J-1502000.pdf
PDF 2 MB Posted
- Solicitation number
- N4008519R9243
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N40085-19-R-9243 0005.pdf | ||
| ELINS J-0200000-17 Revised.xlsx | XLSX spreadsheet | |
| 1502000 C Revised.docx | DOCX document | |
| N40085-19-R-9243 0004.pdf | ||
| J-0200000-17-ELINs Revised.xlsx | XLSX spreadsheet | |
| N40085-19-R-9243 0003.pdf | ||
| N40085-19-R-9243 Site visit List of Attendees.pdf | ||
| N40085-19-R-9243 0002.pdf | ||
| N40085-19-R-9243- 0001.pdf | ||
| SECNAV_ 5512_1.pdf | ||
| J- 1501000.pdf | ||
| J-0200000-17-ELINs.xlsx | XLSX spreadsheet | |
| J- 0200000.pdf | ||
| N40085-19-R-9243 RFP.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION J
DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS
TABLE OF CONTENTS
ATTACHMENT NUMBER ATTACHMENT TITLE
J-1502000-01 Definitions and Acronyms
J-1502000-02 References and Technical Documents
J-1502000-03 Norfolk Naval Shipyard Portsmouth Distribution Facility Inventory
J-1502000-04 Reserved
J-1502000-05 Reserved
J-1502000-05-01 Reserved
J-1502000-05-02 Reserved
J-1502000-05-03 Reserved
J-1502000-05-04 Reserved
J-1502000-05-05 Reserved
J-1502000-05-06 Reserved
J-1502000-06 Reserved
J-1502000-07 Emergency Generator And Electrical Distribution Systems Inventory For PM NAS Oceana, Building NX101 NEXCOM Beverly Building., Virginia Beach
J-1502000-08 Emergency Generator And Electrical Distribution Systems Inventory For PM Naval Weapons Station Yorktown
J-1502000-09 Emergency Generator System Equipment Inventory For PM Norfolk Naval Shipyard Portsmouth
J-1502000-10 Monthly Tank Inspection Checklist
J-1502000-11 Historical IMP Repairs
J-1502000-12 HVAC And Refrigeration System Inventory For IMP Naval Station Norfolk Building W143
J-1502000-13 Control System Inventory For IMP Naval Station Norfolk Building W143
J-1502000-14 Compressed Air Systems Inventory For IMP Naval Station Norfolk Building W143
J-1502000-15 Chill Water Flow Diagram Naval Station Norfolk Building W143
J-1502000-16 Condenser Water Flow Diagram Naval Station Norfolk Building W143
J-1502000-17 Emergency Generator And Electrical Distribution Inventory For IMP Naval Station Norfolk Building W143
J-1502000-18 Temperature Standards Naval Station Norfolk Building W143
J-1502000-19 HVAC Water Testing and Treatment Services Inventory Naval Station Norfolk Building W143
ATTACHMENT J-1502000-01
DEFINITIONS AND ACRONYMS
DEFINITION DESCRIPTION
ADJUSTING The varying of system flows by partially opening and closing balancing devices, such as dampers and valves, and varying fan speeds to achieve optimum system operating conditions within design and installation limitations.
BALANCING The methodical proportioning of flows through a system mains, branches, and terminal devices using acceptable procedures to achieve the specified airflow within installation, testing and design limitations.
CRANE, CATEGORY 1 Portal cranes, Hammerhead cranes, Locomotive cranes, Derricks, Floating cranes (YD), Tower cranes, Container cranes, Mobile cranes (except those indicated as category 4), including truck, cruiser, crawler, warehouse/industrial cranes, and cranes used for dragline, pile driving, clamshell, magnet, bucket work, and Aircraft crash cranes.
CRANE, CATEGORY 2 & 3 Cranes with rated capacities of 20,000 pounds or greater are category 2.
Examples are Over head traveling cranes, Gantry cranes (rail mounted), Wall cranes, Jib cranes, Pillar cranes, Pillar jib cranes, Monorails and associated hoists, Fixed hoists, including chain falls. Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities less than 2,000 pounds.
