This document provides details for a federal construction solicitation. The Indian Health Service is seeking a contractor to construct a new 14,557 square foot administration office building at the Whiteriver Indian Hospital in Whiteriver, Arizona for between $5 million to $10 million. Scope of work includes site demolition and preparation, structural work, architectural, interiors, mechanical, electrical and telecommunications installations. The period of performance is 335 calendar days from notice to proceed. The contract type will be firm fixed price. The solicitation number is 75H701-23-R-00022 and responses are due according to the dates specified in the solicitation document.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WHITERIVER INDIAN HOSPITAL
INDIAN HEALTH SERVICE - PHX AREA OFFICE
200 WEST HOSPITAL DRIVE, WHITERIVER, AZ 85941
ADMINISTRATION OFFICE BUILDING
IHS Contract No: HHSI102201800007I IHS Project: PH15WR02H8
Issue Date: November 3, 2022
FI
N A L C O N S T R U C T
IO
N D O C U M E N T P A C K A G E
FI
N A L C O N S T R U C T
IO
N D O C U M E N T P A C K A G E t
Z
TR
I
AR
Da
EC
ni g
UONA,
.A.S.
VERNON
ROSAMOND
ee S d:
ET
I AFIC
ON .R
EG
I S
TER
ED ARCH I TEC
T
RVI
HP S
NI
D
C E
I
A
A N
HE TL H SE
E
H
N M E
AR P
T
OF
T
C D
SU
S
A
E
TAE L &H
N
VI
S E R
UM
A
H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3 /2 2:
:0
PM
Au to de sk D oc s:
//2 1- W hi te riv er A dm in v /2 1- A rc h W R A dm in 2.
rv t
G000
COVER SHEET
BD
SP
21-020 11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
DEFERRED SUBMITTAL ITEMS:
1. SHOP-FABRICATED WOOD TRUSSES
2. HVAC POWER VENTILATORS UNIT HANGERS AND SUPPORTS
3. WET-PIPE SPRINKLER SYSTEM
4. HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
5. DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
No. Date Description
VICINITY MAP
A PORTION OF THE WHITE MOUNTAIN APACHE IHS AREA
SITUATED IN GOVERNMENT LOTS 1 AND 2 OF
SECTION31, TOWNSHIP 6 NORTH, RANGE 23 EAST, PER
THE BLM DEPENDENT RESURVEY AND SURVEY OF
FEBRUARY 4TH 1993 OF THE GILA AND SALT RIVER
MERIDIAN, NAVAJO COUNTY, ARIZONA
PROJECT
LOCATION
TO PINETOP
TO WHITERIVER
NAVAJO DR
H
IG
H W
A Y
PHOENIX
FLAGSTAFF
TUCSON
PROJECT
LOCATION
WHITERIVER
APACHE CIR
t
Z
TR
I
AR
D a
E C ni g
UON A,
.A.S.
VERNON
ROSAMOND
e e
S d:
ET
I AFIC
ON
R E
G I S
TERED ARCH
I T
E C
T
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
1.
