N4008521B2509AsbestosSurveyReport.pdf
PDF 10 MB Posted
- Attached to
- Infrastructure Reset Demo Buildings - Package E Federal contract opportunity
- Solicitation number
- N4008521B2509
About this file
This document provides details on a federal solicitation and related asbestos survey report. The solicitation number is N4008521B2509 and concerns the demolition of various buildings at Naval Facilities Engineering Command in accordance with the plans and specifications. The opportunity type is a solicitation for the Infrastructure Reset Demo Buildings - Package E project. The solicitation is seeking demolition services and the attached asbestos survey report pertains to the buildings slated for demolition under this project with the Department of the Navy Naval Facilities Engineering Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| N4008521B2509 Amendment08.pdf | ||
| EMD Decision Memorandum.pdf | ||
| N4008521B2509 Amendment07.pdf | ||
| N4008521B2509 Amendment06.pdf | ||
| Amended Section 01 35 29 Safety and Occupational Health Requirements.pdf | ||
| Amended Section 02 82 16 Removal of Asbestos Materials.pdf | ||
| N4008521B2509 Amendment05.pdf | ||
| N4008521B2509 Amendment04.pdf | ||
| N4008521B2508 Amendment04.pdf | ||
| N4008521B2509 Amendment03.pdf | ||
| N4008521B2509 Amendment02.pdf | ||
| Contractor_Environmental_Guide.pdf | ||
| N4008521B2509 Amendment01.pdf | ||
| N4008521B2509 Solicitation.pdf | ||
| N4008521B2509LeadSurveyReport.pdf | ||
| N4008521B2509 Dwgs.pdf | ||
| N4008521B2509 Specs.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey FY20 Infrastructure Reset Demo Buildings
Marine Corps Base Camp Lejeune Project # 20-0001
Package E
Report Prepared By:
Christopher B. Walker The Walker Group Architecture, Inc
September 28th, 2020 WGA Project No. – 2001.IR20
Project Information
The Walker Group Architecture, Inc. was contracted by Camp Lejeune to conduct an asbestos sampling survey for Buildings/Structures: 133, 222, 226, 402, 429, 432, 509, 824, AS849, AS912, AS913, M401, M402, M408, TC562, TC804, TC1005. The specified buildings or structures are slated for demolition on board Marine Corps Base Camp Lejeune. An asbestos survey has been requested prior to disturbance of any potential asbestos containing materials (ACM).
Scope of Services
A. The survey was performed on 06/08/16, 02/02/18, 03/23/18, 03/11/18, 05/02/19, 04/20/20, 04/22/20, 05/13/20, 05/21/20, 09/15/20 by Christopher B. Walker (NC Accredited Inspector #12878, expires January 31, 2021). The sampling was conducted in general accordance with the U.S. Environmental Protection Agency (EPA) requirements as defined in the asbestos Hazards Emergency Response Act (40 CFR Part 763) guidelines (AHERA) and in general accordance with the North Carolina Health Hazards Control Unit (NCHHCU).
B. The survey was conducted to identify the presence of asbestos containing materials (ACM) prior to repairs to the building.
C. The building was assessed to determine homogenous areas (groups of materials appearing to have been installed in the same general time period and uniform in color and texture).
D. As per AHERA, sufficient samples were collected from random locations of each homogenous area, with the number of samples based on the following criteria:
a. Thermal Insulation Materials (piping, breeching, boiler insulation, etc.) – A minimum of (3) samples are required. Patch areas (less than 6 square or liner feet) may have (2) sample collected.
b. Surfacing Materials (plaster, fireproofing, etc.) – A minimum of (7) samples are to be taken for areas greater than 5,000 square feet, five (5) samples for areas greater than 1,000 square feet, but less than 5,000 square feet, three
(3) samples for areas less than 1,000 square feet, two (2) samples for patching materials.
c. Miscellaneous Materials (flooring, adhesives, roofing, wallboard, etc.) – A minimum of (2) samples are required.
If any one sample of a material from a homogenous area is found to be positive, then that material is considered positive, regardless of results of other samples of that material, within that area.
Samples
A. The Walker Group Architecture collected suspect samples and shipped them to EMSL Analytical, Inc. (NVLAP Accredited Laboratory 102104-0) for PLM (polarized Light Microscopy) analysis. In an effort to reduce cost, the Walker Group instructed the laboratory to Stop Analysis at the first positive sample for each suspect material HGA and not to analyze the remaining samples from the same HGA.
