MP04-M4-0.pdf

PDF 348 KB Posted

Attached to
GLENDALE FIRE STATION State and local contract opportunity
Solicitation number
ITB 24-29
Issued by
Walton County, Florida

About this file

This is a technical drawing specification document for the vehicle exhaust system installation at the Glendale Fire Station project, prepared by Winton Engineering for the Walton County Board of County Commissioners in Florida. The drawing details the mechanical specifications for a ceiling-mounted exhaust fan system designed to remove vehicle emissions from the fire station garage. The system includes a CF363-5 fan with 3,300 CFM airflow capacity operating at 3,450 RPM, powered by 208-230 volt, 3-phase electrical service with a 5 HP motor requiring a 30 AMP breaker and #8 THHN wire. The vehicle exhaust system consists of four hose drops at 600 CFM per drop, utilizing spiral seam galvanized steel ductwork fabricated and installed in accordance with Chapter 6 OBBC MC and SMACNA standards. The specification includes a control panel (Part # 500179-08), rain cap (Part # 500157-12), suction rails, transition elbows, high-temperature hose, nozzles, tailpipe connectors, and a fresh air intake system. The document is dated August 2023 and includes general construction notes requiring contractors to verify all dimensions through field measurement, comply with 2017 ICC Building Code standards, coordinate with manufacturers' recommendations, and obtain prior approval from the City Fire Department for any roof penetrations or cutting operations.

The drawing specifies that all materials and methods shall conform to applicable federal, state, and local codes with strict adherence to building standards and manufacturer specifications. The contractor is required to balance the exhaust system to meet specified air quantities and coordinate exact equipment locations with existing fire department infrastructure, lighting, and conditions. The specification notes that wireless control panel activation and automatic fan control components may be required for complete installation. As indicated in the remarks section, this design represents the sole property of the designer, Magnegrip, and any approved substitutions are at the risk of the owner. The document was professionally sealed by Robin Winton, a Florida-licensed Professional Engineer (License No. 56206), with an owner change dated May 14, 2024, reflecting design modifications during the project development phase.

View the file

Other files for this state and local contract opportunity

Other files attached to GLENDALE FIRE STATION, newest first.
File Type Posted
MP04-M4-0.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q&A_II_Published.pdf PDF
ITB_24-29_Q&A_II_Published.pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CEILING

STRUCTURE

VIBRATION

ISOLATORS

FAN MOUNTING

SYSTEM

CF FAN

RAIN CAP

EXHAUST

STACK

BRACING

WALL

FAN ELEVATION

STRAIGHT SUCTION RAIL

FRONT ELEVATION

MOUNTING LEG

ASSEMBLY

RAIL

STRAIGHT SUCTION RAIL

SIDE ELEVATION

INLET PLENUMCEILING LINE

RAIL LIPS

LIFTING BALANCER

ELBOW

CRAB ASSEMBLY

SYSTEM

CONTROL

PANEL

12"Ø 10"Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

"Ø

SS

R

M

PR

O -7

SS

R

M

PR

O -7

SS

R

M

PR

O -7

TO MAIN

SERVICE

PANEL

GENERAL CONSTRUCTION NOTES:

1. FOR THE PURPOSE OF CLEARNESS AND LEGIBILITY DRAWINGS ARE DIAGRAMMATIC AND DESIGN

INTENT ONLY.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE BEGINNING ANY

FABRICATION OR CONSTRUCTION.

2. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES

IN ACCORDANCE WITH 2017 ICC (IBC, IMC).

3. ALL NEW MATERIAL METHODS, AND EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH

THE BUILDING STANDARDS AS APPROVED.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT N STRICT ACCORDANCE WITH MANUFACTURES'

RECOMMENDATIONS.

5. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF EXHAUST FANS, DUCTWORK, AND EXHAUST DROPS WITH EXISTING IN-PLACE CITY FIRE DEPARTMENTS EQUIPMENT, LIGHTING, AND ALL EXISTING

CONDITIONS.

