J- 1501000.pdf

PDF 384 KB Posted

Attached to
Regional Maintenance of Emergency Generators and HVAC Equipment
Solicitation number
N4008519R9243
Issued by

View the file

Other files

File Type Posted
N40085-19-R-9243 0005.pdf PDF
ELINS J-0200000-17 Revised.xlsx XLSX spreadsheet
1502000 C Revised.docx DOCX document
N40085-19-R-9243 0004.pdf PDF
J-0200000-17-ELINs Revised.xlsx XLSX spreadsheet
N40085-19-R-9243 0003.pdf PDF
N40085-19-R-9243 Site visit List of Attendees.pdf PDF
N40085-19-R-9243 0002.pdf PDF
N40085-19-R-9243- 0001.pdf PDF
SECNAV_ 5512_1.pdf PDF
J-0200000-17-ELINs.xlsx XLSX spreadsheet
J-1502000.pdf PDF
J- 0200000.pdf PDF
N40085-19-R-9243 RFP.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION J

DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

TABLE OF CONTENTS

ATTACHMENT NUMBER ATTACHMENT TITLE

J-1501000-01 Definitions and Acronyms

J-1501000-02 References and Technical Documents

J-1501000-03 Meter Group Descriptions and Direct Condition Rating Guidance

J-1501000-04 General Direct Condition Rating Guidance

ATTACHMENT J-1501000-01

DEFINITIONS AND ACRONYMS

TERM DEFINITION

CONDITION BASED

MAINTENANCE

MANAGEMENT

A maintenance philosophy that encompasses a condition management cycle that is sustained throughout the entire life-cycle of a facility and its constituent component sections, or assets.

FACILITIES LIFE CYCLE A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.

INFRASTRUCTURE

CONDITION ASSESSMENT

PROGRAM

A foundational component of Condition Based Maintenance Management (CBMM). ICAP comprises three of the four CBMM quadrants: Inventory, Assessment, and Analysis.

FACILITIES MAINTENANCE

MANAGEMENT

The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”

LIFE-CYCLE COSTS A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.

REAL PROPERTY Land and improvements to land (i.e., facilities). It includes equipment affixed and built into the facility as an integral part of the facility (such as heating systems), but not movable equipment (e.g., plant equipment, industrial equipment, buoys).

RESTORATION Restoration of real property to such a condition that it can be used for its intended purpose. Includes repair or replacement work to restore facilities damaged by inadequate sustainment, excessive age, natural disaster, fire, accident or other causes.

SUSTAINMENT Maintenance and repair activities necessary to keep a typical inventory of facilities in “normal working condition”. Sustainment includes regularly scheduled maintenance as well as cyclical major repairs or replacement of components that occur periodically over the expected service life of the facilities.

UNIFORMAT

CLASSIFICATION

A standard classification of building components established by the National Institute of Standards and Technology.

Acronym Title BFR Basic Facility Requirements CBMM Condition Based Maintenance Management ICAP Infrastructure Condition Assessment Program IMP Integrated Maintenance Program MDI Mission Dependency Index MILCON Military Construction PM Preventive Maintenance POAM Plan of Action and Milestones RSIP Regional Shore Infrastructure Plan

ATTACHMENT J-1501000-02

REFERENCES AND TECHNICAL DOCUMENTS

Reference Title NAVFAC P-78 Real Property Inventory Procedures Manual OPNAVINST 11011.10 Utilization of Navy Real Property SECNAVINST 11011.47 Acquisition, Management, and Disposal of Real Property and Real Property

Interests by the Department of the Navy

ATTACHMENT J-1501000-03

METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE

D3030135 - Chiller, Reciprocating, Air Cooled Meter & Description Direct Condition Rating Guidance Condition CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5305 - Record the condition of the Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired

CR-5520 - Record the condition of the Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5565 - Record the condition of the Receiver Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3030903 - Packaged DX Refrigerant System Meter & Description Direct Condition Rating Guidance Condition CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5185 - Record the condition of the Condensing Coils