CRANE, CATEGORY 4 Commercial truck mounted cranes, Truck mounted articulating boom cranes, Pedestal mounted commercial boom assemblies (fixed length, telescoping, and articulating types) attached to stake trucks, trailers, flatbeds, or railcars, or stationary mounted to piers, etc., with OEM rated capacities of 2,000 pounds and greater. Commercial truck mounted cranes and truck mounted articulating boom cranes with OEM capacities of 2,000 pounds and greater require a licensed operator even if the cranes are down rated below 2,000 pounds capacity for administrative purposes.
DEBRIS Undesirable or discarded material including but not limited to rocks, paper, cans and bottles, otherwise referred to as trash and litter. Includes cut or trimmed vegetation, grass clippings, fallen tree limbs, twigs, leaves, pine straw, seedlings, and dirt deposited in gutters. Also includes waste generated by maintenance, repair and construction operations including roofing work.
Does not include hazardous waste.
EQUIPMENT, COLLATERAL Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.
EQUIPMENT, INSTALLED Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.
EQUIPMENT, PERSONAL
PROPERTY
Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed aster erection or installation without substantial loss of value or damage thereto or to the premises where installed.
DEFINITION DESCRIPTION
FACILITIES LIFE CYCLE A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
FACILITIES MAINTENANCE
MANAGEMENT
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
INTEGRATED MAINTENANCE
PROGRAM (IMP)
IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness. Service calls will not be issued for accomplishment of repairs on systems and equipment maintained under IMP.
LIFE-CYCLE COSTS A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
MAINTENANCE,
PREVENTIVE
Maintenance designed to increase the availability of the facilities/equipment by reducing the number of unexpected breakdowns or service interruptions. It is any planned maintenance activity that improves equipment life and avoid any unplanned maintenance requirements.
MANAGEMENT
INFORMATION SYSTEMS-
MAINTENANCE
A computerized system that will provide sufficient information for management to evaluate differences between budgets and actual costs and evaluate performance.
REPAIR Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition.
REPLACEMENT Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.
RESTORATION Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.
DEFINITION DESCRIPTION
SERVICE ORDER Any work required to return a facility, system, equipment or component to normal working condition. Service orders are minor facility problem requests or requests for other non-recurring work that is too small to be planned and estimated.
The purpose of a service order is to provide the Government with a means of issuing work up to a defined liability limit for requirements occurring outside of the specified recurring work. The Government may utilize service orders to accomplish any work up to the respective liability limit based on the service order classification.
SERVICE ORDER CYCLE Count down starts when the customer is notified that the work has been accepted to be accomplished to the time when the work chit is turned in by the craftsmen as complete is one complete cycle period for a service order.
SERVICE ORDER,
EMERGENCY
Emergency is defined as any facility deficiency that immediately compromises the mission or life, health and safety. Always includes, but is not limited to, failure of any utility, fire protection, environmental control, or security alarm systems.
SUSTAINMENT Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.
TESTING Utilizing specialized and calibrated instruments to measure temperature, pressure, vapor flow, airflow, fluid flow, fluid quantities, rotational speed, electrical characteristics, velocity, sound and vibration level, air and hydronic quantities, and other data to determine performance.
TESTING, ADJUSTING and
BALANCING (TAB)
A process applied to HVAC systems, water systems and other environmental systems, to achieve and document flow rates.
WEIGHT HANDLING
EQUIPMENT (WHE)
Weight handling equipment consists of cranes (e.g., portal cranes, jib cranes), rigging gear (e.g., slings, shackles), and associated equipment (e.g., portable hoists, dynamometers). For purposes of this technical sub-annex, WHE does not include mobile or transportable truck, crawler, and railway mounted locomotive cranes covered in 1700000 BSVE.
