Encl(1)_Government_Response_A0003.pdf
PDF 65 KB Posted
- Solicitation number
- N4008420B5402
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Encl(2)_3_English_DS_MSDS_Test_Foam.pdf | ||
| 20B5402_A0005.pdf | ||
| Encl(1)_Government_Response_A0005.pdf | ||
| 20B5402_A0004.pdf | ||
| Encl(2)_Amendment_List_A0004.pdf | ||
| Encl(1)_PWS_Replacement_Pages_A0004.pdf | ||
| Atch(2)_J-0200000-16_ELINs_A0004.xlsx | XLSX spreadsheet | |
| 20B5402_A0003.pdf | ||
| 20B5402_A0002.pdf | ||
| Encl(1)_Goverment_Response_A0002.pdf | ||
| Encl(1)_Government_Response_A0001.pdf | ||
| Encl(3)_Amendment_Llist_A0001.pdf | ||
| Encl(2)_PWS_Replacement_Pages_A0001.pdf | ||
| 20B5402_A0001.pdf | ||
| 20B5402_SF1449.pdf | ||
| Atch(2)_J-0200000-16_ELINs.xlsx | XLSX spreadsheet | |
| Atch(4)_PreBid_Inquiry_Form.xlsx | XLSX spreadsheet | |
| Atch(3)_1-Day_Official_Entry-Exit_Request.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLICITATION NO. N4008420B5402
PROJECT TITLE/LOCATION: FIRE PROTECTION SYSTEMS MAINTENANCE, TESTING, REPAIR AND INSTALLATION SERVICES AT U.S. MCAS IWAKUNI, JAPAN
GOVERNMENT PRE‐BID INQUIRY FORM Amendment 0003 Enclosure (1)
Page Section Para.
1 12‐Jun‐20 Amend 0001, government answers number 35
Question #35, we were mainly referring to the “Wet Chemical System” for the kitchen hoods.
It’s a semi‐annual frequency in the UFC 3‐601‐02 Table 2‐19.
Many buildings in the inventory has the wet chemical circled with the manufacture name listed but without quantities of kitchen hoods. Please confirm that the semi‐annual frequency stated in UFC 3‐601‐02 Table 2‐19 is not included in this contract.
When there is no quantity in the inventory, that means it is not included.
The tasks in UFC 3‐601‐02 Table 2‐19 shall apply only to the buildings with the quantities of wet chemical systems equipment specified in the inventory.
2 12‐Jun‐20 Amend 0001, government answers number 36
Question #36, sprinkler heads are included in UFC 3‐601‐02 Table 2‐2.
Frequency: As part of building Inspection Component: Entire System Tasks: Visual checks of sprinklers for obstruction.
Please confirm that the Annual frequency stated in UFC 3‐601‐ 02 Table 2‐2 is not included in this contract.
The tasks in UFC 3‐601‐02 (in all tables) required "as part of building inspection"are not included in this contract.
The tasks required annually are included and shall be performed under this contract.