6. ALL EXHAUST DUCTWORK SHALL BE SPIRAL SEAM GALVANIZED STEEL FABRICATED AND INSTALLED

IN ACCORDANCE WITH CHAPTER 6 OBBC MC AND SMACNA STANDARD MANUAL.

7. SHEETMETAL DUCT DIMENSIONS SHOWN ARE AIRWAY DIMENSIONS.

8. BALANCE EXHAUST SYSTEM AND EACH EXHAUST DROP MEET AIR QUANTITIES AS REQUIRED.

9. CONTRACTOR SHALL COORDINATE WITH CITY FIRE DEPARTMENT PRIOR TO ANY PENETRATION OR

ROOF CUTTING.

FAN SCHEDULE

FAN TYPE ID#

AIRFLOW

(CFM) RPM

STATIC

PRESSURE

(IN - WC)

VOLTS /

PHASE HP BREAKER WIRE

MAGNEGRIP CF363-5 3300 3450 6 SP

208-230v 3ph 4w 5 30 AMP #8THHN

VEHICLE EXHAUST SYSTEM

DESCRIPTION PART # QTY REMARKS

CONTROL PANEL 500179-08 1

RAIN CAP 500157-12 1

SUCTION RAIL SSRMPRO-721 2 1 HOSE DROP EACH

SUCTION RAIL SSRMPRO-722 1 2 HOSE DROPS EACH

TOTAL # OF HOSE DROPS: 4 CFM PER HOSE DROP: 600 CFM

REMARKS:

A. ITEM HAS BEEN SPECIFIED FOR QUALITY AND PERFORMANCE ANY APPROVED SUBSTITUTION

IS AT THE RISK OF THE OWNER.

B. PROVIDE TRACK OR RAIL SYSTEM, TRANSITION ELBOW, HIGH TEMPERATURE HOSE, HOSE

CLAMPS, NOZZLES, TAILPIPE CONNECTORS, FRESH AIR INTAKE, AND OTHER ITEMS REQUIRED

FOR A COMPLETE INSTALLATION.

C. PROVIDE WIRELESS CONTROL PANEL ACTIVATION, PRESSURE SENSORS,WIRELESS

TRANSMITTERS, AND ADDITIONAL COMPONENTS IF REQUIRED FOR AUTOMATIC FAN CONTROL.

D. VEHICLE EXHAUST SYSTEM DESIGN AND DRAWING IS THE SOLE PROPERTY OF THE

DESIGNERS, MAGNEGRIP.

E. DETAILS MAY NOT REPRESENT THE SAME KIND OF VEHICLE IN PLAN VIEW.

F. DETAILS ARE MEANT TO ILLUSTRATE “TYPICAL” ELEVATION VIEWS.

5/

/2

8:

:2

AM

D:

\W

IN

TO

N

EN

GI

NE

ER

IN

G\

JO

BS

\2

3\

-5

GL

EN

DA

LE

F

IR

ST

S

TA

TI

ON

DE

W

BE

RR

Y\ M

PS

HE

ET

S.

DW

G

A

54321

B

C

D

E

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SCALE

SEAL

REVISIONS

NO. DESCRIPTION DATE

PRELIMINARY

877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759

ROBIN WINTON, P.E. 56206

8'0' 16'

SCALE: 1/8" = 1' - 0"

4'

M4.0

VEHICLE EXHAUST

PLAN

RPW

RPW

AUGUST 2023

50150622

GL

EN

DA

LE

F

IR

E

ST

AT

IO

N

BO

AR

D

OF

C

OU

NT

Y

CO

M M

IS

SI

ON

ER

S W

AL

TO

N

CO

UN

TY

FL

OR

ID

A

RPW

ROBIN WINTON, STATE OF FLORIDA, PROFESSIONAL ENGINEER. LICENSE NO. 56206. THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBIN WINTON ON THE DATE INDICATED HERE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

1 OWNER CHANGES 5/14/24

AutoCAD SHX Text

VEHICLE EXHAUST PLAN

AutoCAD SHX Text

SCALE: 3/16" = 1'0"

Sheets and Views
MP04-M4-0