ATTACHMENT B - 1745518_DESIGN REVISION 1_DWGS.pdf

PDF 15 MB Posted

Attached to
DESIGN-BID-BUILD, LAG-105 REPLACE H SUBSTATION, NAVAL STATION NORFOLK, NORFOLK, VIRGINIA
Solicitation number
N4008524R2743
Issued by

About this file

This document appears to be ATTACHMENT B - 1745518_DESIGN REVISION 1_DWGS.pdf, which is related to the federal contract opportunity for LAG-105 Replace H Substation at Naval Station Norfolk, solicitation number N4008524R2743.

The contract opportunity is a Design-Bid-Build, Indefinite Delivery/Indefinite Quantity (IDIQ), Firm Fixed Price (FFP), Multiple Award Construction Contract (MACC) for facilities primarily in the Hampton Roads area. It is limited to 8(a) contractors who hold one of the specified IDIQ contracts with the Department of the Navy Naval Facilities Engineering Command. The project involves the replacement of the H Substation at Naval Station Norfolk. No additional details about the required products, services, response dates, award dates, or pricing terms are provided in this document. This appears to be a design drawing attachment rather than a statement of work or other procurement-related document.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

G-001

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

VICINITY MAP SYMBOLS LEGEND GENERAL NOTES

ABBREVIATIONS

LAG-105

REPLACE H SUBSTATION.

NAVAL STATION NORFOLK ° NORFOLK, VIRGINIA

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND MID-ATLANTIC

PUBLIC WORKS DEPARTMENT

FACILITIES ENGINEERING AND ACQUISITION DIVISION

NORFOLK, VIRGINIA

B2 DETAIL OR SECTION TITLE

SEQUENCE OF CONSTRUCTION

DE

SI

G

N

RE

VI

SI

O N

/2 4/

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

G-002

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

LIST OF SHEETS

SHEETNO. NAVFAC

DWG. NO. SHEET TITLE

GENERAL

CIVIL

STRUCTURAL

ELECTRICAL

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-001

WATER SYMBOLS

C

SURFACE FEATURES LINE TYPES

STORM DRAIN SYMBOLS

SANITARY SYMBOLS

POWER SYMBOLS

OTHER UTILITY SYMBOLS

SURFACE FEATURES SYMBOLSSURVEY SYMBOLS

UTILITY LINE TYPES

CIVIL SYMBOL LEGEND

ABBREVIATIONS

GENERAL NOTES

NEW WORK LEGEND

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

EARTHWORK NOTES

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-101

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 0+66.33 T0 TO STA 5+00

KEY MAP

N

CIVIL SITE PLAN - STA 5+00 T0 TO STA 10+50

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-102

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 10+50 TO STA 15+00

KEY MAP

N

CIVIL SITE PLAN - STA 15+00 TO STA 20+00

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

IP

SF

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-103

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 20+000 TO STA 25+00

KEY MAP

N

CIVIL SITE PLAN - STA 25+00 TO STA 27+10

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

EROSION & SEDIMENT LEGEND

SF

IP

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-104

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 50+00 TO STA 55+50

KEY MAP

N

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-105

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 55+500 TO STA 59+00

KEY MAP

N

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-106

GRAPHIC SCALE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

CIVIL SITE PLAN - STA 59+000 TO STA 63+40.42

KEY MAP

N

C-101 C-102 C-102 C-103

C-101

C-104

C-105

C-106

C-103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-501

INLET PROTECTIONIP

IP

EROSION AND SEDIMENT CONTROL GENERAL NOTES

SILT/SEDIMENT FENCESF

SF

TYPICAL LANDSCAPE AREA

TYPICAL AGGREGATE BASE SURROUND

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

TYPICAL FENCE AND CORNER PANEL ELEVATION TYPICAL FENCE AND BRACED PANEL ELEVATION

TYPICAL 3 STRAND BARBED WIRE AND SINGLE EXTENSION ARM CONFIGURATION

CORNER OR END POSTS LINE POST DETAILS

SINGLE EXTENSION ARM DETAILSGROUNDING DETAIL

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-502

GRAPHIC SCALES

CHAIN LINK FENCING NOTES

TYPICAL PRIVACY PICKET PATTERN DETAIL

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

TYPICAL DOUBLE SWING GATE ELELVATION

PLAN - DOUBLE SWING GATE

GATE HINGE DETAIL GATE LATCH DETAILOFFSET HINGE DETAIL FULCRUM LATCH DETAIL

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

C-503

DETAIL: DROP BAR

GRAPHIC SCALES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CONCRETE

COMPACTED SUBGRADE

CRUSHED STONE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-001

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

ST

R

U C

TU

R

AL

S

YM

BO

LS

, L

EG

EN

D S, A

BB

R

EV

AI

TI

O N

S

AN

D N

O

TE

S

CAH

12,910,488

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

GENERAL NOTES

1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE

ARCH, CIVIL, PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS, AND THE

SPECIFICATIONS. THE CONTRACTOR MUST VERIFY THE REQUIREMENTS OF

OTHER TRADES AS TO SLEEVES, CHASES, HANGERS, INSERTS, ANCHORS,

HOLES, AND ADDITIONAL ITEMS TO BE PLACED OR SET IN THE STRUCTURAL

WORK.

2. THE CONTRACTOR MUST PROVIDE THE TEMPORARY SHORING AND BRACING

REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENT

UNTIL PERMANENT SUPPORTS AND LATERAL BRACING ARE IN PLACE.

3. THE CONTRACTOR MUST FIELD VERIFY THE DIMENSIONS, ELEVATIONS, AND

OTHER REQUIREMENTS NECESSARY FOR THE PROPER CONSTRUCTION AND

ALIGNMENT OF THE NEW PORTIONS OF THE STRUCTURE TO THE EXISTING.

THE CONTRACTOR SHALL MAKE ALL MEASUREMENTS NECESSARY FOR

FABRICATION AND ERECTION OF STRUCTURAL MEMBERS. DISCREPANCIES

SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER

PRIOR TO ORDERING MATERIALS OR BEGINNING WORK (CONSTRUCTION OR

DEMOLITION).

4. THIS STRUCTURE HAS BEEN DESIGNED FOR A MAXIMUM BEARING PRESSURE

OF 1500 PSF.

5. NO UNBALANCED BACKFILLING SHALL BE DONE AGAINST MASONRY OR

CONCRETE WALLS UNLESS WALLS ARE SECURELY BRACED AGAINST

OVERTURNING EITHER BY TEMPORARY CONSTRUCTION BRACING OR BY

PERMANENT CONSTRUCTION.

