B05 Amendment A00009 (75H701-24-R-00035).pdf

PDF 4 MB Posted

Attached to
PIMC ED & CSR (Phoenix, AZ) Federal contract opportunity
Solicitation number
75H701-24-R-00035
Issued by
Department of Health and Human Services Indian Health Service

About this file

This document is Amendment A00009 to Solicitation 75H701-24-R-00035 for the PIMC ED & CSR construction project in Phoenix, AZ. The amendment provides responses to Pre-Proposal Inquiries 5-10, revises clause H.1 Work Hours, incorporates new attachments, and extends the proposal due date from August 21, 2024 to August 27, 2024. Key details include:

  • The project scope is to upgrade ventilation in the Emergency Department and Fast Track waiting areas, and upgrade flooring, walls, and ventilation in the Central Supply Room.
  • The project is a small business set-aside under NAICS code 236220, with a construction magnitude between $1-5 million.
  • The Period of Performance is 180 calendar days from date of notice to proceed.
  • The solicitation is being procured as a Firm Fixed Price contract using Lowest Price Technically Acceptable evaluation criteria.

View the file

Other files for this federal contract opportunity

Other files attached to PIMC ED & CSR (Phoenix, AZ), newest first.
File Type Posted
B05 Amendment A00010 (75H701-24-R-00035).pdf PDF
J02 WD AZ20240039 Mod 5 2024.08.16.pdf PDF
J01j TAB Report PIMC Campus Projects.pdf PDF
J01h After Hours Work Locations.pdf PDF
J01i Mechanical Zoning.pdf PDF
B05 Amendment A00008 (75H701-24-R-00035).pdf PDF
J02 WD AZ20240039 Mod 4 2024.07.19.pdf PDF
B05 Amendment A00007 (75H701-24-R-00035).pdf PDF
B05 Amendment A00006 (75H701-24-R-00035).pdf PDF
J01a Specifications PIMC ED-CSR 2024.01.29 (Conformed w-Addendum 02).pdf PDF
B05 Amendment A00005 (75H701-24-R-00035).pdf PDF
A05 Amendment A00004 (75H701-24-R-00035).pdf PDF
A05 Amendment A00003 (75H701-24-R-00035).pdf PDF
A05 Amendment A00002 (75H701-24-R-00035).pdf PDF
A05 Amendment A00001 (75H701-24-R-00035).pdf PDF
J01c Location Map.pdf PDF
J01d Infection Control Risk Assessment Permit.pdf PDF
J01f PIMC Asbestos Survey - Bldg 233 Hospital (Feb 2003).pdf PDF
J05 Company Specialized Experience Form Construction.pdf PDF
J01e Above Ceiling Work Permit.pdf PDF
J01g GFE PIMC ED-CSR.pdf PDF
J02 WD AZ20240039 Mod 2 2024.05.17.pdf PDF
J07 OF 306 Declaration for Federal Employment.pdf PDF
J08 Addendum to OF-306 (Childcare Form).pdf PDF
B01 RFP 75H70124R00035 PIMC ED CSR.pdf PDF
J06 PPQ.pdf PDF
J01a Specifications - PIMC ED-CSR 2024.01.29.pdf PDF
J01b Drawings - PIMC ED-CSR 2023.08.08.pdf PDF
J03 Self Performed Calculation Sheet.pdf PDF
J04a FORMS_TPT_5000HC_11228.pdf PDF
J04 2024 Exemption Letter for a Qualifying Hospital.pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

A00009

N/A

KELLY J. BRITTON

Project: PH23PH05H6, PIMC ED & CSR

Amendment A00009 is to provide responses to Pre-Proposal Inquires 5-10, revise clause H.1 Work Hours, incorporate Attachments J01h-J01j and extend the proposal due date from August 21, 2024 to August 27, 2024 by 2:00 PM MST. Included in this modification is an updated SF1442, updating Block 13.

SEE CONTINUATION PAGES

Indian Health Service Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104

See Block 6

75H701-24-R-00035

PH23PH05H6

1 27

08/13/2024

05/24/2024

Amendment of Solicitation Amendment A00009 under Solicitation 75H701-24-R-00035 Project PH23PH05H6, PIMC ED & CSR

SUMMARY OF CHANGES

1. The purpose of Amendment A00009 is as follows:

a. Provide responses to Pre-Proposal Inquires 5 through 10, including Attachment 1 - After Hours Work Locations and Attachment 2 - Mechanical Zoning.

b. Section H, Clause H.1 Work Hours is changed as follows:

H.1. WORK HOURS

PIMC’s normal business hours are 8:00 AM – 5:00 PM, Monday through Friday (excluding Federal holidays). Work in and around the PIMC’s ED Waiting Room and ED Fast Track shall be performed during nights and weekends only; Monday through Friday 8:00 PM to 6:00 AM and anytime on Saturday and Sunday. Reference Attachment 1 After Hours Work Locations for exact locations for after-hours work.

Work at other times must be approved by the COR. Requests to work outside normal business hours shall be submitted in writing to the COR not less than 48 hours in advance of the proposed modified schedule. This requirement is due to the need for security of patients, government personnel and property. There must be a 'responsible government agent' on site when any contractor is present on IHS property.

Note: Four (4) day work weeks will be considered upon written request and must be clearly identified in the project schedule.

c. Incorporate the following Attachments:

i. Attachment J01h After Hours Work Locations

ii. Attachment J01i Mechanical Zoning

iii. Attachment J01j TAB Report PIMC Campus Projects

d. Section J – List of Attachments is revised as follows:

SECTION J – LIST OF ATTACHMENTS

Attachment # and Document Title Date # of Pages

J01a Specifications - PIMC ED & CSR (Conformed with Addendum 02) 01/29/2024 276 J01b Drawings - PIMC ED & CSR 08/08/2023 42 Addendum 01 (Amendment A00002) 7/3/2024 2 Addendum 2 (Amendment A00006) 7/18/2024 2 J01c Location Maps N/A 2 J01d Infection Control Risk Assessment Permit N/A 2 J01e Above Ceiling Work Permit N/A 2 J01f PIMC Asbestos Survey - Bldg 233 Hospital Feb 2003 83 J01g Government Furnished Equipment N/A 1 J01h After Hours Work Locations (Amendment A00009) N/A 1 J01i Mechanical Zoning (Amendment A00009) N/A 2 J01j TAB Report PIMC Campus Projects (Amendment A00009) 1/25/2023 18 J02 Wage Determination: General Decision Number Mod 4 AZ20240039

(Amendment A00007) 07/19/2024 5

Amendment A00009 under Solicitation 75H701-24-R-00035 Project PH23PH05H6, PIMC ED & CSR

J03 Self Performed Calculation Sheet N/A 4 J04 2024 Exemption Letter for a Qualifying Hospital 12/29/2023 3 J04a Arizona Form 5000HC – Transaction Privilege Tax Healthcare Exemption

Certificate Nov 2020 2

J05 Company Specialized Experience Form N/A 2 J06 Past Performance Questionnaire N/A 5 J07 OF-306 Declaration for Federal Employment Oct 2019 3 J08 Addendum to OF-306 (Childcare Form) N/A 2

e. The proposal due date is extended from August 21, 2024 to August 27, 2024 by 2:00 PM MST.