Building 133
Findings
A. Building Description and Findings (Inspected 06-08-16)
Building 133 is used as an office facility currently. The existing exterior is brick and cmu cavity walls with interior wood stud and gypsum walls. The building has a drop down acoustical tile ceiling throughout. The roof consists of wood framing and asphalt shingles
B. Laboratory Results
Material Material
Type Location Friability Laboratory Result Approx.Quantity
Window Caulk Misc. Windows NF Non-Detected N/A
Door Caulk Misc. Exterior Doors NF Non-Detected N/A Asphalt Shingles Misc. Roof NF Non-Detected N/A VCT/ Mastic Misc. Floors NF Non-Detected N/A Rubber Base Mastic Misc. Walls NF Non-Detected N/A Gypsum Board/ Joint Compound
Misc. Walls F Non-Detected N/A
2x2 Acoustical Ceiling Tile
Misc. Ceiling F Non-Detected N/A
Gypsum Trowel Finish Ceiling
Surface Ceiling above Grid. F Non-Detected N/A
Duct Elbow Mudding Misc. Ductwork F Non-Detected N/A
Based on the sample analysis, none of the materials tested were found to be Asbestos Containing Materials.
Building 222
A. Building Description and Findings (Inspected 05-02-19)
Building 222 is an operational office building. The building exterior is brick. Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Concrete Expansion Joint Misc. Exterior NF 10% Chrysotile 400LF Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior NF Non-Detected N/A Textured Gypsum Board Ceiling Surf. Interior NF Non-Detected N/A Asphalt Shingles Misc Interior NF Non-Detected N/A 9x9 Black VCT Misc Interior NF Non-Detected N/A 9x9 Black VCT (Mastic) Misc Interior NF 10% Chrysotile 880SF
Based on the sample analysis, the following materials were found to be Asbestos Containing Materials.
12x12 Cream VCT (Mastic) Roof Membrane and Coating Roof Flashing at Parapet
Materials found to contain asbestos in current inspection report and government provided inspection report should all be considered for the purpose of any demolition/renovation activities and disturbance.
ACM Materials found in previous government report in area of work:
-Exterior Caulking at Doors/Windows – approx. 224LF purpose of any demolition/renovation activities and disturbance.
Building 226
A. Building Description and Findings (Inspected 05-13-20)
Building 226 is an occupied office/storage building. The building exterior is brick.
Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Plaster Walls/Ceiling Surf. Interior Ceiling in Storage areas
NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Black Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A 2x2 ACT Misc. Ceiling NF Non-Detected N/A Cream VCT/Mastic Misc Interior under
Carpet NF Non-Detected N/A
Black Tar on interior Wood Wall Misc Interior Wall NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Asphalt Shingles Misc. Roof NF Non-Detected N/A Sealant at Roof Vents Misc. Roof NF Non-Detected N/A
Based on the sample analysis, none of the materials were found to be Asbestos
Building 402
A. Building Description and Findings (Inspected 05-13-20)
Building 402 is an occupied storage building. The building exterior is brick. Interior
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc. Roof NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Concrete Expansion Joint Misc. Concrete Floor NF Non-Detected N/A
Building 429
A. Building Description and Findings (Inspected 09-15-20)
Building 429 is an unoccupied storage building. The building exterior is brick. Interior
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Concrete Expansion Joint Misc Interior Floor NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A
Additional items were found to be asbestos containing materials on previous government provided reports. See attached Appendix A for further information.
- Transite Panel Material – approx. 20SF
- Concrete Expansion Joint Material- approx. 50LF
- Exterior Caulking- approx. 156LF
Materials found to contain asbestos in current inspection report and
Building 432
C. Building Description and Findings (Inspected 03-11-18)
Building 432 is an organizational storage facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are painted brick with a gypsum board ceiling
D. Laboratory Results
Material Material Type
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A Concrete Expansion Joint Misc Exterior NF 20% Chrysotile 60LF Exterior Window Caulk Misc Exterior NF Non-Detected N/A Gypsum/Joint Compound Misc Interior Wall F Non-Detected N/A 12x12 VCT/Mastic Misc Floor NF Non-Detected N/A Rubber Base/Mastic Misc Wall NF Non-Detected N/A
Concrete Expansion Joint
Building 509
A. Building Description and Findings (Inspected 05-21-20)
Building 509 is an organizational storage and office facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are gypsum board and plaster with acoustical and plaster ceilings.
Interior Plaster Surf. Walls/Ceiling NF Non-Detected N/A
Concrete Expansion Joint Misc Conc. Floor NF Non-Detected N/A Asphalt Shingles Misc. Roof NF Non-Detected N/A Exterior Window Caulk Misc Exterior NF Non-Detected N/A Gypsum/Joint Compound Misc Interior Wall NF Non-Detected N/A Residual Caulk at Brick Misc Exterior Brick NF Non-Detected N/A 12x12 Cream VCT/Mastic Misc Floor NF Non-Detected N/A Rubber Base/mastic Misc Wall Base NF Non-Detected N/A 2x2 ACT Misc Ceilings F Non-Detected N/A Built Up Roof Flashing Misc Flat Roof NF Non-Detected N/A Built Up Roof Misc Flat Roof NF Non-Detected N/A Gray Flashing at Roof Vents Misc Pitched
Roof Vents NF 8% Chrysotile 72SF
Flashing at Roof Vents
- Fibrous Debris – approx. 3SF
- Transite Panel- approx. 6SF
- Roof Sealant at Flat Roof Flashing- approx. 36SF
Materials found to contain asbestos in current inspection report and
Building 824
A. Building Description and Findings (Inspected 03-23-18)
Building 824 is a training readiness facility. The building consists of a pre-fabricated metal building structure with exterior metal panels at the walls and pvc membrane roof.