Acronym Title ASHRAE American Society of Heating, Refrigerating and Air Conditioning
Engineers CFC Chlorofluorocarbons EPA Environmental Protection Agency HAZMAT Hazardous Material HAZWASTE Hazardous Waste HCFCs Hydro-Chlorofluorocarbons HVAC Heating, Ventilation, and Air Conditioning ICAP Infrastructure Condition Assessment Program IMP Integrated Maintenance Program NAVFAC Naval Facilities Engineering Command OEM Original Equipment Manufacturer PM Preventative Maintenance SRM Sustainment, Restoration and Modernization UFC Unified Facilities Criteria WHE Weight Handling Equipment
ATTACHMENT J-1502000-02
REFERENCES AND TECHNICAL DOCUMENTS
Reference Title NAVFAC P-307 Management of Weight Handling Equipment UFC 3-410-01 Heating, Ventilating and Air Condition UFC 3-430-07 Operations and Maintenance: Inspection and Certification of Boilers and
Unfired Pressure Vessels UFC 3-560-01 Electrical Safety
ATTACHMENT J-1502000-03
NORFOLK NAVAL SHIPYARD PORTSMOUTH DISTRIBUTION FACILITY INVENTORY
Facility Number Facility Description Facility Size Construction
Date 1604 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
1605 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
1606 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
1607 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
1608 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
1609 Electrical Distribution Building 20-FT X 13-FT X 10-FT 15-June-2005
Building 1733 Uninterruptable Power Supply System
ATTACHMENT J-1502000-06
HISTORICAL SERVICE ORDER WORKLOAD
Labor Categories
Emergency Service Orders (received during Government regular working hours)
Emergency Service Orders (received after Government regular working hours)
Urgent Service Orders Routine Service Orders
Number of Calls
Avg Hrs to Complete
Number of Calls
Avg Hrs to Complete
Number of Calls
Avg Hrs to Complete
Number of Calls
Avg Hrs to Complete
Electrical Carpentry Plumbing Painting Sheet metal Signage
Total Service Orders
ATTACHMENT J-1502000-07
EMERGENCY GENERATOR AND ELECTRICAL DISTRIBUTION SYSTEMS INVENTORY FOR PM NAS
OCEANA, BUILDING NX101 NEXCOM BEVERLY BUILDING., VIRGINIA BEACH
Location Manufacturer Type of Equipment Model No. Quantity Other Information
Ground Level in a closed and locked room Building
NX101
Caterpillar Diesel Generator 3512 1 1250 KW
Mechanical Room (M1) Building
NX101
SQUARE-D
Automatic transfer switch (ATS1) 1200 amp 480 volt located on northwest wall mechanical room
Fuel Storage Tank
Steel Double Bottom Double Wall
1 2200 GL
Fuel Storage Tank Double Wall Steel
1 5000 GL
ATTACHMENT J-1502000-08
EMERGENCY GENERATOR AND ELECTRICAL DISTRIBUTION SYSTEMS INVENTORY FOR PM
NAVAL WEAPONS STATION YORKTOWN
Location Manufacturer Type of
Equipment Model No. Quantity Asset # Tank Type Gallons
Other Information
CHEANN-CAD109 GENERAC
Diesel
Generator
SD25 1 600661
Belly Double Wall
54 25 KW
CHEANN-CAD119 OLYMPIAN
Diesel
Generator 96A05558-S 1 602654
Belly Double Wall
190 40 KW
CHEANN-CAD270
Left side of Bldg. 270
KOHLER
Diesel
Generator
20REOZJB 1 708238
Belly Double Wall
60 25 KW
CHEANN-CAD483
Left of front entrance
GENERAC
Natural Gas Generator
E13.3MSN34
9A2
1 700077 Tied into base gas line
N/A 300 KW
CHEANN-CAD483
Left of front entrance
GENERAC
Natural Gas Generator
E13.3MSN34
9A2
1 700076 Tied into base gas line
N/A 300 KW
CHEANN-CAD504
Northside of Bldg.
CUMMINS
Natural Gas Generator
GGHE-
1507079
1 709102 Tied into base gas line
N/A 60 KW
CHEANN-CAD513
Right side of Gate 1 when entering
KOHLER
Diesel Generator
20REOZJB 1 708232
Belly
Double Wall
60 25 KW
CHEANN-CAD564
Rear parking lot
CUMMINS
Natural Gas Generator
GGHE-
1507079
1 709100 Tied into base gas line
N/A 60 KW
CHEANN-CAD565
North west corner of
Bldg.
CUMMINS
Natural Gas Generator
GGHH-
1711189
1 709101 Tied into base gas line
N/A 100 KW
YORK-1351
Back of Bldg.
CATERPILLAR
Diesel
Generator
2717970100 1 BA2600194
Belly Double Wall
275 KW
Above Ground Single Wall
YORK-1595
Back of Bldg.