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040114 - Air Handling Unit, Rooftop Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5235 - Record the condition of the Dampers

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5340 - Record the condition of the Fan(s) Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5495 - Record the condition of the Louvers

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

D3040220 - Fan System, Centrifugal In-Line Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5235 - Record the condition of the Dampers

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040230 - Fan System, Utility Set Meter & Description Direct Condition Rating Guidance Condition CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5630 - Record the condition of the Switches Controls

GREEN: Switches function properly AMBER: None RED: Switches do not function properly

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3040240 - Fan System, Roof Exhaust Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5235 - Record the condition of the Dampers

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040330 - Circulating Pump, End Suction Meter & Description Direct Condition Rating Guidance Condition CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

D3040340 - Circulating Pump, Double Suction Meter & Description Direct Condition Rating Guidance Condition CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

D3040620 - Heat Exchanger, Shell Tube Meter & Description Direct Condition Rating Guidance Condition CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5375 - Record the condition of the Frame/Supports

GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured

CR-5465 - Record the condition of the Insulation

GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5570 - Record the condition of the Relief Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired

CR-5590 - Record the condition of the Steam Modulating Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally impaired

D3050170 - Split Systems With Air Cooled Condensing Units Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5460 - Record the condition of the Indoor Fan Motor Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3050185 - Computer Room Cooling Units Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5150 - Record the condition of the Condensate Pump

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

CR-5210 - Record the condition of the Controls/Sensors

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5450 - Record the condition of the Humidifier

GREEN: Pan has minimal damage or corrosion AMBER: Pan has noticeable damage or corrosion, but no leaks RED: Pan has significant damage or corrosion, and noticeable leaks

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3050201 - Packaged A/C, Air Cooled, Elec Heat Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5275 - Record the condition of the Duct Connectors

GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

D3050201 - Packaged A/C, Air Cooled, Elec Heat Meter & Description Direct Condition Rating Guidance Condition CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3050203 - Packaged A/C, Air Cooled, HW Heat Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5175 - Record the condition of the Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5275 - Record the condition of the Duct Connectors

GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

D3050203 - Packaged A/C, Air Cooled, HW Heat

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

DIRECT CONDITION RATING GUIDANCE BY METER GROUP AND UNIFORMAT

D3050210 - Packaged A/C, Water Cooled, Elec Heat Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3050220 - Packaged A/C, Water Cooled, HW Heat Meter & Description Direct Condition Rating Guidance Condition CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the condition of the Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

ATTACHMENT J-1501000-03

METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE

D5010901 - Transfer Switch Meter & Description Direct Condition Rating Guidance Condition CR-5245 - Record the condition of the Disconnect/Safety Switch

GREEN: Disconnect/Safety Switch is present and works properly AMBER: None RED: Disconnect/Safety Switch is missing or not functional

CR-5295 - Record the condition of the Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5405 - Record the condition of the Ground System

GREEN: No damage to grounding system, all connections are secure, fully operational AMBER: Slight damage or corrosion, but connections are secure and Grounding System is operational RED: Significant damage or corrosion, loose or missing connections, inadequately grounded

D5010902 - Transformer

CR-5070 - Record the condition of the Bushings/Insulators

GREEN: Busings/Insulators show little to no signs of damage or wear, fully operational AMBER: Bushings/Insulators have noticeable damage or wear, but still operational RED: Busings/Insulators have significant damage or wear, operationally impaired

CR-5335 - Record the condition of the Fan(s)

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5390 - Record the condition of the Gaskets/Seals

GREEN: Gaskets/Seals are fully intact, no leaks AMBER: Gaskets/Seals experience slight leaking RED: Gaskets/Seals show noticeable signs of leaks

CR-5405 - Record the condition of the Ground System

GREEN: No damage to grounding system, all connections are secure, fully operational AMBER: Slight damage or corrosion, but connections are secure and Grounding System is operational RED: Significant damage or corrosion, loose or missing connections, inadequately grounded

CR-5510 - Record the condition of the Motor Rotor

GREEN: Motor Rotor has minimal wear, fully functional AMBER: Motor Rotor has noticeable signs of wear, still operational RED: Motor Rotor shows excessive signs of wear or damage, operationally impaired

CR-5535 - Record the condition of the Pressure Relief Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally

D5010906 - Panelboards

CR-5055 - Record the condition of the Breakers/Fuses

GREEN: Breaker successfully trips when circuit is overloaded/shorted out. Fuse is not burnt out.