Interior walls are gypsum board and the ceilings are texture covered gypsum board.
Location Friabilit y
Laboratory Result Approx.Quantit y
12x12 VCT Misc. Interior Floor NF Non-Detected N/A Gypsum Board/Joint Compound Misc. Interior Wall F Non-Detected N/A Rubber Base/Mastic Misc. Interior NF Non-Detected N/A Ceiling Texture Surface Ceiling F Non-Detected N/A
Building AS849
A. Building Description and Findings (Inspected 04-20-20)
Building AS849 is an operational marine rescue facility. The building exterior is masonry and metal wall panel. Interior partitions are wood framed with gypsum board and the roof is steel framed with a standing seam, membrane roof system and asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
12x12 Beige VCT/Mastic Misc Floor NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Acoustical Ceiling Misc Ceiling F Non-Detected N/A Ext. Masonry Expansion Joint Misc Exterior
Masonry Wall
NF 8% Chrysotile 48LF
Asphalt Shingles Misc Roof NF Non-Detected N/A Rubber Base/Mastic Misc Wall Base NF Non-Detected N/A Gypsum Board/Joint Compound Misc Walls NF Non-Detected N/A
Exterior Masonry Expansion Joint
Additional items were found to be asbestos containing materials on previous
- Drywall & Joint Compound Material- 40SF
Building AS912 & AS913
C. Building Description and Findings (Inspected 04/22/20)
Building AS912 and AS913 is a temporary modular office building. The building exterior is metal paneling with wood framing and the interior is wood framed with gypsum board. The roof is wood framed with asphalt shingles.
D. Laboratory Results
Location Friability Laboratory Result Approx.Quantity
Gypsum Board/Joint Compound Misc. Interior Walls NF Non-Detected N/A Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A Textured Ceiling Misc Interior Ceiling NF Non-Detected N/A 12x12 Cream VCT/Mastic Misc Interior Floor NF Non-Detected N/A
12x12 Cream VCT Mastic (2nd tile type)
Misc Interior Floor NF Non-Detected N/A
12x12 Green VCT/Mastic Misc Interior Floor NF Non-Detected N/A
Building M401
A. Building Description and Findings (Inspected 05-21-20)
Building M401 is an unoccupied office building. The building exterior is stucco and masonry with a wood framed roof with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc. Roof NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A Exterior Door Caulk Misc Exterior Doors NF Non-Detected N/A Exterior Stucco Surf. Exterior Walls NF Non-Detected N/A Carpet & Residual Mastic Misc Interior Floor NF Non-Detected N/A Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A
Additional items were found to be asbestos containing materials on previous
- Exterior Caulking at Windows/Doors- 154LF
Building M402
Building M402 is an occupied office building. The building exterior is stucco and
Location Friability Laboratory Result Approx.Quantity
Exterior Stucco Surf. Roof NF Non-Detected N/A 2x2 ACT Misc Ceiling F Non-Detected N/A 12x12 Cream VCT (Tile Only) Misc Interior Walls NF Non-Detected N/A 12x12 Cream VCT (Mastic Only)
Misc. Interior Floor NF 3% Chrysotile 2000SF
Exterior Door/Window Caulk Misc Exterior Doors NF Non-Detected N/A
12x12 Cream VCT (Mastic Only)
- 12” Beige VCT- 2000SF
Building M408
Building M408 is an occupied storage building. The building exterior is stucco and
Exterior Stucco Surf. Exterior Walls NF Non-Detected N/A Asphalt Shingles Misc Roof NF Non-Detected N/A Transite Panel Ceiling Misc Interior Ceiling NF 30% Chrysotile 1850SF 12x12 Cream VCT/Mastic Misc. Interior Floor NF Non-Detected N/A Exterior Door/Window Caulk Misc Exterior Doors NF Non-Detected N/A
Transite Panel Ceiling
Building TC562
Building TC562 is an operational storage/supply building. The building consists of a metal structure with metal wall panels and a standing seam metal roof. The interior floor is sealed concrete.
Location Friability Laboratory Result Approx.Quantity
Concrete Expansion Joint Misc. Expansion Joint at interior Concrete
Based on the sample analysis, none of the materials were found to be Asbestos Containing
- Window Glazing Material – approx. 3LF
- Debris- approx. 3SF
Materials found to contain asbestos in current inspection report and
Building TC804
A. Building Description and Findings (Inspected 02-02-18)
Building TC804 is an academic instruction facility. The building exterior is cmu cavity walls. The roof consists of wood framing and asphalt shingles. Interior walls are steel stud framed and cmu. The building has a gypsum board ceiling throughout.