MTU
Diesel
Generator
DS00500D6S
RAH1483
1 704509
Above Ground Double Wall
5000 500 KW
YORK-1806
Right side of Bldg. 1806
GENERAC
Diesel
Generator 89A03442-S 1 708211
Belly Double Wall
150 KW
Above Ground Double Wall
YORK-1808
Right side, Back of Bldg.
CATERPILLAR
Diesel
Generator
SR4B 3406C 1 708218
Belly Double Wall
600 300 KW
YORK-1816
Left side of Bldg.
CATERPILLAR
Diesel
Generator 3406 1 708241
Belly Double Wall
300 300 KW
YORK-1830
When inside Gate 1, On left side (R-3 Pier)
KOHLER
POWER
Diesel Generator
250REOZV 1 708223
Above Ground Single Wall
260 KW
Above Ground Double Wall
YORK-1893
Next to pump station
KOHLER
Diesel
Generator
100RE0ZJF 1 708216
Belly Double Wall
140 100 KW
YORK-1894
Beside pump station
MTU
Diesel
Generator
DS00200D6S
RAK0574
1 706758
Belly Double Wall
370 200 KW
YORK-1896
Next to pump station
OLYMPIAN
Portable Diesel
Generator 96A02043-S 1 A68897 Belly 250 75 KW
Equipment Model No. Quantity Asset # Tank Type Gallons
Other Information
YORK-1958
Next to pump station
MARATHON
Diesel
Generator
284FDR1016
AA W
1 UMA02000407
Above Ground Double Wall
500 62.5 KW
YORK 1959
Small green generator, Back side of Bldg. 1959
ONAN
Diesel Generator
DGFB-
3383146
1 711592 Belly
Double Wall
300 175 KW
YORK-1959
Tan generator nest to cooling tower
KOHLER
POWER
Diesel Generator
500REOZV 1 BA2601235
Belly
Double Wall
650 505 KW
YORK-1973
Front of guardhouse at
Gate 13
KOHLER
POWER
Diesel Generator
20REOZJB 1 708239
Belly
Double Wall
60 20 KW
YORK-2021
Right side of Bldg. 2021
CARERPILLAR
Diesel
Generator
6DA03715 1 708233
Belly Single Wall
350 KW
Above Ground Single Wall
YORK-2086
Back of Bldg. 2086 next to cooling tower
CUMMINS
Diesel Generator
1000DFHD-
5762775
1 708221 Belly
Double Wall
1500 275 KW
YORK-2130
Bldg. 2130 left of Bldg.
KOHLER
POWER
Natural Gas Generator
400REZXB 1 700013
Tied into base gas line N/A
YORK-31
Back of Bldg.
KOHLER
POWER
Diesel Generator
1 BA2602577
Belly
Double Wall
950 100 KW
YORK-376
Rear of Bldg. 376
KOHLER
Diesel
Generator
125REOZJB 1 708242
Belly Double Wall
240 125 KW
YORK-381
Left side of Bldg.
KOHLER
POWER
Diesel Generator
50REOZJB 1 708256
Above Ground
Single Wall
300 50 KW
YORK-461
Right side of Bldg. 461
ONAN
Diesel
Generator
DGGD-
5627303
1 708236 Belly
Double Wall
75 35 KW
YORK-5
Right side of Bldg.
CATERPILLAR
Diesel
Generator
LC6 1 706745
Belly Double Wall
660 50 KW
YORK-702
To the Right of the front entrance to Bldg. 702
OLYMPIAN
Diesel Generator
D200P4 1 708213 Belly
Double Wall
400 200 KW
YORK-2019 (702)
Located at Building 702, Front of Bldg., Right side
KOHLER
POWER
Diesel Generator
50REOZJB 1 706712
Belly
Double Wall
237 50 KW
YORK-703
Genset
KOHLER
Diesel
Generator
125REOZJB 1 12502
Above Ground Double Wall
500 125 KW
YORK-705
Rear of Bldg. 705
CATERPILLAR
Diesel
Generator
3406B DI 1 401052
Belly Single Wall
80 330 KW
CHEANN-CAD1 OLYMPIAN
Diesel
Generator D100P1 1 603050
Belly Double Wall
200 100 KW
CHEANN-CAD108 OLYMPIAN
Diesel
Generator
D200P3 1 BA2604343
Belly Double Wall
420 200 KW
Equipment Model No. Quantity Asset # Tank Type Gallons
Other Information
CHEANN-CAD250 CATERPILLAR
Diesel
Generator D175.2 1 715030
Belly Double Wall
393 175 KW
CHEANN-CAD505 CATERPILLAR
Diesel
Generator C6.6 D125-6
E6M2650 1 603052
Belly Double Wall
393 125 KW
CHEANN-CAD593 OLYMPIAN
Diesel
Generator
D75P3 1 BA2606958
Belly Double Wall
150 75 KW
CHEANN-CAD618 IVENO
Diesel
Generator
MEC60DSA 1 603053
Belly Double Wall
200 60 KW
YORK-2122
Right side of Bldg. 2122
KOHLER
POWER
Diesel Generator
1 716056 Belly
Double Wall
758 200 KW
YORK-1959
EOC Room-117
POWERWARE
Uninterruptible Power Supply
80 1 700074 N/A N/A
YORK-2130
(CENSECFOR)
Inside Bldg.
