This document is a detailed engineering plan for the Vehicle Exhaust System at the Glendale Fire Station, prepared by Winton Engineering, P.A. for the Walton County Board of County Commissioners in Florida. The plan includes a comprehensive vehicle exhaust system design with specific technical specifications for a fire station, featuring a CF363-5 fan with 3,300 CFM airflow, operating at 3,450 RPM, and powered by a 208-230v 3-phase 5 HP electrical system. The design incorporates multiple suction rails, hose drops, a control panel, rain cap, and other specialized components for a complete vehicle exhaust management system.

The technical drawing provides precise installation guidelines, emphasizing compliance with 2017 ICC building codes and requiring contractors to verify all dimensions through field measurements. The system is designed with four total hose drops, each capable of handling 600 CFM, and includes provisions for wireless control panel activation, pressure sensors, and additional automatic fan control components. The plan is specifically tailored for the Glendale Fire Station project, with all design details proprietary to Magnegrip, and includes specific requirements for coordination with the local fire department, ensuring a customized and code-compliant exhaust ventilation solution.

View the file

Other files for this state and local contract opportunity

Other files attached to GLENDALE FIRE STATION, newest first.
File Type Posted
MP04-M4-0.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_ADDENDUM_III_Published.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Pre-Bid_Attendance_Sheet.pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Submittal_Checklist_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E1.2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_Revised_Sheet_E0-2_(ref_Addendum_II).pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_II_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_ADDENDUM_I_Published.pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Sample_Submittal_for_Fire_Protection_(ref_Q&A_III).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheets_A1.1-A1.8_C7.1-C7.2_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Revised_Sheet_M2.0_(ref_Addendum_I).pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
ITB_24-29_Q&A_III_Published.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Revised_Submittal_Checklist_ITB_24-29_Glendale_Fire_Station.pdf PDF
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Building_Signage_Proposal.pdf PDF
Signage_Spec_WCFR_Glendale_Bldg_-_R3.jpg JPG image
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
Glendale_Fire_Station_Road_Signage_Proposal.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q_and_A_Published.pdf PDF
ITB_24-29_Q&A_II_Published.pdf PDF
ITB_24-29_Q&A_II_Published.pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
Attorney_Approval_of_ITB_24-29_(with_Marked_Changes).pdf PDF
ITB_24-29_Legal_Ad_v.pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
50150622-Glendale_FD_3-20-24_FOR_BID.pdf PDF
50150622_Glendale_Fire_Station_Specs_2024.pdf PDF
ITB_24-29_Glendale_Fire_Station.pdf PDF
Show all 45

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CEILING

STRUCTURE

VIBRATION

ISOLATORS

FAN MOUNTING

SYSTEM

CF FAN

RAIN CAP

EXHAUST

STACK

BRACING

WALL

FAN ELEVATION

STRAIGHT SUCTION RAIL

FRONT ELEVATION

MOUNTING LEG

ASSEMBLY

RAIL

STRAIGHT SUCTION RAIL

SIDE ELEVATION

INLET PLENUMCEILING LINE

RAIL LIPS

LIFTING BALANCER

ELBOW

CRAB ASSEMBLY

SYSTEM

CONTROL

PANEL

12"Ø 10"Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

8" Ø

"Ø

SS

R

M

PR

O -7

SS

R

M

PR

O -7

SS

R

M

PR

O -7

TO MAIN

SERVICE

PANEL

GENERAL CONSTRUCTION NOTES:

1. FOR THE PURPOSE OF CLEARNESS AND LEGIBILITY DRAWINGS ARE DIAGRAMMATIC AND DESIGN

INTENT ONLY.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE BEGINNING ANY

FABRICATION OR CONSTRUCTION.

2. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES

IN ACCORDANCE WITH 2017 ICC (IBC, IMC).

3. ALL NEW MATERIAL METHODS, AND EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH

THE BUILDING STANDARDS AS APPROVED.

4. CONTRACTOR SHALL INSTALL ALL EQUIPMENT N STRICT ACCORDANCE WITH MANUFACTURES'

RECOMMENDATIONS.

5. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF EXHAUST FANS, DUCTWORK, AND EXHAUST DROPS WITH EXISTING IN-PLACE CITY FIRE DEPARTMENTS EQUIPMENT, LIGHTING, AND ALL EXISTING

CONDITIONS.

6. ALL EXHAUST DUCTWORK SHALL BE SPIRAL SEAM GALVANIZED STEEL FABRICATED AND INSTALLED

IN ACCORDANCE WITH CHAPTER 6 OBBC MC AND SMACNA STANDARD MANUAL.

7. SHEETMETAL DUCT DIMENSIONS SHOWN ARE AIRWAY DIMENSIONS.

8. BALANCE EXHAUST SYSTEM AND EACH EXHAUST DROP MEET AIR QUANTITIES AS REQUIRED.

9. CONTRACTOR SHALL COORDINATE WITH CITY FIRE DEPARTMENT PRIOR TO ANY PENETRATION OR

ROOF CUTTING.

FAN SCHEDULE

FAN TYPE ID#

AIRFLOW

(CFM) RPM

STATIC

PRESSURE

(IN - WC)

VOLTS /

PHASE HP BREAKER WIRE

MAGNEGRIP CF363-5 3300 3450 6 SP

208-230v 3ph 4w 5 30 AMP #8THHN

VEHICLE EXHAUST SYSTEM

DESCRIPTION PART # QTY REMARKS

CONTROL PANEL 500179-08 1

RAIN CAP 500157-12 1

SUCTION RAIL SSRMPRO-721 2 1 HOSE DROP EACH

SUCTION RAIL SSRMPRO-722 1 2 HOSE DROPS EACH

TOTAL # OF HOSE DROPS: 4 CFM PER HOSE DROP: 600 CFM

REMARKS:

A. ITEM HAS BEEN SPECIFIED FOR QUALITY AND PERFORMANCE ANY APPROVED SUBSTITUTION

IS AT THE RISK OF THE OWNER.

B. PROVIDE TRACK OR RAIL SYSTEM, TRANSITION ELBOW, HIGH TEMPERATURE HOSE, HOSE

CLAMPS, NOZZLES, TAILPIPE CONNECTORS, FRESH AIR INTAKE, AND OTHER ITEMS REQUIRED

FOR A COMPLETE INSTALLATION.

C. PROVIDE WIRELESS CONTROL PANEL ACTIVATION, PRESSURE SENSORS,WIRELESS

TRANSMITTERS, AND ADDITIONAL COMPONENTS IF REQUIRED FOR AUTOMATIC FAN CONTROL.

D. VEHICLE EXHAUST SYSTEM DESIGN AND DRAWING IS THE SOLE PROPERTY OF THE

DESIGNERS, MAGNEGRIP.

E. DETAILS MAY NOT REPRESENT THE SAME KIND OF VEHICLE IN PLAN VIEW.

F. DETAILS ARE MEANT TO ILLUSTRATE “TYPICAL” ELEVATION VIEWS.

5/

/2

8:

:2

AM

D:

\W

IN

TO

N

EN

GI

NE

ER

IN

G\

JO

BS

\2

3\

-5

GL

EN

DA

LE

F

IR

ST

S

TA

TI

ON

DE

W

BE

RR

Y\ M

PS

HE

ET

S.

DW

G

A

54321

B

C

D

E

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SCALE

SEAL

REVISIONS

NO. DESCRIPTION DATE

PRELIMINARY

877 CR 393 North Santa Rosa Beach, FL 32459 850.267.0759

ROBIN WINTON, P.E. 56206

8'0' 16'

SCALE: 1/8" = 1' - 0"

4'

M4.0

VEHICLE EXHAUST

PLAN

RPW

RPW

AUGUST 2023

50150622

GL

EN

DA

LE

F

IR

E

ST

AT

IO

N

BO

AR

D

OF

C

OU

NT

Y

CO

M M

IS

SI

ON

ER

S W

AL

TO

N

CO

UN

TY

FL

OR

ID

A

RPW

ROBIN WINTON, STATE OF FLORIDA, PROFESSIONAL ENGINEER. LICENSE NO. 56206. THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY ROBIN WINTON ON THE DATE INDICATED HERE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

1 OWNER CHANGES 5/14/24

AutoCAD SHX Text

VEHICLE EXHAUST PLAN

AutoCAD SHX Text

SCALE: 3/16" = 1'0"

Sheets and Views
MP04-M4-0