Location Friability Laboratory Result Approx.Quantit y
VCT cream with specks Misc Floor NF Non-Detected N/A Gypsum/joint compound Misc Interior Walls F Non-Detected N/A Exterior door/window sealant Misc Exterior window/doors
Asphalt shingles/felt Misc Roof NF Non-Detected N/A Roofing sealant at exhaust fan Misc Roof NF 8% Chrysotile 8SF
Notes: TSI-Thermal Systems Insulation Surface-Surfacing Material Misc.- Miscellaneous Material F-Friable NF-Non-Friable
Containing Materials:
Roofing sealant at exhaust fans
Building TC1005
Building TC1005 is an abandoned office building. The building exterior is masonry.
Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc. Exterior Walls NF Non-Detected N/A 12x12 Cream VCT (VCT Only) Misc Interior Floor NF Non-Detected N/A 12x12 Cream VCT (Mastic Only)
Misc Interior Floor NF 3% Chrysotile 3200SF
Gypsum Board/Joint Compound Misc Ceilings NF Non-Detected N/A Rubber Base/Mastic Misc Exterior
Windows NF Non-Detected N/A
Exterior Expansion Joint at Pilaster
Misc Roof NF 3% Chrysotile 40LF
Sealant at Roof Vents Misc Roof NF 5% Chrysotile 12SF
12x12 Cream VCT (Mastic Only) Exterior Expansion Joint at Pilaster Sealant at Roof Vents
- Residual Mastic – approx. 3200SF
- Transite Panel Material in attic- approx. 6SF
Materials found to contain asbestos in current inspection report and
Disposal
A. In accordance with the NCHHCU regulations, asbestos containing materials (ACM) waste should be taken to an approved landfill. All demolition/renovation work must be performed in accordance with NESHAP asbestos regulations, 40CFR61, Subpart M, and OSHA Regulations 29 CFR 1926.1101. Any disturbance should be conducted in accordance with federal, state, and local regulations.
Recommendations
A. Any demolition/renovation work in which ACM is disturbed must be in compliance with, EPA, OSHA and the state of North Carolina regulations.
Abatement work shall be conducted by NC Accredited asbestos workers under the supervision of a NC accredited asbestos supervisor. The contractor conducting asbestos abatement activities must notify the North Carolina Department of Health and Human Services (HHS) ten (10) days prior to the disturbance of ACM if it is friable and greater than or equal to 160 square feet, 260 linear feet or 35 cubic feet.
B. If additional suspect materials are discovered during demolition/renovation, they should be classified presumed to be asbestos-containing until sampling by a state of North Carolina licensed Asbestos Building Inspector personnel and analysis by a NVLAP-Accredited and state of North Carolina licensed laboratory can be performed.
See attached for Accreditations, Asbestos Lab Results and Chain of Custody. If further information is required, please contact me at 1-252-636-8778
Report Prepared by:
Christopher B. Walker North Carolina Asbestos Inspector Accreditation# 12878 The Walker Group Architecture, Inc., PO Box 541, New Bern, NC 28560
DRAWING NO.DATE
DRAWN BY
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 222
MCB CAMP LEJEUNE
1/16"=1'-0"
09-28-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\222\222.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN BLACK VCT MASTIC APPROX. 880SF.
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN EXPANSION JOINT MATERIAL AT PERIMETER AND CENTER SLAB JOINTS, TYPICAL APPROX, 400LF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\432\432.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 432
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXPANSION JOINT MATERIAL
LINE INDICATES ASBESTOS IDENTIFIED IN CONCRETE EXPANSION JOINT.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 509
MCB CAMP LEJEUNE
1/64"=1'-0"
09-28-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\509\509-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
ROOF SEALANT AT MECHANICAL VENTS ON ROOF - APPROX. 72SF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING AS849
MCB CAMP LEJEUNE
3/32"=1'-0"
05/08/20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\AS849\AS849.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS LOCATED IN MASONRY EXPANSION JOINTS AROUND PERIMETER OF BUILDING. APPROX. 48LF
*SEE GOV'T ASBESTOS REPORT AND PLAN FOR ADDITIONAL ASBESTOS CONTAINING MATERIAL LOCATIONS
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING M402
MCB CAMP LEJEUNE
1/16"=1'-0"
09-28-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\M402\M402.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
12x12 CREAM VCT (MASTIC ONLY) - APPROX. 2000SF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING M408
MCB CAMP LEJEUNE
1/16"=1'-0"
09-28-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\M408\M408.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
TRANSITE PANEL CEILING - APPROX. 1850SF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\TC804\TC804.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING TC804
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN ROOF SEALANT AT EXHAUST VENT
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN ROOFING SEALANT AT EXHAUST FANS, APPROX. 8SF.
DRAWING NO.