Included in this modification is an updated SF1442, updating Block 13.

END OF SUMMARY OF CHANGES

Amendment A00009 under Solicitation 75H701‐24‐R‐00035 Project PH23PH05H6, PIMC ED & CSR

INDIAN HEALTH SERVICE

DIVISION OF ENGINEERING

SERVICE

PRE-PROPOSAL INQUIRIES

Solicitation 75H701-24-R-00035

PROJECT: PIMC ED & CSR

LOCATION: Phoenix AZ

PROJECT NO: PH23PH05H6

DOCUMENT

OWNER:

Kelly Britton PHONE: 602-364-5081 DOCUMENTS:

DATE: 8/13/2024 DEPARTMENT: IHS/PAO/DFE

Item No.

Reference Drawing, Spec, Page COMMENTS POC IHS Approved Response

Amendment A00009 dated 8/13/2024

5.

Spec Section 015010

Will it be required to work out of an ICRA containment cart? PIMC/ Derrick

All ICRA requirements are contained under SECTION 015010 of the specifications. The procedures on how to submit an Infection Control Plan and how it is approved is also contained under this section.

6. H.1. Work Hours

Will we be required to work off hours for all this work? I read this is normal business hours

PIMC/

Derrick

Reference revised clause H.1. WORK HOURS which adds after‐hours work for in and around the PIMC’s ED Waiting Room and ED Fast Track. See attached Attachment J01h After Hours Work Locations for exact locations for after‐hours work.

7. I would like to see the original balance reports. Spec states the COTR will supply them if asked.

PIMC/

Derrick

See attached Attachment J01j TAB Report PIMC Campus Projects, dated January 25, 2023

8. Do we know which air hander unit serves which area, I am not locating them on the drawings?

PIMC/

Derrick/

BWS

See attached Attachment J01i Mechanical Zoning drawings for areas served.

9. Just to confirm that the due date is still August 21, 2024? Kelly Reference Amendment A00009

10. L.9 Is it OK to leave the Gantt chart in the excel‐type format? Kelly As stated in L.9., “The offeror’s proposal package shall be submitted electronically in PDF format only.”

x

T

T

T

T

T

T

4-1

8Ø

8∅

T

T

T

T

T

T

T

T

T

SH.

31 29 23 19 5

X

BB

FF

JJ

E.W.F.

F.H.C.

WOMENS

TOILET

E-102

MEN'S TOILET

E-103

DPFS OFFICE

M-49

ED WAITING

1-039

WATING

CIRCULATION

C1-23

ED WAITING

SPILL OVER

AREA

1-037

WORK AREA 1

1-034

WORK AREA 2

1-035RECEPTION

1-033

WORK AREA 3

1-032

OPEN OFFICE

1-031

MED ROOM

1-024

EXAM1

1-023

EXAM 2

1-022

EXAM 3

1-021

STAFF

WORKROOM

1-019

RECEPTION

M-24

VITALS

1-014

WAITING

M-24A

EAST

CORRIDOR 1

C1-22

EXPRESS

CARE

CORRIDOR

C1-17

WAITING

1-089

PHARMACY

CORRIDOR

C1-19

CORRIDOR

C1-18

CORRESP.

CLERK

1-028

INCOMPLETE

CHART

1-027

SUPV

1-025

INCOMPLETE

CHART

1-026

CHIEF - HR

OFFICE

M-46

CORRIDOR

C1-20

CORRIDOR

C1-21

MED ROOM

E-117

EXAM 9

E-124

EXAM 10

E-123

TELECOMM

E-110

MEDICAL

DIRECTOR

E-109

NURSE SUPV.

E-108

EXIT

E-107

OBSERVATION

E-106

VITALS

E-105

NURSE FIRST

TRIAGE

E-104

16x16 EXH. DTR.

24x24 EG

700 CFM

VAV

46-B-2

VAV

45-B-2

VAV

39-B-2

(E) CD

225 CFM

(E) EG

250 CFM

(E) EG

100 CFM

(E) CD

150 CFM

(E) RG

125 CFM

(E) CD

75 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) EG

125 CFM

(E) CD

75 CFM

(E) CD

100 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) CD

75 CFM

(E) RG

50 CFM

(E) CD

75 CFM

(E) RG

50 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

75 CFM

(E) CD

75 CFM

(E) CD

75 CFM

(E) RG

500 CFM

(E) CD

150 CFM

(E) RG

150 CFM

(E) EG

100 CFM

(E) EG

100 CFM

(E) CD

75 CFM

(E) CD

150 CFM

22x22 EG

400 CFM

(E) CD

125 CFM

MAKE CONNECTION

TO EXIST. TRUNK

DUCT

MAKE CONNECTION

TO EXIST. TRUNK

DUCT

14x14

16x16

(E) CD

500 CFM

(E) CD

500 CFM

(E) RG

450 CFM

(E) CD

525 CFM

(E) CD

200 CFM

(E) RG

200 CFM

(E) RG

300 CFM

(E) CD

75 CFM

(E) CD

50 CFM

(E) CD

250 CFM

(E) CD

300 CFM (E) RG

450 CFM

(E) CD

500 CFM

(E) SD

225 CFM

(E) SD

200 CFM

(E) SD

225 CFM

(E) CD

225 CFM

(E) EG

250 CFM

(E) CD

125 CFM

(E) CD

125 CFM

(E) CD

75 CFM

(E) CD

50 CFM

(E) CD

125 CFM

(E) EG

75 CFM

(E) CD

50 CFM

14"x14"

14x14 EHX. DTR

10" RND

10" RND

6" RND

6" RND

6" RND

6" RND

14"x12"

24"x12"

14"x12"

23090

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

(520) 323-3858

PROJECT No.

www.ZonaMEP.com

TECHNICAL ENGINEERING, PLLC.

MECHANICAL . PLUMBING . ELECTRICAL

R

VI

H

P

S

N I D

C E

I

A

A N

HE

TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

8/8/23 - CONSTRUCTION DOCS

1818.015.1

75H70123F30021

8/15/23 OWNER COMMENTS

M2.20

MECHANICAL FIRST

FLOOR PLAN

Indian Health Service

PIMC ED & CSR

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 520.321.4625

MEP

Zona Technical Eng 6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

STRUCTURAL

Turner Structural Eng 2806 N Alvernon Way, 400 Tucson, AZ 85712 Phone: 520.323.3422

4212 N 16TH ST

PHOENIX, AZ

1/8" = 1'-0"M2.20

1 MECHANICAL FIRST FLOOR PLAN

Expires 12/31/202112/31/2024

08/

24 42

J01h After Hours Work Locations

DABuck Cloud+

DABuck Cloud+ Night and weekend work.