LEIBERT
Uninterruptible Power Supply
38SA080A0
A00
1 700075 N/A N/A
YORK-476
Inside Boiler Room
POWER
SOLUTIONS
Uninterruptible Power Supply
SMG/150/48
0/60/440/60
1 702932 N/A N/A 120 KW
YORK-479
Inside Boiler Room
POWER
SOLUTIONS
Uninterruptible Power Supply
IMG313-
Q6PS-BH0F
1 702935 N/A N/A 250 KW
YORK-2122
Room-114
LEIBERT
Uninterruptible Power Supply
1 716057 N/A N/A
Equipment Room
PATTERSON
PUMPS
Diesel Fire Pump
JUGH-UF-
ABL8
1 708486 Above Ground Double Wall
PATTERSON
PUMPS
Diesel Fire
Pump
JUGH-UP-10 1 603466
Above Ground Single Wall
PATTERSON
PUMPS
Diesel Fire
Pump
FTA1100-
JL12N
1 606439
Above Ground Double Wall
YORK-1990
Right side of Bldg.
CATERPILLAR
Diesel
Generator*
SR-4 1 708234
Underground* Double Wall
350 KW
Belly Double Wall
* Underground Fuel Tank is not part of this contract and will be monitored by Environmental. During Generator Inspection, if a tank alarm is sounding, notify Yorktown Environmental.
ATTACHMENT J-1502000-09
EMERGENCY GENERATOR SYSTEM EQUIPMENT INVENTORY FOR NORFOLK NAVAL SHIPYARD
PORTSMOUTH
1500 CATERPILLAR Diesel Generator D100-6 1 100 KW
1500 CATERPILLAR Diesel Generator
Generator Mod: SR4
1 370 KW
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1604 CATERPILLAR Diesel Generator D150P1 1 150 KW
1604 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1604 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1604 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1604 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1604 Lighting Control Box 1 Junction Box with timer
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1605 CATERPILLAR Diesel Generator D150P1 1 150 KW
1605 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1605 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1605 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1605 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1605 Lighting Control Box 1 Junction Box with timer
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1606 CATERPILLAR Diesel Generator D150P1 1 150 KW
1606 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1606 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1606 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1606 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1606 Lighting Control Box 1 Junction Box with timer
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1607 CATERPILLAR Diesel Generator D150P1 1 150 KW
1607 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1607 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1607 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1607 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1607 Lighting Control Box 1 Junction Box with timer
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1608 CATERPILLAR Diesel Generator D150P1 1 150 KW
1608 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1608 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1608 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1608 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1608 Lighting Control Box 1 Junction Box with timer
Electric Distribution
Enclosure 1 20’ X 13’ X 10’
1609 CATERPILLAR Diesel Generator D150P1 1 150 KW
1609 CATERPILLAR
Kinetic Uninterruptible
Power Supply
UPS-150 1 150 KVA
CUTLER
HAMMER
Automatic Transfer
Switch
ATH2/ATV2 1
225 AMP
480 VAC
1609 SENS Battery Charger FCA12-10-22114 1 12 VDC 10 AMP
1609 Power Panel Square D Type NF 1
225 AMP
480/277 VAC
1609 Lighting Panel Square D Type NQOD 1
100 AMP
208/120 VAC
1609 Lighting Control Box 1 Junction Box with timer
1618 CATERPILLAR Diesel Generator 1 500 KW
1733 EATON
Uninterruptible Power
Supply System-9390
Model-80
1500 ECOVAULT
Fuel Storage Tank
Above Ground
1 2000 GL
Under Generator
Fuel Storage Tank
250 GL
Disconnected and not in use
Fuel Stowage Tank Belly - Double Wall
1 200 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
6 300 GL
Fuel Stowage Tank Belly - Double Wall
1 2500 GL
ATTACHMENT J-1502000-10
MONTHLY TANK INSPECTION
CHECKLIST
ATTACHMENT J-1502000-11
HISTORICAL IMP REPAIRS
Facility
Name/Description Equip # Manufacturer
Model No.