GROUP
ARCHITECTURE
WALKER
th e DATE
DRAWN BY
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING TC1005
MCB CAMP LEJEUNE
N.T.S
05-11-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package E\TC1005\TC1005.dwg
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN ROOFING SEALANT AT EXHAUST FANS, APPROX. 12SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN ROOF SEALANT AT EXHAUST VENT
AutoCAD SHX Text *SEE GOV'T ASBESTOS REPORT AND PLAN FOR ADDITIONAL ASBESTOS CONTAINING MATERIAL LOCATIONS
AutoCAD SHX Text
12X12 CREAM VCT (MASTIC ONLY) - APPROX. 3200SF
AutoCAD SHX Text
EXTERIOR EXPANSION JOINT AT PILASTER- APPROX. 40LF
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN PILASTER EXPANSION JOINTS. APPROX. 40LF
EMSL Analytical, Inc.
706 Gralin Street Kernersville, NC 27284
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021604144EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 06/27/2016 11:45 AM
Analysis Date:New Bern, NC 28563 06/28/2016 - 06/29/2016
Collected Date: 06/08/2016
Project: Building 133
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021604144-0001
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
Window Caulk
021604144-0002
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
Window Caulk
021604144-0003
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Cellulose<1%White
Non-Fibrous
Homogeneous
Door Caulk
021604144-0004
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
White
Non-Fibrous
Homogeneous
Door Caulk
021604144-0005
None DetectedNon-fibrous (Other)95%Glass5%Brown/Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
Composite Result
021604144-0006
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Brown/Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
Composite Result.
021604144-0007
None DetectedQuartz
Non-fibrous (Other)
20%
80%
Gray/White
Non-Fibrous
Homogeneous
VCT/Mastic
White/Blue Streaks
No mastic present
08-Floor Tile
021604144-0008
None DetectedQuartz
Non-fibrous (Other)
20%
80%
White/Blue/Beige
Non-Fibrous
Homogeneous
VCT/Mastic
White/Blue Streaks
08-Mastic
021604144-0008A
None DetectedNon-fibrous (Other)100%Cellulose<1%Yellow/Gold
Non-Fibrous
Homogeneous
VCT/Mastic
White/Blue Streaks
021604144-0009
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan
Non-Fibrous
Homogeneous
Base Mastic
021604144-0010
None DetectedNon-fibrous (Other)100%Cellulose<1%Beige
Non-Fibrous
Homogeneous
Base Mastic
021604144-0011
None DetectedCa Carbonate
Non-fibrous (Other)
5%
90%
Cellulose5%Brown/Gray/White
Fibrous
Heterogeneous
Gyp/Joint
Composite Result
021604144-0012
None DetectedCa Carbonate
Non-fibrous (Other)
5%
75%
Cellulose20%Brown/Gray/White
Fibrous
Heterogeneous
Gyp/Joint
Composite Result.
021604144-0013
None DetectedPerlite
Non-fibrous (Other)
20%
10%
Cellulose
Min. Wool
30%
40%
Gray/Tan/White
Fibrous
Heterogeneous
2x2 ACT
Initial Report From: 06/29/2016 13:13:39
Page 1 of 2ASB_PLM_0008 - 1.71 Printed: 6/29/2016 1:13 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021604144EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021604144-0014
None DetectedPerlite
Non-fibrous (Other)
30%
10%
Cellulose
Min. Wool
45%
15%
Gray/Tan
Fibrous
Homogeneous
2x2 ACT
021604144-0015
None DetectedCa Carbonate
Non-fibrous (Other)
30%
70%
White
Non-Fibrous
Homogeneous
GYP Trowel Finish
Ceiling
021604144-0016
None DetectedCa Carbonate
Non-fibrous (Other)
30%
70%
White
Non-Fibrous
Homogeneous
GYP Trowel Finish
Ceiling
021604144-0017
None DetectedCa Carbonate
Non-fibrous (Other)
30%
70%
Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
GYP Trowel Finish
Ceiling
021604144-0018
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan
Non-Fibrous
Homogeneous
Duct Elbow Mudding
021604144-0019
None DetectedNon-fibrous (Other)100%Cellulose<1%Beige
Non-Fibrous
Homogeneous
Duct Elbow Mudding
Analyst(s)
Nicole Shutts (10)
Scott Combs (10)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial Report From: 06/29/2016 13:13:39
Page 2 of 2ASB_PLM_0008 - 1.71 Printed: 6/29/2016 1:13 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021903032EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 05/02/2019 11:30 AM
Analysis Date:New Bern, NC 28563 05/03/2019 - 05/06/2019
Collected Date: 04/30/2019
Project: Bldg 222
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021903032-0001
10% ChrysotileNon-fibrous (Other)85%Cellulose5%Brown/Black
Fibrous
Heterogeneous
Concrete Expansion
Joint
021903032-0002
Positive Stop (Not Analyzed)Concrete Expansion
Joint
021903032-0003
None DetectedNon-fibrous (Other)100%Gray/Red/Black
Non-Fibrous
Homogeneous
Exterior Door/
Window Caulk
021903032-0004
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray/Red/Rust
Non-Fibrous
Homogeneous
Exterior Door/
Window Caulk
021903032-0005
None DetectedCa Carbonate
Non-fibrous (Other)
5%
53%
Cellulose
Glass
40%
2%
Brown/White/Beige
Fibrous
Heterogeneous
Gypsum Board/ Joint
Compound
Composite result
021903032-0006
None DetectedCa Carbonate
Non-fibrous (Other)
5%
69%
Cellulose
Glass
25%
1%
Brown/Gray/White
Fibrous
Heterogeneous
Gypsum Board/ Joint
Compound
Composite result.