6. EXCAVATION MADE WITH POWER-DRIVEN EQUIPMENT IS NOT PERMITTED

WITHIN TWO FEET OF KNOWN UTILITIES OR SUBSURFACE CONSTRUCTION.

FOR WORK IMMEDIATELY ADJACENT TO, OR FOR EXCAVATIONS EXPOSING A

UTILITY OR OTHER BURRIED OBSTRUCTION, EXCAVATE BY HAND.

7. POROUS FILL MUST BE COURSE AGGREGATE VDOT NO. 57.

8. REUSE EXCAVATED MATERIAL TO THE BEST EXTENT POSSIBLE. REMOVE ALL

UNUSED EXCAVATED MATERIAL AND DISPOSE OF OFF SITE, FOR BIDDING

PURPOSES, ASSUME ALL EXCAVATED MATERIAL THAT IS NOT REUSED AS

CONTAMINATED.

9. ALL DISTURBED AREAS MUST BE GRADED TO PROMOTE POSITIVE DRAINAGE.

10. ALLOWABLE SOIL PRESSURE PER IBC:

A. DEAD LOAD + LIVE LOAD = 1000 PSF

B. DEAD LOAD + LIVE LOAD + LATERAL LOAD = 1500 PSF

11. PRIOR TO FABRICATION AND CONSTRUCTION, VERIFY THE (5) PIECES OF

ELECTRICAL EQUIPMENT SELECTED WILL MEET THE 12" OR 30" MINIMUM

OFFSET REQUIREMENTS (DEPENDING ON LOCATION) NOTED ON THE

STRUCTURAL DRAWINGS. NOTIFY THE CONTRACTING OFFICER IMMEDIATELY

IF THE SELECTED SWITCH DOES NOT MEET THE REQUIREMENTS AND

DIMESIONS CALLED OUT IN THE STRUCTURAL DRAWINGS.

12. LOCATE AND PROTECT ALL EXISTING UNDERGROUND UTILITIES.

13. COORDINATE WITH CIVIL SHEETS FOR LOCATION AND SITE PLAN

INFORMATION.

14. COORDINATE WITH ELECTRICAL SHEETS FOR EQUIPMENT PLACEMENT AND

CONDUIT INFORMATION.

GENERAL SCOPE OF WORK

1 REINFORCING MATERIALS MUST BE AS FOLLOWS:

A. REINFORCING BARS – ASTM A615, GRADE 60, DEFORMED

B. TIES AND STIRRUPS – ASTM A615, GRADE 40

2 PLACE REINFORCING STEEL IN ACCORDANCE WITH THE CONCRETE

REINFORCING STEEL INSTITUTE (CRSI) “MANUAL OF STANDARD PRACTICE”.

REINFORCING STEEL MUST NOT CONTAIN RUST, SCALE, OIL, GREASE, CLAY,

OR FOREIGN SUBSTANCES THAT WOULD REDUCE THE BOND. REMOVE

LOOSE RUST PRIOR TO PLACEMENT.

3 UNLESS OTHERWISE NOTED, THE FOLLOWING MINIMUM CONCRETE COVER

MUST BE PROVIDED FOR CONCRETE PROTECTION OF REINFORCING, AS

WELL AS PLACING AND FABRICATION OF REINFORCING, IN ACCORDANCE

WITH RECOMMENDATIONS IN ACI 318:

A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO

EARTH = 3"

B. CONCRETE CAST IN FORMS AND EXPOSED TO EARTH OR WEATHER:

I. STRUCTURAL SLAB ON GRADE = 2 1/2”

II. #5 BAR, W31 OR D31 WIRE & SMALLER = 1-1/2"

4 EACH REINFORCING BAR MUST BE WIRED TO A CROSS BAR AT A MAXIMUM

SPACING OF 2’-0” ON CENTER.

5 DETAIL BARS IN ACCORDANCE WITH ACI DETAILING MANUAL, LATEST

EDITION. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT

REINFORCING IN POSITIONS SHOWN. BAR SUPPORTS AND HOLDING BARS

MUST BE PROVIDED FOR ALL REINFORCING STEEL TO INSURE MINIMUM

CONCRETE COVER. BAR SUPPORTS MUST BE PLASTIC TIPPED OR STAINLESS

STEEL.

6 SHOP DRAWINGS MUST BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION

AND DELIVERY OF REINFORCING STEEL.

7 ALL REINFORCING STEEL, DOWELS, ANCHORS RODS, AND OTHER HARDWARE

TO BE SET IN CONCRETE MUST BE TIED IN PLACE PRIOR TO THE PLACEMENT

OF CONCRETE TO PREVENT DISPLACEMENT BEYOND PERMITTED

TOLERANCES.

8 LAP CONTINUOUS REINFORCING STEEL A MINIMUM LENGTH OF 36 X BAR

DIAMETER OF SMALLER BAR BEING LAPPED.

STRUCTURAL ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

ARCH ARCHITECT, -URAL

B.P.A. BASE PLATE

BLDG BUILDING

BOD BOTTOM OF DECK

BOT BOTTOM

BRCG BRACING

BRDG BRIDGING

C CHANNEL

CJ CONTROL JOINT

CL CENTER LINE

CLR CLEAR

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

DEMO DEMOLISH

DOR DESIGNER OF RECORD

DIA (OR) Ø DIAMETER

DIM(S) DIMENSION(S)

DWGS DRAWINGS

E, EXIST EXISTING

E.W. EACH WAY

EA EACH

EF EACH FACE

EL, ELEV ELEVATION

EQ, EQUIV EQUAL, EQUIVALENT

F'C COMPRESSIVE STRESS

FDN FOUNDATION

FF EL FINISHED FLOOR ELEVATION

FRP FIBERGLASS REINFORCED PLASTIC

FY ALLOWABLE YIELD STRESS

GA GAUGE

HDG, GALV HOT DIPPED GALVANIZED

HORIZ HORIZONTAL

HSS HOLLOW STRUCTURAL SHAPES

IAW IN ACCORDANCE WITH

INFO INFORMATION

INT INTERIOR

KSI KILOPOUNDS (KIPS) PER SQUARE INCH

L ANGLE

LB, LBS POUNDS

LF LINEAR FEET

LONG LONGITUDINAL

MATL MATERIAL

MAX MAXIMUM

MFR MANUFACTURER

MIN MINIMUM

MOS MID-DEPTH OF SLAB

MPH MILES PER HOUR

NTS NOT TO SCALE

OC ON CENTER

OPH OPPOSITE HAND

PL PLATE

PLF POUNDS PER LINEAR FOOT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

RE, REF REFERENCE

REINF REINFORCE, -MENT

REQD REQUIRED

SF SQUARE FEET

SIM SIMILAR

SPA SPACING

SPEC CONTRACT SPECIFICATIONS

SQ SQUARE

STD STANDARD

T&B TOP AND BOTTOM

THK THICKNESS

TOC TOP OF CONCRETE

TOS TOP OF STEEL

TS THICKENED SLAB

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VERT VERTICAL

W/, W/O WITH, WITHOUT

~ , APPROX APPROXIMATELY

1. THE GENERAL SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO:

(1) 33' - 0" x 10' - 6" ELEVATED, REINFORCED CONCRETE SLAB WITH CABLE

WELL OPENINGS ON FOUNDATION WALLS AND STRIP FOOTINGS TO SUPPORT

THE FOLLOWING EQUIPMENT:

A. (1) 15 KV SF6 PAD MOUNTED SWITCH. WEIGHT: 1,100 LBS

B. (1) 2,500 KVA PAD MOUNTED TRANSFORMER. WEIGHT: 14,000 LBS

C. (1) 5 WAY 15 KV SF6 PAD MOUNTED SWITCH. WEIGHT: 1,375 LBS

D. (1) 15 KVA PAD MOUNTED TRANSFORMER. WEIGHT: 550 LBS

(1) SET OF CONCRETE STAIRS TO ALLOW ACCESS TO THE ELEVATED SLAB.

(1) SLAB ON GRADE TO SUPPORT THE FOLLOWING EQUIPMENT:

A. 15 KV SF6 PAD MOUNTED SWITCH. WEIGHT: 1,100 LBS

ANY INCIDENTAL RELATED WORK SHOWN ON OTHER DISCIPLINE DRAWINGS.

CAST-IN-PLACE CONCRETE NOTES

1. CONCRETE WORK MUST CONFROM TO THE REQUIREMENTS OF ACI 318-14

"BUILDING CODE REQUIRMENTS FOR STRUCTURAL CONCRETE".

2. CONCRETE MUST BE NORMAL WEIGHT AND MUST OBTAIN A 28 DAY

COMPRESSIVE STRENGTH OF 4,000 PSI.

3. BEFORE PLACING CONCRETE, EMBEDDED ITEMS MUST BE PROPERLY

LOCATED, ACCURATELY POSITIONED, AND MAINTAINED SECURELY IN PLACE.

DO NOT FIELD BEND BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE

UNLESS INDICATED OR APPROVED BY THE CONTRACTING OFFICER.

4. EDGES OF PERMANENTLY EXPOSED CONCRETE SURFACES MUST BE

CHAMFERED 3/4" UNLESS OTHERWISE NOTED.

5. FORMWORK MUST REMAIN IN PLACE UNTIL CONCRETE HAS OBTAINED AT

LEAST 70% OF ITS 28 DAY COMPRESIVE STRENGTH. THE CONTARCTOR MUST

PROVIDE ALL SHORING AND RESHORING.

6. SLAB/PAD FINISH TOLERANCE IN ACCORDANCE WITH ACI 301, CLASS A.

7. CONCRETE MUST BE MECHANICALLY VIBRATED IN ACCORDANCE WITH ASTM

309R.

8. ANCHOR RODS WITH UPSET THREADS ARE NOT ALLOWED.

9. REFER TO THE ELECTRICAL AND CIVIL DRAWINGS FOR EXACT LOCATIONS

AND DIMENSIONS OF CONCRETE PADS.

10. SLOPE EXTERIOR SLAB(S) TO DRAIN. COORDINATE WITH CIVIL DRAWINGS AT

LOCATIONS WHERE STRUCTURAL WORK REQUIRES DEMOLITION OF

EXISITING SITE ELEMENTS (PARKING LOTS, SIDEWALKS,ETC.) AND AT WORK

COMPLETION, PATCHING OF THOSE ELEMENTS TO MATCH ADJACENT.

ADHESIVE THREADED ANCHOR NOTES

1 SUBMIT PRODUCT DATA FOR GOVERNMENT APPROVAL PRIOR TO ORDERING.

ALL ANCHORS MUST BE SUITABLE AND INDEPENDENTLY TESTED FOR USE IN

CRACKED AND UNCRACKED CONCRETE.

2 FOLLOW MANUFACTURER’S RECOMMENDATIONS INCLUDING THOSE FOR

SAFE HANDLING, MIXING, PLACEMENT, AND CURING OF ADHESIVE.

3 CHEMICAL ANCHORS MUST BE A TWO-COMPONENT, 100% SOLIDS EPOXY

BASED SYSTEM SUPPLIED IN MANUFACTURER’S STANDARD CARTRIDGE AND

DISPENSES THROUGH A STATIC-MIXING NOZZLE SUPPLIED BY THE

MANUFACTURER. ANCHORING ADHESIVE MUST HAVE BEEN TESTED AND

QUALIFIED FOR SEISMIC LOADING, DAMP HOLES, FREEZE THAW CONDITIONS,

AND FOR CRITICAL AND MINIMUM EGE DISTANCE AND SPACING.

4 POSITIVELY LOCATE EXISTING REINFORCING STEEL BY NONDESTRUCTIVE

MEANS PRIOR TO DRILLING HOLES. USE NON-REBAR CUTTING DRILL BITS. DO

NOT CUT EXISTING REINFORCING STEEL UNLESS APPROVED BY THE

CONTRACTING OFFICER. ASSUME A MINIMUM OF 10% OF ANCHORS WILL

REQUIRE OFFSET TO AVOID EXISTING REINFORCING (ASSUME 2" OFFSET FOR

BID PURPOSES). ANY HOLES MADE FOR ANCHORS THAT ARE NOT USED MUST

BE FILLED WITH HIGH STRENGTH, NON-SHRINK, NON-METALLIC EPOXY

GROUT.

5 EPOXY MUST MEET THE MINIMUM REQUIREMENTS OF ASTM C881 FOR TYPE I,

II, IV, AND V, GRADE 3, CLASS B AND C, AND MUST DEVELOP A MINIMUM OF

12,650 PSI f'c (YIELD) AFTER SEVEN-DAY CURE. EPOXY MUST HAVE A HEAT

DEFLECTION TEMPERATURE OF 136 DEGREES F (MINIMUM).