Serial No.
Year Purchase
Type of Repair
ATTACHMENT J-1502000-12
HVAC AND REFRIGERATION SYSTEM INVENTORY FOR IMP NAVAL STATION NORFOLK
BUILDING W143
Roof TRANE Air Cooled Chiller
RTAC3504U1BNUAFNL4
WY1CDBNN6TN11AREEXN
4 350 Ton
TRANE Refrigerant Monitor
RMWERMWERG411,
DO1001AE
EIT
Carbon Monoxide
Monitor 5301 1
EIT Natural Gas Monitor 4688-1-1-2 1 MAGIC AIR Fan Coil Unit 1 Old Battery Room
Roof 6039/6040
TRANE HVAC Unit
YSH150F4RLA0900C5A
1060107000000000000000
Roof West Offices
TRANE HVAC Unit
YSH180F4RLB090HC5A
1060004000000000000000
Roof North Offices
TRANE HVAC Unit
YSH300F4RVB080GC5A
1060004000000000000000
Roof East Offices
TRANE HVAC Unit
YCH360B4MM1B2EJ50B
C0000HJB00L0R00000000
6033 TRANE Central A/C Unit GFCD-07734 9
6th Floor LIEBERT Computer Room A/C
Unit
FH-376-C-A00 20
LIEBERT Computer Room A/C Unit
FH-376-CAC-1 1
LIEBERT Computer Room A/C Unit
FH-302-C-A00 2
LIEBERT Computer Room A/C Unit
FH-200-C-A00 2
LIEBERT Computer Room A/C Unit
FH-147-C-A00 2
6029 TRANE Variable Air Volume (VAV) box
VSWF1200S 1
6026 TRANE Variable Air Volume (VAV) box
VSWF1000Q 1
6027 TRANE Variable Air Volume (VAV) box
VSWF1000Q 2
667C TRANE Variable Air Volume (VAV) box
VSWF1000Q 2
667B TRANE Variable Air Volume (VAV) box
VSWF1000Q 1
667C TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
628 TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
625 TRANE Variable Air Volume (VAV) box
VSWF0600P 1
625 TRANE Variable Air Volume (VAV) box
VSWF0800P 1
627 TRANE Variable Air Volume (VAV) box
VSWF1000Q 4
627 TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
613 TRANE Variable Air Volume (VAV) box
VSWF0600P 1
615 TRANE Variable Air Volume (VAV) box
VSWF0600P 1
617 TRANE Variable Air Volume (VAV) box
VSWF0800P 1
608 TRANE Variable Air Volume (VAV) box
VSWF1000Q 3
606 TRANE Variable Air Volume (VAV) box
VSWF0800P 1
603 TRANE Variable Air Volume (VAV) box
VSWF0800P 1
6024 TRANE Variable Air Volume (VAV) box
VSWF1000Q 1
6020 TRANE Variable Air Volume (VAV) box
VSWF1200Q 1
6019 TRANE Variable Air Volume (VAV) box
VSWF1200Q 1
6018 TRANE Variable Air Volume (VAV) box
VSWF1200S 1
6017 TRANE Variable Air Volume (VAV) box
VSWF1200S 1
6016 TRANE Variable Air Volume (VAV) box
VSWF0600P 2
6014A TRANE Variable Air Volume (VAV) box
VSWF1000Q 2
6000 TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
6010 TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
6006 TRANE Variable Air Volume (VAV) box
VSWF0800P 1
6006 TRANE Variable Air Volume (VAV) box
VSWF1200S 1
6000B TRANE Variable Air Volume (VAV) box
VSWF0800Q 1
6003 TRANE Variable Air Volume (VAV) box
VSWF1000Q 1
Roof/628 PENNBARRY Exhaust Fan DX10R 1
Roof/633 PENNBARRY Exhaust Fan DX16R 1 Roof/6001 PENNBARRY Exhaust Fan DX10R 1