021903032-0007
None DetectedCa Carbonate
Mica
Non-fibrous (Other)
5%
20%
75%
White/Beige
Non-Fibrous
Homogeneous
Textured Gypsum
Board Ceiling
021903032-0008
None DetectedCa Carbonate
Mica
Non-fibrous (Other)
5%
20%
75%
White/Beige
Non-Fibrous
Homogeneous
Textured Gypsum
Board Ceiling
021903032-0009
None DetectedCa Carbonate
Mica
Non-fibrous (Other)
5%
20%
75%
White/Beige
Non-Fibrous
Homogeneous
Textured Gypsum
Board Ceiling
021903032-0010
None DetectedCa Carbonate
Mica
Non-fibrous (Other)
5%
20%
75%
White/Beige
Non-Fibrous
Homogeneous
Textured Gypsum
Board Ceiling
021903032-0011
None DetectedCa Carbonate
Mica
Non-fibrous (Other)
5%
20%
75%
Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
Textured Gypsum
Board Ceiling
021903032-0012
None DetectedNon-fibrous (Other)92%Glass8%Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
021903032-0013
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Brown/Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
14-Floor Tile
021903032-0014
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Black
Non-Fibrous
Homogeneous
9x9 Black VCT/Mastic
14-Mastic
021903032-0014A
8% ChrysotileNon-fibrous (Other)92%Black
Non-Fibrous
Homogeneous
9x9 Black VCT/Mastic
Initial report from: 05/06/2019 14:59:53
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/6/2019 2:59 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021903032EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
15-Floor Tile
021903032-0015
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Black
Non-Fibrous
Homogeneous
9x9 Black VCT/Mastic
15-Mastic
021903032-0015A
Positive Stop (Not Analyzed)9x9 Black VCT/Mastic
Analyst(s)
Nicole Shutts (10)
Scott Combs (5)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 05/06/2019 14:59:53
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/6/2019 2:59 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002860EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 05/18/2020 8:00 PM
Analysis Date:New Bern, NC 28563 05/19/2020 - 05/20/2020
Collected Date:
Project: 226
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
022002860-0001
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0002
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0003
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0004
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0005
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0006
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0007
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0008
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Tan/Beige
Non-Fibrous
Heterogeneous
Plaster Wall/Ceiling
022002860-0009
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
40%
10%
50%
Cellulose<1%Tan
Non-Fibrous
Homogeneous
Plaster Wall/Ceiling
022002860-0010
None DetectedCa Carbonate
Non-fibrous (Other)
10%
80%
Cellulose10%Brown/Gray/White
Fibrous
Heterogeneous
Gypsum Board/ Joint
Compound
Composite Result.
022002860-0011
None DetectedCa Carbonate
Non-fibrous (Other)
5%
83%
Cellulose12%Brown/Gray/White
Fibrous
Homogeneous
Gypsum Board/ Joint
Compound
Composite Result.
022002860-0012
None DetectedNon-fibrous (Other)100%Cellulose<1%White/Black/Yellow
Non-Fibrous
Heterogeneous
Black Rubber base/
Mastic
Composite Result.
022002860-0013
None DetectedNon-fibrous (Other)100%Cellulose<1%Black/Beige
Non-Fibrous
Homogeneous
Black Rubber base/
Mastic
Composite Result.
