ITB_24-29_Q&A_II_Published.pdf

PDF 199 KB Posted

Attached to
GLENDALE FIRE STATION State and local contract opportunity
Solicitation number
ITB 24-29
Issued by
Walton County, Florida

About this file

This document is a Questions and Answers (Q&A) addendum for Invitation to Bid (ITB) 24-29 issued by the Walton County Board of County Commissioners' Office of Central Purchasing in DeFuniak Springs, Florida, related to the Glendale Fire Station project. The Q&A addresses technical details and clarifications for potential bidders, including specifics about the fire station's design and equipment requirements. Key topics covered include confirmation of the station's floor plan layout, bay configurations for ambulances, shower installation types, fire alarm system manufacturers, overhead door specifications, and detector requirements for various station areas.

The document provides critical bidding guidance, such as acceptable fire alarm system manufacturers (EST, Silent Knight, Firelite, and Kidde), approval of Raynor overhead doors, and confirmation that combo smoke and carbon monoxide detectors should be included in bunk rooms, corridors, dining room, and day areas. Additional technical details include the requirement for sounder bases in detectors and a pending decision from the County Building Department regarding strobes in sleeping quarters. The Q&A explicitly states that these questions and answers now become part of the original ITB, making the information binding for potential contractors submitting bids for the Glendale Fire Station project.

View the file

Other files for this state and local contract opportunity

Other files attached to GLENDALE FIRE STATION, newest first.
File Type Posted
MP04-M4-0.pdf PDF
MP04-M4-0.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q&A_II_Published.pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Walton County Board of County Commissioners

Office of Central Purchasing

176 Montgomery Circle

DeFuniak Springs, FL 32435

(850) 892-8176

QUESTIONS AND ANSWERS II

ITB 24-29 GLENDALE FIRE STATION

We are providing the exhaust extraction system for the new Choctaw Beach Fire Station, and this appears to be the same floorplan…just confirming?

Response: Correct.

We have the (2) drop bay for the ambulances as the first bay closest to the living quarters for

Choctaw Beach, is it the same for Glendale? I just want our drawings to be correct for each station.

Response: Proposed bay layout is same as Choctaw Beach fire station.

Are the showers supposed to be inserts or Epoxy Floors and Walls?

Response: Inserts/prefab.

Please provide signage spec section.

Response: Spec section for signage will be added soon, obtaining from Owner.

After reviewing the specs and drawings I don't see where it calls out the manufacturer of the Fire

Alarm System that is required. Do you know the name of the Fire Alarm System that is allowed?

Are the following acceptable manufacturers to bid with .... EST, Silent Knight, Firelite, and or

Kidde.

Response: The above manufacturers mentioned are acceptable. Fire Alarm System must meet minimum Florida building code requirements.

We would like to request that Raynor overhead doors be considered for a product substation.

Per the ITB, we are only submitting questions and requests here. Where and how do we upload product data to be considered?

Response: Raynor is acceptable.

Should the Bunk Rooms, Corridor’s and Dining Room & Day Area include Combo Smoke and

Carbon Monoxide Detectors?

Response: Yes, include combo Smoke and Carbon Monoxide detectors in lump sum bid price.

Walton County Board of County Commissioners

Office of Central Purchasing

176 Montgomery Circle

DeFuniak Springs, FL 32435

(850) 892-8176

Have strobes been approved for the sleeping quarters?

Response: TBD by County Building Dept. Please account for strobe device in lump sum bid.

Should these Detectors in Bunk Rooms include Sounder Bases?

Response: Yes.

This Question and Answer now becomes a part of the original ITB.