0532_A_HTLT_Freshwater_System_Flush_REV_1.doc

DOC document 61 KB Posted

Attached to
USNS WASHINGTON CHAMBERS ROH/DD Federal contract opportunity
Solicitation number
N32205-18-R-4259
Issued by
Department of the Navy Military Sealift Command

About this file

Remove WI 0531 Industrial Support for SAWS Install (T-ALT 439) and 0802 Auxiliary Prestage Area Refrigeration Installation (T-ALT 485) from the solicitation and revise WI 0532 HT LT Freshwater System Flush REV 1 and 0606 Flight Deck Non-Skid renewal REV 1. Revised J-2 Document.

View the file

Other files for this federal contract opportunity

Other files attached to USNS WASHINGTON CHAMBERS ROH/DD, newest first.
File Type Posted
ROH_AMENDMENT_UNSN_CHAMBERS.docx DOCX document
Chambers_ROH_Amendment_0006.docx DOCX document
0606_Flight_Deck_Non-Skid_Renewal_Rev_-_(CSI)_REV_2.doc DOC document
0621_B_Replace_Deck_Covering_in_Various_Heads_(VR17-024)REV_1.doc DOC document
0030_B_Continution_of_Services_REV_1.doc DOC document
Chamber_ROH_Amendment_0005.docx DOCX document
0606_Flight_Deck_Non-Skid_Renewal_Rev_-_(CSI)_REV_1.doc DOC document
J_-_2_Category_A_Items_CHAMBERS.xls XLS spreadsheet
Chambers_ROH_Amendment_0005.docx DOCX document
BQ_-_0007_WI_802_GFS_scope_Response.doc DOC document
BQ_-_0006_WI_531_Dwgs_Response.doc DOC document
8394521_-SaWS_Support_-_Mechanical_Dwg.pdf PDF
SAWS_INSTL_LIST_OF_CONNECTIONS_439-8394524.pdf PDF
Questions_and_Answers.docx DOCX document
0214_8_Cylinder_Main_Diesel_Engine_24000_Hour_Scheduled_Maintenance_(CSI).doc DOC document
0503_Self_Contained_Breathing_Appratus_(SCBA)_Air_Compressor_and_Re-Filling_Station_Inspection_and_Maintenance_Rev_-_(CSI).doc.doc DOC document
USNS_Chambers_ROH_Solicitation_0004.docx DOCX document
J_-_2_Category_A_Items_CHAMBERS_-_REV_1.xls XLS spreadsheet
0012_Information_Technology_Services_Rev_16July18.doc DOC document
0021__Clean_and_Gas_Free_Tanks_Voids_Cofferdams_and_Spaces.doc.doc DOC document
0010_Furnish_Office_for_Overhaul_Management_Team(OMT)_Rev16July18.doc DOC document
USNS_Chambers_ROH_Solicitation_0004.docx DOCX document
N3220518R4259_Amendment_0003.docx DOCX document
0532_A_HTLT_Freshwater_System_Flush.doc DOC document
0916_Underwater_Hull_Blast_&_Paint_(Spot_Blast)-_REV_(1).docx DOCX document
N3220518R4259_AMENDMENT_0002.docx DOCX document
USNS_CHAMBERS_ROH_AMENDMENT.docx DOCX document
USNS_CHAMBERS_ROH.docx DOCX document
J_&_A_N32205-18-Q-4259_Redacted.pdf PDF
J_Attachments_and_GFM.zip ZIP file
USNS_WASHINGTON_CHAMBERS_ROH.docx DOCX document
CDRLS.zip ZIP file
SYNOPSIS_N32205-18-R-4259.docx DOCX document
Show all 33

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USNS Chambers

( TAKE 11 )

AUXILIARY MACHINERY
CONTRACT NO. N32205-18-R-4259
ITEM NO. 0532
CATEGORY "A"
2018-09-10
HTLT Freshwater System Flush REV 1
Escobar, Daniel

1.0

ABSTRACT

This item describes the Industrial Assist for the flushing High Temperature (HTFW), Low Temperature Freshwater(LTFW) Cooling Systems