022002860-0014
None DetectedPerlite
Non-fibrous (Other)
40%
12%
Cellulose
Glass
45%
3%
Gray/Tan/White
Fibrous
Homogeneous
2x2 ACT
022002860-0015
None DetectedPerlite
Non-fibrous (Other)
40%
10%
Cellulose
Min. Wool
45%
5%
Tan/White
Fibrous
Homogeneous
2x2 ACT
Initial report from: 05/20/2020 14:07:26
Page 1 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/20/2020 2:07 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002860EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
16-Top Mastic
022002860-0016
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan/Yellow
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
16-Top Tile
022002860-0016A
None DetectedQuartz
Non-fibrous (Other)
30%
70%
White
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
16-Mastic Between Tiles
022002860-0016B
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
16-Bottom Tile
022002860-0016C
None DetectedQuartz
Non-fibrous (Other)
30%
70%
White/Beige
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
16-Bottom Mastic
022002860-0016D
None DetectedNon-fibrous (Other)97%Cellulose3%Black
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
17-Top Mastic
022002860-0017
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
17-Top Tile
022002860-0017A
None DetectedQuartz
Non-fibrous (Other)
25%
75%
White
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
17-Mastic Between Tiles
022002860-0017B
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
17-Bottom Tile
022002860-0017C
None DetectedQuartz
Non-fibrous (Other)
25%
75%
White
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
17-Bottom Mastic
022002860-0017D
None DetectedNon-fibrous (Other)98%Cellulose2%Black
Non-Fibrous
Homogeneous
Cream VCT/ Mastic under Carpet
022002860-0018
None DetectedNon-fibrous (Other)100%Cellulose
Glass
<1%
<1%
Black
Non-Fibrous
Homogeneous
Black Tar on Interior
Wood Wall
022002860-0019
None DetectedNon-fibrous (Other)100%Cellulose
Glass
<1%
<1%
Black
Non-Fibrous
Homogeneous
Black Tar on Interior
Wood Wall
022002860-0020
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Gray/White/Beige
Non-Fibrous
Homogeneous
Ext. Door/ Window
Caulk
022002860-0021
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Gray/White
Non-Fibrous
Homogeneous
Ext. Door/ Window
Caulk
022002860-0022
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Gray/Black
Fibrous
Heterogeneous
Asphalt Shingle
022002860-0023
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Gray/Black
Fibrous
Homogeneous
Asphalt Shingle
022002860-0024
None DetectedNon-fibrous (Other)95%Cellulose5%Black
Fibrous
Homogeneous
Sealant at Roof Vent
022002860-0025
None DetectedNon-fibrous (Other)95%Cellulose5%Black
Fibrous
Homogeneous
Sealant at Roof Vent
Page 2 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/20/2020 2:07 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002860EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Analyst(s)
Kristie Elliott (13)
Scott Combs (20)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Page 3 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/20/2020 2:07 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002985EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 05/26/2020 8:00 AM
Analysis Date:New Bern, NC 28563 05/27/2020
Collected Date:
Project: 402
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
022002985-0001
None DetectedNon-fibrous (Other)95%Glass5%Brown/Gray/Black
Fibrous
Homogeneous
Asphalt Shingles/Felt
No Felt Present
022002985-0002
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Brown/Tan/Black
Fibrous
Heterogeneous
Asphalt Shingles/Felt
No Felt Present.
022002985-0003
None DetectedNon-fibrous (Other)89%Cellulose
Glass
10%
1%
Brown/Gray
Fibrous
Homogeneous
Gypsum Board/Joint
Compound
No Joint Compound Present
022002985-0004
None DetectedNon-fibrous (Other)94%Cellulose
Glass
5%
1%
Brown/Gray
Fibrous
Heterogeneous
Gypsum Board/Joint
Compound
No Joint Compound Present.
022002985-0005
None DetectedNon-fibrous (Other)100%Cellulose<1%Gray/Beige
Non-Fibrous
Homogeneous
Ext. Door/Window
Caulk
022002985-0006
None DetectedNon-fibrous (Other)100%Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
Ext. Door/Window
Caulk
022002985-0007
None DetectedNon-fibrous (Other)90%Cellulose10%Brown/Black
Fibrous
Homogeneous
Concrete Expansion
Joint
022002985-0008
None DetectedQuartz
Non-fibrous (Other)
30%
69%
Cellulose1%Gray/Green/Rust
Non-Fibrous
Heterogeneous
Concrete Expansion
Joint
Analyst(s)
Kristie Elliott (4)
Scott Combs (4)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 05/28/2020 08:27:30
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 5/28/2020 8:27 AM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022005519EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 09/22/2020 10:00 AM
Analysis Date:New Bern, NC 28563 09/22/2020
Collected Date:
Project: 429
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
022005519-0001
None DetectedNon-fibrous (Other)92%Glass8%Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
022005519-0002
None DetectedNon-fibrous (Other)94%Cellulose
Glass
<1%
6%
Gray/Black
Fibrous
Homogeneous
Asphalt Shingles
022005519-0003
None DetectedNon-fibrous (Other)94%Cellulose6%Black
Fibrous
Homogeneous
Interior Expansion
Joint at concrete floor
022005519-0004
None DetectedNon-fibrous (Other)88%Cellulose12%Brown/Black
Non-Fibrous
Homogeneous
Interior Expansion
Joint at concrete floor
022005519-0005
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Beige
Non-Fibrous
Homogeneous
Exterior Door Window
Caulk
022005519-0006
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Gray/Tan/White
Non-Fibrous
Homogeneous
Exterior Door Window
Caulk
Analyst(s)
Cameron Evans (3)
Ryan Rains (3)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 09/23/2020 09:06:51
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 9/23/2020 9:06 AM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021801829EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 03/15/2018 1:45 PM
Analysis Date:New Bern, NC 28563 03/19/2018 - 03/20/2018
Collected Date: 03/11/2018
Project: Installation Reset FY18 - Building 432
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021801829-0001
None DetectedNon-fibrous (Other)92%Cellulose
Glass
<1%
8%
Brown/Black/Green
Fibrous
Heterogeneous
Asphalt Shingles/Felt
021801829-0002
None DetectedNon-fibrous (Other)92%Cellulose
Glass
<1%
8%
Gray/Black/Beige
Fibrous
Heterogeneous
Asphalt Shingles/Felt
021801829-0003
20% ChrysotileNon-fibrous (Other)77%Cellulose3%Brown/Black
Fibrous
Homogeneous
Concrete Expansion
Joint
021801829-0004
Positive Stop (Not Analyzed)Concrete Expansion
Joint
021801829-0005
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Cellulose<1%White/Beige
Non-Fibrous
Homogeneous
Exterior Window
Caulk
021801829-0006
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Cellulose<1%Beige
Non-Fibrous
Heterogeneous
Exterior Window
Caulk
021801829-0007
None DetectedCa Carbonate
Non-fibrous (Other)
5%
74%
Cellulose
Glass
20%
1%
Brown/Gray/White
Fibrous
Heterogeneous
Gypsum/Joint
Compound
Wall System Composite.