.2
/3 /2
:4 :4
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
A rc h W
R A d m in
.r v t
12" = 1'-0"
G001
INFORMATION
SHEET
BD
SP
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
BLK(G) BLOCK(ING)
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRG BEARING
BRK BRICK
BSMT BASEMENT
BUR BUILT UP ROOFING
C CHANNEL
C/C CENTER TO CENTER
CAB CABINET
CB CHALK BOARD,CATCH BASIN
CEM CEMENT
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR(ANCE)
CMP CORRUGATED METAL PIPE
CMTSCOMMENTS
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS OR CONTINUE
CORR CORRIDOR,CORRUGATED
CPT CARPET
CR CLEAN ROOM
CSK COUNTERSINK
CT CERAMIC TILE
CU CUBIC
CU FT CUBIC FOOT (FEET)
CW COLD WATER
D DEPTH
DEMO DEMOLISH, DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DITTO
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DTL DETAIL
DWG DRAWING
DWC DRYWALL CHANNELS (HAT)
E EAST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEC ELECTRIC(AL)
ELEV ELEVATION,ELEVATOR
EMER EMERGENCY
EP EPOXY PAINT
EPS EXPANDED POLYSTYRENE
EQ EQUAL EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
EST ESTIMATE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVAT(E)(ION)
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXT EXTERIOR
EIFS EXT. INSULATION FINISH SYSTEM
F FAHRENHEIT
FA FIRE ALARM
FAB FABRICATE
FD FLOOR DRAIN
FDN FOUNDATION
FE(C) FIRE EXTINGUISHER(CABINET)
FF FINISH FLOOR
FHC FIREHOSE CABINET
FHR FIREHOSE RACK
FIN FINSH(ED)
FL FLOOR
FLA FLASHING
FLEX FLEXIBLE
FLUOR FLUORESCENT
FO FACE OF
FP FIREPROOF
FR FIRE RETARDANT
FRP FIBER REINFORCED PLASTIC
FT FOOT,FEET
FTG FOOTING
FUR FURRED(ING)
FUT FUTURE
GA GAGE,(GUAGE)
GALV GALVANIZED
GC GENERAL CONTRACT(OR)
GD GRADE
GL GLASS, GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
H(T) HEIGHT
HB HOSE BIBB
HC HOLLOW CORE
HDBD HARDBOARD
HD HEAVY DUTY
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HORZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING/VENTILATING/ AIR
CONDITIONING
HW HOT WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCH(ES)
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JC JANITORS CLOSET
JST JOIST
JT JOINT
KD KNOCKED DOWN
KIT KITCHEN
KO KNOCK OUT
KP KICK PLATE
L LENGTH,LONG
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LF LINEAL FEET
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LT LIGHT
LTWT LIGHTWEIGHT
LVR LOUVER
MAS MASONRY
MAX MAXIMUM
MATL MATERIAL
MED MEDIUM
MECH MECHANICAL
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MM MILLIMETER
MIN MINIMUM
MISC MISCELLANOUS
MO MASONRY OPENING
MOD MODULAR
MOV MOVABLE
MTD MOUNTED
MWP METAL WALL PANEL (SYSTEM)
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENTS
NTS NOT TO SCALE
NO NUMBER
OA OVERALL
OC ON CENTER(S)
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD,OPPOSITE HAND
OPG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PAINT(ED)
PAR PARALLEL
PART PARTITION
PART BD PARTICLE BOARD
PC PIECE
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PREFAB PERFORATE(D)
PERIM PERIMETER
PERP PERPENDICULAR
PF PREFABRICATED
PJ PANEL JOINT
PL PLASTER,PLATE,PROPERTY LINE
PLBG PLUMBING
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAL FOOT
PNL PANEL
PO POWER OPERATED
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTD PAPER TOWEL DISPENSER
PTR PAPER TOWEL RECEPTOR
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
PLWD PLYWOOD
QT QUARRY TILE
QTR QUARTER
QTY QUANTITY
(R) RECESSED
R RADIUS,RISER ROUND
RA RETURN AIR
RB RESILIENT BASE
RCP REINFORCED CONCRETE PIPE,
REFLECTED CEILING PLAN
RD ROOF DRAIN
RE(F) REFERENCE
RELO RELOCATION
REPL REPLACE
RES RESILIENT
REV REVISION(S),REVISED
RF RIGID FIBERGLASS
RFG ROOFING
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RRF ROLLED RUBBER FLOORING
REQ'D REQUIRED
RWL RAINWATER LEADER
S SEALED, SOUTH
(S) SURFACE MOUNTED
SC SOLID CORE, SEALED CONCRETE
SCHED SCHEDULE
SECT SECTION
SD STORM DRAIN
SDG SIDING
SF SQUARE FEET
SHT SHEET
SHWR SHOWER
SIM SIMILAR
SL SHEET LINOLEUM
SM SHEET METAL
SP SOUNDPROOF
SPECS SPECIFICATIONS
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SERVICE SINK
SST STAINLESS STEEL
STD STANDARD ST STEEL, STREET
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SEAMLESS VINYL
SW SWITCH
SWR SEWER
SYM SYMMETRY(ICAL)
T THICKNESS, TEE
TD TRENCH DRAIN
T&G TONGUE AND GROOVE
TB TACKBOARD TEL TELEPHONE
TEMP TEMPERATURE,TEMPORARY
TERR TERRAZZO
THK THICK(NESS)
