J01f PIMC Asbestos Survey - Bldg 233 Hospital (Feb 2003).pdf

PDF 19 MB Posted

Attached to
PIMC ED & CSR (Phoenix, AZ) Federal contract opportunity
Solicitation number
75H701-24-R-00035
Issued by
Department of Health and Human Services Indian Health Service

About this file

This document is an Asbestos Survey for Building 233 of the Phoenix Indian Medical Center (PIMC) Hospital, dated February 2003. It is related to the upcoming federal contract solicitation 75H701-24-R-00035 for the PIMC Emergency Department (ED) and Central Supply Room (CSR) Construction project in Phoenix, Arizona.

The solicitation is for a Firm Fixed Price construction contract to upgrade the ventilation in the ED and Fast Track waiting areas, and to renovate the flooring, walls, and ventilation in the CSR. The work is in support of the Indian Health Service (IHS). The project is set aside for small businesses under NAICS code 236220 with a $45 million size standard. A site visit is scheduled for June 10, 2024, and the Period of Performance is 180 calendar days from the notice to proceed. The contract magnitude is anticipated to be between $1 million and $5 million. Proposal submission details and deadlines will be provided in the solicitation documents.

View the file

Other files for this federal contract opportunity

Other files attached to PIMC ED & CSR (Phoenix, AZ), newest first.
File Type Posted
B05 Amendment A00010 (75H701-24-R-00035).pdf PDF
J02 WD AZ20240039 Mod 5 2024.08.16.pdf PDF
B05 Amendment A00009 (75H701-24-R-00035).pdf PDF
J01j TAB Report PIMC Campus Projects.pdf PDF
J01h After Hours Work Locations.pdf PDF
J01i Mechanical Zoning.pdf PDF
B05 Amendment A00008 (75H701-24-R-00035).pdf PDF
B05 Amendment A00007 (75H701-24-R-00035).pdf PDF
J02 WD AZ20240039 Mod 4 2024.07.19.pdf PDF
B05 Amendment A00006 (75H701-24-R-00035).pdf PDF
J01a Specifications PIMC ED-CSR 2024.01.29 (Conformed w-Addendum 02).pdf PDF
B05 Amendment A00005 (75H701-24-R-00035).pdf PDF
A05 Amendment A00004 (75H701-24-R-00035).pdf PDF
A05 Amendment A00003 (75H701-24-R-00035).pdf PDF
A05 Amendment A00002 (75H701-24-R-00035).pdf PDF
A05 Amendment A00001 (75H701-24-R-00035).pdf PDF
J01c Location Map.pdf PDF
J01d Infection Control Risk Assessment Permit.pdf PDF
J05 Company Specialized Experience Form Construction.pdf PDF
B01 RFP 75H70124R00035 PIMC ED CSR.pdf PDF
J06 PPQ.pdf PDF
J01a Specifications - PIMC ED-CSR 2024.01.29.pdf PDF
J01b Drawings - PIMC ED-CSR 2023.08.08.pdf PDF
J03 Self Performed Calculation Sheet.pdf PDF
J04a FORMS_TPT_5000HC_11228.pdf PDF
J04 2024 Exemption Letter for a Qualifying Hospital.pdf PDF
J01e Above Ceiling Work Permit.pdf PDF
J01g GFE PIMC ED-CSR.pdf PDF
J02 WD AZ20240039 Mod 2 2024.05.17.pdf PDF
J07 OF 306 Declaration for Federal Employment.pdf PDF
J08 Addendum to OF-306 (Childcare Form).pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS SURVEY

At

PHOENIX INDIAN MEDICAL CENTER

Building #233 – Hospital

For

Phoenix Area Indian Health Service Two Renaissance Square

40 N. Central Avenue Phoenix, AZ 85004

By

U.S. Public Health Service Federal Occupational Health

2201 Sixth Avenue, M/S Rx-21 Seattle, Washington 98121-2500

(206) 615-2441

February 2003

1f

TABLE OF CONTENTS

Section Title Page No.

1.0 Introduction

2.0 Description of Inspected Area

3.0 Survey Procedures

4.0 Findings

5.0 Abatement Cost Estimate

6.0 Liability Limitations

Appendices

1 Bulk Sample Log and Location of Functional Spaces

2 Laboratory Results

3 Certifications

Area Wide Asbestos Building Inspection Indian Health Service Facilities

Phoenix Indian Medical Center Campus Building #233 – Hospital

Phoenix, Arizona

1.0 INTRODUCTION

As requested by the Phoenix Area Indian Health Services, bulk sampling of suspect asbestos-containing building materials was conducted in Building #233, Hospital, located at the Phoenix Indian Medical Center (PIMC) at 4212 North 16th Street in Phoenix, Arizona, between November 13 and November 21, 2002.

Bulk samples of suspect asbestos-containing materials (ACMs) were collected throughout the interior and exterior of the building.

Messrs. Mark Updike and James Marshall, representing Federal Occupational Health (FOH), performed the asbestos inspection of the subject property. Messrs. Updike and Marshall both hold current Asbestos Hazard Emergency Response Act (AHERA) accreditation as Asbestos Building Inspectors. Sampling of suspect asbestos-containing materials was conducted using procedures similar to the Environmental Protection Agency (EPA) AHERA regulations, 40 CFR 763. The Federal Occupational Health EH Environmental Laboratory in Denver, Colorado, performed the laboratory analysis of the asbestos samples.

Laboratory analysis indicates that floor tiles, floor tile mastics, HVAC duct tape, pipe elbow insulation, and roof mounted HVAC insulation materials in Building #233, Hospital, contain asbestos.

2.0 DESCRIPTION OF INSPECTED AREA

This inspection focused on the entire interior and exterior of the building. The building is a five-story building, which also includes a ground level built below the grade. The building has a concrete exterior with a built up roofing system.

Suspect building materials identified and sampled in the subject property included the following: various floor tiles and mastics, various sheet vinyl and mastics, ceramic floor tile grout, carpet mastic, stairwell tread mastic, various gypsum drywall materials, plaster materials, ceramic wall tile grout, stucco, various acoustical ceiling tiles, HVAC duct tape, duct sealant, pipe elbow insulation, various covebase mastics, HVAC insulation, and various roofing materials.

3.0 SURVEY PROCEDURES

Each room was assigned unique functional space numbers. Each functional space was visually inspected for suspect asbestos-containing materials. Materials were mapped and quantified on maps provided by the IHS or on hand made maps of the existing floor plan.

Each suspect ACM was designated as a distinct homogeneous area, which is a single material, uniform in texture and appearance, installed at one time, and unlikely to consist of more than one type or formulation of material. The inspectors touched each suspect material in order to determine friability.

A sufficient number of samples were collected of each material to satisfy the Occupational Safety and Health Administration (OSHA) and the National Emission Standard for Hazardous Air Pollutants (NESHAP) regulations for the determination of asbestos content. A total of 144 samples were collected from Building #233

Each sample was assigned a unique sample identification number and assessed for damage and friability classifications. The samples, with Chain of Custody documentation were delivered to FOH EH Environmental Laboratory for analysis. The FOH EH Environmental Laboratory is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP) for bulk-asbestos sample analysis conducted by the National Institute of Standards and Technology.

A description of the samples taken, location, and summary of laboratory results are located in Appendix

1. The asbestos laboratory reports are included as Appendix 2.

4.0 FINDINGS

Results of the asbestos inspection are as follows:

Phoenix Indian Medical Center Building #233-Hospital

Ground Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

G5, G8, G10, G23, G24, G25, G26, G41, G42, G49, G50, G51, 000, 002, 008, 008A, 010, 019, 019A, 019B, 021, 023, 024, 027, 029, 030, 032, 033, 038, 039, 059, 061, 062, 066, 067, 071, 076, 076A

Yes: 8-10% Chrysotile

Good 12,400 sf

1B Dark Ceramic Floor Tile

Grout

000, 009, 016, 017, 020, 022, 025, 031, 033, 034,035. 035A, 036, 037, 040, 041, 043, 044, 045, 046, 047, 052, 053, 054, 055, 057, 064, 066, 068, 069, 078

No Good 6,489 sf

1D White 12”x12” Floor Tile w/

Tan Specs and Mastic

G40, 068 No Good 110 sf

1E Lt. Blue 12”x12”

Marble floor Tile and Mastic

G38, G39 No Good 176 sf

1F 12”x12” Beige Floor Tile w/

White Streaks and Mastic

G1, G2, G3, G4, G6, G7, G32, G48, G49, G53, G54, 024, 028 075

Yes: 8-10% Chrysotile

Good 3,380 sf

1G 12”x12” White Floor Tile w/ Dark Streaks and Mastic

G9, G37 Yes: 6-8% Chrysotile

Good 920 sf

1H Carpet Mastic G5, G11-G19 No Good 8,470 sf 1V Stair Tread

Mastic G22, G99 No Good 300 sf

2A Plaster Wall & Ceilings

Throughout No Good 64,615 sf

2B Gypsum Drywall

G25, G29, G45, G46, 029, 075, 076

No Good 3,464 sf

2C Drywall Joint Compound

G25, G29, G45, G46, 029, 075, 076

No Good 3,464 sf

2D Ceramic Wall Tile Grout

000, 009, 016, 017, 020, 022, 026, 031, 034, 035, 035A, 036, 037, 040, 041, 044, 045, 046, 047, 052, 053, 054, 055, 057, 059, 061, 062, 064, 065, 066, 068, 069, 071, 078

No Good 13,835 sf

2E (New Area) Gypsum Drywall

G11-G19, G22 No Good 9,960 sf

2F (New Area) Drywall Joint

Compound

G11-G19, G22 No Good 9,960 sf

3A 2’x4’ Spaced Fissured

Ceiling Tiles

G1, G2, G3, G4, G6, G7, G23, G24, G25, G26, G31, G32, G33, G35, G38, G39, G40, G41, G48, G49, G53, G54, 000, 002, 008, 019, 024, 027, 028, 029, 032, 033, 038, 039, 041, 075, 076, 076A

No Good 9,992 sf

3B 2’x4’ & 2’x2’ Tight Fissured Ceiling Tiles

G2, G3, G4, G5, G6, G7, G8, G11-G19, G26, G41,G49, G53, G54, 002, 008, 024, 029, 043, No Good 11,949 sf

3C 2’x4’ Flat Ceiling Tiles

G9, 034, 035 No Good 3,845 sf

3D 2’x4’ Pinhole Ceiling Tiles

G42 No Good 1,300 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30% Chrysotile

Good 1,175 sf

4B HVAC Duct Sealant

G46 No Good 6 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 270 Elbows

7A Brown Covebase

Mastic

G1, G2, G3, G4, G6, G7, G9, G10, G24, G25, G27, G31, G32, G33, G35, G36, G37, G38, G39, G40, G41, G42, G48, G50, G51, 008, 008A, 010, 019, 019A, 019B, 021, 023, 024, 027, 028, 029, 030, 032, 033, 048, 067, 075, 076

No Good 884 sf

7B White Covebase

Mastic

G11 – G19 No Good 277 sf

7C Yellow Covebase

Mastic

G5 No Good 4 sf

Phoenix Indian Medical Center Building #233-Hospital

First (1st) Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

101, 102, 106-112, 119, 121, 122,169-176, 178- 188, 198, 199, F2, F12-, F16-19, F21, F23-25, F27-30, F33-42, F46, F47, F49, F63, F65, F98, M23, M24, M48, M53- 56, M62, M63, M65-70, M78, M82-M87, M92, M106, M107, 1119, 1131, 1142, 1143, 1150, 1154, 1158, 1165A, 1172, 1173, 1199, 1201-1205, 1205A, Yes: 8-10% Chrysotile

Good 41,080 sf

1B Dark Ceramic Floor Tile

Grout

140-142, 160, 169, 196, M4, M5, M20, M21, M60, M61, M64, M89-M91, M139-M141, 1124, 1125, 1161, 1167, 1175, 1179, 1185, 1206-1210, 1215, 1216, 1238

No Good 1,205 sf

1D White 12”x12” Floor Tile w/

Tan Specs and Mastic

F51-F57 No Good 1,617 sf

1F 12”x12” Beige Floor Tile w/

White Streaks and Mastic

M-49 Yes: 8-10% Chrysotile

Good 540 sf

1H Carpet Mastic F20, F21, 1170A, 1185, No Good 2,316 sf

1I White 12”x 12” Floor Tile w/ Blue Specs and Mastic

F1, F4, F5, F6, F9, F10, F58, F59, F73, 1112 –

1115, Yes: 8-10% Chrysotile

Black Mastic

Good 4,728 sf

1J Orange/ Multicolor

12”x 12”Floor Tile and Mastic

101, F27, F28, F30, F47, F65, F98, F99, Yes: 8-10% Chrysotile

Good 1,185 sf

1K White 12”x12” Marble Floor Tile w/ Dark Streaks and

Mastic

F15, F44, 123, 124, 1155, 1170, 1200, Yes: 8-10% Chrysotile

Black Mastic

Good 842 sf

1L 12”x 12” Gray Marble Floor

Tile w/ Streaks and

Mastic

F32, 1131 Yes: 8-10% Chrysotile

Good 252 sf

1M Lt. Blue 12”x 12” Floor Tile w/ Streaks and

Mastic

F7, F11, F65, F60, F72, 1101, 1104, 1213, 1219

Yes: 8-10% Chrysotile

Black Mastic

Good 1,122 sf

1N Tan 12”x 12” Marble Floor

Tile and Mastic

F37, F43, M-95, M-97, M-102, M-102A, 1131, 1160, 1170A, 1183, 1185A, 1187, Yes: 8-10% Chrysotile

Black Mastic

Good 1,268 sf

1P Pink-Orange 12”x 12” Floor

Tile and Mastic

F48, F48A Yes: 8-10% Chrysotile

Black Mastic

Good 450 sf

1Q Red 12”x 12” Floor Tile and

Mastic

F47, F56 No Good 81 sf

1V Stair Tread Mastic

F3, F26, F50 No Good 540 sf

2A Plaster Walls & Ceilings

Throughout No Good 103,455 sf

2B Gypsum Drywall

F6, F7, F8, F12, F15, F44, F58, F59, F60, F64, F70, F71, F72, F73, M-24, M- 92, M102-B, 119, 121, 122, 123, 124, 171, 178, 1155, 1170, 1213, 1222

No Good 4,320 sf

2C Drywall Joint Compound

F6, F7, F8, F12, F15, F44, F58, F59, F60, F64, F70, F71, F72, F73, M-24, M- 92, M102-B, 119, 121, 122, 123, 124, 171, 178, 1155, 1170, 1213, 1222

No Good 4,320 sf

2D Ceramic Wall Tile Grout

140-142, 159, 160, 196, F45-F48, F48A, F70, M4, M5, M20, M21, M59, M60, M64, M89-91, M106, M139-M141,1124, 1125, 1136, 1161, 1175, 1179, 1186, 1190-1193, 1197, 1198, 1204, 1205, 1205A, 1206, 1207, 1209, 1210, 1215, 1216

No Good 9,280 sf

3A 2’x 4’ Spaced Fissured

Ceiling Tiles

169-176, 178-180, 182- 188, 196, 197, F1, F2, F19, F21, F23-F25, F27- 36, F46, F48, F63-F65, M23, M48, M49, M53- M58, M62, M63, M65, M66, M69, M70,.M78, M82, M84-M88, M92, 1119, 1142, 1143, 1150, 1154, 1172, 1173, 1202, 1204, 1205

No Good 28,700 sf

3B 2’x 4’ & 2’x 2’ Tight Fissured Ceiling Tiles

101, 119, 121-124, F2, F4- F6, F8-F11, F13, F15-18, F20, F22, F36, F37, F43, F44, F46, F48, F51-F62, F73, M24, M49, M82, M87, M88, M92, M95, M97, M102, M102A, M102B, 1101, 1104, 1112-1115, 1142, 1155, 11601163, 1165A, 1167, 1170A, 1172, 1173, 1202, 1204, 1205, 1213, 1222

No Good 14,925 sf

3E 1’x1’ Pinhole Ceiling Tiles

M-83 No Good 210 sf

3F 2’x2’ Flat Ceiling Tiles

F46, 1189-1198 No Good 3,672 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30% Chrysotile

Good 2,445 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 556

Covebase

Mastic

Throughout; EXCEPT all rooms with ceramic tile walls and rooms F1, F2, and 1222

No Good 1,265 sf

7B White Covebase

Mastic

1222 No Good 32 sf

7C Yellow Covebase

Mastic

F1, F2 No Good 76 sf

Phoenix Indian Medical Center Building #233-Hospital

Second (2nd) Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

217, 221A, 222,227, 227A 227B, 228, 2-47, 262, 263, Yes: 8-10% Chrysotile

Good 3,684 sf

1B Dark Ceramic Floor Tile

Grout

2-31, 2-32, 201A, 204A, 205A, 207A, 208A, 209A, 210A, 211A, 212A, 213A, 214A, 215A, 216A, 218A, 219A, 220A, 222A, 224, 225, 226, 229, 230, 231, 232, 249

No Good 940 sf

1D White 12”x12” Floor Tile w/

Tan Specs and Mastic

221, 222, 223, 225, 226, 227, 228, 233, 234, 236, 243, 244, 246

No Good 3,195 sf

1N Tan 12”x12” Marble Floor

Tile and Mastic

221 Yes: 8-10% Chrysotile

Black Mastic

Good 42 sf

1R 9”x 9” Gray- Green Floor Tile w/ Spots and Mastic

201, 204, 205, 207, 208, 209, 210, 211, 212, 213, 214, 215, 216, 218, 219, 220, 260

Yes: 6-8% Chrysotile

Good 2,848 sf

1V Stair Tread Mastic

297, 298, 299 No Good 392 sf

1W Dark Green 12”x12” Floor Tile & Mastic

2-48 No Good 12 sf

2A Plaster Wall & Ceilings

Throughout No Good 41,753 sf

2D Ceramic Wall Tile Grout

2-31, 2-32, 201A, 204A, 205A, 207A, 208A, 209A, 210A, 211A, 212A, 213A, 214A, 215A, 216A, 218A, 219A, 220A, 222A, 224, 225, 226, 229, 230, 231, 232, 249

No Good 5,768 sf

3B 2’x4’ & 2’x2’ Tight Fissured Ceiling Tiles

2-33, 2-34, 2-35, 2-36, 2- 37, 2-40, 2-43, 2-44, 2-45, 2-46, 2-62, 2-63, 2-65, 221, 221A, 222, 223, 227B, 228, 233, No Good 5,018 sf

3C 2’x4’ Flat Ceiling Tiles

ICU-1 – ICU-11, 229, 238,

239, 241, 242

No Good 2,288 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30% Chrysotile

Good 875 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 180 Elbows

7B White Covebase

Mastic

2-33, 2-34, 2-35, 2-36, 2- 37, 2-38, 2-39, 2-40, 2-41, 2-42, 2-43, 2-44, 2-45, 2-

46, 221, 227, 228

No Good 305 sf

7C Yellow Covebase

Mastic

204, 205, 207, 208, 209, 210, 211, 212, 213, 214, 215, 216, 218, 219, 220, 221, 221A, 222, 223, 227, 227A, 227B, 228, 233

No Good 407 sf

Phoenix Indian Medical Center Building #233-Hospital

Third (3rd) Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

321, 321A, 322, 323, 328, 329, 330, 331, 331A, 337, 338, 341A, 344, 345, 346, 349, 349A, 350, 351, 351A, 351B, 363, 393, 394, 395, 396

Yes: 8-10%

Good 4,985 sf

1B Dark Ceramic Floor Tile

Grout

301A, 304A, 305A, 306A, 307A, 308A, 308B, 309A, 309B, 310A, 311A, 312A, 313A, 314A, 315, 316A, 317A, 318A, 319A, 320, 322A, 324, 325, 326, 327, 332, 333, 334, 335, 336, 339, 340, 342, 343, 347, 348, 352, 354A, 356A, 357A, 358A, 359A, 360A, 361A, 362A

No Good 1,275 sf

1D White 12”x12” Floor Tile w/

Tan Specs and Mastic

341 No Good 210 sf

1H Carpet Mastic 356B No Good 70 sf 1R 9”x 9” Gray-

Green Floor Tile w/ Spots and Mastic

301 – 314, 316, 317, 318, 319, 353, 355, 356, 357, 358, 358A, 359, 359A, 359B, 360, 361, 362

Yes: 6-8% Chrysotile

Good 3,975 sf

1S Wood Patterned Sheet

Vinyl and Mastic

354 No Good 221 sf

1V Stair Tread Mastic

397, 398, 399 No Good 351 sf

2A Plaster Wall & Ceilings

Throughout No Good 48,425 sf

2B Gypsum Drywall

356B No Good 340 sf

2C Drywall Joint Compound

356B No Good 340 sf

2D Ceramic Wall Tile Grout

301A, 304A, 305A, 306A, 307A, 308A, 308B, 309A, 309B, 310A, 311A, 312A, 313A, 314A, 315, 316A, 317A, 318A, 319A, 320, 322A, 324, 325, 326, 327, 332, 333, 334, 335, 336, 339, 340, 342, 343, 347, 348, 352, 354A, 356A, 357A, 358A, 359A, 360A, 361A, 362A

No Good 7,940 sf

3B 2’x4’ & 2’x2’ Tight Fissured Ceiling Tiles

321, 321A, 322, 323, 328, 329, 330, 331, 331A, 337, 341, 341A, 344, 345, 346, 363, 393, 394, 395, 396

No Good 5,650 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30%

Good 813 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 178 Elbows

7A Brown Covebase

Mastic

301 – 314, 316 – 319, 321, 321A, 322, 323, 328, 329, 330, 331, 331A, 337, 341, 341A, 344, 345, 346, 349, 349A, 350, 351, 351A, 351B, 353, 355, 356, 356B, 357, 358, 358A, 359, 359A, 359B, 360, 361, 362, 363

No Good 730 sf

Phoenix Indian Medical Center Building #233-Hospital

Fourth (4th) Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

408, 418, 419, 419A, 419B, 420, 421, 421A, 422, 423, 426, 427, 429, 432, 434, 440, 441, 443, 445, 455, 453A, 458, 459, 461, 462

Yes: 8-10% Chrysotile

Good 6,655 sf

1B Dark Ceramic Floor Tile

Grout

401, 402A, 403A, 404A, 405A, 406A, 407A, 407B, 409C, 410A, 411A, 412A, 413A, 415, 416A, 417A, 422A, 424, 425, 428, 430, 431, 433, 435, 437, 438, 439A, 440, 442A, 444A, 446, 447A, 448, 448A, 448B, 450, 451, 452, 454A, 456, 458

No Good 1,720 sf

1D White 12”x12” Floor Tile w/

Tan Specs and Mastic

453 No Good 42 sf

1R 9”x 9” Gray- Green Floor Tile w/ Spots and Mastic

403, 404, 405, 406, 407, 409, 409A, 409B, 410, 411, 412, 413, 414, 416, 417, 437, 439, 447, 448

Yes: 6-8% Chrysotile

Good 3,450 sf

1T Dark Aqua 12”x 12” Floor

Tile and Mastic

438 Yes: 8-10% Chrysotile

Black Mastic

Good 255 sf

1V Stair Tread Mastic

497, 498, 499 No Good 450 sf

2A Plaster Wall & Ceilings

Throughout No Good 40,661 sf

2D Ceramic Wall Tile Grout

401, 402A, 403A, 404A, 405A, 406A, 407A, 407B, 409C, 410A, 411A, 412A, 413A, 415, 416A, 417A, 422A, 424, 425, 428, 430, 431, 433, 435, 437, 438, 439A, 440, 442A, 444A, 446, 447A, 448, 448A, 448B, 450, 451, 452, 454A, 456, 458

No Good 9,048 sf

3A 2’x4’ Spaced Fissured

Ceiling Tiles

402, 418, 419, 419A, 419B, 420, 421, 421A, 422, 427, 429, 438, 443, 445, 453, 454, 455, 458, 459, 461, 462, 480, 481, 482, 483, 484

No Good 8,050 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30% Chrysotile

Good 950 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 193 Elbows

7A Brown Covebase

Mastic

403, 404, 405, 406, 407, 408, 409, 409A, 409B, 410, 411, 412, 413, 414, 416, 417, 418, 419, 419A, 419B, 420, 421, 421A, 422, 423, 426, 427, 429, 432, 437, 438, 439, 440, 441, 443, 445, 447, 448, 453, 453A, 455, 458, 459

No Good 578 sf

7B White Covebase

Mastic

453 No Good 9 sf

Phoenix Indian Medical Center Building #233-Hospital

Fifth (5th) Floor

HA # Material Functional Space ACM Condition Quantity 1A 9”x 9” Gray

Floor Tiles w/ White Streaks and Mastic

502, 503, 510, 511, 512, 516, 534, 536, 537, 547, 548, 553, 554, 555, 556, 557, 558, 559, 560, 563, 564, 565, 566, 567, 567A, 568, 569

Yes: 8-10%

Good 7,782 sf

1B Dark Ceramic Floor Tile

Grout

501, 504, 506, 506A, 507, 507A, 509, 513, 514, 515, 519, 519A, 520, 520A, 523, 523A, 524, 524A, 528, 529, 531, 531A, 532, 532A, 535, 539, 541, 541A, 542, 542A, 545, 545A, 546, 549, 551, 552, 562, 570, 571

No Good 2,084 sf

1H Carpet Mastic 000 No Good 110 sf

1R 9”x 9” Gray- Green Floor Tile w/ Spots and Mastic

505, 508, 518, 521, 522, 525, 526, 530, 533, 540, 543, 544

Yes: 6-8% Chrysotile

Good 2,505 sf

1U Peach 12”x12” Floor Tile and

Mastic

517 Yes: 8-10% Chrysotile

Good 240 sf

1V Stair Tread Mastic

597, 598, 599 No Good 450 sf

2A Plaster Wall & Ceilings

Throughout No Good 41,793 sf

2D Ceramic Wall Tile Grout

501, 504, 506, 506A, 507, 507A, 509, 513, 514, 515, 519, 519A, 520, 520A, 523, 523A, 524, 524A, 528, 529, 531, 531A, 532, 532A, 535, 539, 541, 541A, 542, 542A, 545, 545A, 546, 549, 551, 552, 562, 570, 571

No Good 7,288 sf

3A 2’x4’ Spaced Fissured

Ceiling Tiles

501, 502, 504, 510, 511, 512, 547, 548, 554, 555, 556, 557, 558, 559, 560, 565, 566, 567, 567A, 568, No Good 5,977 sf

3B 2’x4’ & 2’x2’ Tight Fissured Ceiling Tiles

554, 555, 556 No Good 665 sf

4A HVAC Duct Tape

Throughout Plenum Yes: 25-30% Chrysotile

Good 637 sf

5A Pipe Elbow Insulation

Throughout Plenum Yes: 25-30% Chrysotile &

6-8% Amosite

Good 266

Covebase

Mastic

000, 503, 505, 508, 510, 511, 516, 517, 518, 521, 522, 525, 526, 530, 533, 534, 536, 537, 540, 543, 544, 547, 548, 556, 557, 558, 559, 560, 563, 564, 565, 566, 567, 567A, 568, No Good 600 sf

Phoenix Indian Medical Center Building #233-Hospital

Roofs

HA # Material Functional Space ACM Condition Quantity 8A Roof Core Roof No Good 168,970 sf 8B Roof Mastic Roof No Good 35 sf 8C Expansion

Joints Roof No Good 43 sf

8D Black Insulation Coat

Roof No Good 250 sf

8E HVAC Duct Tape

Roof Yes: 25-30% Chrysotile

Good 308 sf

8F HVAC

Insulation

Roof Yes: 25-30% Chrysotile

Good 1,968 sf

Laboratory analysis of the bulk samples collected from the Phoenix Indian Medical Center Building #233, Hospital, indicates that floor tiles, floor tile mastics, HVAC duct tape, pipe elbow insulation, and roof mounted HVAC materials contain asbestos.

Floor tile and mastics are a non-friable NESHAP Category I material. Removal or disturbance to this material should be performed by appropriately trained and certified personnel. Removed flooring material may be disposed at a landfill that accepts non-friable asbestos waste. Landfills should be checked for acceptance of this material prior to the disposal of waste materials.

The HVAC duct tape, HVAC insulation and pipe elbow insulation are friable, regulated asbestos-containing materials (RACM). If disturbance to these materials is required, it must be treated as a friable NESHAP RACM. OSHA Class I removal regulations apply, unless the material can be removed intact.

Removal of these materials should be performed by appropriately trained and certified personnel. Friable materials must be disposed of at a regulated landfill, approved by the EPA for disposal of friable asbestos waste.

5.0 ABATEMENT COST ESTIMATE

Following is the programming cost estimate for the removal of asbestos-containing materials.

Identified asbestos-containing materials (ACMs) consist of floor tiles & mastics (107,588 sf), pipe elbow insulation (1,684 elbows), duct tape and insulation (7,203 sf).

This programming cost estimate was derived by use of the Means Cost Guide and by consultation with experienced local contractors. It reflects current industry pricing. Future fluctuations in industry pricing, both natural and seasonal, may affect this estimate.

This estimate is for abatement contractor costs only. Additional costs which are not included in this estimate are those of an environmental consultant and replacement of materials that have been removed.

Phoenix Indian Medical Center Building #233-Hospital

Asbestos-Containing Material

Quantity of Material

(sf)

Unit Cost (per sf) Total

Floor Tiles & Mastic 107,588 sf $2.00 $215,176.00 Pipe Elbow Insulation 1,684 elbows $25.00 $42,100.00

Duct Tape and Insulation

7,203 sf $40.00 $288,120.00

Total $545,396.00

6.0 LIABILITY LIMITATIONS

This asbestos inspection was performed using procedures and a level of diligence typically exercised by professional consultants performing similar services.

Asbestos-containing material (ACM) can be present in a structure, but not identified using normal, non-destructive, investigative procedures.

No survey can completely eliminate uncertainty regarding the presence of ACM. FOH’s level of diligence and investigative procedures are intended to reduce, but not eliminate, potential uncertainty regarding the presence of ACM. The procedures used for this survey attempt to establish a balance between the competing goals of limiting investigative costs, time, and building damage, and reducing the uncertainty about unknown conditions.

Therefore, the determinations in this report should not be construed as a guarantee that all ACM present in the subject property has been included in this report. This report presents FOH’s professional determinations, which are dependent upon information obtained during the performance of the consulting services. FOH assumes no responsibility for omissions or errors resulting from inaccurate information provided by sources outside of FOH.

No warranty or guarantee, expressed or implied, is made regarding the findings, conclusions, or recommendations contained in this report. The limitations presented above supersede the requirements on provisions of all other contracts on scope of work, implied or otherwise, except those stated or acknowledged herein.

Refer to the report for laboratory results of the inspection. The Table in Appendix 1 lists the bulk samples that were collected from homogeneous areas of suspect ACM. The laboratory results are included in Appendix 2.

APPENDIX 1

Bulk Sample Log

Location of Functional Spaces

Project: Indian Health Service Phoenix Service Unit

Building #233 – Hospital 1st Floor Functional Space Locations

Asbestos-Containing Materials Inspection

Figure No.

Project No.

02P-3514

Pr oj ec t:

I nd ia n

H ea lth S er vi ce Ph oe ni x Se rv ic e U ni t

B ui ld in g #2

H os pi ta l 2 nd

Fl oo r Fu nc tio na l S pa ce

L oc at io ns As be st os -C on ta in in g M at er ia ls

In sp ec tio n

Fi gu re N o.

oj ec t N

P-ia n

H ea lth S er vi ce Ph oe ni x Se rv ic e U ni t

B ui ld in g #2

H os pi ta l 3 rd

Fl oo r Fu nc tio na l S pa ce

L oc at io ns As be st os -C on ta in in g M at er ia ls

In sp ec tio n

Fi gu re oj ec ia n

H ea lth S er vi ce Ph oe ni x Se rv ic e U ni t

B ui ld in g #2

H os pi ta l 4 th

Fl oo r Fu nc tio na l S pa ce

L oc at io ns As be st os -C on ta in in g M at er ia ls

In sp ec tio n

Fi gu re oj ec t N o.

P-ia n

H ea lth S er vi ce Ph oe ni x Se rv ic e U ni t

B ui ld in g #2

H os pi ta l 5 th

Fl oo r Fu nc tio na l S pa ce

L oc at io ns As be st os -C on ta in in g M at er ia ls

In sp ec tio n

Fi gu re oj ec

APPENDIX 2