DABuck Cloud+

DABuck Cloud+ Night and weekend work.

FD

STERILIZATION

PREP

OFFICE

PREP

101A DECONTAMINATION

BREAK ROOM

LOBBY /

SUPPLIES

SUPPLIES

OFFICE

STERILIZATION

VAV

14-A-1

VAV

21-A-1

VAV

19-A-1

VAV

20-A-1

SUPPLY ROOM

101B

24"x16"

16"x12" 12"x12"

"x

28"x16"

"x

"x

"x

22"x16"

"x

"x

EXISTING RETURN DUCT

EXISTING EXHAUST DUCT

EXISTING

SUPPLY

DUCTS

12x12 FCDA

300 CFM

(TYP. 2 PL.)

22x22 RGA

550 CFM

EXISTING SUPPLY DUCT

9x9 FCDA

200 CFM

(TYP. 2 PL.)

22x22 RGA

550 CFM

(TYP. 2 PL.)

9x9 FCDA

250 CFM

(TYP. 4 PL.)

9x9 FCDA

150 CFM

12x12 FCDA

300 CFM

EXISTING RETURN DUCT

12x12 CDA

400 CFM

6x6 EGA

100 CFM

12x12 CDA

300 CFM

(TYP. 2 PL.)

9x9 CDA

250 CFM

(TYP. 3 PL.)

22x22 RGA

650 CFM

12x12 CDA

400 CFM

22x10 RGA

475 CFM

9x9 CDA

275 CFM

12x12 FCDA

300 CFM

22x10 EGA

400 CFM

(TYP. 2 PL.)

9x9 FCDA

225 CFM

(TYP. 4 PL.)

22x22 RGA

850 CFM

22x10 EGA

175 CFM

(TYP. 2 PL.)

22x10 EGA

250 CFM

VAV

13-A-1(E)

(E) RGA REBAL.

TO 125 CFM

(E) EGA

REBAL. TO

650 CFM

20"x16"

16"x16"

16"x12"

20"x16"

PROVIDE AP

IN DUCT

PROVIDE AP

IN DUCT

NOTE:

MECHANICAL CONTRACTOR SHALL MODIFY (E) S/A

DUCTWORK FROM (E) VAV 13-A-1 UNDER THIS

CONTRACT IN COORDINATION WITH INSTALLATION

OF S/A DUCTWORK FROM VAV 14-A-1

TAB CONTRACTOR SHALL REBALANCE (E)

TERMINAL UNIT BASED ON PRE-DEMOLITION TAB

REPORT & REMOVAL OF SUPPLY TO SUPPLY

ROOM #101B. PROVIDE FINAL CALCULATION IN

NOTES FOR TERMINAL UNIT W/ FINAL BALANCE

REPORT.

H T

T

T

T

JANITOR'S CLOSET

(E) EGA REBAL.

TO 50 CFM

REMOVE & REPLACE SANITARY

FLOOR DRAIN. CONN. TO (E)

PLUMBING ROUGH-IN & PATCH

AS NECESSARY.

P-1

ELECTRICAL

MECHANICAL

CORRIDOR

1B

CORRIDOR

100A

23090

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

(520) 323-3858

PROJECT No.

www.ZonaMEP.com

TECHNICAL ENGINEERING, PLLC.

MECHANICAL . PLUMBING . ELECTRICAL

R

VI

H

P

S

N I D

C E

I

A

A N

HE

TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

8/8/23 - CONSTRUCTION DOCS

1818.015.1

75H70123F30021

8/15/23 OWNER COMMENTS

M2.10

MECHANICAL GROUND

FLOOR PLAN

Indian Health Service

PIMC ED & CSR

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 520.321.4625

MEP

Zona Technical Eng 6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

STRUCTURAL

Turner Structural Eng 2806 N Alvernon Way, 400 Tucson, AZ 85712 Phone: 520.323.3422

4212 N 16TH ST

PHOENIX, AZ

1/8" = 1'-0"M2.10

1 MECHANICAL GROUND FLOOR PLAN

Expires 12/31/202112/31/2024

08/

(E) AHU-1

J01i Mechanical Zoning x

T

T

T

T

T

T

4-1

8Ø

8∅

T

T

T

T

T

T

T

T

T

SH.

31 29 23 19 5

X

BB

FF

JJ

E.W.F.

F.H.C.

WOMENS

TOILET

E-102

MEN'S TOILET

E-103

DPFS OFFICE

M-49

ED WAITING

1-039

WATING

CIRCULATION

C1-23

ED WAITING

SPILL OVER

AREA

1-037

WORK AREA 1

1-034

WORK AREA 2

1-035RECEPTION

1-033

WORK AREA 3

1-032

OPEN OFFICE

1-031

MED ROOM

1-024

EXAM1

1-023

EXAM 2

1-022

EXAM 3

1-021

STAFF

WORKROOM

1-019

RECEPTION

M-24

VITALS

1-014

WAITING

M-24A

EAST

CORRIDOR 1

C1-22

EXPRESS

CARE

CORRIDOR

C1-17

WAITING

1-089

PHARMACY

CORRIDOR

C1-19

CORRIDOR

C1-18

CORRESP.

CLERK

1-028

INCOMPLETE

CHART

1-027

SUPV

1-025

INCOMPLETE

CHART

1-026

CHIEF - HR

OFFICE

M-46

CORRIDOR

C1-20

CORRIDOR

C1-21

MED ROOM

E-117

EXAM 9

E-124

EXAM 10

E-123

TELECOMM

E-110

MEDICAL

DIRECTOR

E-109

NURSE SUPV.

E-108

EXIT

E-107

OBSERVATION

E-106

VITALS

E-105

NURSE FIRST

TRIAGE

E-104

16x16 EXH. DTR.

24x24 EG

700 CFM

VAV

46-B-2

VAV

45-B-2

VAV

39-B-2

(E) CD

225 CFM

(E) EG

250 CFM

(E) EG

100 CFM

(E) CD

150 CFM

(E) RG

125 CFM

(E) CD

75 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) EG

125 CFM

(E) CD

75 CFM

(E) CD

100 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

125 CFM

(E) CD

75 CFM

(E) RG

50 CFM

(E) CD

75 CFM

(E) RG

50 CFM

(E) CD

125 CFM

(E) RG

100 CFM

(E) CD

75 CFM

(E) CD

75 CFM

(E) CD

75 CFM

(E) RG

500 CFM

(E) CD

150 CFM

(E) RG

150 CFM

(E) EG

100 CFM

(E) EG

100 CFM

(E) CD

75 CFM

(E) CD

150 CFM

22x22 EG

400 CFM

(E) CD

125 CFM

MAKE CONNECTION

TO EXIST. TRUNK

DUCT

MAKE CONNECTION

TO EXIST. TRUNK

DUCT

14x14

16x16

(E) CD

500 CFM

(E) CD

500 CFM

(E) RG

450 CFM

(E) CD

525 CFM

(E) CD

200 CFM

(E) RG

200 CFM

(E) RG

300 CFM

(E) CD

75 CFM

(E) CD

50 CFM

(E) CD

250 CFM

(E) CD

300 CFM (E) RG

450 CFM

(E) CD

500 CFM

(E) SD

225 CFM

(E) SD

200 CFM

(E) SD

225 CFM

(E) CD

225 CFM

(E) EG

250 CFM

(E) CD

125 CFM

(E) CD

125 CFM

(E) CD

75 CFM

(E) CD

50 CFM

(E) CD

125 CFM

(E) EG

75 CFM

(E) CD

50 CFM

14"x14"

14x14 EHX. DTR

10" RND

10" RND

6" RND

6" RND

6" RND

6" RND

14"x12"

24"x12"

14"x12"

23090

6422 E. SPEEDWAY BLVD. Suite 130

TUCSON, ARIZONA, 85710

(520) 323-3858

PROJECT No.

www.ZonaMEP.com

TECHNICAL ENGINEERING, PLLC.

MECHANICAL . PLUMBING . ELECTRICAL

R

VI

H

P

S

N I D

C E

I

A

A N

HE

TL H

S

E

E

H

N M

E

A R

P

T O F

T

C

D

SU

S

A

E

TAE L

H

N V I

S E R

U M A

H U. S. DEPARTMENT

OF HEALTH AND

HUMAN SERVICES

INDIAN HEALTH SERVICE

DIVISION OF FACILITIES ENGINEERING

PHOENIX AREA

ARCHITECTS

4636 N. 32nd Street

480.980.9054 Fax 520.795.6171

www.bwsarchs.com

BURNS WALD-HOPKINS SHAMBACH ARCHITECTS

DRAWN BY:

CONSULTANTS

Phoenix, Arizona 85018

CHECKED BY:

CAD DWG FILE:

PROJECT NO:

ISSUE:

SHEET OF

REVIEWED:

DFE ENGINEER/PROJECT MANAGER

APPROVED:

DFE BRANCH CHIEF

CONCURRENCE:

DFE CHIEF

DATE

DATE

DATE

REV DATE DESCRIPTION

IHS PROJECT NO.

C

B

A

C

B

A

SHEET TITLE

8/8/23 - CONSTRUCTION DOCS

1818.015.1

75H70123F30021

8/15/23 OWNER COMMENTS

M2.20

MECHANICAL FIRST

FLOOR PLAN

Indian Health Service

PIMC ED & CSR

CIVIL

EEC, Inc 555 E. River Road, #301 Tucson, AZ 85704 Phone: 520.321.4625

MEP

Zona Technical Eng 6422 E. Speedway Blvd., Unit 130 Tucson, AZ 85710 Phone: 520.200.2612

STRUCTURAL

Turner Structural Eng 2806 N Alvernon Way, 400 Tucson, AZ 85712 Phone: 520.323.3422

4212 N 16TH ST

PHOENIX, AZ

1/8" = 1'-0"M2.20

1 MECHANICAL FIRST FLOOR PLAN

Expires 12/31/202112/31/2024

08/

(E) AHU-2

(E) AHU-4

J01i Mechanical Zoning

Project: PIMC CAMPUS PROJECTS

Location: 4212 N 16TH STREET, PHOENIX AZ 85016

Engineer: ZONA TECHNICAL ENGINEERING

Prepared for: ZONA TECHNICAL ENGINEERING

Project Number:

Date:

Michael Ziegler

Test & Balance Engineer

TAB Technology, Inc.

1912 North Rosemont

Mesa, Az 85205 480-964-0187

25-Jan-23

Associated Air Balance Council Certificate No: 98-01-42

TEST AND BALANCE REPORT

This is to certify that TAB Technology, Inc. has balanced the systems described herein to their optimum performance capabilities. The testing and balancing has been performed in accordance with the standard requirements and procedures of the Associated Air Balance Council and the results are herein recorded.

J01j TAB Report PIMC Campus Projects

TTI

TAB Technology Inc.

Date: 1/10/2022 Tech: BW

Note #

1 AHU-2 was in full economizer at time of readings. It appears we only

EF-27 has a bad motor and is not running at this time.

pre-read a small portion of the areas served by this air handler. The unit traverse CFM is far more than the total from VAV pre-reads.

AHU-4 Is a multi zone system, the return grill total is much less than the return traverse total indicating leakage somewhere in the ceiling.

Technician Notes

The OSA damper was 100% closed at the time of testing.

EF-3A & 3B These fans are setup for one to be a stand by. Both fans were rotated in the cycle to acquire CFM Readings.

Air Handler Test

Project: Date:

System: Tech:

Print ID:

4.06 0.25

4.06 1.08

-0.40 0.82

3.84 0.22

Hz: 65 C to C:

4bn-/78.75/pf/mb/55/pf/sx5g

AHU-2

4.06

3.84

Pre-read VAV Total

5.06

Required Final Traverse Total

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

AHU-2 BW

Alliance Air Products

6038 34320

01/19/23

3.81

2.98

-1.22

-1.22

4 @20 1848.0

AHU-2 Was in full economizer at the time of testing

DIRECT

DRIVE

VFD

1.15

System Static Set Point:

100%

In - Out - Delta P

Humidifier In - Out -

Delta P

Mark

Manufacturer

Model, Size

Conditions

Total CFM

External/Total Fan

Static Press.

Fan Static Press.

Inlet - Outlet

Cooling Coil

In - Out - Delta P

Heating Coil

In - Out - Delta P

Filter

In - Out - Delta P

Remarks:

NA NA

Motor HP - RPM

Motor Voltage

Motor Amps

Service Factor

Motor Frame

Outside Air

Drive Belts

Fan Pulley

Motor Sheave

Fan RPM

Motor AdJ

IN/OUT:

23.30

480/483/480/3460/3 16.2/16.3/16.3 16.3/16.6/16.4 16.3/16.4/16.4 16.5/16.3/16.4

1848/1854/1843/1851

VAV Box Schedule with Terminal Device

Project: Date: 12/21/22 System: Tech: BW/CD

Print ID:

Area Plan Control Size /

Served Tag Tag Diameter Max Min Max Min

40-B-2 8"/8" NA NA 241 NA

41-B-2 8"/8" NA NA 312 NA

42-B-2 12"/12" NA NA 421 NA

44-B-2 "8/8" NA NA 349 NA

45-B-2 8"/8' NA NA 631 NA

Terminal Normal Cooling Heating

No. Size Velocity CFM Velocity CFM Velocity CFM

40-1 12X12 241 236 247

40-B-2 TOTAL 241 236 247

41-1 12X12 312 319 294

41-B-2 TOTAL 312 319 294

42-1 10X10 122 182 144 42-2 6X12 100 111 102 42-3 6X12 78 90 82 42-4 6X12 121 284 250

42-B-2 TOTAL 421 667 578

44-1 12X12 349 377 339

44-B-2 TOTAL 349 377 339

45-1 10X10 138 131 122 45-2 10X10 136 137 120 45-3 10X10 111 119 112 45-4 10X10 93 90 107 45-5 10X10 153 163 149

45-B-2 TOTAL 631 640 610

Remarks:

TTI

TAB Technology, Inc.

Required CFM Final CFM "K"

Factor Notes

Exsiting Pneumatic Dual Duct VAV

PIMC CAMPUS PROJECTS

Room

Number "K" Notes with Terminal Device

Project: Date: 12/21/22 System: Tech: BW/CD

Print ID:

Area Plan Control Size /

Served Tag Tag Diameter Max Min Max Min

46-B-2 12"/12" NA NA 1,084 NA

48-B-2 8"/8" NA NA 437 NA

49-B-2 8"/8" NA NA 430 NA

Terminal Normal Cooling Heating

No. Size Velocity CFM Velocity CFM Velocity CFM

46-1 10''Ø 129 143 115 46-2 12X12 322 419 332 46-3 12X12 318 442 348 46-4 12X12 315 432 341

46-B-2 1,084 1,436 1,136

48-1 12X12 437 432 386

48-B-2 TOTAL 437 432 386

49-1 10X10 225 280 237 49-2 10X10 205 267 243

49-B-2 TOTAL 430 547 480

Remarks:

Room

Number "K" Notes

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

Exsiting Pneumatic Dual Duct VAV

Required CFM Final CFM "K"

Factor Notes with Terminal Device

Project: Date: 12/21/22 System: Tech: ME,DE

Print ID:

Area Plan Control Size /

Served Tag Tag Diameter Max Min Max Min

VB-01 8" / 8" NA NA 355 NA

VB-03 8" / 8" NA NA 847 NA

VB-04 8" / 8" NA NA 297 NA

Terminal AS IS Cooling Heating

No. Size Velocity CFM Velocity CFM Velocity CFM

E154 01-1 08''Ø 88 85 54 E122 01-2 08''Ø 85 88 66 E121 01-3 08''Ø 103 97 70 E155 01-4 08''Ø 79 82 67

355 352 257

E127 03-1 08''Ø 231 215 190 E129 03-2 08''Ø 200 217 186 E131 03-3 08''Ø 154 116 106 E155 03-4 08''Ø 262 225 186

847 773 668

E124 04-1 08''Ø 63 154 61 E123 04-2 08''Ø 55 171 54 E128 04-3 08''Ø 42 120 46 E130 04-4 08''Ø 63 206 65 E132 04-5 08''Ø 74 191 75

297 842 301

Remarks:

Room

Number "K" Notes

VB-01 TOTAL

VB-03 TOTAL

VB-04 TOTAL

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

EXISTING VAVS

Required CFM Final CFM "K"

Factor with Terminal Device

Project: Date: 12/21/22 System: Tech: ME,DE

Print ID:

Area Plan Control Size /

Served Tag Tag Diameter Max Min Max Min

VB-05 8" / 8" NA NA 288 NA

VB-06 8" / 8" NA NA 346 NA

Terminal AS IS Cooling Heating

No. Size Velocity CFM Velocity CFM Velocity CFM

E113 05-1 08''Ø 35 47 28 E108 05-2 08''Ø 87 82 52 E109 05-3 08''Ø 69 77 40

E110 05-4 08''Ø NA NA NA (1)

E111 05-5 08''Ø 97 115 71

288 321 191

E106 06-1 08''Ø 289 286 169

CORR 06-2 08''Ø 57 72 42

346 358 211

Remarks:

Room

Number "K" Notes

1. Locked door no key

VB-05 TOTAL

VB-06 TOTAL

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

EXISTING VAVS

Required CFM Final CFM "K"

Factor

Terminal Device

Schedule

Project: Date: 01/19/23 System: Tech: BW/DH Print ID:

No. Size Velocity CFM Velocity CFM Velocity CFM

E121 2-1 08''Ø 1.00 238 238 237 E122 2-2 08''Ø 1.00 220 219 217 E104 2-3 08''Ø 1.00 62 60 66 E156 2-4 12''Ø 1.00 501 512 510 E156 2-5 12''Ø 1.00 722 734 730 E124 2-6 08''Ø 1.00 155 146 147 E123 2-7 08''Ø 1.00 249 254 245

E108 2-8 08''Ø 1.00 NA 142 139

E109 2-9 08''Ø 1.00 148 159 162

E110 2-10 12''Ø 1.00 NA NA NA (1)

E111 2-11 10''Ø 1.00 157 166 155 E130 2-12 08''Ø 1.00 209 211 217 E129 2-13 08''Ø 1.00 270 272 267 E127 2-14 08''Ø 1.00 203 204 198 137 2-15 24X12 1.00 673 688 674

Waiting 2-16 24X12 1.00 570 571 532 Waiting 2-17 24X12 1.00 372 384 399

NA 2-18 18X12 1.00 64 65 64

131 2-19 12X6 1.00 316 302 312 132 2-20 12X6 1.00 36 31 30 132 2-21 12X6 1.00 10 10 11 135 2-22 12X8 1.00 154 153 154 134 2-23 12X8 1.00 215 214 216 130 2-24 12X6 1.00 302 289 289 126 2-25 12X6 1.00 420 427 427 138 2-26 12X6 1.00 180 183 185 127 2-27 18X6 1.00 364 409 405 127 2-28 12X6 1.00 358 365 372 129 2-29 18X6 1.00 536 523 524 125 2-30 12X8 1.00 500 514 507 124 2-31 12X8 1.00 312 311 310 123 2-32 12x6 1.00 200 203 204

8,716 8,959 8,905

All outlets tested with a digital flow hood, which is self-compensating for altitude and back pressure.

Remarks:

Notes

1. Door locked no key.

AHU-2 RETURN TOTAL

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

AHU-2 RETURN TOTAL

Room

Number

Terminal "K"

NORMAL COOLING HEATING

Air Handler Test

Project: Date:

System: Tech:

Print ID:

4.15 0.02

4.15

-0.11 0.81

4.17 0.33

4.15 0.33

Hz: 60 C to C:

C8254-FCH-L

AHU-4

3.84

4.15

Preliminary

5.07

Required Final Traverse Total

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

AHU-4 BW

ENERGY LABS

01/19/23

4.17

4.15

-0.92

-0.92

5.0 1765+/-

3.82

1 OSA DAMPER 100% CLOSED

DIRECT

DRIVE

VFD

184T

1.15

System Static Set Point:

(1)

Cold Deck Final

Filter In - Out

Hot Deck Final Filter

In - Out

Mark

Manufacturer

Model, Size

Conditions

Total CFM

External/Total Fan

Static Press.

Fan Static Press.

Inlet - Outlet

Cooling Coil

In - Out - Delta P

Heating Coil

In - Out - Delta P

Filter

In - Out - Delta P

Remarks:

NA NA NA

Motor HP - RPM

Motor Voltage

Motor Amps

Service Factor

Motor Frame

Outside Air

Drive Belts

Fan Pulley

Motor Sheave

Fan RPM

Motor AdJ

IN/OUT:

6.20

480/483/480/3460/3

5.2/5.3/5.2

J01j TAB Report PIMC Campus Projects dave Highlight 0.0 dave Highlight

Exhaust Fan Test

Project: Date: 01/19/23 System: Tech: BW Print ID:

Req'd Final Req'd Final Req'd Final Req'd Final

3,552 19,907

0.86 1.68

-0.69 -1.35

0.17 0.33

2.0 2 @15.0

1755 1762 1770 1383/1385

460/3 480/480 483/3 460/3 480/480

483/3

2.75 1.2/1.2

1.1 17.90

10.1/10.4/ 10.6

10.6/10.5/

1762 1383/1385

Remarks:

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

RF-4 and RF-2

Conditions

Mark RF-4 RF-2

Manufacturer ENERGY LABS Alliance Air Products

Motor RPM

Model, Size C8254-FCH-L 4BN-78.75

Total CFM

Fan Static Pressure

Fan Inlet Pressure

Fan Outlet Pressure

Motor HP

Motor Volts/Phase

Motor Amps

Fan RPM

Motor Sheave DIRECT

Fan Pulley DRIVE DRIVE

DIRECT

Motor Frame 145T 254

Drive Belt(s) VFD VFD

Center to Center NA NA

Motor Service Factor 1.15 1.15

Sys Static Set Point NA NA

Motor Adjust In/Out NA NA

Herts 60.00 56.00

Schedule

Project: Date: 12/21/22 System: Tech: ME/DE Print ID:

No. Size Velocity CFM Velocity CFM Velocity CFM

E101 Z1-1 10''Ø 117 117 254 E101 Z1-2 10''Ø 103 103 222 E101 Z1-3 10''Ø 96 96 191 E101 Z1-4 10''Ø 101 101 246

417 417 913

E120 Z2-1 12''Ø 269 269 516 E153 Z2-2 10''Ø 247 247 532 E118 Z2-3 08''Ø 143 143 522 E118 Z2-4 08''Ø 166 166 523

825 825 2,093

E153 Z3-1 10''Ø 57 57 111 E116 Z3-2 10''Ø 61 61 124 E115 Z3-3 10''Ø 76 76 138 E115 Z3-4 10''Ø 66 66 119 E105 Z3-5 08''Ø 104 104 132 E117 Z3-6 06''Ø 36 36 76

400 400 700

All outlets tested with a digital flow hood, which is self-compensating for altitude and back pressure.

Remarks:

Notes

1. Not installed

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

AHU-B-2 RETURN

Room

Number

Terminal "K"

AS IS COOLING HEATING

ZONE 1 TOTAL

ZONE 2 TOTAL

ZONE 3 TOTAL

J01j TAB Report PIMC Campus Projects dave Highlight dave Highlight 2,093 dave Highlight dave Highlight dave Highlight dave Highlight dave Text Box 1,642 dave Text Box 3,706

Schedule

Project: Date: 12/21/22 System: Tech: ME,DE Print ID:

No. Size Velocity CFM Velocity CFM Velocity CFM

E119 EXR-4-1 14''Ø 1.00 35 38 37

E120 EXR-4-2 10''Ø 1.00 302 312 318

E153 EXR-4-3 14''Ø 1.00 478 469 487

E101 EXR-4-4 14''Ø 1.00 337 332 330

E101 EXR-4-5 14''Ø 1.00 310 312 317

AHU 4 RETURN TOTAL 1,462 1,463 1,489

All outlets tested with a digital flow hood, which is self-compensating for altitude and back pressure.

Remarks:

Notes

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

AHU-4 RETURN TOTAL

Room

Number

Terminal "K"

NORMAL COOLING HEATING

Duct Traverse Test Sheet

Project: Date: 01/19/23 System: Tech: BW Print ID:

Design Preliminary Final

FPM CFM FPM CFM FPM CFM Static Pressure

AHU-4

ZONE 1 953 (1)

ZONE 2 14"X12" 1.160 1896 2212 2.35

ZONE 3 18"X12" 1.500 498 747 3.16

SUPPLY TOTAL 3912 3.16

AHU-4 24"X24" 4.000 888 3552 -0.49

RETURN TOTAL

AHU-2

SUPPLY TOTAL 120"X96" 80.000 429 34320

AHU-2

RETURN TOTAL18 @ 3.25"X47.5"19.290 1032 19907

AHU-2

OSA 1 19 @ 4"X55" 29.020 699 20285

OSA 2 19 @ 4"X37" 19.520 688 13430

OSA TOTAL 33715

EF-3A&3B 12''Ø 0.785 1519 1192 -1.21

EF-27 18''Ø 1.760 (2)

Remarks:

1. Calculated air flow, no reliable traverse location found

2. Fan has a bad motor, not running.

TTI

TAB Technology, Inc.

DUCT TRAVERSE

System

Zone/Branch

Duct

Size

Area

(sq. ft.)

PIMC CAMPUS PROJECTS

Exhaust Fan Test

Project: Date: 01/19/23 System: Tech: BW Print ID:

Req'd Final Req'd Final Req'd Final Req'd Final

586 596 (2)

NA NA

-1.21 -1.27

NA NA

0.5 0.5 2.0

1725 NA 1725 NA 1740

208/1 211/1 208/1 211/1 208/1

3.70 2.50 3.70 2.40 11.80

NA NA

Remarks:

1. Unable to shut fan down due to COVID

2. Bad motor not running.

Motor RPM

Motor HP

60.00

Motor Frame

60.00

2"/2" 2"/2" 4"/2"

NA NA

Herts

Sys Static Set Point

Motor Adjust In/Out

Center to Center

Conditions

Motor Service Factor 1.25 1.25 1.00

16" 16" 18"

NA

Model, Size

Manufacturer

Drive Belt(s)

Fan Pulley

Motor Sheave

Fan RPM

Motor Amps

Total CFM

Fan Outlet Pressure

Fan Inlet Pressure

Fan Static Pressure

Motor Volts/Phase

NA NA AX49

56 56 182T

1VL40 X 5/8 1VL40 X 5/8 1vl56 x 1 1/8

NA NA NA

TWIN CITY FAN TWIN CITY FAN TWIN CITY FAN

TFE-90C7 TFE-90C7 TFE-15OC11

TTI

TAB Technology, Inc.

EF-3A EF-3B EF-27

PIMC CAMPUS PROJECTS

EF-3A, EF-3B, EF-27

Mark

Schedule

Project: Date: 12/21/22 System: Tech: ME/DE Print ID:

No. Size Velocity CFM Velocity CFM Velocity CFM

E119 1A-1 8 1.00 119 E102 1-1 08''Ø 1.00 173 E103 1-2 08''Ø 1.00 132 E125 1-3 06''Ø 1.00 20 E126 1-4 06''Ø 1.00 30 E131 1-5 08''Ø 1.00 500 E132 1-6 08''Ø 1.00 577 E112 1-7 06''Ø 1.00 44

All outlets tested with a digital flow hood, which is self-compensating for altitude and back pressure.