AMBER: Breaker has been tripped RED: Breaker does not successfully trip when circuit is overloaded/shorted out. Fuse is burnt out.

CR-5245 - Record the

Disconnect/Safety Switch

GREEN: Disconnect/Safety Switch is present and works properly AMBER: None RED: Disconnect/Safety Switch is missing or not functional

CR-5295 - Record the

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5690 - Record the

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D5090210 - Generators

CR-5030 - Record the condition of the Batteries

GREEN: Batteries provide adequate power to the device.

AMBER: None.

RED: Batteries do not provide adequate power to the device.

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5220 - Record the condition of the Cooling System/Radiator

GREEN: Radiator has minimal damage and corrosion, Fins are straight allowing good airflow, Flow rate is adequate AMBER: Radiator has noticeable damage and corrosion, some Fins are bent but still allow good airflow though system, Flow rate is less than usual, but still functional RED: Radiator has significant damage and corrosion, many fins are bent and preventing air flow, Flow is blocked or slowed, operationally

CR-5300 - Record the condition of the Engine

GREEN: Engine operates properly, free of excessive noise/vibration, no fluid leaks or overheating AMBER: Engine exhibits unusual noise/vibration, minor fluid leaks but still operational, may require maintenance RED: Engine exhibits excessive noise/vibration, overheating, noticeable fluid leaks, and/or operation is significantly impaired

CR-5315 - Record the condition of the Exhaust System

GREEN: Exhaust has minimal damage and corrosion, suppresses engine noise AMBER: Exhaust has noticeable damage and corrosion, engine noise is louder than usual RED: Exhaust has significant damage and corrosion, engine noise not being surprised

CR-5385 - Record the condition of the Fuel Tank and Pump

GREEN: Fuel Tank and Pump has little to no damage, no leaks, fully operational AMBER: Fuel Tank and Pump has some noticeable damage, but no leaks and fully operational RED: Fuel Tank and Pump has significant damage and corrosion, may have leaks, or is operationally impaired

CR-5400 - Record the

Generator

GREEN: Generator is fully operational, no excess noise, vibration, or overheating AMBER: Generator exhibits excess noise or vibration, but no overheating and is still operational RED: Generator exhibits excess noise, vibration, or overheating, and/or is operationally impaired

CR-5530 - Record the

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5585 - Record the

Silencer/Muffler

GREEN: Silencer/Muffler has minimal damage and corrosion, baffles effectively suppress exhaust noise AMBER: Silencer/Muffler has noticeable damage / corrosion, exhaust noise is unusually loud, still functional RED: Silencer/Muffler has significant damage / corrosion, exhaust noise is excessively loud, not functional

D5090210 - Generators

CR-5690 - Record the condition of the Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D5090904 - Uninterruptible Power Supply

CR-5030 - Record the condition of the Batteries

GREEN: Batteries provide adequate power to the device.

AMBER: None.

RED: Batteries do not provide adequate power to the device.

CR-5035 - Record the condition of the Battery Rack

GREEN: Battery Rack shows little to no signs of corrosion or damage.

AMBER: Battery Rack shows minimal to noticeable corrosion or damage, but rack is structurally sound RED: Battery Rack shows significant signs of corrosion and/or the rack is significantly damaged, rack is structurally unsound.

CR-5195 - Record the condition of the Control Panel

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5295 - Record the

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5680 - Record the condition of the UPS Alarm System

GREEN: UPS Alarm System functions properly AMBER: None RED: UPS Alarm System does not function properly

ATTACHMENT J-1501000-04

GENERAL DIRECT CONDIDTION RATING GUIDANCE

File details come from the government source that posted it. Updated .