STRUCTURAL SYMBOLS

REINFORCING STEEL NOTES

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

N/A

UP

33' - 0"

6"

A1 S-301

1' - 0" 6' - 7"

MI

NI

MU

M

2'

- 6

5'

- 5

1' - 0" 6' - 0" 1' - 0" 10' - 6"

MINIMUM

3' - 0" 2' - 9" 1' - 2"

8'

- 3

5'

- 5

2'

- 4

1/ 2"

3 2

6"

C1 S-301

A4 S-301

38' - 0"

5' - 8"

2' - 8"

TY

P8"

6 6

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-101

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

O

VE

R

AL

L

EQ

U

IP

M

EN

T

PL

AN

CAH

12,910,489

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

PLAN

NORTH

A ALL EQUIPMENT IS REQUIRED TO HAVE A MINIMUM EDGE DISTANCE FROM

WALL FACE OF 12" UNLESS OTHERWISE NOTED.

B DIMENSIONS OF EQUIPMENT ARE ASSUMED. IF EQUIPMENT SELECTED DOES

NOT COMPLY WITH THE OFFSET REQUIREMENTS OR WEIGHTS STATED ON

S-001, NOTIFY THE CONTRACTING OFFICER IMMEDIATELY.

SCALE: 3/4" = 1'-0"B1 OVERALL EQUIPMENT PLAN

KEYNOTESGENERAL SHEET NOTES

6 1" DEEP CONTRACTION JOINT PLACED BETWEEN EQUIPMENT.1 8" THICK ELEVATED CONCRETE SLAB, REINFORCED WITH #5 BARS AT 5"

O.C. E.W., WITH DEPTH OF BAR = 4.5" FROM TOP OF SLAB.

2 CONTINUOUS 8" THICK CONCRETE FOUNDATION WALLS REINFORCED

WITH #5 BARS AT 10" O.C., E.W.

3 CONTINUOUS 2'-8" WIDE X 12" DEEP CONCRETE STRIP FOOTING

REINFORCED WITH (5) #5 LONGITUDINAL BARS SPACED EVENLY AND (1)

#5 HORIZONTAL BAR AS SHOWN. SEE SECTION C1/S-301 FOR MORE

INFORMATION.

4 PROVIDE (3) 10' - 6" WIDE STEPS W/ 12" RISER AND 12" RUN. SEE

SECTION A4/S-301 FOR MORE INFORMATION.

5 5' - 8" WIDE X 12" THICK STRIP FOOTING REINFORCED W/ #5 BARS @ 6"

O.C., E.W.

# (THIS SHEET ONLY)

0' 1' 2' 3'

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

DE

SI

GN

R

EV

IS

IO

N

/24

/20

A1 S-301

33' - 0"

3 2

1' - 3 1/2" 6' - 0" 1' - 5" 5' - 9" 1' - 9 1/2" 7' - 0" 6' - 2 1/2" 2' - 0" 10 1/2"

1'

- 4

1'

- 5

1/ 2"

1'

- 9

3'

- 1

1/ 2"

2'

- 1

0 1 /2"

1'

- 4

4'

- 1

3/ 4"

1'

- 0

TY

P

(3 ) S

ID

ES

W /O

UT

S

TA

IR

S

2'

- 8

TY

P

AL

L A

R O

UN

D

8"

C1 S-301

A4 S-301

C1 S-501

7 7

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-102

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

O

VE

R

AL

L

FO

U N

D

AT

IO

N

A N

D S

LA

B

PL

AN

CAH

12,910,490

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

KEYNOTESGENERAL SHEET NOTES

6 5' - 8" WIDE X 12" THICK STRIP FOOTING REINFORCED W/ #5 BARS @ 6" O.C.,

E.W.

7 1" DEEP CONTRACTION JOINT PLACED BETWEEN EQUIPMENT.

1 8" THICK ELEVATED CONCRETE SLAB, REINFORCED WITH #5 BARS AT 5" O.C.

E.W., WITH DEPTH OF BAR = 4.5" FROM TOP OF SLAB.

2 CONTINUOUS 8" THICK CONCRETE FOUNDATION WALLS REINFORCED WITH

#5 BARS AT 10" O.C., E.W.

3 CONTINUOUS 2'-8" WIDE X 12" DEEP CONCRETE STRIP FOOTING

REINFORCED WITH (5) #5 LONGITUDINAL BARS SPACED EVENLY AS SHOWN

AND (1) #5 HORIZONTAL BAR AS SHOWN.

4 CABLE WELL OPENING.

5 PROVIDE (3) 10' - 6" WIDE STEPS W/ 12" RISER AND 12" RUN. SEE DETAIL

A4/S-301 FOR MORE INFORMATION.

A ALL EQUIPMENT IS REQUIRED TO HAVE A MINIMUM EDGE DISTANCE FROM

WALL FACE OF 12" UNLESS OTHERWISE NOTED.

B DIMENSIONS OF EQUIPMENT ARE ASSUMED. IF EQUIPMENT SELECTED DOES

NOT COMPLY WITH THE OFFSET REQUIREMENTS OR WEIGHTS STATED ON

S-001, NOTIFY THE CONTRACTING OFFICER IMMEDIATELY.

C ENSURE CABLE WELL OPENING SIZES COMPLY WITH SELECTED EQUIPMENT

REQUIREMENTS.

SCALE: 3/4" = 1'-0"B1 OVERALL FOUNDATION AND SLAB PLAN

PLAN

NORTH

0' 1' 2' 3'

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

DE

SI

GN

R

EV

IS

IO

N

/24

/20

FINISH GRADE

0' - 0"

8" THICK ELEVATED CONCRETE

SLAB, REINFORCED WITH #5 BARS

AT 5" O.C. E.W., WITH DEPTH OF

BAR = 4.5" FROM TOP OF SLAB.

CONTINUOUS 8" THICK CONCRETE

FOUNDATION WALLS

REINFORCED WITH #5 BARS AT

10" O.C., E.W.

CONTINUOUS 2'-8" WIDE X

12" DEEP CONCRETE STRIP

FOOTING REINFORCED WITH

(5) #5 LONGITUDINAL BARS

SPACED EVENLY AS SHOWN

AND (1) #5 HORIZONTAL BAR

AS SHOWN.

8"

3'

- 0

1'

- 0

1'

- 0

2' - 8"

10' - 6"

6" TYP

SELECT

STRUCTURAL

BACKFILL.

PROVIDE 12" THICK LAYER

OF #57 VA GRADE STONE,

EXTEND 6" BEYOND EDGE

OF FOOTING

2'

- 4

3" M

IN

3" MIN

1' - 0" 8" 1' - 0"

3'

- 4

"4'

- 0

2" X 4" SHEAR KEY W/ 1"X1"

CONT. WATERSTOP (TYP).

COMPACTED EXISTING

SUBGRADE.