TO TOP OF
TOC TOP OF CONCRETE
TOIL TOILET
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TV TELEVISION
TYP TYPICAL
U URINAL
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VNR VENEER
VPL VENEER PLASTER
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDTH, WIDE, WEST
W/ WITH
W/O WITHOUT
W/W WALL TO WALL
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WALL HUNG, WATER HEATER
WI WROUGHT IRON
WM WIRE MESH
WP WATERPROOFING
WR WATER REPELLENT
WS WEATHERSTRIP
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
ABBREVIATIONS PROJECT DIRECTORY
CODE DATA & STANDARDS
1. ALL DIMENSIONS GIVEN ARE TO FACE OF STUD AND TO FACE OF STEM WALL.
EXCEPTIONS AS INDICATED ON THE DOCUMENTS.
2. LARGE SCALE DETAILS AND PLANS TAKE PRECEDENCE OVER SMALL SCALE
DRAWINGS.
3. CIVIL DRAWINGS FINISH FLOOR DATUM ELEVATION EQUALS ARCHITECTURAL
ELEVATION OF 0'=0" FOR EACH BUILDING INDEPENDANT OF OTHER BUILDINGS.
4. COORDINATE AND VERIFY ALL DIMENSIONS, OPENINGS AND CONDITIONS WITH
CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL AND ALL OTHER PERTINENT
DRAWINGS AND TRADES PRIOR TO CONSTRUCTION. NOTIFY ARCHITECT OF
DISCREPANCIES PRIOR TO FABRICATION AND INSTALLATION.
5. FIRE RATINGS SHALL BE MAINTAINED AT FIRE RATED PARTITIONS BY A U.L.
ASSEMBLY AT GAPS AND VOIDS CREATED BY PENETRATIONS, STRUCTURAL
MEMBERS AND INTERSECTIONS WITH ADJACENT SURFACES.
6. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE CODES
AND REGULATIONS.
OWNER
INDIAN HEALTH SERVICE
DIVISION OF FACILITIES ENGINEERING
- PHOENIX AREA
TWO RENAISSANCE SQUARE
40 N. CENTRAL AVE., SUITE 720
PHOENIX, AZ 85004
CONTACT: VERNON CLASHIN
PHONE: (602) 364-5062
CIVIL ENGINEER
DOWL ENGINEERS
430 W. WARNER ROAD
TEMPE, AZ 85284
CONTACT: ERIN O'BRIEN
PHONE: (480) 753-0800
STRUCTURAL ENGINEER
SCHNEIDER STRUCTURAL ENGINEERS, INC
435 E. 9TH ST.
TUCSON, AZ 85705
CONTACT: RON SCHNEIDER
PHONE: (520) 512-8183
ARCHITECT
JOHNSON SMITTHIPONG & ROSAMOND
5120 E. WILLIAMS CIR, SUITE 600
TUCSON, AZ 85711
CONTACT: BILL DRAPER
PHONE: (520) 547-7904
ELECTRICAL/MECHANICAL
ENGINEERING
TME/BERNARD
2990 N SWAN RD., SUITE 227
TUCSON, AZ 85712
CONTACT: JACOB CLARK
PHONE: (520) 323-2381
INTERIOR DESIGN
AVIAR DESIGN
7650 E. BROADWAY BLVD, SUITE 212
TUCSON, AZ 85710
CONTACT: KATHRYN VICKERS
PHONE: (520) 216-5509
OCCUPANCY B
CONSTRUCTION TYPE VB
SEISMIC ZONE REFER TO STRUCTURAL
SPRINKLERS FULLY SPRINKLERED
GENERAL ARCHITECTURAL NOTES
PROJECT LOCATION
INTERNATIONAL BUILDING CODE 2018
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL MECHANICAL CODE
2017 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2019 A/E DESIGN GUIDE
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
2018 INTERNATIONAL FIRE CODE
2018 NFPA 101 - LIFE SAFETY CODE
2019 NFPA 72
2019 NFPA 13
N
No. Date Description
SHEET INDEX
Sht No Sheet Name
GENERAL
G000 COVER SHEET
G001 INFORMATION SHEET
G101 CODE SHEET
CIVIL
C001 COVER SHEET
C002 NOTES SHEET
C100 DEMOLITION PLAN
C200 SITE PLAN
C300 GRADING & DRAINAGE PLAN
C400 SANITARY SEWER PLAN & PROFILE
C401 WATER PLAN
C500 DETAILS
C501 DETAILS
C502 MAG STANDARD DETAILS
C503 MAG STANDARD DETAILS
C504 MAG AND CITY OF PHOENIX DETAILS
C600 STORMWATER MANAGEMENT PLAN COVER
C601 STORMWATER MANAGMENT PLAN DETAILS
C602 STORMWATER MANAGMENT PLAN
STRUCTURAL
S101 G.S.N.
S102 G.S.N. & I.O.D.
S103 SPECIAL INSPECTIONS CHART
S104 TYPICAL DETAILS
S105 TYPICAL DETAILS
S106 TYPICAL DETAILS
S107 SCHEDULES
S201 FOUNDATION PLAN
S202 ROOF FRAMING PLAN
S203 TRAILER FOUNDATION PLAN
S301 FOUNDATION DETAILS
S401 FRAMING DETAILS
S402 FRAMING DETAILS
S403 FRAMING DETAILS
ARCHITECTURAL
A001 WALL TYPES & MOUNTING HEIGHTS
A101 SITE PLAN EXISTING
A102 REFERENCE SITE PLAN NEW
A121 FLOOR PLAN
A131 DIMENSION PLAN
A141 REFLECTED CEILING PLAN
A151 ROOF PLAN
A201 EXTERIOR ELEVATIONS
A202 INTERIOR ELEVATIONS
A301 BUILDING SECTIONS
A401 ENLARGED PLANS
A501 EXTERIOR DETAILS
A502 INTERIOR DETAILS
A503 MILLWORK DETAILS
A504 DOOR DETAILS
A505 WINDOW DETAILS
A601 ROOM FINISH SCHEDULES
A602 DOOR & WINDOW SCHEDULE
A603 SIGNAGE FLOOR PLAN
A604 SIGNAGE SCHEDULE
INTERIORS
I001 FURNITURE PLAN
I002 MODULAR FURNITURE ELECTRICAL PLAN
I003 PANEL PLAN
FIRE PROTECTION
F001 GENERAL NOTES - FIRE PROTECTION
F101 FIRST FLOOR PLAN -FIRE PROTECTION
F501 DETAILS - FIRE PROTECTION
F502 DETAILS - FIRE PROTECTION
SHEET INDEX
Sht No Sheet Name
PLUMBING
P001 LEGENDS, DETAILS AND SCHEDULES -
PLUMBING
P101 PLUMBING SITE PLAN
P121 FIRST FLOOR PLAN - PLUMBING DOMESTIC
P131 FIRST FLOOR PLAN - PLUMBING SANITARY
P501 RISERS - PLUMBING
MECHANICAL
M001 GENERAL NOTES & LEGEND
M111 FIRST FLOOR PLAN - HVAC DUCTWORK
M112 FIRST FLOOR PLAN - HVAC ZONES
M113 ROOF HVAC PLAN
M601 SCHEDULES - HVAC
ELECTRICAL
E001 SCHEDULES, LEGENDS & GENERAL NOTES
E002 EQUIPMENT CONNECTION SCHEDULES
E101 SITE PLAN - DEMOLITION
E102 SITE PLAN
E103 SITE PLAN - SSB BUILDING
E121 LIGHTING PLAN
E131 POWER PLAN - NORTH
E132 POWER PLAN - SOUTH
E141 MECHANICAL POWER PLAN
E142 ROOF POWER PLAN
E151 FIRE ALARM PLAN
E161 SYSTEMS PLAN
E401 ENLARGED PLANS
E601 PANEL SCHEDULES
E602 PANEL SCHEDULES
E701 ONE-LINE DIAGRAM
2018 IECC SUMMARY: TABLE C402.1.2 - CLIMATE ZONE 5
INSULATON ENTIRELY ABOVE ROOF DECK: R-30ci rigid insulation WOOD FRAME WALL: R-18 wall cavity + R-3.8ci rigid insulation SLAB ON GRADE: R-10 for 24" below; vertical & horizontal combined
A A
B
C
D D
E
F F
52' - 6" 12 sec
124' - 8" 28 sec
55' - 1" 13 sec
14' - 2" 3 sec
+/- 48' - 11"
91' - 8" 21 sec
79' - 7" 18 sec
122' - 5" 28 sec
72' - 6" 16 sec
106' - 6" 24 sec
56' - 4" 13 sec
10 41
10 41
10 41
10 41
10 41
LEGEND
OCCUPANCY @ EXIT
EGRESS START (OR OPTION)
EGRESS PATH
EGRESS DIRECTION
EGRESS DISTANCE &
TRAVEL TIME
1 HOUR RATED WALL
2 HOUR RATED WALL
SMOKE BARRIER
a.