2.0

REFERENCES

2.1 MSC Dwg. No. 256-8499057; Central Seawater Cooling System Diagram

2.2 MSC Dwg. No. 532-8499061; Diesel Generator High Temperature Freshwater Cooling System Diagram

2.3 MSC Dwg. No. 532-8499083; Low Temperature Freshwater Cooling System Diagram

2.4 Drew Marine Flushing Procedure – Maxigard to Liquidewt

3.0 ITEM LOCATION/DESCRIPTION

3.1 Location/Quantity

3.1.1 Main Machinery Room (MMR)

3.1.2 Auxiliary Machinery Room (AMR)

3.1.3 System Capacities:

HTFW ≈ 2500 Gallons

LTFW ≈ 14750 Gallons

3.2 Contractor Furnished Equipment:

3.2.1 Contractor shall furnish all hoses, tanks, pumps, heat exchanger, valves, piping, elbows, plugs, etc. necessary to perform a satisfactory flush. Provide a measurement device able to measure the pH level of cleaning fluid, rinse, and final fill fluid.

3.2.1 Rainmaker or Distillate water to refill Distillate tanks.

3.2.1.1 30,000 Gallons of Distilled Water

3.2.2 Quantities are considered estimates. The contractor shall provide the exact quantities and (reasonable) additional material such as hose, hangers, sealant, screws, etc., in order to flush and install a fully functional system that meets the requirements of this specification.

4.0 GOVERNMENT FURNISHED EQUIPMENT/MATERIAL/SERVICES:

4.1 The following materials will be Government furnished:

4.1.1 Liquidewt ≈ 50 Pails

4.2 Government Furnished Services (GFS): None

5.0 NOTES:

5.1 The contractor and all subcontractors, regardless of tier, must consult the General Technical Requirements (GTR) to determine applicability to this work item. In performance of this work item, the contractor and all subcontractors regardless of tier must comply with the requirements of all applicable GTRs.

5.2 The contractor and all subcontractors regardless of tier are advised to review the other work items under this contract to determine their effect on the work required under this work item.

5.3 THIS SHIP CONTAINS HIGH VOLTAGE (HV) ELECTRICAL SYSTEMS. OBEY ALL POSTED AND VERBAL INSTRUCTIONS REGARDING SAFETY AND EXCLUSION FROM HIGH VOLTAGE AREAS. AT NO TIME APPROACH, WORK ON, OR ENTER A HIGH VOLTAGE AREA WITHOUT PROPER AUTHORIZATION.

5.4 T-AKE CLASS ELECTRICAL COLOR CODING DOES NOT FOLLOW CONSISTENT COLOR SCHEME. THE SHIP IS KNOWN TO HAVE CURRENT CARRYING CONDUCTORS COLORED GREEN, BLUE, BLACK, AND WHITE. ASSUME ALL ELECTRICAL CABLES ARE ENERGIZED UNTIL TESTED AND PROVEN OTHERWISE. TEST ALL ELECTICAL CABLES TO ENSURE THEY ARE DE-ENERGIZED PRIOR TO WORKING ON THE ITEM.

6.0 QUALITY ASSURANCE REQUIREMENTS: None additional.

7.0 STATEMENT OF WORK REQUIRED

7.1 Open and clean expansion tanks in accordance with Work Item 021.

7.1.1 Provide a Call Out for MSCREP to verify that all sludge and debris is removed and tank is dry.

7.2 Upon completion of tank cleaning, close tanks with new gaskets and wicking grommets.

7.2.1 Remove all coolant from the ship’s Drain Tank system and dispose of in accordance with Work Item 023 “Hazardous Waste Management and Disposal” and all Federal, State, and Local regulations.

7.2.2 Approximately 18,000 Gals of MAXIGARD Distillate Mix.

7.3 Use References 2.0 as guidance.

7.4 Fill Distillate Tanks with Distillate or Rain Maker water, Approximately 30,000 Gal.

7.5 Manufacturer Representative: None Additional

8.0 GENERAL REQUIREMENTS: None additional.

0532 - 1