Remarks:

Notes

1. Bad Fan Motor

TTI

TAB Technology, Inc.

PIMC CAMPUS PROJECTS

Exhaust

Room

Number

Terminal "K"

Required Preliminary Final

0.004

-0.008

+0.003

-0.005

Wall -0.002

-0.004

-0.11-0.006-0.003

REVIEW DURRANT

REMODEL FROM 2009

Emergency Department

41-1 44-1

40-1

42-2 42-342-4

42-1

46-2 46-3 46-4 46-5

45-1

45-2 45-3 45-4 45-5

49-1

49-2

49-3

2-15 2-16 2-17

2-18

2-19

2-20 2-21

2-22

2-23

2-24

2-25

2-26

2-27

2-

2-

2-

2-

2-32

VB

VB

VB

R-1

8Ø

R-1

8Ø

VB-3

VB-4

VB-5

NOTE:

REFER TO SHEET M4A FOR

MECHANICAL SYMBOLS SCHEDULE.

NOTE:

REFER TO ARCHITECTURAL RCP FOR

SUPPLY/DIFFUSER GRILLE PLACEMENT.

VB

VB

8"Ø UP TO

EF-3 ON ROOF

VB

R-1

12Ø

T-2

6Ø

T-1

6Ø

T-2

6Ø

T-1

6Ø

8"Ø UP TO

EF-2 ON ROOF

VB-BOX

26X10

CONNECT

TO EXISTING

12X6

CONNECT

TO EXISTING

GENERAL NOTES:

A. CONTRACTOR TO FIELD VERIFY EXISITING CONDITIONS.

B. MECHANICAL CONTRACTOR TO COORDINATE DEMOLITION

AND NEW CONSTRUCTION WITH OTHER TRADES.

M2A

HVAC NEW CONSTRUCTION

PHASE 1

TD

JH

4' 8'0 16'

NORTH

EMERGENCY DEPARTMENT HVAC NEW CONSTRUCTION PLAN

P H

O E

N I X

N

D I A

N

M

E D

I C

A L

C

E N

T E

R

R E

M O

D E

L

P

H A

S E

P H

O E

N I X

A

R I Z

O N

A

R

D ANTRU R

E M

E R

G E

N C

Y

D

E P

A R

T M

E N

T

C C

E

A

S B

U I L T

T

REVISIONS

AS-BUILT SET 3-6-120

01-1

01-4

1-4 1-3

2-5 2-4

2-6 2-7

03-1

03-2

03-3

03-4

04-1 04-2

04-3

04-4

04-5

06-1

06-2

05-1

05-2

05-3

05-4

05-5

1-5 1-6

1-7

2-8

2-9

2-10

2-11

2-12

2-13

2-14

-0.015

-0.010

-0.006

-0.009

-0.007 -0.010

-0.004

-0.005

+0.009

0.006

-0.009

-0.010

-0.021

-0.029

14x6

VB

VB

S-1

8Ø

S-1

10Ø

S-1

12Ø

S-3

10Ø

S-3

10Ø

S-3

10Ø

S-3

10Ø

S-1

8Ø

S-1

10Ø

S-1

10Ø

S-2

6Ø

E-1

6Ø

R-1

12Ø

E-2

14Ø

VB

10Ø UP TO

EF-1 ON ROOF

T-1

8Ø

VB-7

4-3

VB-1

VB-2

VB-6

4-1

4-2

NOTE:

SEE SHEET M4B FOR MECHANICAL

SYMBOLS SCHEDULE.

NOTE:

REFER TO ARCHITECTURAL RCP FOR

SUPPLY/DIFFUSER GRILLE PLACEMENT.

T

T

T

T

T

T

T

E-2

8Ø

T-1

8Ø

E-1

14Ø

T-2

6Ø

T-1

6Ø

T-2

6Ø

T-2

6Ø

T-1

6Ø

T-1

6Ø

T-2

6Ø

T-1

6Ø

T-2

6Ø

T-1

6Ø

Ø

Ø

Ø

Ø

6Ø

6Ø

8X8

GENERAL NOTES:

A. CONTRACTOR TO FIELD VERIFY EXISITING CONDITIONS.

B. MECHANICAL CONTRACTOR TO COORDINATE DEMOLITION

AND NEW CONSTRUCTION WITH OTHER TRADES.

M2B

HVAC NEW CONSTRUCTION

PHASE 2

TD

JH

P H

O E

N

X

N

D I A

N

M

E D

I C

A L

C

E N

T E

R

R E

M O

D E

L

P

H A

P H

O E

N I X

A

R I Z

O N

A

E M

E R

G E

N C

Y

D

E P

A R

T M

E N

T

4' 8'0 16'

NORTH

EMERGENCY DEPARTMENT HVAC NEW CONSTRUCTION PLAN

C C

E

A

S B

U I L T

T

REVISIONS

AS-BUILT SET 3-6-120

C O

N F

IR

M

S T

A T

U S

O F

H A

N D

S K

E T

C H

E D

M O

D

IF

IC

A

T

IO

N S

IN

N

E X

T S

H E

E T

01-1

01-2

01-3

01-4

Z1-1

Z1-2

Z1-3

Z1-4

Z2-1

Z2-2

Z2-3

Z2-4

Z3-1

Z3-2

Z3-3

Z3-4

Z3-5

Z3-6

4-1

4-2

2-1

4-3

2-2

4-4

4-5

2-3

2-4

2-5

2-6

1-1

1-2

1-31-4

1A-1

2-7

+0.009

+0.002

-0.012

0.002

0.006 -0.009

-0.012

-0.008

-0.011

0.002

(See ).

SOLICITATION, OFFER,

AND AWARD

(Construction, Alteration, or Repair) IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.

9. FOR

INFORMATION CALL:

NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid and "bidder".

SOLICITATION

1. SOLICITATION NUMBER

5. REQUISITION/PURCHASE REQUEST NUMBER

CODE

6. PROJECT NUMBER

8. ADDRESS OFFER TO

4. CONTRACT NUMBER

7. ISSUED BY

10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS (Title, identifying number, date)

11. The contractor shall begin performance within

12a. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?

(If "YES", indicate within how many calendar days after award in Item 12b.)

13. ADDITIONAL SOLICITATION REQUIREMENTS:

a. Sealed offers in original and

b. An offer guarantee

c. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.

d. Offers providing less than

STANDARD FORM 1442 (REV. 12/2022)

Prescribed by GSA - FAR (48 CFR) 53.236-1(d) calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.

is, is not required.

local time containing offers shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.