021801829-0008
None DetectedCa Carbonate
Non-fibrous (Other)
5%
83%
Cellulose
Glass
10%
2%
Gray/White/Black
Fibrous
Heterogeneous
Gypsum/Joint
Compound
Wall System Composite.
021801829-0009
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Cellulose<1%Gray/Yellow
Non-Fibrous
Heterogeneous
12x12 VCT/Mastic
021801829-0010
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Cellulose<1%Gray/Tan
Non-Fibrous
Homogeneous
12x12 VCT/Mastic
021801829-0011
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Rubber Base/Mastic
No Mastic Present.
021801829-0012
None DetectedNon-fibrous (Other)100%Cellulose<1%Black/Beige
Non-Fibrous
Heterogeneous
Rubber Base/Mastic
Initial report from: 03/20/2018 08:26:30
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 3/20/2018 8:26 AM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021801829EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Analyst(s)
Stephen Bennett (5)
Scott Combs (6)
Stephen Bennett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Kernersville, NC NVLAP Lab Code 102104-0, CA ELAP 2689, Virginia 3333-000228, West Virginia LT000321
Initial report from: 03/20/2018 08:26:30
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 3/20/2018 8:26 AM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002982EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 05/26/2020 8:00 AM
Analysis Date:New Bern, NC 28563 06/03/2020 - 06/04/2020
Collected Date:
Project: 509
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
022002982-0001
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Gray/Tan/White
Non-Fibrous
Heterogeneous
Int. Plaster
Composite Result.
022002982-0002
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Gray/Tan/White
Non-Fibrous
Heterogeneous
Int. Plaster
022002982-0003
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
44%
Cellulose1%Gray/Tan
Non-Fibrous
Heterogeneous
Int. Plaster
022002982-0004
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Gray/Tan/White
Non-Fibrous
Heterogeneous
Int. Plaster
Composite Result.
022002982-0005
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Gray/Tan
Non-Fibrous
Heterogeneous
Int. Plaster
022002982-0006
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Gray/Tan
Non-Fibrous
Heterogeneous
Int. Plaster
022002982-0007
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
45%
10%
45%
Cellulose<1%Gray/Tan/White
Non-Fibrous
Heterogeneous
Int. Plaster
022002982-0008
None DetectedNon-fibrous (Other)90%Cellulose10%Brown/Gray
Fibrous
Heterogeneous
Int. Plaster
Sample Matrix Appears to be Drywall.
022002982-0009
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
40%
10%
50%
Cellulose<1%Gray/Tan/White
Non-Fibrous
Homogeneous
Int. Plaster
022002982-0010
None DetectedQuartz
Non-fibrous (Other)
30%
40%
Cellulose
Synthetic
30%
<1%
Brown/Gray/Tan
Fibrous
Heterogeneous
Expansion Joint at
Concrete Floor
022002982-0011
None DetectedQuartz
Non-fibrous (Other)
30%
40%
Cellulose
Synthetic
30%
<1%
Brown/Black
Fibrous
Homogeneous
Expansion Joint at
Concrete Floor
022002982-0012
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Gray/Black
Fibrous
Heterogeneous
Asphalt Shingles
022002982-0013
None DetectedNon-fibrous (Other)95%Cellulose
Glass
<1%
5%
Gray/Black
Fibrous
Homogeneous
Asphalt Shingles
022002982-0014
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Gray/Beige
Non-Fibrous
Homogeneous
Ext. Window/Door
Caulk
022002982-0015
None DetectedNon-fibrous (Other)100%Cellulose<1%White
Non-Fibrous
Homogeneous
Ext. Window/Door
Caulk
Initial report from: 06/04/2020 17:53:24
Page 1 of 3ASB_PLM_0008_0001 - 1.78 Printed: 6/4/2020 5:53 PM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
022002982EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID: