Channels_2017.xlsx
XLSX spreadsheet 50 KB Posted
- Solicitation number
- N4008519R9031
About this file
Channels_2017.xlsx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N4008519R9031-0009_UN_PRICED_ELINS_19-R-9031.xls | XLS spreadsheet | |
| Attachment_J-0200000-06.pdf | ||
| N4008519R9031-0009.pdf | ||
| N4008519R9031-0008.pdf | ||
| Vehicle-_CESE_Inventory_for_Consolidated_Service_Contract.xlsx | XLSX spreadsheet | |
| ATTACHMENT_C-_PPQ.pdf | ||
| N4008519R9031-0007.pdf | ||
| N4008519R9031-0006.pdf | ||
| N4008519R9031_Questions_and_Responses.pdf | ||
| J-1502000-03_thru_08_Inventory.xlsx | XLSX spreadsheet | |
| N4008519R9031-0005.pdf | ||
| N4008519R9031-Attachments.zipx | ZIPX file | |
| 1502000_J_Facility_Investment_ver_2.4.pdf | ||
| Attachment_J-1502000-07.zipx | ZIPX file | |
| N4008519R9031-0004.pdf | ||
| N4008519R9031-0003.zipx | ZIPX file | |
| J-1502000-03_thru_08_Inventory.xlsx | XLSX spreadsheet | |
| N4008519R9031-0003.pdf | ||
| 1501000_FAP_Facility_Management_v2.0.pdf | ||
| Amendment_0002.pdf | ||
| UN_PRICED_ELINS_19-R-9031.xls | XLS spreadsheet | |
| N4008519R9031-Section_J_Attachments.zipx | ZIPX file | |
| N4008519R9031-0001.pdf | ||
| N4008519R9031.pdf |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| node_name | card_slot | channel_slot | device_signal_tag | description | enable | channel_type |
| B3 | 9 | 7 | AI-0600 | Water Hardness High | T | DI_HD_CHAN |
| B1 | 1 | 1 | AIT-1701A | Analog Input Channel | T | AI_CHAN |
| B2 | 13 | 1 | AIT-2701A | Boiler 2 CO | T | AI_CHAN |
| B3 | 9 | 9 | ALM_BPST | Alarm BPST | T | DI_HD_CHAN |
| B1 | 9 | 7 | ALM-FT-HIGH | Spare | T | DI_HD_CHAN |
| B1 | 10 | 4 | AT-0302 | DA Disolved O2 | T | AI_CHAN |
| B1 | 10 | 1 | AT-1701 | Boiler 1 Flue Gas O2 | T | AI_CHAN |
| B1 | 1 | 4 | AT-1801 | Analog Input Channel | T | AI_CHAN |
| B2 | 1 | 1 | AT-2701 | Boiler 2 Flue Gas Oxygen | T | AI_CHAN |
| B2 | 1 | 4 | AT-2801 | Boiler 2 Opacity Monitor | T | AI_CHAN |
| B1 | 10 | 5 | AT-3720 | B3 Opacity (Instantaneous) | T | AI_CHAN |
| B3 | 1 | 4 | AT-3720A | Boiler 3 6-Minute Opacity | T | AI_CHAN |
| B4 | 1 | 1 | AT-4701 | B4 Flue Gas Oxygen | T | AI_CHAN |
| B4 | 1 | 3 | AT-4801 | B4 Flue Gas Opacity | T | AI_CHAN |
| B4 | 1 | 4 | AT-4801A | 6-MIN AVERAGE OPACITY | T | AI_CHAN |
| B1 | 10 | 7 | B1C10CH07 | spare | F | AI_CHAN |
| B1 | 10 | 8 | B1C10CH08 | Analog Input Channel | F | AI_CHAN |
| B1 | 9 | 14 | B1-FLAME | Flame Failure | T | DI_HD_CHAN |
| B1 | 9 | 10 | B1-H1STMPRESS | High Steam Press | T | DI_HD_CHAN |
| B1 | 9 | 13 | B1-HIFURNPRESS | High Furnace Pressure | T | DI_HD_CHAN |
| B1 | 9 | 16 | B1-HIGASPRESS | High Gas Pressure | T | DI_HD_CHAN |
| B1 | 9 | 22 | B1-HILOOILTEMP | High/Low Oil Temperature | T | DI_HD_CHAN |
| B1 | 9 | 12 | B1-LCOMBAIR | Low Combustion Air Press | T | DI_HD_CHAN |
| B1 | 9 | 21 | B1-LOATOMFLW | Low Atomizing Media Flow | T | DI_HD_CHAN |
| B1 | 9 | 20 | B1-LOATOMPRESS | Low Atomizing Media Pressure | T | DI_HD_CHAN |
| B1 | 9 | 25 | B1-LOFURNDRAFT | Low Furnance Draft | T | DI_HD_CHAN |
| B1 | 9 | 17 | B1-LOGASPRESS | Low Gas Pressure | T | DI_HD_CHAN |
| B1 | 9 | 15 | B1-LOINSTRAIR | Low Instrument AIr Pressure | T | DI_HD_CHAN |
| B1 | 9 | 23 | B1-LOOILPRESS | Low Oil Press | T | DI_HD_CHAN |
| B1 | 9 | 24 | B1-LOWO2 | Low O2 Level | T | DI_HD_CHAN |
| B1 | 9 | 11 | B1-RECYCLE | Recycle In Progress | T | DI_HD_CHAN |
| B2 | 5 | 7 | B1-STACKTEMP | Boiler 1 Stack Temp | T | AI_HART_CHAN |
| B1 | 9 | 19 | B1-WTRLVLALM | Water Level Alarm | T | DI_HD_CHAN |
| B1 | 9 | 18 | B1-WTRLVLCO | Water Level Cutout | T | DI_HD_CHAN |
| B2 | 2 | 7 | B2C02CH07 | Analog Input Channel | F | AI_CHAN |
| B2 | 3 | 5 | B2C03CH05 | Analog Input Channel | F | AI_CHAN |
| B2 | 4 | 4 | B2C04CH04 | Analog Input Channel | F | AI_CHAN |
| B2 | 5 | 4 | B2C05CH04 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 1 | B2C06CH01 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 2 | B2C06CH02 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 3 | B2C06CH03 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 4 | B2C06CH04 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 5 | B2C06CH05 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 6 | B2C06CH06 | Analog Input Channel | F | AI_CHAN |
| B2 | 6 | 8 | B2C06CH08 | Analog Input Channel | F | AI_CHAN |
| B2 | 7 | 4 | B2C07CH04 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B2 | 7 | 7 | B2C07CH07 | Boiler 2 Fuel Gas Flow Control Valve | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 2 | B2C08CH02 | Spare | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 3 | B2C08CH03 | Spare | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 4 | B2C08CH04 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 5 | B2C08CH05 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 6 | B2C08CH06 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B2 | 8 | 8 | B2C08CH08 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B2 | 9 | 6 | B2C09CH06 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 7 | B2C09CH07 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 8 | B2C09CH08 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 9 | B2C09CH09 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 30 | B2C09CH30 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 31 | B2C09CH31 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 9 | 32 | B2C09CH32 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B2 | 10 | 1 | B2C10CH01 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 2 | B2C10CH02 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 3 | B2C10CH03 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 4 | B2C10CH04 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 5 | B2C10CH05 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 6 | B2C10CH06 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 7 | B2C10CH07 | Discrete Input Channel | F | DI_CHAN |
| B2 | 10 | 8 | B2C10CH08 | Discrete Input Channel | F | DI_CHAN |
| B2 | 13 | 2 | B2C13CH02 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 3 | B2C13CH03 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 4 | B2C13CH04 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 5 | B2C13CH05 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 6 | B2C13CH06 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 7 | B2C13CH07 | Analog Input Channel | F | AI_CHAN |
| B2 | 13 | 8 | B2C13CH08 | Analog Input Channel | F | AI_CHAN |
| B2 | 9 | 14 | B2-FLAMEFAIL | Flame Failure | T | DI_HD_CHAN |
| B2 | 9 | 13 | B2-HIFURNDRAFT | High Furnance Draft | T | DI_HD_CHAN |
| B2 | 9 | 16 | B2-HIGASPRS | High Gas Pressure | T | DI_HD_CHAN |
| B2 | 9 | 22 | B2-HILOOILTMP | High/Low Oil Temperature | T | DI_HD_CHAN |
| B2 | 9 | 10 | B2-HISTMPRESS | High Steam Pressure | T | DI_HD_CHAN |
| B2 | 9 | 21 | B2-LOATOMFLW | Low Atomizing Media Flow | T | DI_HD_CHAN |
| B2 | 9 | 20 | B2-LOATOMPRS | Low Atomizing Media Pressure | T | DI_HD_CHAN |
| B2 | 9 | 12 | B2-LOCOMBAIR | Low Combustion Air Pressure | T | DI_HD_CHAN |
| B2 | 9 | 25 | B2-LOFURNDRFT | Low Furnance Draft | T | DI_HD_CHAN |
| B2 | 9 | 17 | B2-LOGASPRS | Low Gas Pressure | T | DI_HD_CHAN |
| B2 | 9 | 15 | B2-LOINSTRAIR | Low Instrument AIr Pressure | T | DI_HD_CHAN |
| B2 | 9 | 23 | B2-LOOILPRS | Low Oil Pressure | T | DI_HD_CHAN |
| B2 | 9 | 24 | B2-LOWO2 | Low Oxygen Level | T | DI_HD_CHAN |
| B2 | 9 | 11 | B2-RECYCLE | Recycle In Progress | T | DI_HD_CHAN |
| B2 | 5 | 8 | B2-STACKTEMP | Boiler 2 Stack Temp | T | AI_HART_CHAN |
| B2 | 9 | 19 | B2-WTRLVLALM | Water Level Alarm | T | DI_HD_CHAN |
| B2 | 9 | 18 | B2-WTRLVLCO | Water Level Cutout | T | DI_HD_CHAN |
| B3 | 13 | 2 | B3_C13_CH02 | Spare Pulse Input Channel | F | PIN_CHAN |
| B3 | 11 | 7 | B3_MUA | B3 Make Up Air Okay | T | DO_CHAN |
| B3 | 2 | 4 | B3C02CH04 | F | AI_CHAN | |
| B3 | 2 | 8 | B3C02CH08 | F | AI_CHAN | |
| B3 | 3 | 3 | B3C03CH03 | Spare | F | AI_CHAN |
| B3 | 4 | 2 | B3C04CH02 | Spare | F | AI_CHAN |
| B3 | 4 | 3 | B3C04CH03 | Spare | F | AI_CHAN |
| B3 | 4 | 5 | B3C04CH05 | Spare | F | AI_CHAN |
| B3 | 7 | 4 | B3C07CH04 | Spare | F | AO_DISABLED_HART_CHAN |
| B3 | 8 | 1 | B3C08CH01 | Spare | F | AO_DISABLED_HART_CHAN |
| B3 | 9 | 8 | B3C09CH08 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B3 | 9 | 12 | B3C09CH12 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 19 | B3C09CH19 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 20 | B3C09CH20 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 21 | B3C09CH21 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 22 | B3C09CH22 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 23 | B3C09CH23 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 24 | B3C09CH24 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 25 | B3C09CH25 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 26 | B3C09CH26 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 27 | B3C09CH27 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 28 | B3C09CH28 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 29 | B3C09CH29 | Spare | F | DI_HD_CHAN |
| B3 | 9 | 30 | B3C09CH30 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B3 | 9 | 32 | B3C09CH32 | Spare | F | DI_HD_CHAN |
| B3 | 10 | 8 | B3C10CH08 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B3 | 11 | 8 | B3C11CH08 | Discrete Output Channel | F | DO_CHAN |
| B3 | 14 | 4 | B3C14CH04 | Analog Input Channel | F | AI_CHAN |
| B3 | 14 | 5 | B3C14CH05 | Analog Input Channel | F | AI_CHAN |
| B3 | 14 | 6 | B3C14CH06 | Analog Input Channel | F | AI_CHAN |
| B3 | 14 | 7 | B3C14CH07 | Analog Input Channel | F | AI_CHAN |
| B3 | 14 | 8 | B3C14CH08 | Analog Input Channel | F | AI_CHAN |
| B3 | 15 | 4 | B3C15CH04 | Discrete Output Channel | F | DO_CHAN_SER2 |
| B3 | 15 | 5 | B3C15CH05 | Discrete Output Channel | F | DO_CHAN_SER2 |
| B3 | 15 | 6 | B3C15CH06 | Discrete Output Channel | F | DO_CHAN_SER2 |
| B3 | 15 | 7 | B3C15CH07 | Discrete Output Channel | F | DO_CHAN_SER2 |
| B3 | 15 | 8 | B3C15CH08 | Discrete Output Channel | F | DO_CHAN_SER2 |
| B3 | 9 | 31 | B3CH09CH31 | SPARE | F | DI_HD_CHAN |
| B3 | 9 | 10 | B3OPCR5_WARN | D-R 290 AW RELAY 5 | T | DI_HD_CHAN |
| B3 | 9 | 11 | B3OPCR6_CAL | D-R 290 AW RELAY 6 | T | DI_HD_CHAN |
| B4 | 1 | 8 | B4C01CH08 | Analog Input Channel | F | AI_CHAN |
| B4 | 2 | 7 | B4C02CH07 | Spare | F | AI_CHAN |
| B4 | 6 | 7 | B4C06CH07 | Analog Input Channel | F | AI_CHAN |
| B4 | 6 | 8 | B4C06CH08 | Analog Input Channel | F | AI_CHAN |
| B4 | 8 | 5 | B4C08CH05 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B4 | 8 | 6 | B4C08CH06 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B4 | 8 | 7 | B4C08CH07 | HART Disabled Analog Output Channel | F | AO_DISABLED_HART_CHAN |
| B4 | 9 | 11 | B4C09CH11 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 14 | B4C09CH14 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 15 | B4C09CH15 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 16 | B4C09CH16 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 17 | B4C09CH17 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 18 | B4C09CH18 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 19 | B4C09CH19 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 20 | B4C09CH20 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 21 | B4C09CH21 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 22 | B4C09CH22 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 23 | B4C09CH23 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 24 | B4C09CH24 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 25 | B4C09CH25 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 26 | B4C09CH26 | Discrete Input Channel (HD) | F | DI_HD_CHAN |
| B4 | 9 | 12 | B4OPCR5_WARN | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B4 | 9 | 13 | B4OPCR6_CAL | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B3 | 9 | 6 | BAD_IO96 | Bad Input Do Not Use | F | DI_HD_CHAN |
| B3 | 1 | 6 | BLR1-2_STM_BLKT | Steam Blanket | T | AI_CHAN |
| B3 | 7 | 2 | BM-555 | Blr #3 Boiler Mate rto PLC | T | AO_DISABLED_HART_CHAN |
| B3 | 7 | 3 | BO3C07CH03 | Spare | F | AO_DISABLED_HART_CHAN |
| B3 | 10 | 1 | BPST-PSET | Steam Turbine Backpressure Setpoint | T | AO_DISABLED_HART_CHAN |
| B4 | 11 | 5 | CCSLIGHTOFF | CCS At Lightoff | T | DO_CHAN |
| B4 | 11 | 6 | CCSPURGE | CCS At Purge | T | DO_CHAN |
| B1 | 7 | 1 | CCV-1202 | Boiler 1 Blowdown Conductivity Control Valve | T | AO_ENABLED_HART_CHAN |
| B2 | 7 | 1 | CCV-2202 | Boiler 2 Conducivity Control Valve | T | AO_ENABLED_HART_CHAN |
| B3 | 7 | 1 | CCV-3202 | Analog Output Channel | T | AO_DISABLED_HART_CHAN |
| B4 | 7 | 1 | CCV-4202 | B4 Blowdown Control Valve | T | AO_ENABLED_HART_CHAN |
| B1 | 10 | 2 | CT-1202 | Boiler 1 Conductivity Analyzer | T | AI_CHAN |
| B1 | 10 | 3 | CT-2202 | Boiler 2 Conductivity Analyzer | T | AI_CHAN |
| B1 | 10 | 6 | CT-3202 | B3 Conductivity | T | AI_CHAN |
| B4 | 1 | 5 | CT-4202 | B4 Blowdwn Cond | T | AI_CHAN |
| B3 | 9 | 1 | DI-BFP2 | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B3 | 9 | 4 | DI-BFP3 | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B3 | 9 | 2 | DI-BFP4 | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B3 | 9 | 3 | DI-BFP5 | Discrete Input Channel (HD) | T | DI_HD_CHAN |
| B3 | 14 | 3 | DPT_001 | Building Differential Pressure Transmitter | T | AI_CHAN |
| OIL | 8 | 5 | EW-FSH-005 | Eyewash Shower 1 Flow | T | DI_CHAN |
| OIL | 8 | 6 | EW-FSH-006 | Eyewash Shower 2 Flow | T | DI_CHAN |
| OIL | 14 | 6 | F0-ANN-11 | FO Storage tank 1 High Level | T | DO_CHAN |
| OIL | 5 | 3 | F0-ANN-RESET | Annunciator Reset | T | DI_CHAN |
| B1 | 11 | 1 | FCD-1601A-O | Open FD Fan Damper | T | DO_CHAN |
| B1 | 11 | 4 | FCD-1602-C | Close Windbox Damper | T | DO_CHAN |
| B1 | 11 | 3 | FCD-1602-O | Open Windbox Damper | T | DO_CHAN |
| B1 | 11 | 5 | FCD-1702A-O | Open ID Fan Damper | T | DO_CHAN |
| B1 | 11 | 8 | FCD-1703-C | Close Flue Gas Recirc Damper | T | DO_CHAN |
| B1 | 11 | 7 | FCD-1703-O | Open Flue Gas Recirc Damper | T | DO_CHAN |
| B2 | 11 | 2 | FCD-2601A-C | Boiler 2 FD Fan Damper Drive Close | T | DO_CHAN |
| B2 | 11 | 1 | FCD-2601A-O | Boiler 2 FD Fan Damper Drive Open | T | DO_CHAN |
| B2 | 11 | 4 | FCD-2602-C | Boiler 2 Windbox Damper Drive Close | T | DO_CHAN |
| B2 | 11 | 3 | FCD-2602-O | Boiler 2 Windbox Damper Drive Openl | T | DO_CHAN |
| B2 | 11 | 6 | FCD-2702A-C | Boiler 2 ID Fan Damper Drive Close | T | DO_CHAN |
| B2 | 11 | 5 | FCD-2702A-O | Boiler 2 ID Fan Damper Drive Open | T | DO_CHAN |