4 1 /2"

M

IN

PROVIDE #5 "L" BARS AS

SHOWN. HORIONZTAL LEG =

12" & VERTICAL LEG = 1' - 6"

FINISH GRADE

0' - 0"

5' - 8" WIDE X 12" THK MAT

FOUNDATION REINFORCED W/

#5 BARS @ 6" O.C., E.W.

3" T

YP

2" X 4" SHEAR KEY W/ 1"X1"

CONT. WATERSTOP (TYP). 8 5

/8"

CONTINUOUS 8" THICK

CONCRETE FOUNDATION

WALLS REINFORCED WITH #5

BARS AT 10" O.C., E.W.

5' - 8"

1'

- 0

" 1' - 0" TYP

#5 BARS @ 8" O.C., E.W.

DOWEL INTO SLAB AS

SHOWN. MINIMUM

EMBEDDMENT = 2' - 0"

8" TYP

2' - 0" MIN

SELECT

STRUCTURAL

FILL. BACKFILL

TO BE FLUSH

WITH BOTTOM

OF PAD.

PROVIDE CONTINUOUS #5 "L"

BAR AS SHOWN. TIE SLAB

INTO WALL

" T

YP

12" TYP

PROVIDE #5 STRAIGHT BAR

THRU LENGTH OF EACH

TREAD. PROVIDE MIN 1 1/2"

COVER.

PROVIDE (3) 10' - 6" WIDE

STEPS W/ 12" RISER AND 12"

RUN.

PROVIDE #5 "L" BARS AS

SHOWN. HORIONZTAL LEG =

12" & VERTICAL LEG = 1' - 6"

PROVIDE 12" THICK LAYER

OF #57 VA GRADE STONE,

EXTEND 6" BEYOND EDGE

OF FOOTING

8" THICK ELEVATED CONCRETE

SLAB, REINFORCED WITH #5 BARS

AT 5" O.C. E.W., WITH DEPTH OF

BAR = 4.5" FROM TOP OF SLAB.

COMPACTED EXISTING

SUBGRADE.

2 1/2" X 1 1/2" X 1/4" NOSING

ANGLE, TYP EACH STEP

FINISH GRADE

0' - 0"

8" THICK ELEVATED CONCRETE

SLAB, REINFORCED WITH #5 BARS

AT 5" O.C. E.W., WITH DEPTH OF

BAR = 4.5" FROM TOP OF SLAB.

SELECT STRUCTURAL FILL.

BACKFILL TO BE

COMPACTED FLUSH WITH

BOTTOM OF PAD.

CONTINUOUS 8" THICK

CONCRETE FOUNDATION

WALLS REINFORCED WITH #5

BARS AT 10" O.C., E.W.

PROVIDE CONTINUOUS #5 "L"

BAR AS SHOWN. TIE SLAB

INTO WALL

PROVIDE #5 "L" BARS AS

SHOWN. HORIONZTAL LEG =

12" & VERTICAL LEG = 1' - 6"

CONTINUOUS 2'-8" WIDE X

12" DEEP CONCRETE STRIP

FOOTING REINFORCED WITH

(5) #5 LONGITUDINAL BARS

SPACED EVENLY AS SHOWN

AND (1) #5 HORIZONTAL BAR

AS SHOWN.

PROVIDE 12" THICK LAYER

OF #57 VA GRADE STONE,

EXTEND 6" BEYOND EDGE

OF FOOTING

6" TYP

1'

- 0

1'

- 0

3'

- 0

3" MIN

3" M

IN

2" X 4" SHEAR KEY W/ 1"X1"

CONT. WATERSTOP (TYP).

COMPACTED EXISTING

SUBGRADE.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-301

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

ST

R

U C

TU

R

AL

S

EC

TI

O N

S

CAH

12,910,491

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

SCALE: 1" = 1'-0"

B1

S-101 A1 Section - TYPICAL SLAB REINFORCEMENT

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

DE

SI

GN

R

EV

IS

IO

N

/24

/20

N/A

SCALE: 1" = 1'-0"

B1

S-101 A4 SECTION - THRU STAIRS

SCALE: 1" = 1'-0"

B1

S-101 C1 SECTION - TYPICAL WALL CONDITION

S-102

S-102

1' 2'0' 6"

1' 2'0' 6" 1' 2'0' 6"

TYP REINFORCEMENT PATTERN

W/ #5 BARS AT 5" O.C. E.W. DEPTH

OF BAR = 4.5" FROM TOP OF SLAB.

PROVIDE (6) ADDITIONAL #5 BARS

W/ SPACING SHOWN TYP OF ALL

SIDES OF CABLEWELLS. TIE INTO

TYP REINFORCMENT PATTERN.

MEET MIN COVER REQUIRMENTS.

NOTE: DETAIL IS TYPICAL OF

ALL (4) CABLEWELL OPENINGS

SHOWN ON S-101 & S-102.

ELEVATED 8" THICK

CONCRETE SLAB

PER LOCATION

VARIES

8"

PROVIDE 90 DEGREE BEND TO #5

BARS AS SHOWN. TYP FOR EVERY

CONTINUOUS HORIZONTAL BAR ON

ALL SIDES OF CABLE WELL OPENINGS.

1 1/2" MIN

1 1 /2"

M

IN

PROVIDE (3) CONTINUOUS

#5 BARS IN DROP PANEL

SECTION TYP OF EVERY

SIDE OF CABLE WELL

OPENING AS SHOWN.

5" T

YP

1'

- 2 " T

YP1'

- 1

0"

ELECTRICAL CONDUIT

TERMINATION 22" MIN

BELOW TOP OF PAD.

SELECT

STRUCTURAL

BACKFILL.

CABLE WELL TO REMAIN VOID OF

STRUCTURAL BACKFILL AS SHOWN.

5" TYP

CABLEWELL OPENING

(2) 2' - 0" LONG (#5)

DIAGONAL BARS MID-

DEPTH AS SHOWN TYP AT

EACH CORNER OF EVERY

CABLE WELL.

NOTE: TERMINATE BARS

SHORT IF CONDITION

OCCURS WHERE BARS

CAN'T MEET COVER

REQUIRMENTS.

