38.40 975[ ]
12.00 305[ ]
ADJUSTABLE
ENCLOSURE
MOUNTING
UP TO
28.00 711[ ]
35.00 889[ ]
70.54 1792[ ]
MAXIMUM LID
TRAVEL
70.65 1794[ ]
TYP.
1.25 32[ ]
ELECTRICAL INFORMATION
SEE NOTES FOR LIMITATIONS
MAXIMUM DESIGN VOLTAGE 15.5 KV
IMPULSE LEVEL (BIL) 95 KV
CONTINUOUS CURRENT, RMS SYM 600 A
AC 1 MINUTE WITHSTAND (DRY) 34 KV
DC 15 MINUTE WITHSTAND 53 KV
IN SERVICE WEIGHT APPROX. 500 LBS/227 KG
SHIPPING WEIGHT APPROX. 700 LBS/318 KG
POSITION BUSHING ELECTRICAL CHARACTERISTICS IEEE 386 INTERFACE
1 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
2 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
3 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
4 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
5 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
D
H S
D W G
N O
D
M O D E L
M C
E R R O R S
D R A W I N G
M C
E R R O R S
D
M O D E L
L A S T
C H E C K E D
T h u
J u l
G M T
C U S T O M E R
D R A W I N G
L A S T
C H E C K E D
T h u
J u l
G M T
S T A N D A R D
S H E E T o f
1 of 1SHEET:SCALE:Dec-09-25DATE:CLNAPPR BY:
REV
OR
DRAWING NO.
D9904 0004 HS0Dec-09-25DATE:AC ACENG/DES:
PME-3-JB56666615PCAT. NO.:
3 PHASE, 5 POSITION JUNCTION BAR CABINET
PME-3-JB56666615P
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
FINAL REVIEW
CLNAC
WY
REVISIONS
REV. EC0 ENG DES DATE
SEE ENCLOSURE
MOUNTING
DETAIL "A"
NOTES:
1. 304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL 7GY3.29/1.5.
ENCLOSURE DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH IEEE C37.62, C37.74, AND C37.75 (AS APPLICABLE). DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS
ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
2. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO
THE JUNCTION BAR, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF
THE LOWEST RATED COMPONENT OF THE ASSEMBLY.
3. MOUNTING INFORMATION: THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE
PAD. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT
ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED
ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING
DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD
MOUNT ENCLOSURE TO THE PAD.
PLAN VIEW
ENCLOSURE
MOUNTING
(4 PLACES)
FRONT VIEW
SECTION A-A
= APPROXIMATE CENTER OF GRAVITY
(2) LIFTING PROVISIONS
PARKING STAND
(ONE PER BUSHING)
GROUNDING PROVISION
WITH 1/2"-13 THREAD
FOR J-BAR CABINET
GROUND NUT
WITH 1/2"-13 THREAD
(ONE PER PHASE)
NAMEPLATE AND
5-LINE DIAGRAM
LID HANDLE
(BOTH SIDES)
REMOVABLE LIFTING
PROVISION WITH
1.38 DIA HOLE
(2 PLACES)
"A" PHASE
JUNCTION BAR
"B" PHASE
JUNCTION BAR
"C" PHASE
JUNCTION BAR
DEADBREAK
APPARATUS BUSHING
(ALL POSITION
ON ALL PHASES)
CABLE
TRAINING
OUTLINE
LID IS EQUIPPED WITH
STAINLESS STEEL
HINGES FOR OPENING
HINGED LID EQUIPPED
WITH PENTA HEAD BOLT
AND PROVISION FOR PADLOCK
FLIP TOP LID
LID SWING OUTLINE
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
CONCRETE
PAD
.19" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G &W
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
2.19
56MM
TYP.
M M
M I N
ENCLOSURE
ENCLOSURE
MOUNTING
DETAIL "A"
Printed on 2026.03.06 at 9:16 AM.
Th is d ra wi ng a nd t he i nf or ma ti on t he re on a re a nd r em ai n th e pr op er ty o f G &W a nd a re n ot t o be c op ie d, r ep ro du ce d or d ic lo se d to o th er s wi th ou t th e ex pr es se d wr it te n co ns en t of G
&W
G&W ELECTRIC Co.
* ALL PRIMARY DIMENSIONS ARE IN INCHES.
ALL SECONDARY DIMENSIONS ARE IN MILLIMETERS.
34.00 864[ ]
TYP.
3.63 92[ ]
24.00 610[ ]
CABLE
COMPARTMENT
DEPTH
24.13 613[ ]
TYP.
1.69 43[ ]
72.73 1847[ ]
TYP.
7.00 178[ ]
TYP.
1.63 41[ ]
5.98 152[ ]
TYP.
21.76 553[ ]
TYP.
4.00 102[ ]
TYP.
4.00 102[ ]
3.00 76[ ]
66.73 1695[ ]
ENCLOSURE
MOUNTING
68.36 1736[ ]
1.48 38[ ]
TYP
2.19 56[ ]
4.00 102[ ]
21.75 552[ ]
ADJUSTABLE
ENCLOSURE
MOUNTING
UP TO
28.00 711[ ]
35.00 889[ ]
TYP.