| B2 | 11 | 8 | FCD-2703-C | Boiler 2 Flue Gas Recirc Damper Drive Close | T | DO_CHAN |
| B2 | 11 | 7 | FCD-2703-O | Boiler 2 Flue Gas Recirc Damper Drive Open | T | DO_CHAN |
| B4 | 8 | 4 | FCD-4601A | HART Disabled Analog Output Channel | T | AO_DISABLED_HART_CHAN |
| B4 | 7 | 2 | FCD-4602 | B4 Windbox Inlet Damper | T | AO_DISABLED_HART_CHAN |
| B4 | 8 | 3 | FCD-4707 | HART Disabled Analog Output Channel | T | AO_DISABLED_HART_CHAN |
| B1 | 8 | 7 | FCV-1130 | Atomizing Steam Valve Output | T | AO_DISABLED_HART_CHAN |
| B1 | 7 | 6 | FCV-1201 | Boiler 1 Feedwater Flow Control Valve | T | AO_ENABLED_HART_CHAN |
| B1 | 7 | 7 | FCV-1401 | Boiler 1 Fuel Gas Flow Control Valve | T | AO_ENABLED_HART_CHAN |
| B1 | 7 | 8 | FCV-1501 | Boiler 1 Fuel Oil Flow Control Valve | T | AO_ENABLED_HART_CHAN |
| B2 | 8 | 7 | FCV-2130 | Atomizing Steam Pressure Output | T | AO_DISABLED_HART_CHAN |
| B2 | 7 | 6 | FCV-2201 | Boiler 2 Feedwater Control Valve | T | AO_ENABLED_HART_CHAN |
| B2 | 7 | 5 | FCV-2401 | FCV-2401A | T | AO_ENABLED_HART_CHAN |
| B2 | 7 | 8 | FCV-2501 | Boiler 2 Fuel Oil Flow Control Valve | T | AO_ENABLED_HART_CHAN |
| B4 | 8 | 8 | FCV-4130 | HART Disabled Analog Output Channel | T | AO_DISABLED_HART_CHAN |
| B4 | 7 | 6 | FCV-4201 | B4 Feedwater Control Valve | T | AO_ENABLED_HART_CHAN |
| B4 | 7 | 7 | FCV-4401 | B4 Fuel Gas Control valve | T | AO_DISABLED_HART_CHAN |
| B4 | 7 | 8 | FCV-4501 | B4 Fuel Oil Control Valve | T | AO_DISABLED_HART_CHAN |
| B1 | 11 | 2 | FDC-1601A-C | Close FD Fan Damper | T | DO_CHAN |
| B1 | 11 | 6 | FDC-1702-A-C | Close ID Fan Damper | T | DO_CHAN |
| B3 | 6 | 6 | FIBB_1 | Water Cooling Flow Meter | T | AI_HART_CHAN |
| OIL | 14 | 7 | FO-ANN-12 | FO Storage tank 1 High High Level | T | DO_CHAN |
| OIL | 14 | 8 | FO-ANN-13 | Unloading Pipe Low Temperature | T | DO_CHAN |
| OIL | 15 | 1 | FO-ANN-14 | Storage Tank Piping Low Temperature | T | DO_CHAN |
| OIL | 15 | 2 | FO-ANN-21 | FO Storage tank 2 High Level | T | DO_CHAN |
| OIL | 15 | 3 | FO-ANN-22 | FO Storage tank 2 High High Level | T | DO_CHAN |
| OIL | 15 | 4 | FO-ANN-23 | Loading Piping Low Temperature | T | DO_CHAN |
| OIL | 15 | 5 | FO-ANN-24 | Fill Line Piping Low Temperature | T | DO_CHAN |
| OIL | 15 | 6 | FO-ANN-31 | FO Day Tank 1 High High Level | T | DO_CHAN |
| OIL | 15 | 7 | FO-ANN-32 | FO Day Tank 2 High High Level | T | DO_CHAN |
| OIL | 15 | 8 | FO-ANN-33 | Day Tank Piping Low Temperature | T | DO_CHAN |
| OIL | 16 | 1 | FO-ANN-34 | Hot Water Piping Low temperature | T | DO_CHAN |
| OIL | 16 | 2 | FO-ANN-41 | EFSO | T | DO_CHAN |
| OIL | 16 | 3 | FO-ANN-42 | Pump room Leak Detected | T | DO_CHAN |
| OIL | 16 | 4 | FO-ANN-43 | Emergemcy Shower Activated | T | DO_CHAN |
| OIL | 16 | 5 | FO-ANN-44 | Storage Tank High temperature | T | DO_CHAN |
| OIL | 5 | 2 | FO-ANN-ACK | annunciator Acknowledge | T | DI_CHAN |
| OIL | 16 | 6 | FO-ANN-HORN | Annunciator Horn | T | DO_CHAN |
| OIL | 5 | 1 | FO-ANN-TEST | Annunciator Lamp Test | T | DI_CHAN |
| OIL | 9 | 2 | FO-EFSO | Emergency Fuel Oil Stop (CR2A) | T | DI_CHAN |
| OIL | 5 | 4 | FO-EGEN | Emergency Generator | T | DI_CHAN |
| OIL | 3 | 1 | FO-FS-001A | Unloading Pump P1 Flow 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 1 | FO-FS-001B | Unloading Pump P1 Flow 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 2 | FO-FS-002A | Unloading Pump P2 Flow 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 2 | FO-FS-002B | Unloading Pump P2 Flow 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 5 | FO-FS-003A | Transfer Pump P3 Flow 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 5 | FO-FS-003B | Fuel Transfer Pump P3 Flow 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 6 | FO-FS-004A | Transfer Pump P4 Flow 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 6 | FO-FS-004B | Fuel Transfer Pump P4 Flow 2 | T | DI_CHAN_SER2 |
| OIL | 11 | 3 | FO-HLV1-OPN | FO Storage Tank 1 Inlet Vlv Open Command | T | DO_CHAN |
| OIL | 6 | 5 | FO-HLV1-ZSC | FO Storage Tank 1 Inlet Valve Closed | T | DI_CHAN |
| OIL | 6 | 6 | FO-HLV1-ZSO | FO Storage Tank 1 Inlet Valve Open | T | DI_CHAN |
| OIL | 12 | 3 | FO-HLV2-OPN | FO Storage Tank 2 Inlet Vlv Open Command | T | DO_CHAN |
| OIL | 7 | 2 | FO-HLV2-ZSC | FO Storage Tank 2 Inlet Valve Closed | T | DI_CHAN |
| OIL | 7 | 3 | FO-HLV2-ZSO | FO Storage Tank 2 Inlet Valve Open | T | DI_CHAN |
| OIL | 11 | 6 | FO-HLV3-OPN | FO Day Tank 1 Inlet Vlv Open Command | T | DO_CHAN |
| OIL | 9 | 3 | FO-HLV3-ZSC | FO Day Tank 1 Inlet Vlv Closed | T | DI_CHAN |
| OIL | 9 | 4 | FO-HLV3-ZSO | FO Day Tank 1 Inlet Vlv Open | T | DI_CHAN |
| OIL | 12 | 5 | FO-HLV4-OPN | FO Day Tank 2 Inlet Vlv Open Command | T | DO_CHAN |
| OIL | 10 | 1 | FO-HLV4-ZSC | FO Day Tank 2 Inlet Vlv Closed | T | DI_CHAN |
| OIL | 10 | 2 | FO-HLV4-ZSO | FO Day Tank 2 Inlet Vlv Open | T | DI_CHAN |
| OIL | 13 | 1 | FO-HT1-ON | Loading HT ON/OFF | T | DO_CHAN |
| OIL | 13 | 2 | FO-HT2-ON | Unloading HT ON/OFF | T | DO_CHAN |
| OIL | 13 | 3 | FO-HT3-ON | Storage Tanks HT ON/OFF | T | DO_CHAN |
| OIL | 13 | 4 | FO-HT4-ON | Fill Line Heat Trace ON/OFF | T | DO_CHAN |
| OIL | 13 | 5 | FO-HT5-ON | Day Tank Heat Trace ON/OFF | T | DO_CHAN |
| OIL | 13 | 6 | FO-LR-06 | FO Storage Tank 1 Level Low Light | T | DO_CHAN |
| OIL | 13 | 7 | FO-LR-07 | FO Storage Tank 1 Level High Light | T | DO_CHAN |
| OIL | 13 | 8 | FO-LR-08 | FO Storage Tank 2 Level Low Light | T | DO_CHAN |
| OIL | 14 | 1 | FO-LR-09 | FO Storage Tank 2 Level High Light | T | DO_CHAN |
| OIL | 14 | 2 | FO-LR-10 | FO Day Tank 1 Level Low Light | T | DO_CHAN |
| OIL | 14 | 3 | FO-LR-11 | FO Day Tank 1 Level High Light | T | DO_CHAN |
| OIL | 14 | 4 | FO-LR-12 | FO Day Tank 2 Level Low Light | T | DO_CHAN |
| OIL | 14 | 5 | FO-LR-13 | FO Day Tank 2 Level High Light | T | DO_CHAN |
| OIL | 8 | 4 | FO-LSH-003 | FO Pump House Sump Level High | T | DI_CHAN |
| OIL | 3 | 3 | FO-LSHH-001A | Fuel Oil Tank 1 Level Hi Hi 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 3 | FO-LSHH-001B | Fuel Oil Tank 1 Level Hi Hi 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 4 | FO-LSHH-002A | Fuel Oil Tank 2 Level Hi Hi 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 4 | FO-LSHH-002B | Fuel Oil Tank 2 Level Hi Hi 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 7 | FO-LSHH-003A | Fuel Oil Day Tank 1 Level Hi Hi 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 7 | FO-LSHH-003B | Fuel Oil Day Tank 1 Level Hi Hi 2 | T | DI_CHAN_SER2 |
| OIL | 3 | 8 | FO-LSHH-004A | Fuel Oil Day Tank 2 Level Hi Hi 1 | T | DI_CHAN_SER2 |
| OIL | 4 | 8 | FO-LSHH-004B | Fuel Oil Day Tank 2 Level Hi Hi 2 | T | DI_CHAN_SER2 |
| OIL | 1 | 1 | FO-LT-001 | Fuel Oil Tank 1 Level | T | AI_HART_CHAN |
| OIL | 1 | 2 | FO-LT-002 | Fuel Oil Tank 2 Level | T | AI_HART_CHAN |
| OIL | 2 | 1 | FO-LT-003 | Fuel Oil Day Tank 2 Level | T | AI_CHAN |
| OIL | 2 | 2 | FO-LT-004 | Fuel Oil Day Tank 1 Level | T | AI_CHAN |
| OIL | 11 | 2 | FO-P1-EN | FO Unloading Pump 1 Enable Command | T | DO_CHAN |
| B2 | 9 | 26 | FO-P1-LO | Fuel Oil Pump Skid P-1 Low Flow | T | DI_HD_CHAN |
| OIL | 6 | 3 | FO-P1-RUN | Unloading Pump P1 Run Status | T | DI_CHAN |
| OIL | 11 | 1 | FO-P1-STRT | FO Unloading Pump 1 Start Command | T | DO_CHAN |
| OIL | 12 | 2 | FO-P2-EN | FO Unloading Pump 2 Enable Command | T | DO_CHAN |
| B2 | 9 | 27 | FO-P2-LO | Fuel Oil Pump Skid P2 Low Flow | T | DI_HD_CHAN |
| OIL | 7 | 1 | FO-P2-RUN | Unloading Pump P2 Run Status | T | DI_CHAN |
| OIL | 12 | 1 | FO-P2-STRT | FO Unloading Pump 2 Start Command | T | DO_CHAN |
| OIL | 11 | 5 | FO-P3-EN | FO Xfer Pump 3 Enable Command | T | DO_CHAN |
| B2 | 9 | 28 | FO-P3-LO | Fuel Oil Pump Skid P3 Low Flow | T | DI_HD_CHAN |
| OIL | 8 | 3 | FO-P3-RUN | FO Xfer Pump P3 Run Status | T | DI_CHAN |
| OIL | 12 | 4 | FO-P4-EN | FO Xfer Pump 4 Enable Command | T | DO_CHAN |
| OIL | 9 | 1 | FO-P4-RUN | Xfer Pump P4 Run Status | T | DI_CHAN |
| B2 | 5 | 5 | FO-PT-001 | Fuel Oil Pump Skid Pressure | T | AI_HART_CHAN |
| B2 | 9 | 29 | FO-RTT-BLK | Fuel Oil Skid RTT Blocked | T | DI_HD_CHAN |
| OIL | 11 | 4 | FO-TCV1-OPN | FO Xfer Pump Bypass Vlv Open Command | T | DO_CHAN |
| OIL | 8 | 1 | FO-TCV1-ZSC | FO Xfer Pump Bypass Vlv Closed | T | DI_CHAN |
| OIL | 8 | 2 | FO-TCV1-ZSO | FO Xfer Pump Bypass Vlv Open | T | DI_CHAN |
| OIL | 5 | 5 | FO-TR2-ON | Unloading Heat Trace On | T | DI_CHAN |
| OIL | 5 | 6 | FO-TR3-ON | Storage Tank Heat Trace On | T | DI_CHAN |
| OIL | 5 | 7 | FO-TR4-ON | Fill Line Heat Trace On | T | DI_CHAN |
| OIL | 5 | 8 | FO-TR5-ON | Day Tank Heat Trace On | T | DI_CHAN |
| OIL | 6 | 1 | FO-TSL-001 | Loading Piping Low Temperature | T | DI_CHAN |
| OIL | 6 | 2 | FO-TSL-002 | Fill Line Piping Low Temperature | T | DI_CHAN |
| OIL | 7 | 4 | FO-TSL-005 | Storage Tank Piping Low Temperature | T | DI_CHAN |
| OIL | 7 | 5 | FO-TSL-006 | Storage Tank Piping Low Temperature | T | DI_CHAN |
| OIL | 7 | 6 | FO-TSL-007 | Storage Tank Piping Low Temperature | T | DI_CHAN |
| B2 | 5 | 6 | FO-TT-001 | Fuel Oil Pump Skid Temperate | T | AI_HART_CHAN |
| OIL | 1 | 3 | FO-TT-001A | Fule Oil Tank 1 Temperature | T | AI_HART_CHAN |
| OIL | 1 | 4 | FO-TT-002A | Fuel Oil Tank 2 Temperature | T | AI_HART_CHAN |
| OIL | 1 | 5 | FO-TT-003 | Day Tank Fill Piping | T | AI_CHAN |
| OIL | 1 | 6 | FO-TT-004 | Storage Tank Suction Piping Temp | T | AI_CHAN |
| OIL | 1 | 7 | FO-TT-005 | Storage Tank Fill Piping Temp | T | AI_CHAN |
| OIL | 1 | 8 | FO-TT-006 | Load/Unload Piping Temperature | T | AI_CHAN |
| OIL | 2 | 3 | FO-TT-007 | Hot Water Piping Temp | T | AI_CHAN |
| OIL | 9 | 6 | FO-UNLOAD-AUTO | Unloading Pump Auto Selected | T | DI_CHAN |
| OIL | 9 | 5 | FO-UNLOAD-P1 | Unloading Pump P1 Selected | T | DI_CHAN |
| OIL | 9 | 7 | FO-UNLOAD-P2 | Unloading Pump P2 Selected | T | DI_CHAN |
| OIL | 6 | 4 | FO-UNLOAD-STRT | Unloading Pumps Start Request (CR3) | T | DI_CHAN |
| OIL | 10 | 6 | FO-XFER-DTK | FO Transfer Day Tank Selected | T | DI_CHAN |
| OIL | 10 | 7 | FO-XFER-LOAD | FO Transfer Load Selected | T | DI_CHAN |
| OIL | 10 | 8 | FO-XFER-TKTK | FO Transfer Tank To Tank Selected | T | DI_CHAN |
| B1 | 2 | 5 | FT-0100A | Peir Steam Flow | T | AI_CHAN |
| B1 | 2 | 7 | FT-0100B | Main Steam Flow | T | AI_HART_CHAN |
| B3 | 2 | 3 | FT-0201 | 5 LBS Steam Flow | T | AI_HART_CHAN |
| B1 | 5 | 6 | FT-0500 | Raw Water Flow | F | AI_CHAN |
| B1 | 2 | 2 | FT-1101 | Boiler 1 Steam Outlet Header Flow | T | AI_HART_CHAN |
| B1 | 2 | 3 | FT-1201 | Boiler 1 Feedwater Flow | T | AI_CHAN |
| B3 | 4 | 1 | FT-1202 | Spare | T | AI_CHAN |
| B1 | 2 | 4 | FT-1401 | Boiler 1 Fuel Gas Flow | T | AI_CHAN |
| B1 | 1 | 3 | FT-1501 | SSCB20050920 | T | AI_HART_CHAN |
| B1 | 2 | 6 | FT-1601 | Boiler 1 Combustion Air Flow | T | AI_CHAN |
| B2 | 2 | 2 | FT-2101 | Boiler 2 Steam Outlet Header Flow | T | AI_HART_CHAN |
| B2 | 2 | 3 | FT-2201 | Boiler 2 Feedwater Flow | T | AI_CHAN |
| B2 | 4 | 5 | FT-2202 | B2 FEEDWATER FLOW (VORTEX) | T | AI_HART_CHAN |
| B2 | 2 | 4 | FT-2401 | Boiler 2 Fuel Gas Flow | T | AI_CHAN |
| B2 | 1 | 3 | FT-2501 | Boiler 2 Fuel Oil Flow | T | AI_CHAN |
| B2 | 2 | 6 | FT-2601 | Boiler 2 Combustion Air Flow | T | AI_CHAN |
| B2 | 2 | 5 | FT-2601A | Analog Input Channel | F | AI_CHAN |
| B1 | 4 | 5 | FT-2A | South Area Steam Flow | T | AI_HART_CHAN |
| B3 | 3 | 4 | FT2B | North Steam Flow | T | AI_HART_CHAN |
| B3 | 2 | 1 | FT-3201 | B3 Feedwater Flow | T | AI_HART_CHAN |
| B3 | 2 | 2 | FT-3609 | AHU Gas Flow XMTR | T | AI_CHAN |
| B3 | 6 | 8 | FT-3B | North Area Gilflow | T | AI_CHAN |
| B4 | 2 | 2 | FT-4101 | B4 Steam Flow | T | AI_HART_CHAN |
| B4 | 6 | 3 | FT-4101B | Compensted Steam Flow (3095) | T | AI_HART_CHAN |
| B4 | 4 | 4 | FT-4201 | B4 Feedwatrer Flow | T | AI_HART_CHAN |
| B4 | 4 | 5 | FT-4401 | B4 Fuel Gas Flow | T | AI_HART_CHAN |
| B4 | 4 | 7 | FT-4501 | B4 Fuel Oil Flow | T | AI_HART_CHAN |
| B4 | 5 | 3 | FT-4601 | B4 Air Flow | T | AI_HART_CHAN |
| B4 | 5 | 8 | FT-4711 | B4 Flue Gas Recirc Flow | T | AI_CHAN |
| B4 | 1 | 7 | FT-4810 | Cooling Water Flow to HTR | F | AI_CHAN |
| B3 | 2 | 5 | FT-STM-BPST | Steam Flow to Back Pressure Steam Turbine | F | AI_HART_CHAN |
| B1 | 4 | 4 | FT-WS-01 | Water Softner #1 Flow | T | AI_CHAN |
| B1 | 5 | 4 | FT-WS-02 | Water Softner #2 Flow | F | AI_CHAN |
| B1 | 5 | 8 | FT-WS-03 | Water Softner #3 Flow | F | AI_CHAN |
| B3 | 13 | 3 | FT-WS-2 | Water Softner #2 Flow | T | DIN_CHAN |
| B3 | 13 | 4 | FT-WS-3 | Water Softner #3 Flow | T | PIN_CHAN |
| B3 | 1 | 8 | FT-WST | Soft Water Total Flow | T | AI_CHAN |
| B3 | 11 | 3 | FV-800A | Main DA Vent Cooling BFW Solenoid Valve | T | DO_CHAN |
| B3 | 11 | 4 | FV-800B | Aux DA Vent Cooling BFW Solenoid Valve | T | DO_CHAN |
| B3 | 6 | 7 | GFI_1 | GFI in Generator Room | T | AI_CHAN |
| B4 | 9 | 9 | HS-0506A | Fuel Oil Pump 1 Run Status | T | DI_HD_CHAN |
| B4 | 9 | 10 | HS-0506B | Fuel Oil Pump No. 2 Run Status | T | DI_HD_CHAN |
| B1 | 9 | 6 | HS-0506C | Fuel Oil Pump No. 3 Run Status | T | DI_HD_CHAN |
| B3 | 15 | 1 | HS-LV1 | OPEN Make Up Air Louver #1 | T | DO_CHAN_SER2 |
| B3 | 15 | 2 | HS-LV2 | OPEN Make Up Air Louver #2 | T | DO_CHAN_SER2 |
| B3 | 15 | 3 | HS-LV3 | OPEN Make Up Air Louver #3 | T | DO_CHAN_SER2 |
| OIL | 6 | 7 | HTW-BCP1-RUN | Boiler Circ Pump 1 Run Status | T | DI_CHAN |
| OIL | 7 | 7 | HTW-BCP2-RUN | Boiler Circ Pump 2 Run Status | T | DI_CHAN |
| OIL | 11 | 7 | HTW-CCP1-EN | Coil Circ Pump 1 Enable Command | T | DO_CHAN |
| OIL | 6 | 8 | HTW-CCP1-RUN | Coil Circ Pump 1 Run Status | T | DI_CHAN |
| OIL | 12 | 6 | HTW-CCP2-EN | Coil Circ Pump 2 Enable Command | T | DO_CHAN |
| OIL | 7 | 8 | HTW-CCP2-RUN | Coil Circ Pump 2 Run Status | T | DI_CHAN |
| OIL | 8 | 8 | HTW-CCP-STRT | Coil Circ Pump Start Request ( Master Boiler Control) | T | DI_CHAN |
| OIL | 10 | 4 | HTW-COIL-AUTO | Coil Circ Pump Auto Selected | T | DI_CHAN |
| OIL | 10 | 3 | HTW-COIL-P1 | Coil Circ Pump P1 Selected | T | DI_CHAN |
| OIL | 10 | 5 | HTW-COIL-P2 | Coil Circ Pump P2 Selected | T | DI_CHAN |
| OIL | 8 | 7 | HTW-FS-003 | Coil Circ Pump 1 Flow | T | DI_CHAN |
| OIL | 9 | 8 | HTW-FS-004 | Coil Circ Pump P4 Flow | T | DI_CHAN |
| B3 | 6 | 1 | KWT-BPST | Steam Turbine KiloWatts | F | AI_CHAN |
| B1 | 7 | 5 | LCV_0302 | Main DA Level Control Valve | T | AO_ENABLED_HART_CHAN |
| B3 | 8 | 4 | LCV-1 | LCV-1 Main Condensate Receiver | T | AO_DISABLED_HART_CHAN |
| B3 | 8 | 5 | LCV-2 | LCV-2 #2 Deaerator Level | T | AO_ENABLED_HART_CHAN |
| B4 | 7 | 4 | LCV-4204 | B4 Blowdown Tank Level Control Valve | T | AO_ENABLED_HART_CHAN |
| B1 | 9 | 28 | LSH-10 | Flash Tank Level High | T | DI_HD_CHAN |
| B1 | 6 | 2 | LT-0301 | Common Main Deaerator Level | T | AI_HART_CHAN |
| B1 | 6 | 1 | LT-0302 | Common Aux Deaerator Level | T | AI_HART_CHAN |
| B3 | 5 | 4 | LT-1 | Main Condensate Receiver Level | T | AI_HART_CHAN |
| B1 | 2 | 8 | LT-1203 | Boiler 1 Steam Drum Level | T | AI_CHAN |
| B3 | 5 | 5 | LT-2 | #2 DA Level | T | AI_CHAN |
| B2 | 2 | 8 | LT-2203 | Boiler 2 Drum Level | T | AI_CHAN |
| B4 | 2 | 5 | LT-4202 | B4 Blowdown Tank Level | T | AI_CHAN |
| B4 | 3 | 1 | LT-4203 | B4 Drum level | T | AI_HART_CHAN |
| OIL | 2 | 4 | OILC02CH04 | Analog Input Channel | F | AI_CHAN |
| OIL | 2 | 5 | OILC02CH05 | Analog Input Channel | F | AI_CHAN |
| OIL | 2 | 6 | OILC02CH06 | Analog Input Channel | F | AI_CHAN |
| OIL | 2 | 7 | OILC02CH07 | Analog Input Channel | F | AI_CHAN |
| OIL | 2 | 8 | OILC02CH08 | Analog Input Channel | F | AI_CHAN |
| OIL | 11 | 8 | OILC11CH08 | Spare | F | DO_CHAN |
| OIL | 12 | 8 | OILC12CH08 | Spare | F | DO_CHAN |
| OIL | 16 | 7 | OILC16CH07 | Spare | F | DO_CHAN |
| OIL | 16 | 8 | OILC16CH08 | Spare | F | DO_CHAN |
| B1 | 7 | 4 | PCV-0506 | FUEL OIL RECIRC VALVE | F | AO_DISABLED_HART_CHAN |
| B4 | 7 | 5 | PCV-4120 | MUD DRUM HEATER | T | AO_ENABLED_HART_CHAN |
| B3 | 4 | 4 | PDT-3710 | Boiler 3 Economizer Differential Pressure | T | AI_HART_CHAN |
| B4 | 3 | 6 | PDT-4710 | B4 Econ Diff Pressure | T | AI_HART_CHAN |
| B3 | 6 | 4 | PHBB_1 | Unit 1 PH | T | AI_HART_CHAN |
| B3 | 6 | 2 | PHBB_2 | Unit 2 PH | T | AI_HART_CHAN |
| B3 | 8 | 3 | PRV-1 | PRV-1 City Water Pressure | T | AO_DISABLED_HART_CHAN |
| B1 | 8 | 1 | PRV-100B | Output to PRV-100B | T | AO_ENABLED_HART_CHAN |
| B3 | 8 | 6 | PRV-2 | PRV-2,3 Winter Only 100# Line | T | AO_DISABLED_HART_CHAN |
| B3 | 10 | 2 | PRV-2B | North Header Pressure Control Valve | T | AO_DISABLED_HART_CHAN |
| B3 | 8 | 7 | PRV-5 | PRV-5 5# Reducing Station | T | AO_ENABLED_HART_CHAN |
| B3 | 10 | 5 | PRV-5A | 5# PRV Aux | T | AO_ENABLED_HART_CHAN |
| B3 | 8 | 2 | PRV-6 | PRV-6 Summer Only | T | AO_DISABLED_HART_CHAN |
| B1 | 6 | 3 | PT-0100 | Common Steam Header Pressure | T | AI_HART_CHAN |
| B1 | 5 | 7 | PT-0100B | 12" Main Steam Press | T | AI_HART_CHAN |
| B1 | 6 | 4 | PT-0211 | Common Feedwater Header Pressure 1 | T | AI_HART_CHAN |
| B1 | 6 | 5 | PT-0212 | Common Feedwater Header Pressure 2 | T | AI_HART_CHAN |
| B1 | 6 | 6 | PT-0518 | Common Fuel Oil Supply Pressure | T | AI_CHAN |
| B3 | 5 | 2 | PT-0700 | Auxiliary Deaerator Pressure | T | AI_HART_CHAN |
| B3 | 5 | 1 | PT-0800 | Plant Air Pressure | T | AI_HART_CHAN |
| B3 | 5 | 3 | PT-1 | PRV-1 City Water Pressure | T | AI_HART_CHAN |
| B1 | 3 | 1 | PT-1101 | Boiler 1 Steam Outlet Header Pressure | T | AI_HART_CHAN |
| B1 | 3 | 2 | PT-1102 | Boiler 1 Steam Drum Pressure | T | AI_CHAN |
| B1 | 6 | 7 | PT-1130 | Atomizing Steam Pressure | T | AI_CHAN |
| B1 | 3 | 3 | PT-1402 | Boiler 1 Fuel Gas Supply Pressure | T | AI_CHAN |
| B1 | 3 | 4 | PT-1403 | Boiler 1 Fuel Gas Burner Pressure | T | AI_HART_CHAN |
| B1 | 3 | 6 | PT-1502 | Boiler 1 Fuel Oil Burner Pressure | T | AI_HART_CHAN |
| B1 | 3 | 7 | PT-1603 | Boiler 1 FD Fan Inlet Pressure | T | AI_CHAN |
| B1 | 3 | 8 | PT-1604 | Boiler 1 FD Fan Discharge Pressure | T | AI_HART_CHAN |
| B1 | 4 | 1 | PT-1605 | Boiler 1 Windbox Pressure | T | AI_HART_CHAN |
| B1 | 4 | 2 | PT-1702 | Boiler 1 Furnace Pressure | T | AI_CHAN |
| B1 | 4 | 3 | PT-1704 | Boiler 1 ID Fan Inlet Pressure | T | AI_HART_CHAN |
| B3 | 5 | 6 | PT-2 | PRV-2,3 Winter Only 100# Steam Line | T | AI_HART_CHAN |
| B2 | 3 | 1 | PT-2101 | Boiler 2 Steam Outlet Header Pressure | T | AI_HART_CHAN |
| B2 | 3 | 2 | PT-2102 | Boiler 2 Steam Drum Pressure | T | AI_CHAN |
| B2 | 6 | 7 | PT-2130 | STMPSI@BRNR2 | T | AI_HART_CHAN |
| B2 | 3 | 4 | PT-2403 | Boiler 2 Fuel Gas Burner Pressure | T | AI_HART_CHAN |
| B2 | 3 | 6 | PT-2502 | Boiler 2 Fuel Oil Burner Pressure | T | AI_HART_CHAN |
| B2 | 3 | 7 | PT-2603 | Boiler 2 FD Fan Inlet Pressure | T | AI_CHAN |
| B2 | 3 | 8 | PT-2604 | Boiler 2 FD Fan Discharge Pressure | T | AI_HART_CHAN |
| B2 | 4 | 1 | PT-2605 | Boiler 2 Windbox Pressure | T | AI_HART_CHAN |
| B2 | 4 | 2 | PT-2702 | Boiler 2 Furnace Pressure | T | AI_CHAN |
| B2 | 4 | 3 | PT-2704 | Boiler 2 ID Fan Inlet Pressure | T | AI_HART_CHAN |
| B3 | 4 | 7 | PT-3402 | B3 Main Gas Supply Pressur | T | AI_HART_CHAN |
| B4 | 2 | 3 | PT-4101 | B4 Steam Outlet Header Pressure | T | AI_HART_CHAN |
| B4 | 4 | 3 | PT-4102 | B4 Steam Drum Pressure | T | AI_HART_CHAN |
| B4 | 2 | 1 | PT-4120 | Analog Input Channel | T | AI_HART_CHAN |
| B4 | 2 | 8 | PT-4130 | B4 Atomizing Steam Pressure | T | AI_HART_CHAN |
| B4 | 4 | 6 | PT-4402 | B4 Fuel Gas Supply Pressure | T | AI_HART_CHAN |
| B4 | 5 | 2 | PT-4403 | B4 Fuel Gas Burner Pressure | T | AI_HART_CHAN |
| B4 | 5 | 1 | PT-4502 | B4 Fuel Oil Burner Pressure | T | AI_HART_CHAN |
| B4 | 5 | 4 | PT-4603 | B4 FD Fan Inlet Pressure | T | AI_HART_CHAN |
| B4 | 5 | 5 | PT-4604 | FD Fan Discharge Pressure | T | AI_HART_CHAN |
| B4 | 5 | 6 | PT-4605 | B4 Windbox Pressure | T | AI_HART_CHAN |
| B4 | 3 | 4 | PT-4702 | B4 Furnace Pressure | T | AI_HART_CHAN |
| B4 | 3 | 5 | PT-4709 | B4 Boiler Outlet Pressure | T | AI_HART_CHAN |
| B3 | 5 | 7 | PT-5 | 5# Reducing Station | T | AI_HART_CHAN |
| B3 | 4 | 8 | PT-BPST-EXH | Steam Turbine Exhaust Pressure | F | AI_HART_CHAN |
| B3 | 5 | 8 | PT-BPST-INLET | Steam Turbine Inlet Pressure | F | AI_HART_CHAN |
| B3 | 14 | 2 | PT-POL | Condensate Polisher Pressure | T | AI_HART_CHAN |
| B3 | 1 | 5 | QCD-555 | Blr #3 Master Demand from PLC | T | AI_CHAN |
| B2 | 3 | 3 | SPARE0303 | Spare | F | AI_CHAN |
| B2 | 5 | 1 | SPARE0501 | Spare | F | AI_CHAN |
| B1 | 9 | 26 | SPARE0926 | spare | F | DI_HD_CHAN |
| B3 | 13 | 1 | SPARE1 | Spare Pulse Input Channel | T | PIN_CHAN |
| B1 | 8 | 5 | SPARE85 | Spare | F | AO_DISABLED_HART_CHAN |
| B1 | 9 | 8 | SPARE908 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 9 | SPARE909 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 27 | SPARE927 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 29 | SPARE929 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 30 | SPARE930 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 31 | SPARE931 | Spare | F | DI_HD_CHAN |
| B1 | 9 | 32 | SPARE932 | Spare | F | DI_HD_CHAN |
| B1 | 8 | 4 | SR-1606 | FD fan Speed Signal Repeated | F | AO_DISABLED_HART_CHAN |
| B3 | 1 | 1 | ST-0202 | BFP speed | T | AI_CHAN |
| B3 | 1 | 2 | ST-0204 | BFP Speed | T | AI_CHAN |
| B3 | 1 | 3 | ST-0205 | BFP speed | T | AI_CHAN |
| B1 | 1 | 2 | ST-1606 | Analog Input Channel | T | AI_CHAN |
| B2 | 1 | 2 | ST-2606 | Boiler 2 FD fan Speed | T | AI_CHAN |
| WIRELESS_GATEWAY | 1 | 1 | ST-3104 | 2nd level behind B1 West wall | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 1 | ST-3104 | 2nd level behind B1 West wall | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 2 | ST-3105 | 2nd lvl @ top of stairs West wall | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 2 | ST-3105 | 2nd lvl @ top of stairs West wall | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 3 | ST-3106 | 2nd level alongside Main DA | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 3 | ST-3106 | 2nd level alongside Main DA | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 4 | ST-3107 | 2nd lvl behind Softeners South Area Line | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 4 | ST-3107 | 2nd lvl behind Softeners South Area Line | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 5 | ST-3108 | North/South Bypass South end @ Cond Rec. | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 5 | ST-3108 | North/South Bypass South end @ Cond Rec. | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 6 | ST-3109 | 2nd lvl 60# red outlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 6 | ST-3109 | 2nd lvl 60# red outlet | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 7 | ST-3110 | 2nd lvl 60# red inlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 7 | ST-3110 | 2nd lvl 60# red inlet | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 8 | ST-3112 | West wall Feed Pump area | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 8 | ST-3112 | West wall Feed Pump area | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 9 | ST-3113 | #3 Feed Pump Outlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 9 | ST-3113 | #3 Feed Pump Outlet | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 10 | ST-3114 | 1st lvl above #4 Feed Pump VFD/Crossover drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 10 | ST-3114 | 1st lvl above #4 Feed Pump VFD/Crossover drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 11 | ST-3115 | 1st lvl above #3 Feed Pump | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 11 | ST-3115 | 1st lvl above #3 Feed Pump | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 12 | ST-3116 | 1st lvl above #4 Feed Pump VFD/Crossover drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 12 | ST-3116 | 1st lvl above #4 Feed Pump VFD/Crossover drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 13 | ST-3117 | 1st lvl above #4 Feed Pump VFD | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 13 | ST-3117 | 1st lvl above #4 Feed Pump VFD | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 14 | ST-3118 | #3 Cond Pump Steam Inlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 14 | ST-3118 | #3 Cond Pump Steam Inlet | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 15 | ST-3119 | 16" Header Drip 2nd level catwalk | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 15 | ST-3119 | 16" Header Drip 2nd level catwalk | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 16 | ST-3120 | 16" Header drip 2nd level catwalk | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 16 | ST-3120 | 16" Header drip 2nd level catwalk | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 17 | ST-3121 | 1st lvl Cond Pump 3 Turbine Outlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 17 | ST-3121 | 1st lvl Cond Pump 3 Turbine Outlet | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 18 | ST-3122 | 1st lvl above #4 Feed Pump VFD | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 18 | ST-3122 | 1st lvl above #4 Feed Pump VFD | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 19 | ST-3123 | 1st lvl behind B2 @ #11 Flash Tank | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 19 | ST-3123 | 1st lvl behind B2 @ #11 Flash Tank | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 20 | ST-3124 | 1st lvl behind B2 - air preheater | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 20 | ST-3124 | 1st lvl behind B2 - air preheater | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 21 | ST-3125 | 1st lvl behind B2 - air preheater | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 21 | ST-3125 | 1st lvl behind B2 - air preheater | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 22 | ST-3126 | 1st lvl behind B1 - air preheater | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 22 | ST-3126 | 1st lvl behind B1 - air preheater | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 23 | ST-3127 | 1st lvl behind B1 - air preheater | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 23 | ST-3127 | 1st lvl behind B1 - air preheater | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 24 | ST-3128 | 1st lvl @ Flash Tank #1 near DO Anal | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 24 | ST-3128 | 1st lvl @ Flash Tank #1 near DO Anal | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 25 | ST-3129 | 16" Header Drip 2nd lvl catwalk | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 25 | ST-3129 | 16" Header Drip 2nd lvl catwalk | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 26 | ST-3130 | 1st lvl North Wall @ Gen Room | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 26 | ST-3130 | 1st lvl North Wall @ Gen Room | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 27 | ST-3131 | 1st lvl @ Flash Tank #2 NW Corner | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 27 | ST-3131 | 1st lvl @ Flash Tank #2 NW Corner | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 28 | ST-3132 | 1st lvl @ Flash Tank #1above #1Feed Pump | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 28 | ST-3132 | 1st lvl @ Flash Tank #1above #1Feed Pump | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 29 | ST-3133 | North Area Pit | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 29 | ST-3133 | North Area Pit | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 30 | ST-3134 | 2nd level behind 60# red station | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 30 | ST-3134 | 2nd level behind 60# red station | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 31 | ST-3135 | 2nd lvl Catwalk @ Unit Heater in front of B2 | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 31 | ST-3135 | 2nd lvl Catwalk @ Unit Heater in front of B2 | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 32 | ST-3136 | 2nd lvl catwalk @ North/South Bypass North End | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 32 | ST-3136 | 2nd lvl catwalk @ North/South Bypass North End | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 33 | ST-3137 | 2nd lvl catwalk @ Unit Heater in front of B2 | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 33 | ST-3137 | 2nd lvl catwalk @ Unit Heater in front of B2 | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 34 | ST-3138 | 1st lvl South Area pit | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 34 | ST-3138 | 1st lvl South Area pit | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 35 | ST-3139 | #2 Burner Platform North/South Bypass | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 35 | ST-3139 | #2 Burner Platform North/South Bypass | T | WIRELESS_HART_INPUT_CHAN | |
| B4 | 1 | 2 | ST-4606 | B4 FD fan Speed | F | AI_CHAN |
| WIRELESS_GATEWAY | 1 | 36 | ST-5442 | B2 Superheater Outlet upper lvl | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 36 | ST-5442 | B2 Superheater Outlet upper lvl | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 37 | ST-5443 | B1Superheater Outlet upper level | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 37 | ST-5443 | B1Superheater Outlet upper level | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 38 | ST-5444 | Upper lvl 60# Bypass @ new Triple Offset Valve | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 38 | ST-5444 | Upper lvl 60# Bypass @ new Triple Offset Valve | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 40 | ST-5446 | B2 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 40 | ST-5446 | B2 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 41 | ST-5447 | B2 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 41 | ST-5447 | B2 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 42 | ST-5448 | B1 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 42 | ST-5448 | B1 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 43 | ST-5449 | B1 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 43 | ST-5449 | B1 Steam Atomizer Line | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 44 | ST-5593 | Unit Heater Corridor to B4 | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 44 | ST-5593 | Unit Heater Corridor to B4 | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 45 | ST-5594 | B4 Area Unit Heater above LOTO corner | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 45 | ST-5594 | B4 Area Unit Heater above LOTO corner | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 46 | ST-5595 | B4 Area Heat Trace for Crossover Piping | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 46 | ST-5595 | B4 Area Heat Trace for Crossover Piping | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 47 | ST-5596 | B4 Area Heat Trace for Crossover Piping | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 47 | ST-5596 | B4 Area Heat Trace for Crossover Piping | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 48 | ST-5597 | B4 Area Makeup Air Handler Coil | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 48 | ST-5597 | B4 Area Makeup Air Handler Coil | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 49 | ST-5598 | B4 Mud Drum Heater | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 49 | ST-5598 | B4 Mud Drum Heater | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 50 | ST-5599 | B4 Steam Atomizer Main Drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 50 | ST-5599 | B4 Steam Atomizer Main Drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 51 | ST-5600 | B4 Steam Atomizer LLP Drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 51 | ST-5600 | B4 Steam Atomizer LLP Drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 52 | ST-5601 | B4 Unit Heater@ Overhead Door | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 52 | ST-5601 | B4 Unit Heater@ Overhead Door | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 53 | ST-5602 | B4 Sootblower Drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 53 | ST-5602 | B4 Sootblower Drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 54 | ST-5603 | B4 Bott Blow Tank Area @ Flash Tank | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 54 | ST-5603 | B4 Bott Blow Tank Area @ Flash Tank | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 55 | ST-5604 | B4 Unit Heater above Bott Blow Tank | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 55 | ST-5604 | B4 Unit Heater above Bott Blow Tank | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 56 | ST-5605 | B4 under non-return | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 56 | ST-5605 | B4 under non-return | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 57 | ST-5606 | B4 Superheater Drain | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 57 | ST-5606 | B4 Superheater Drain | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 58 | ST-5607 | B4 Unit Heater above HVAC Unit | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 58 | ST-5607 | B4 Unit Heater above HVAC Unit | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 59 | ST-5608 | B4 Overhead drip above Condensate Receiver | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 59 | ST-5608 | B4 Overhead drip above Condensate Receiver | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 60 | ST-5609 | B4 HVAC Coil Drain | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 60 | ST-5609 | B4 HVAC Coil Drain | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 61 | ST-5610 | B4 Flash Tank adjacent to HVAC | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 61 | ST-5610 | B4 Flash Tank adjacent to HVAC | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 63 | ST-5612 | 3rd lvl near top of Main DA | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 63 | ST-5612 | 3rd lvl near top of Main DA | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 69 | ST-5614 | BPST | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 69 | ST-5614 | BPST | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 70 | ST-5615 | BPST | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 70 | ST-5615 | BPST | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 72 | ST-5617 | BPST | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 72 | ST-5617 | BPST | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 64 | ST-5618 | B4 Upper lvl adjacent to Makeup Air Handler | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 64 | ST-5618 | B4 Upper lvl adjacent to Makeup Air Handler | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 65 | ST-5619 | Fuel Skid area, oil heater drain | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 65 | ST-5619 | Fuel Skid area, oil heater drain | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 66 | ST-5620 | Fuel Skid area, oil heater drain | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 66 | ST-5620 | Fuel Skid area, oil heater drain | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 67 | ST-5621 | Fuel Skid area, steam inlet drip | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 67 | ST-5621 | Fuel Skid area, steam inlet drip | T | WIRELESS_HART_INPUT_CHAN | |
| WIRELESS_GATEWAY | 1 | 68 | ST-5622 | Feed Pump #3 Steam Inlet | T | WIRELESS_HART_INPUT_CHAN |
| 1 | 68 | ST-5622 | Feed Pump #3 Steam Inlet | T | WIRELESS_HART_INPUT_CHAN | |
| B1 | 8 | 6 | STMFLO_CHEM | Steam Flow To Chemical Injection | T | AO_DISABLED_HART_CHAN |
| B3 | 7 | 6 | SY-0202 | BFP speed | T | AO_DISABLED_HART_CHAN |
| B3 | 7 | 5 | SY-0203 | BFP speed | T | AO_DISABLED_HART_CHAN |
| B3 | 7 | 7 | SY-0204 | BFP speed | T | AO_DISABLED_HART_CHAN |
| B3 | 7 | 8 | SY-0205 | BFP speed | T | AO_DISABLED_HART_CHAN |
| B3 | 14 | 1 | T-1 | Temp Desuperheater Transmitter | T | AI_HART_CHAN |
| B4 | 7 | 3 | TCV-4205 | B4 Blowoff Tank Control Valve | T | AO_ENABLED_HART_CHAN |
| B4 | 8 | 1 | TCV-4812 | Blowdown Htr FCV | T | AO_DISABLED_HART_CHAN |
| B3 | 10 | 4 | TCVBB_1 | Temp Control Valve | T | AO_ENABLED_HART_CHAN |
| B2 | 8 | 1 | TD1601C | Boiler #2 FD Fan Turbine Drive | F | AO_DISABLED_HART_CHAN |
| B3 | 10 | 3 | TIK-1 | Valve Desuperheater | T | AO_ENABLED_HART_CHAN |
| B1 | 3 | 5 | TT-0100 | Main Steam Temperature | T | AI_HART_CHAN |
| B3 | 3 | 8 | TT-0301 | Aux DA Temperature | T | AI_HART_CHAN |
| B1 | 2 | 1 | TT-1101 | SUPER HEATER OUT | T | AI_HART_CHAN |
| B1 | 4 | 6 | TT-1607 | Boiler 1 FD Fan Inlet Temperature | T | AI_HART_CHAN |
| B1 | 4 | 7 | TT-1608 | Boiler 1 Ambient Air Temperature | T | AI_HART_CHAN |
| B1 | 4 | 8 | TT-1705 | Boiler 1 Flue Gas Temperature | T | AI_HART_CHAN |
| B1 | 5 | 1 | TT-1706 | Boiler 1 Fuel Gas Temperature | T | AI_CHAN |
| B1 | 5 | 2 | TT-1707 | Boiler 1 Flue Gas Recirc Temperature | T | AI_HART_CHAN |
| B1 | 5 | 3 | TT-1708 | Boiler 1 Flue Gas Recirc / FD Mix Temperature | T | AI_CHAN |
| B1 | 5 | 5 | TT-2 | #100 steam temperature | T | AI_HART_CHAN |
| B2 | 2 | 1 | TT-2101 | Boiler 2 Superheat Temp | T | AI_HART_CHAN |
| B2 | 4 | 6 | TT-2607 | Boiler 2 FD Fan Inlet Temperature | T | AI_HART_CHAN |
| B2 | 4 | 7 | TT-2608 | Boiler 2 Outdoor Air Temperature | T | AI_CHAN |
| B2 | 4 | 8 | TT-2705 | Boiler 2 Flue Gas Temperature Transmitter | T | AI_HART_CHAN |
| B2 | 5 | 2 | TT-2707 | Boiler 2 Flue Gas Recirc Temperature | T | AI_HART_CHAN |
| B2 | 5 | 3 | TT-2708 | Boiler 2 Flue Gas Recirc / FD Fan Mix Temperature | T | AI_HART_CHAN |
| B3 | 3 | 7 | TT-3210 | B3 FW Economizer Inlet Temperature | T | AI_HART_CHAN |
| B3 | 3 | 5 | TT-3211 | B3 FW Economizer Outlet Temperature | T | AI_HART_CHAN |
| B3 | 3 | 6 | TT-3711 | Boiler 3 Economizer Flue Gas Outlet Temperature | T | AI_HART_CHAN |
| B4 | 2 | 4 | TT-4101 | B4 Steam Outlet Header Temperature | T | AI_HART_CHAN |
| B4 | 2 | 6 | TT-4205 | B4 Blowoff Tank Temperature | T | AI_HART_CHAN |
| B4 | 3 | 2 | TT-4208 | B4 Econ Inlet FW Temperature | T | AI_HART_CHAN |
| B4 | 3 | 3 | TT-4209 | B4 Econ Outlet FW Temperature | T | AI_HART_CHAN |
| B4 | 5 | 7 | TT-4607 | B4 FD Fan In Temp | T | AI_HART_CHAN |
| B4 | 4 | 8 | TT-4608 | Ambient Air Temp | T | AI_HART_CHAN |
| B4 | 3 | 7 | TT-4705 | B4 Econ Flue Gas Inlet Temperature | T | AI_HART_CHAN |
| B4 | 3 | 8 | TT-4706 | B4 Econ Flue Gas Outlet Temperature | T | AI_HART_CHAN |
| B4 | 4 | 1 | TT-4707 | B4 Flue Gas Recirc Temperature | T | AI_HART_CHAN |
| B4 | 4 | 2 | TT-4708 | B4 Flue Gas Recirc / FD Mix Temp | T | AI_HART_CHAN |
| B4 | 6 | 4 | TT-4810 | Blwd Hrt Cooling Water Inlet Temp | T | AI_CHAN |
| B4 | 6 | 5 | TT-4811 | Blwd Hrt Cooling Water Outlet Temp | T | AI_CHAN |
| B4 | 6 | 6 | TT-4812 | Blwd Hrt Water Outlet Temp | T | AI_CHAN |
| B3 | 2 | 6 | TT-801A | Main DA Vent Condensor BFW Inlet Temp | T | AI_HART_CHAN |
| B3 | 3 | 1 | TT-801B | Aux DA Vent Condensor BFW Inlet Temp | T | AI_HART_CHAN |
| B3 | 2 | 7 | TT-802A | Main DA Vent Condensor BFW Outlet Temp | T | AI_HART_CHAN |
| B3 | 3 | 2 | TT-802B | Aux DA Vent Condensor BFW Outlet Temp | T | AI_HART_CHAN |
| B3 | 6 | 5 | TTBB_1 | Unit 1 Temp | T | AI_CHAN |
| B3 | 6 | 3 | TTBB_2 | Unit 2 Temp | T | AI_CHAN |
| B1 | 6 | 8 | TT-DA-TEMP | Large DA Tank Temperature | T | AI_HART_CHAN |
| B4 | 11 | 4 | UA-CCF | Combustion Control Failure | T | DO_CHAN |
| OIL | 12 | 7 | UNLOAD | Unloading Pump Drop Out | T | DO_CHAN |
| B3 | 10 | 6 | VFD-CP1 | Condensate Pump 1 | T | AO_DISABLED_HART_CHAN |
| B3 | 10 | 7 | VFD-CP2 | Condensate Pump 2 | T | AO_DISABLED_HART_CHAN |
| B1 | 8 | 2 | VSD-1601B | Boiler 1 FD Fan Variable Speed Drive | T | AO_DISABLED_HART_CHAN |
| B1 | 8 | 3 | VSD-1702B | Boiler 1 ID Fan Variable Speed Drive | T | AO_DISABLED_HART_CHAN |
| B2 | 7 | 2 | VSD-2601B | FD FAN SPEED DEMAND | T | AO_DISABLED_HART_CHAN |
| B2 | 7 | 3 | VSD-2702B | ID FAN SPEED DEMAND | T | AO_DISABLED_HART_CHAN |
| B4 | 8 | 2 | VSD-4601B | B4 FD Fan VFD | T | AO_DISABLED_HART_CHAN |
| B1 | 7 | 3 | XA-0301 | Aux DA level Repeated to Main Panel | T | AO_DISABLED_HART_CHAN |
| B1 | 7 | 2 | XA-0302 | Main DA Level Repeated To Main Panel | T | AO_DISABLED_HART_CHAN |
| B3 | 9 | 5 | XI-1920 | Blr #3 DeltaV Take Control | T | DI_HD_CHAN |
| B3 | 11 | 5 | XO-1809 | Blr #3 Delta V InCtrl | T | DO_CHAN |
| B3 | 11 | 6 | XO-1812 | Blr #3 DeltaV Stop | T | DO_CHAN |
| B3 | 1 | 7 | XT-0500 | Chemical Feed Pump Rate NexGuard | T | AI_CHAN |
| B4 | 11 | 7 | XV_4204 | Discrete Output Channel | T | DO_CHAN |
| B3 | 11 | 1 | XV-1204 | Discrete Output Channel | T | DO_CHAN |
| B3 | 11 | 2 | XV-2204 | Discrete Output Channel | T | DO_CHAN |
| B4 | 11 | 1 | XV-4103 | Superheater Drain Valve Open | T | DO_CHAN |
| B4 | 11 | 2 | XV-4707A | Flue Gas Recirc Low Load | T | DO_CHAN |
| B4 | 11 | 3 | XV-4707B | Flue Gas Recirc High Load | T | DO_CHAN |
| B1 | 9 | 1 | ZS-1901 | Boiler 1 Combustion Control To Lightoff | T | DI_HD_CHAN |
| B1 | 9 | 2 | ZS-1902 | Combustion Control To Purge Position | T | DI_HD_CHAN |
| B1 | 9 | 3 | ZS-1903 | Boiler 1 Combustion Control To Modulation | T | DI_HD_CHAN |
| B1 | 9 | 4 | ZS-1904 | Boiler 1 Fuel Gas Select In Gas | T | DI_HD_CHAN |
| B1 | 9 | 5 | ZS-1905 | Boiler 1 Fuel select In Oil | T | DI_HD_CHAN |
| B2 | 9 | 1 | ZS-2901 | Boiler 2 To Lightoff position | T | DI_HD_CHAN |
| B2 | 9 | 2 | ZS-2902 | Boiler 2 to Purge Position | T | DI_HD_CHAN |
| B2 | 9 | 3 | ZS-2903 | Boiler 2 Release To Modulation | T | DI_HD_CHAN |
| B2 | 9 | 4 | ZS-2904 | Boiler 2 in Gas position | T | DI_HD_CHAN |
| B2 | 9 | 5 | ZS-2905 | Boiler 2 in Oil Position | T | DI_HD_CHAN |
| B4 | 9 | 1 | ZS-4901 | Lightoff Position | T | DI_HD_CHAN |
| B4 | 9 | 2 | ZS-4902 | Purge Position | T | DI_HD_CHAN |
| B4 | 9 | 3 | ZS-4903 | Release To Modulation | T | DI_HD_CHAN |
| B4 | 9 | 4 | ZS-4904 | Gas Selected | T | DI_HD_CHAN |
| B4 | 9 | 5 | ZS-4905 | Oil Selected | T | DI_HD_CHAN |
| B4 | 9 | 6 | ZS-4906 | B4 FD Fan Run Indication | T | DI_HD_CHAN |
| B3 | 9 | 14 | ZSC_LV1 | MUA Louver #1 Closed Limit Switch | T | DI_HD_CHAN |
| B3 | 9 | 16 | ZSC_LV2 | MUA Louver #2 Closed Limit Switch | T | DI_HD_CHAN |
| B3 | 9 | 18 | ZSC_LV3 | MUA Louver #3 Closed Limit Switch | T | DI_HD_CHAN |
| B4 | 9 | 7 | ZSC-4103 | Superheat Drain Valve Closed | T | DI_HD_CHAN |
| B3 | 9 | 13 | ZSO_LV1 | MUA Louver #1 Open Limit Switch | T | DI_HD_CHAN |
| B3 | 9 | 15 | ZSO_LV2 | MUA Louver #2 Open Limit Switch | T | DI_HD_CHAN |
| B3 | 9 | 17 | ZSO_LV3 | MUA Louver #3 Open Limit Switch | T | DI_HD_CHAN |
| B4 | 9 | 8 | ZSO-4103 | Suerheat Drain Valve Opened | T | DI_HD_CHAN |
| B4 | 6 | 2 | ZT_4601A | B4 Damper Feedback | T | AI_CHAN |
| B4 | 6 | 1 | ZT_4707 | Analog Input Channel | T | AI_CHAN |
| B1 | 1 | 5 | ZT-1601A | Analog Input Channel | T | AI_CHAN |
| B1 | 1 | 6 | ZT-1602 | Analog Input Channel | T | AI_CHAN |
| B1 | 1 | 7 | ZT-1702A | Analog Input Channel | T | AI_CHAN |
| B1 | 1 | 8 | ZT-1703 | Analog Input Channel | T | AI_CHAN |
| B2 | 1 | 5 | ZT-2601A | Boiler 2 FD Fan Damper Position | T | AI_CHAN |
| B2 | 1 | 6 | ZT-2602 | Boiler 2 Windbox Damper position | T | AI_CHAN |
| B2 | 1 | 7 | ZT-2702A | Boiler 2 ID Fan Damper Position | T | AI_CHAN |
| B2 | 1 | 8 | ZT-2703 | Boiler 3 Flue Gas Damper Position | T | AI_CHAN |
| B4 | 1 | 6 | ZT-4106B | FD Fan VFD Speed FB | T | AI_CHAN |
| B1 | 8 | 8 | Was Repeat LVL of Main DA Spare as of 12/8/10 | F | AO_DISABLED_HART_CHAN | |
| B3 | 4 | 6 | Fuel Oil Burner Pressure unused spare channel | F | AI_CHAN | |
| B3 | 8 | 8 | spare | F | AO_ENABLED_HART_CHAN | |
| B4 | 9 | 27 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 9 | 28 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 9 | 29 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 9 | 30 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 9 | 31 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 9 | 32 | Discrete Input Channel (HD) | F | DI_HD_CHAN | |
| B4 | 11 | 8 | Discrete Output Channel | F | DO_CHAN |