Roof/Penthouse PENNBARRY Exhaust Fan 1 Roof/6013 MITSUBISHI HVAC Air Handler PUY-A12NHA6 1
6013 MITSUBISHI HVAC Air Handler PKA-A12HA6 1
6013/6033 MITSUBISHI
HVAC Condensing
Water Pump
VCMA-20ULS 1
Penthouse SYSTECON HVAC Condensing
Water Pump
SIVCH1418EFCK08X1 1
Men’s Bath GNOC MODINE Cabinet Unit Heater 1 Woman’s Bath
GNOC
MODINE Cabinet Unit Heater 1
GNOC Locker Room
MODINE Cabinet Unit Heater 1
EDS Bathrooms MODINE Cabinet Unit Heater 1
CARNES,
PROPELLAIR,
BROAN
Fans and Blowers 11 Various Fractional
HP Motors
PROPELLAIR Ventilation Fan CDP36 4D09-J 1 1.5HP, 460V, 3PH
Shell & Tube Heat
Exchanger
S1436ZA 1 2700 MBH
Penthouse
ALLIS
CHALMERS
Hot Water Pump 2000 4X3X9 2 40HP, 230/460V
ATTACHMENT J-1502000-13
CONTROL SYSTEM INVENTORY FOR IMP NAVAL STATION NORFOLK
Facility # Description Manufacturer Other Information
Penthouse Pneumatic Control System ROBERTSHAW Most of the original system has changed over to Metasys. There are still some pneumatic controls in operation.
ATTACHMENT J-1502000-14
COMPRESSED AIR SYSTEMS INVENTORY FOR IMP NAVAL STATION NORFOLK
Penthouse QUINCY Pneumatic Control Air
Compressor
QC015BRSK3 1
HANKISON Control Air Drier 8010 1
10 SCFM @
160PSI @ 100°
ATTACHMENT J-1502000-15
CHILL WATER FLOW DIAGRAM NAVAL STATION NORFOLK
ATTACHMENT J-1502000-16
CONDENSER WATER FLOW DIAGRAM NAVAL STATION NORFOLK
ATTACHMENT J-1502000-17
EMERGENCY GENERATOR AND ELECTRICAL DISTRIBUTION INVENTORY FOR IMP NAVAL
STATION NORFOLK BUILDING W143
Roof GENERAC Emergency Generator SB2S-260 4 Roof/Way 3 of 223 SQUARE D Transformer 1
Penthouse from
MSB
SQUARE D Transformer EE75T3H47DBST20 1 75 KVA
Penthouse from
MSB
SQUARE D Transformer EE30T3H42DBST20 1 30 KVA
Penthouse SQUARE D Automatic Transfer
Switch 36221870-018 1
Ground Level Fuel Storage Tank and Associated Equipment
Double Wall
AST-01 1 8000 GL
VEEDER ROOT
Tank Level Monitoring
System
TLS-300C 1
Generator Fuel Tank Monitor
Fuel Storage Tank and Associated Equipment
Single Wall
AST-02 1 75 GL
Fuel Storage Tank and Associated Equipment
Single Wall
AST-03 1 75 GL
Ground Level Water Pump 1 2 HP
Belly Fuel Tank
Single Wall
4 260 GL
ATTACHMENT J-1502000-18
TEMPERATURE STANDARDS FOR IMP NAVAL STATION NORFOLK
Area Cooling Season* Heating Season*
Living & Admin Areas (Inactive Employment) 78 70 (+/-4) Working Areas 78 60 (+/-4) Storage Areas 78 40 (+/-4) Computer Areas 70 70 (+/-4) Training Areas 75 70 (+/-4)
*Degrees F. dry bulb
ATTACHMENT J-1502000-19
HVAC WATER TESTING AND TREATMENT SERVICES INVENTORY
NAVAL STATION NORFOLK BUILDING W143
Loop Type Quantity Chilled Water (Closed) 1
Condenser Water (Open) 2 Heating Hot Water Loop (Closed) 1
File details come from the government source that posted it. Updated .