b.
c.
d.
e.
1.
1.
2.
A.
B.
3.
BUILDING OCCUPANCY CLASSIFICATION SUMMARY:
NFPA 101 - Life Safety Code
Occupancy: New Business (Chapter 38) NOTE: Conference Spaces are less than 50 occupants and Assembly will not apply.
Multiple Occupancy (6.1.14) N/A Most Restrictive Occupancy requirements in each building is utilized. (6.1.14.3.2) N/A Construction Type: Construction Type V (000) (8.2.1.2 ref NFPA 220 Chapter 11) Height and Area Limitations (IBC Chapter 5): Business 60 feet and 36,000 SF.
Actual Area: 14,557 SF
f. Means of Egress:
Components (38.2.2)- Doors 101A, 135A, 135B and 136A have card access and are part of the Means of Egress by being “fail-safe” where the doors unlock in direction of egress during fire alarm activation.
Occupant Loads (Table 7.3.1.2)
Business 14,186 SF / 100 142 occupants Mechanical 371 SF /500 1 occupant
Load and Capacity (7.3.1) 143 occ x .2 29 inches
4. Number of Exits: 2 Required, 3 Provided (38.2.4)
5. Dead-end Corridors: 50 feet (38.2.5.2.1)
6. Common Path of Travel: 100 feet (38.2.5.3.1)
7. Travel Discharge to Exits: 300 feet (38.2.6.3)
8. Exit Discharge: Exiting is directly to the outside to the finished ground level to a public way protected from the building. (7.7)
g. Protection of Vertical Openings: N/A
h. Protection of Hazardous Areas: Ordinary Hazard Classification (38.1.5)
i. Interior Finishes: Class A, B, or C <300 occupants. (10.2).
j. Fire and Smoke Detection, Alarm, and Notification: Provided
k. Automatic Sprinkler Systems: Provided per NFPA 13
l. Corridor Construction: Interior corridors protection not required if sprinklered.
m. Corridor Construction: Corridor Width: 44 inches serving 50 or more persons. (38.2.3.2).
n. Smoke Compartments and Smoke Barriers: N/A
o. Fire Resistant Rated Separations: N/A
p. Suites: N/A
SEMI RECESSED
FIRE EXTINGUISHER
CABINET. SEE SPECS
5/8" GWB BOTH SIDES
4" MAX. PER ADA
PREFINISHED
STL. TRIM
METAL STUD FRAMING
SOUND BATT
WHERE NOTED
RETURN GWB
GWB
R
EQ
U
IR
EM
EN
TS
C O N
FI
R M W
ID
TH
H T.
O
PE
N
IN
G
+54" A.F.F t
Z
TR
I
AR
Da
EC
ni g
UONA,
.A.S.