SEE PLAN ON S-102

VARIES PER EQUIPMENT

SE

E

PL

AN

O N

S-

VA

RI

ES

P

ER

E

QU

IP

ME

NT

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-501

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

ST

R

U C

TU

R

AL

D

ET

AI

LS

CAH

12,910,492

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

DE

SI

GN

R

EV

IS

IO

N

/24

/20

N/A

SCALE: 1" = 1'-0"

B1

S-102 C1 DETAIL - TYPICAL CABLE WELL DROP PANEL REINFORCEMENT

SCALE: 1" = 1'-0"B1 DETAIL - TYPICAL CABLE WELL DIAGONAL REINFORCEMENT

1' 2'0' 6"

1' 2'0' 6"

9' - 0"

ASSUMED SIZE OF EQUIPMENT

6' - 7"

12" MIN

" M

IN

12" MIN

" M

IN

CABLE WELL

6' - 0"

1'

- 0

1'

- 4

5'

- 8

8'

- 0

AS

S U

ME

D

SI

ZE

O F

EQ

UI

P M

EN

T

5'

- 5

C1 S-502

C3 S-502

REINFORCED CONCRETE PAD

EDGE OF EQUIPMENT

A3 S-502

NOTE: REFER TO CIVIL &

ELETRICAL SITE PLANS

FOR LOCATION OF PAD

12" DEEP X 9" TALL STEP

FINISH GRADE

0' - 0"

TYP

6"

1'

- 0

1'

- 6

2'

- 6

CLR

1 1/2"

TY

P

3" C

LR

EDGE OF EQUIPMENT

REINFORCED CONCRETE PAD

3/4" CHAMFER ALL-AROUND

TOP: (22) #5 BARS W/ 90 DEGREE

HOOK EA END, SPACED A MAXIMUM

OF 5" O.C, E.W. MIN 1 1/2" COVER

#5 STRAIGHT BAR SKIN REINF

ALONG PERIMETER OF PAD, TYP

SPA @ 6" O.C. MAX VERTICALLY.

BOTTOM: (22) #5 STRAIGHT BARS

SPACED A MAXIMUM OF 5" O.C, E.W.

MIN 3" COVER

12" LAYER CRUSHED VDOT #57

STONE OVER COMAPCTED SELECT

MATERIAL EXTENDING 6" WIDER

THAN PAD FOOTPRINT, TYP

COMPACTED EXISTING GRADE

FINISH GRADE

0' - 0"

EDGE OF EQUIPMENT

3/4" CHAMFER ALL-AROUND

COMPACTED EXISTING GRADE

12" LAYER CRUSHED VDOT #57

STONE OVER COMAPCTED SELECT

MATERIAL EXTENDING 6" WIDER

THAN PAD FOOTPRINT, TYP

TYP

6"

1'

- 0

1'

- 6

2'

- 6

1' - 6"

(3) #5 STRAIGHT BARS

(6) #5 STRAIGHT BARS SKIN REINF

REQD ALONG PERIMETER OF PAD &

INTERIOR FACE OF CABLE WELL

OPENING, TYP, SPACED AT 6" O.C.

TOP: (3) #5 BARS W/ 90 DEGREE

HOOK EA END

CABLE WELL

1 1/2" 1 1/2"1' - 3"

1 1 /2"

6" T

YP

3"

#5 STIRRUPS SPA AT 8" O.C. TYP

FINISH GRADE

0' - 0"

1' - 4"

TOP: (14) #5 BARS W/ 90 DEGREE

HOOK EA END, SPACED A MAXIMUM

OF 5" O.C, E.W. MIN 1 1/2" COVER

#5 STRAIGHT BAR SKIN REINF

ALONG PERIMETER OF PAD, TYP

SPA @ 6" O.C. MAX VERTICALLY.

BOTTOM: (19) #5 STRAIGHT BARS

SPACED A MAXIMUM OF 5" O.C, E.W.

MIN 3" COVER

12" LAYER CRUSHED VDOT #57

STONE OVER COMAPCTED SELECT

MATERIAL EXTENDING 6" WIDER

THAN PAD FOOTPRINT, TYP

COMPACTED EXISTING GRADE

COPPER GROUND GRID IN PAD PER

ELECTRICAL DRAWINGS

CONCRETE DUCT ENVELOPE PER

ELECTRICAL.

DUCT/CONDUIT PER ELECTRICAL

DRAWINGS

COPPER GROUND IN DUCTBANK

PER ELECTRICAL DRAWINGS

GROUND ROD PER

ELECTRICAL DRAWINGS

COMPACTED VDOT BACKFILL

CONDUIT MINIMUM 2" ABOVE

FINISHED GRADE PER

ELECTRICAL DRAWINGS

12" LAYER CRUSHED

VDOT #57 STONE

(3) #5 STRAIGHT BARS

(6) #5 STRAIGHT BARS

SKIN REINF REQD

ALONG PERIMETER

OF PAD & INTERIOR

FACE OF CABLE WELL

OPENING, TYP,

SPACED AT 6" O.C.

TOP: (3) #5 BARS W/ 90

DEGREE HOOK EA END

FRONT OF SWITCH

1' - 6"

1'

- 6

1'

- 0

2'

- 6

1 1 /2"1 1/2"

3"

#5 STIRRUPS SPA @ 8"

O.C. TYP

9"

1' - 0"

PROVIDE (4) #5 BARS AS

SHOWN FULL LENGTH OF STEP

2 1/2" X 1 1/2" X 1/4" NOSING

ANGLE, TYP EACH STEP

(2) ROWS OF #5 BARS W/ MIN 18"

EMBEDMENT INTO MAIN PAD SPA

AT 8" O.C.

MIN

1' - 6" 6"22 " F

RO

M

TO

P

OF

P

AD

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 14 SEP 2023

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

MS

C

OM

MA

ND

MI

D-

AT

LA

NT

IC

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

7/ 1/

:1

8:

P M c:

\U se rs

\a nd re w

.d .b ut le r2 \D oc um en ts

\H S

U B

LA

G

_1

_S _R

_a nd re w .d

.b ut le r2

.rv t

S-502

LA

G

-1

R

EP

LA

C E

SU

BS

TA

TI

O N

H

ST

R

U C

TU

R

AL

D

ET

AI

LS

CAH

12,910,493

ADB ADB

05/24/2024

F.V. PEPPERS

1745518

N/A

N O

R

FO

LK

, V

IR

G

IN

IA

N

AV

AL

S

TA

TI

O N

N O

R

FO

LK

JOHN MILLER, P.E.

JAMES SMITH, R.A.