(date). If this is a sealed bid solicitation, offers will be publicly opened at that time. Sealed envelopes copies to perform the work required are due at the place specified in Item 8 by (hour) award, YES NO notice to proceed. This performance period is mandatory negotiable.

calendar days and complete it within calendar days after receiving

a. NAME b. TELEPHONE NUMBER (Include area code) (NO COLLECT CALLS)

12b. CALENDAR DAYS

2. TYPE OF SOLICITATION

SEALED BID (IFB)

INVITATION FOR BID

NEGOTIATED (RFP)

REQUEST FOR PROPOSAL

3. DATE ISSUED PAGE OF PAGES

75H701-24-R-00035

Indian Health Service Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104

Project: PH23PH05H6, PIMC ED & CSR

Location: Phoenix Indian Medical Center (PIMC), 4212 North 16th Street, Phoenix, AZ, 85016

See Section L for Proposal Submittal Instructions and Site Visit Information.

This project will be procured as a 100% Small Business set-aside under North American Industry Classification System (NAICS) code 236220 Commercial and Institutional Building Construction. The associated size standard for this procurement is $45 million.

CONSTRUCTION MAGNITUDE: The magnitude of this construction project is anticipated to be between $1,000,000 and $5,000,000, in accordance with FAR 36.204(f).

Indian Health Service, Phoenix Area OEHE Attn: Kelly Britton 40 N. Central Ave, Suite 720 Phoenix, AZ 85004

Kelly Britton (602) 245-2206 or kelly.britton@ihs.gov

PH23PH05H6

1 5505/24/2024

8/27/2024

2:00 PM

10 days after award

F.2. FAR 52.211-10

AWARD (To be completed by Government)

17. The offeror agrees to perform the work required at the prices specified below in strict accordance with the terms of this solicitation, if this offer is accepted calendar days after the date offers are due. (Insert any number equal to or greater than the minimum requirement by the Government in writing within stated in Item 13d. Failure to insert any number means the offeror accepts the minimum in Item 13d.)

OFFER (Must be fully completed by offeror)

AMOUNTS

18. The offeror agrees to furnish any required performance and payment bonds.

19. ACKNOWLEDGMENT OF AMENDMENTS

(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)

AMENDMENT

NUMBER

DATE

CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE

14. NAME AND ADDRESS OF OFFEROR (Include ZIP Code)

CODE FACILITY CODE

15. TELEPHONE NUMBER (Include area code)

16. REMITTANCE ADDRESS (Include only if different than Item 14.)

20a. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN OFFER (Type or print)

21. ITEMS ACCEPTED:

22. AMOUNT

26. ADMINISTERED BY

30a. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED TO SIGN (Type or print)

31c. DATE

STANDARD FORM 1442 (REV. 12/2022) BACK

31b. UNITED STATES OF AMERICA

BY

31a. NAME OF CONTRACTING OFFICER (Type or print)

29. AWARD (Contractor is not required to sign this document.) Your offer on this solicitation is hereby accepted as to the items listed. This award consummates the contract, which consists of (a) the Government solicitation and your offer, and (b) this contract award. No further contractual document is necessary.

30b. SIGNATURE 30c. DATE

28. NEGOTIATED AGREEMENT (Contractor is required to sign this document and return and deliver all items or perform all work requirements identified on this form and any continuation sheets for the consideration stated in this contract. The rights and obligations of the parties to this contract shall be governed by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certifications, and specifications incorporated by reference in or attached to this contract.

copies to issuing office.) Contractor agrees to furnish

24. SUBMIT INVOICES TO ADDRESS SHOWN IN

(4 copies unless otherwise specified)

23. ACCOUNTING AND APPROPRIATION DATA

ITEM

25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO THE UNITED STATES

CODE AT

27. PAYMENT WILL BE MADE BY

10 U.S.C. 3204(a) ( ) 41 U.S.C. 3304(a) ( )

20b. SIGNATURE 20c. OFFER DATE

B.3.

Indian Health Service, DES - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104

Indian Health Service Attn: Financial Management 40 N Central Avenue, Suite 512 Phoenix, AZ 85004

KELLY J. BRITTON

LUMP SUM TOTAL $________________

J01h After Hours Work Locations.pdf
75H70123F30021 PIMC ED & CSR l Construction Document Submittal
General
G1.10 INDEX, ABBREVIATIONS, SYMBOLS & PROJECT DATA
G1.20 CODE ANALYSIS, CODE REVIEW PLANS
G1.30 ARCHITECTURAL SITE PLAN
Civil
C1.0 COVER SHEET
C2.0 UTILITIES SHEET
C3.0 DETAILS
Architectural
D2.10 LOWER LEVEL DEMOLITION PLAN
D2.10A DEMO EQUIPMENT PLAN
D3.10 DEMOLITION CEILING PLAN -LOWER LEVEL
D3.20 DEMOLITION CEILING PLAN -FIRST FLOOR PLAN
A2.10 LOWER LEVEL FLOOR PLAN
A2.10A LOWER LEVEL EQUIPMENT PLAN
A2.20 TEMPORARY MOBILE TRAILER PLAN
A2.30 ROOM FINISH SCHEDULE & INTERIOR ELEVATIONS
A3.10 REFLECTED CEILING PLAN -LOWER LEVEL
A3.20 REFLECTED CEILING PLAN -FIRST FLOOR
A4.10 ROOF PLAN
A8.10 STAIR PLANS, SECTIONS & DETAILS
Mechanical
M0.10 MECHANICAL GENERAL INFORMATION
MD2.10 MECHANICAL DEMO GROUND FLOOR PLAN
MD2.20 MECHANICAL DEMO FIRST FLOOR PLAN
M2.10 MECHANICAL GROUND FLOOR PLAN
M2.20 MECHANICAL FIRST FLOOR PLAN
M3.10 CSR AIRFLOW DIAGRAM PLAN
M3.20 ED WAITING ROOM AIRFLOW DIAGRAM PLAN
M4.10 MECHANICAL ROOF PLAN
M5.10 MECHANICAL VENTILATION CALCULATIONS
M5.20 MECHANICAL EQUIPMENT SCHEDULES
M6.10 MECHANICAL DETAILS
M7.10 MECHANICAL CONTROLS
M7.20 MECHANICAL CONTROLS
Plumbing
P0.00 PLUMBING GENERAL INFORMATION
P1.00 PLUMBING SITE PLAN
P2.00 PLUMBING ISOMETRICS
Fire Protections
FP2.10 FIRE PROTECTION GROUND FLOOR PLAN
Electrical
E0.01 ELECTRICAL GENERAL INFORMATION
E1.00 ELECTRICAL SITE PLAN
E2.10 ELECTRICAL GROUND FLOOR PLANS
E2.20 ELECTRICAL FIRST FLOOR PLAN
E3.10 ELECTRICAL ONE-LINE
E4.10 ELECTRICAL SCHEDULES
B05 75H70124R00035 Amendment A00009 Page 2.pdf
SECTION J – LIST OF ATTACHMENTS

File details come from the government source that posted it. Updated .