1.25 32[ ]
4.57 116[ ]
40.02 1017[ ]
12.00 305[ ]
73.54 1868[ ]
MAXIMUM LID
TRAVEL
49.78 1264[ ]
MAXIMUM LID
TRAVEL
73.60 1869[ ]
ELECTRICAL INFORMATION
SEE NOTES FOR LIMITATIONS
RATED VOLTAGE (MAXIMUM) 15.5 KV
IMPULSE LEVEL (BIL) 95 KV
CONTINUOUS CURRENT, RMS SYM 600 A
AC 1 MINUTE WITHSTAND (DRY) 34 KV
DC 15 MINUTE WITHSTAND 53 KV
IN SERVICE WEIGHT APPROX. 550 LBS/250 KG
SHIPPING WEIGHT APPROX. 800 LBS/363 KG
POSITION BUSHING ELECTRICAL CHARACTERISTICS IEEE 386 INTERFACE
1 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
2 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
3 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
4 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
5 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
6 15.5KV 600A DEADBREAK APPARATUS BUSHING INTERFACE 11
D
G A
D W G
N O
D
M O D E L
M C
E R R O R S
D R A W I N G
M C
E R R O R S
D
M O D E L
L A S T
C H E C K E D
S u n
J u n
G M T
C U S T O M E R
D R A W I N G
L A S T
C H E C K E D
M o n
J u n
G M T
S T A N D A R D
S H E E T o f
1 of 1SHEET:SCALE:Apr-26-23DATE:SHAPPR BY:
REV
DRAWING NO.
D9904 0004 GA0Apr-26-23DATE:AC ACENG/DES:
PME-3-JB666666615PCAT. NO.:
3 PHASE, 6 POSITION JUNCTION BAR CABINET
PME-3-JB666666615P
ALL DRAWING CHANGES MUST BE MADE ON CAD. ANY MANUAL CHANGES WILL VOID DRAWING.
FINAL REVIEW
SHAC
CLN
REVISIONS
REV. EC0 ENG DES DATE
SEE ENCLOSURE
MOUNTING
DETAIL "A"
NOTES:
1. 304 STAINLESS STEEL ENCLOSURE FINISHED PADMOUNT GREEN MUNSELL No. 7GY-3.29/1.5.
ENCLOSURE IS DESIGNED PER APPLICABLE SECTIONS OF ANSI/IEEE C37.74
AND ANSI C57.12.29. DRAWING IS TYPICAL AND SHOWS OVERALL DIMENSIONS
ONLY. CONSTRUCTION DETAILS MAY VARY FROM THOSE DEPICTED.
2. WHEN ELBOWS, INSERTS, AND ANY OTHER ACCESSORIES ARE CONNECTED TO
THE JUNCTION BAR, THE RATINGS OF EACH CONNECTED ASSEMBLY WILL BE THAT OF
THE LOWEST RATED COMPONENT OF THE ASSEMBLY.
3. MOUNTING INFORMATION: THE PAD MOUNT ENCLOSURE SHOULD BE SECURED TO THE
PAD. EACH PAD MOUNT ENCLOSURE IS SHIPPED WITH 4 SECURING BRACKETS THAT
ARE TO BE USED FOR THIS PURPOSE. THE SECURING BRACKETS CAN BE INSTALLED
ANYWHERE ALONG THE INNER EDGE OF THE ENCLOSURE. SEE ENCLOSURE MOUNTING
DETAIL "A" AND THE PLAN VIEW FOR MORE DETAILS ABOUT SECURING THE PAD
MOUNT ENCLOSURE TO THE PAD.
PLAN VIEW
ENCLOSURE
MOUNTING
(4 PLACES)
FRONT VIEW
SECTION A-A
CONCRETE
PAD
.19" STAINLESS STEEL
ANCHOR BRACKET
WITH .875" X 1.125"
SLOTTED HOLE
SUPPLIED BY G&W
.625" DIA.
HARDWARE
(4)-SUPPLIED
BY USER
2.19
56MM
TYP.
M M
M I N
ENCLOSURE
ENCLOSURE
MOUNTING
DETAIL "A"
(2) LIFTING PROVISIONS
PARKING STAND
(ONE PER BUSHING)
GROUNDING PROVISION
WITH 1/2"-13 THREAD
FOR J-BAR CABINET
GROUND NUT
WITH 1/2"-13 THREAD
(ONE PER PHASE)
DEADBREAK APPARATUS
BUSHING
(ALL POSITIONS OF ALL PHASES)
NAMEPLATE AND
6-LINE DIAGRAM
LID HANDLE
(BOTH SIDES)
REMOVABLE LIFTING
PROVISION WITH
1.25 DIA HOLE
(2 PLACES)
"A" PHASE
JUNCTION BAR
"B" PHASE
JUNCTION BAR
"C" PHASE
JUNCTION BAR
GROUND BUS BAR
WITH .563" DIA.
HOLES
(18 HOLES)
304/304L
STAINLESS
STEEL
MOUNTING
BRACKET
CABLE
TRAINING
OUTLINE
LID IS EQUIPPED WITH
STAINLESS STEEL
HINGES FOR OPENING
HINGED LID EQUIPPED
WITH PENTA HEAD BOLT
AND PROVISION FOR PADLOCK
FLIP TOP LID
LID SWING OUTLINE
304/304L
STAINLESS
STEEL
MOUNTING
FRAME
DATE G&W NO.
CUSTOMER
ORDER NO.
FOR RECORD
FOR APPROVAL-NO MORE WORK TO BE
DONE UNTIL APPROVAL
IS RECEIVED
PRINT IDENTIFICATION
ITEM NO.
Printed on 2026.03.06 at 9:15 AM.
| Sheet 1 |
| Views |
| new_view_9 |
| new_view_10 |
| new_view_13 |
| new_view_24 |
File details come from the government source that posted it. Updated .