M

ID

LA

N

T D

C C

O R

E

S-

Hien Lam

MA

RK

D

ES

CR

IP

TI

ON

DA

TE

DE

SI

GN

R

EV

IS

IO

N

/24

/20

N/A

SCALE: 3/4" = 1'-0"

A1

S-301 A1 PLAN - SWITCH PAD TYPICAL OF ONE LOCATION

SCALE: 1" = 1'-0"

A1

S-502 C1 SECTION - ACROSS SWITCH PAD

SCALE: 1" = 1'-0"

A1

S-502 C3 SECTION - ACROSS CABLE WELL

SCALE: 1" = 1'-0"

A1

S-502 A3 SECTION - THRU CABLE WELL

1' 2'0' 6" 1' 2'0' 6"

1' 2'0' 6"0' 1' 2' 3'

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES001

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GENERAL NOTES

SEQUENCE OF WORK

GENERAL

SITE LEGEND

ABBREVIATIONS

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES101

GRAPHIC SCALE

GENERAL SHEET NOTES

KEYNOTES

ELEC SITE PLAN - STA 0+66.33 T0 TO STA 5+00

KEY MAP

N

ELEC SITE PLAN - STA 5+00 T0 TO STA 10+50

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES102

GRAPHIC SCALE

GENERAL SHEET NOTES

ELEC SITE PLAN - STA 10+50 TO STA 15+00

KEY MAP

N

ELEC SITE PLAN - STA 15+00 TO STA 20+00

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

KEYNOTES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES103

GRAPHIC SCALE

GENERAL SHEET NOTES

ELEC SITE DEMOLITION PLAN - STA 20+000 TO STA 25+00

KEY MAP

N

ELEC SITE DEMOLITION PLAN - STA 25+00 TO STA 27+10

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

KEYNOTES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES104

GRAPHIC SCALE

GENERAL SHEET NOTES

ELEC SITE PLAN - STA 50+00 TO STA 55+50

KEY MAP

N

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

KEYNOTES

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES105

GRAPHIC SCALE

GENERAL SHEET NOTES

ELEC SITE PLAN - STA 55+500 TO STA 59+00

KEY MAP

N

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

KEYNOTES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

ES106

GRAPHIC SCALE

GENERAL SHEET NOTES

ELEC SITE PLAN - STA 59+000 TO STA 63+40.42

KEY MAP

N

ES101 ES102 ES102 ES103

ES101

ES104

ES105

ES106

ES103

KEYNOTES

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

DE

SI

G

N

RE

VI

SI

O N

/2

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES401

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

GENERAL SHEET NOTES

KEYNOTES

A. REFER TO SHEET E-001 FOR LEGEND SYMBOLS, ABBREVIATIONS AND

GENERAL NOTES.

B. EXISTING UNDERGROUND UTILITIES SHOWN ARE BASED ON SURFACE

EVIDENCE AND BEST AVAILABLE RECORDS. THE ELECTRICAL

CONTRACTOR MUST PERFORM SITE INVESTIGATION OF THE EXISTING

CONDITIONS PRIOR TO COMMENCING WORK TO VERIFY ACTIVE MEDIUM

VOLTAGE FEEDERS, MANHOLE LOCATIONS AND CONDITIONS.

COORDINATE ALL SITE INVESTIGATIONS WITH THE CONTRACTING

OFFICER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK.

C. EXISTING EQUIPMENT AND DEVICES TO REMAIN MUST STAY INTACT AND

OPERATIONAL DURING THE CONSTRUCTION PROCESS. IF A DEVICE

REQUIRING POWER IS DISTURBED OR INTERRUPTED, RESTORE THE

DEVICE TO ITS ORIGINAL OPERATIONAL STATE. ANY DEMOLITION WORK

REQUIRING MODIFICATION OF EXISTING ELECTRICAL SYSTEMS MUST

NOT COMPROMISE THE SYSTEMS TO REMAIN.

D. THE CONTRACTOR MUST NOTIFY THE CONTRACTING OFFICER A MINIMUM

OF 15 DAYS IN ADVANCE TO REQUEST A POWER OUTAGE.

(THIS SHEET ONLY)

1. DISCONNECT AND REMOVE EXISTING CABLES FROM LAG-105 (H

SUBSTATION) TO EMH #A-1122. REFER TO SHEET ES501 FOR MANHOLE

LAYDOWNS - DEMOLITION. DEMOLISH EXISTING DUCTBANKS

COMPLETELY.

2. DEMOLISH LAG-105 (H SUBSTATION) COMPLETELY INCLUDING 11.5KV

COMPARTMENTS (BKR #1 & #2) , 6250KVA, 11.5KV-4.16KV, 3ɸ-4W

TRANSFORMER, METERING COMPARTMENT, MAIN, 4.16KV

COMPARTMENTS (CKTS H-1, H-2, H-3 & H-4) AND BATTERY

COMPARTMENTS.

3. DEMOLISH EXISTING CONCRETE PAD. REFER TO SHEET C-103.

4. DEMOLISH EXISTING FENCE. REFER TO SHEET C-103.

SCALE:A1 ENLARGED LAG-105 PLAN - DEMOLITION

1" =20'-0"

TO EMH #A-1122

FRONT

DE

SI

GN

R

EV

IS

IO

N

/24

CABLE WELL

TERMINATIONS

OPERATORS

CABLE WELL

TERMINATIONS

OPERATORS

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES402

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

SCALE:A1 ENLARGED LAG-105 PLAN - DEMOLITION

1" =20'-0"

DE

SI

GN

R

EV

IS

IO

N

/24

/24

(THIS SHEET ONLY)GENERAL SHEET NOTES

A. REFER TO SHEET E-001 FOR LEGEND, ABBREVIATIONS, GENERAL NOTES

AND SEQUENCE OF WORK.

B. REFER TO SHEET ES103 - PARTIAL ELECTRICAL SITE PLAN.

C. REFER TO SHEETS ES506 - ES510 FOR ELECTRICAL MANHOLE LAYOUTS.

D. REFER TO SHEETS ES511 - ES513 FOR ELECTRICAL SITE DETAILS.

E. REFER TO SHEET ES602 - PARTIAL ONE-LINE DIAGRAM.

KEYNOTES

1. PROVIDE 4-WAY 15KV SF6 PAD-MTD SWITCH AND LABEL PS-1111.

2. PROVIDE 2500KVA, 11.5KV-4160V, 3ɸ-4W , PAD-MTD TRANSFORMER AND VFI

WITH PARTIAL CURRENT LIMITING FUSE IN SERIES AND LABEL XFMR H.

3. PROVIDE 5-WAY 15KV SF6 PAD-MTD SMART SWITCH WITH 1 SWITCH WAY.S

AND 4 VFI WAYS EACH VFI WAY WITH OVERCURRENT PROTECTION RELAYS

AND LABEL SWCH 15.

4. PROVIDE 15KVA, 11.5KV-120/240V, 1ɸ-3W PAD-MTD CONTROL

TRANSFORMER AND LABEL XFMR CPT-15.

5. CONCRETE EQUIPMENT PAD, REFER TO STRUCTURAL SHEETS.

GRAPHIC SCALE

3/4"=1'-0" 1' 2' 3'

MANHOLE LAYOUT #A-1122

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULIDID

MANHOLE LAYOUT #A-1123

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSUL

MANHOLE LAYOUT #A-1124

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES501

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

(THIS SHEET ONLY)GENERAL SHEET NOTES

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

KEYNOTES

1. DISCONNECT AND REMOVE EXIST CABLES, MANDREL AND CLEAN DUCT.

2. DISCONNECT AND REMOVE EXIST CABLE. SEAL DUCT PENETRATION

WITH CONCRETE.

3. DEMOLISH EXIST SPLICE.

4. DISCONNECT AND REMOVE EXIST CABLES TO THIS POINT.

TYP OF

ALL DUCTS

TO H SUB

DE

SI

GN

R

EV

IS

IO

N

/24

MANHOLE LAYOUT #A-1125

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

MANHOLE LAYOUT #A-1126

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

MANHOLE LAYOUT #A-1127

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES502

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GENERAL SHEET NOTES (THIS SHEET ONLY) KEYNOTES

1. DISCONNECT AND REMOVE EXIST CABLES, MANDREL AND CLEAN DUCT.

1 1

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

DE

SI

GN

R

EV

IS

IO

N

MANHOLE LAYOUT #A-1128

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

MANHOLE LAYOUT #A-1129

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULIDID DESCRIPTION VOLTAGESIZE LGTHINSUL

MANHOLE LAYOUT #264B

N

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

LID SIZE THROAT

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES503

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GENERAL SHEET NOTES (THIS SHEET ONLY) KEYNOTES

1. DISCONNECT AND REMOVE EXIST CABLES, MANDREL AND CLEAN DUCT.

2. DEMOLISH EXIST SPLICE.

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

DE

SI

GN

R

EV

IS

IO

N

ID DESCRIPTION VOLTAGESIZE LGTHINSUL

MANHOLE LAYOUT #1141

N

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

LID SIZE THROAT

ID DESCRIPTION VOLTAGESIZE LGTHINSUL

MANHOLE LAYOUT #1142

N

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

LID SIZE THROAT

MANHOLE LAYOUT #1143

N

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

ID DESCRIPTION VOLTAGESIZE LGTHINSUL

LID SIZE THROAT

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES504

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

(THIS SHEET ONLY)GENERAL SHEET NOTES KEYNOTES

1. DISCONNECT AND REMOVE EXIST CABLES, MANDREL AND CLEAN DUCT.

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

DE

SI

GN

R

EV

IS

IO

N

MANHOLE LAYOUT #309

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

ID DESCRIPTION VOLTAGESIZE LGTHINSUL

LID SIZE THROAT

MANHOLE LAYOUT #308

N

LENGTH LOCATIONWIDTH HEIGHT OPENING SIZEMANHOLE CONDITION

NO

SCALE

ID DESCRIPTION VOLTAGESIZE LGTHINSUL

LID SIZE THROAT

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES505

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

(THIS SHEET ONLY)GENERAL SHEET NOTES KEYNOTES

1. DISCONNECT AND REMOVE EXIST CABLES, MANDREL AND CLEAN DUCT.

2. DEMOLISH EXIST SPLICE.

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

DE

SI

GN

R

EV

IS

IO

N

MANHOLE LAYOUT #A-1122

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULIDID

MANHOLE LAYOUT #A-1123

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSUL

MANHOLE LAYOUT #A-1124

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES506

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

(THIS SHEET ONLY)GENERAL SHEET NOTES KEYNOTES

1. PROVIDE CABLE AS INDICATED IN FEEDER SCHEDULE.

2. PROVIDE SPLICE.

3. PROVIDE NEW CABLE CIRCUIT TAG.

1 3

1 3

1 31 31 3

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G. TEMPORARY SPLICES MUST MEET ALL THE REQUIREMENTS IN THE

SPECIFICATIONS?

H. CONTRACTOR MUST CONNECT GROUND CABLE SHIELD TO EXIST

GROUND ROD IN EACH MANHOLE.

I. PROVIDE ADDITIONAL MANHOLE RACKS, STEPS AND INSULATORS AS

REQUIRED BY THE SPECIFICATIONS.

DE

SI

GN

R

EV

IS

IO

N

MANHOLE LAYOUT #A-1125

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

MANHOLE LAYOUT #A-1126

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

MANHOLE LAYOUT #A-1127

N

LENGTH LOCATIONWIDTH HEIGHTLID SIZETHROAT DEPTHOPENING SIZEMANHOLE CONDITION

NO

SCALE

DESCRIPTION VOLTAGESIZE LGTHINSULID

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D~

M

ID

-A

TL

AN

TI

C

MI

DL

AN

T

PW

D

NO

RF

OL

K

NA

VS

TA

N

OR

FO

LK

, V A

NA

VA

L

ST

AT

IO

N

NO

RF

O

LK

, V

A

NO

RF

O

LK

, V

A

LA

G

-1

RE

PL

AC

E

SU

B

ST

AT

IO

N H

HIEN LAM

05/24/2024

F.V. PEPPERS

J. MILLER, P.E.

N/A

1745518

N/A

ES507

J. MORTON, PE

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

DES DRW

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAWFORM REVISION: 14 SEP 2023

CHK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

(THIS SHEET ONLY)GENERAL SHEET NOTES KEYNOTES

1. PROVIDE CABLE AS INDICATED IN FEEDER SCHEDULE.

2. PROVIDE NEW CABLE CIRCUIT TAG.

1 2 1 21 2

A. REFER TO PARTIAL ELECTRICAL SITE PLANS SHEETS ES101 - ES 106 FOR

LOCATIONS OF EXISTING ELECTRICAL MANHOLES.

B. TELEPHONE AND ELECTRICAL MANHOLES AT THE WORK SITE THAT ARE

NOT IDENTIFIED ARE NOT IN THIS CONTRACT.

C. THE CONTRACTOR MUST FIELD VERIFY CKT ID, CABLE TERMINATIONS

AND LENGTHS PRIOR TO CUTTING CONDUCTORS.

D. THE CONTRACTOR IS RESPONSIBLE FOR DE-WATERING OF MANHOLES.

E. A GAS FREE TEST IS REQUIRED ON ALL ELECTRICAL MANHOLES PRIOR

TO ENTRY.

F. THE CONTRACTOR MUST PROVIDE "HOT CAPS" ON NEWLY INSTALLED

CABLE AS NEEDED TO MINIMIZE CIRCUIT OUTAGES.

G…