VERNON
ROSAMOND
ee S d:
ET
I AFIC
ON .R
EG
I S
TER
ED ARCH I TEC
T
RVI
HP S
NI
D
C E
I
A
A N
HE TL H SE
E
H
N M E
AR P
T
OF
T
C D
SU
S
A
E
TAE L &H
N
VI
S E R
UM
A
H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3 /2 2:
:1
PM
Au to de sk D oc s:
//2 1- W hi te riv er A dm in v /2 1- A rc h W R A dm in 2.
rv t
As indicated
G101
CODE SHEET
BD
dh
21-020 11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
1/8" 1'-0"A1 CODE FLOOR PLAN
1 1/2" 1'-0"B1 SEMI-RECESSED FIRE CAB.
KEYNOTES
Key # Keynote Text
10 41 SEMI-RECESSED FIRE EXTINGUISHER CABINET.
No. Date Description
(APPLY UNLESS NOTED OTHERWISE)
GENERAL STRUCTURAL NOTES
DESIGN CRITERIA:
2018 EDITION OF THE INTERNATIONAL BUILDING CODE, WITH LOCAL AMENDMENTS.
RISK CATEGORY II.
LOADS:
ROOF LIVE LOAD = 20 PSF (REDUCIBLE).
ROOF RAIN LOAD DESIGN DATA, i = 3 IN/HR.
GROUND SNOW LOAD = 10 PSF. FLAT ROOF SNOW LOAD Pf= 10 PSF. Ce = 1.0.
Is = 1.0. Ct = 1.0, Cs = 1.0, Pd = 10 PSF, WIND DESIGN: BASIC WIND SPEED(V) = 120 MPH (3 SECOND GUST). ALLOWABLE STRESS
DESIGN WIND SPEED (Vasd) = 93 MPH. EXPOSURE C.
SEISMIC DESIGN: Ie = 1.0. Ss = 1.249. S1 = 0.0177. SOIL SITE CLASS = D.
Sds = 0.265. SEISMIC DESIGN CATEGORY B. INTERMEDIATE REINFORCED
GENERAL:
1. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES
NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES
SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO
CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE
RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES
FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE
PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO THE SITE INCLUDE
INSPECTION OF THESE ITEMS). THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
2. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED
CONSTRUCTION. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
3. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS,
SUCH STANDARDS SHALL BE THE LATEST EDITION AND/OR ADDENDA.
4. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL,
MECHANICAL, PLUMBING, AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS,
AND SUBCONTRACTORS PRIOR TO CONSTRUCTION.
5. OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. IF AN OPTION IS CHOSEN, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CHANGES AND SHALL
COORDINATE ALL DETAILS WITH ALL TRADES.
6. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL
STRUCTURAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN,
CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. FOR BIDDING
PURPOSES, WHERE ANY MEMBER IS SHOWN BUT NOT CALLED OUT, THE LARGEST
SIMILAR MEMBER SHALL BE UTILIZED.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL
DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO START OF CONSTRUCTION.
RESOLVE ANY DISCREPANCY WITH THE ARCHITECT. DO NOT USE SCALED DIMENSIONS.
8. ALL DETAILS SHALL BE INCORPORATED INTO THE PROJECT AT ALL APPROPRIATE
LOCATIONS, WHETHER SPECIFICALLY CUT OR NOT. TYPICAL DETAILS MAY NOT
NECESSARILY BE CUT ON PLANS, BUT APPLY UNLESS NOTED OTHERWISE. FOR
CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF FRAMING CONDITION.
9. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL
STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL
GOVERN.
10. ANY ENGINEERING DESIGN, PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW,
SHALL BEAR THE SEAL OF AN ENGINEER REGISTERED IN THE STATE IN WHICH THE
PROJECT OCCURS.
FOUNDATIONS:
1. SOIL REPORT BY ATEK ENGINEERING CONSULTANTS; PROJECT NO. 200276.
SPREAD FOOTINGS SHALL BEAR ON CONTROLLED COMPACTED FILL 2'-0"
MINIMUM BELOW FINISHED GRADE. FINISHED GRADE IS DEFINED AS TOP OF SLAB
FOR INTERIOR FOOTINGS AND LOWEST ADJACENT GRADE WITHIN 5 FEET FOR
PERIMETER FOOTINGS. DESIGN SOIL BEARING VALUE =2000 PSF. FOUNDATION
EXCAVATIONS SHALL BE INSPECTED BY SOILS ENGINEER PRIOR TO PLACEMENT
OF CONCRETE.
2. REMOVE TOPSOIL, ORGANIC MATERIAL, AND DEBRIS FROM BUILDING TO THE
REQUIRED DEPTH PER SOILS REPORT.
3. FOOTING BEARING: ON 2'-0" OF COMPACTED STABILIZED SOIL AND SHALL EXTEND
2'-0" FROM ALL EDGES OF FOOTING (UNLESS OTHERWISE INSTRUCTED BY THE
GEOTECHNICAL ENGINEER).
4. CONCRETE SLABS ON GRADE: ON 4" OF CLEAN WASHED AGGREGATE AND A
MINIMUM OF 18" OF COMPACTED STABILIZED SOIL (UNLESS OTHERWISE NOTED
BY THE GEOTECHNICAL ENGINEER). OMIT 2" SAND AND VAPOR BARRIER AT SLABS
12" AND THICKER.
5. COMPACTION REQUIREMENTS (ASTM D1557):
BELOW FOOTINGS ----------- 95%
BELOW SLABS AND PAVEMENT --- 95%
UNPAVED AREAS ----------- 90%
MAXIMUM LIFT ------------- 6" LOOSE DEPTH
6. SUBGRADE: SCARIFY AND RECOMPACT TOP 8" OF SOIL.
7. BACKFILL: DO NOT PLACE AGAINST BASEMENT WALLS UNTIL FIRST FLOOR IS
PERMANENTLY ATTACHED. DO NOT EXCEED 1'-0" DIFFERENTIAL IN FILL LEVEL ON
OPPOSITE SIDES OF FOUNDATION WALLS.
8. DRAINAGE: PROVIDE POSITIVE SLOPES, BOTH DURING AND AFTER
CONSTRUCTION, FOR SURFACE AND ROOF RUNOFF. MINIMUM 10'-0" FROM
BUILDING FOUNDATIONS.
9. ALL EARTHWORK SHALL BE INSPECTED AND APPROVED BY THE GEOTECHNICAL
ENGINEER.
10. THE STRUCTURES SHALL ALSO BE PROTECTED AT THE BUILDING PERIMETER AND
ALONG LARGE CUTS BY FOUNDATION AND GROUNDWATER INCEPTION DRAINS,
DESIGNED TO REMOVE GROUNDWATER MOVING LATERALLY ACROSS THE SITE.
DRAINS MAY ALSO BE NEEDED FOR THE INTERIOR PORTIONS OF THE BUILDINGS
SHOULD EVIDENCE OF SEEPAGE OR OTHER HYDRAULIC ACTIVITY BE EXPOSED IN
THE SUBGRADE DURING SITE PREPARATION. INTERNAL DRAINS WILL BE
CONNECTED TO THE PERIMETER FOOTING DRAINS. THIS NEED SHALL BY
DETERMINED BY THE GEOTECHNICAL ENGINEER.
CONCRETE:
1. ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 301 AND
ACI 318. CEMENT SHALL CONFORM TO ASTM C150, TYPE II. AGGREGATE SHALL
CONFORMTO ASTM C33. CONCRETE SHALL BE READY MIXED IN ACCORDANCE
WITH ASTM C94 AND SHALL BE DESIGNED FOR A MINIMUM 28-DAY COMPRESSIVE
STRENGTH AS FOLLOWS:
SLABS ON GRADE ----------------------------------------------- 3,000 PSI
FOUNDATIONS ---------------------------------------------------- 3,000 PSI
2. FLY ASH - SHALL CONFORM TO ASTM C618, CLASS F AND SHALL BE LIMITED TO 25%
OF CEMENTITIOUS MATERIALS BY WEIGHT AND SHALL HAVE A REPLACEMENT FACTOR
OF 1.2 RELATIVE TO CEMENT REPLACED. CONCRETE SHALL BE FREE OF CHLORIDE.
MAXIMUM SLUMP 4 1/2" FOR CONCRETE WITHOUT PLASTICIZER. IF PLASTICIZER IS
USED, AN 8" MAXIMUM SLUMP IS ALLOWED AT PLACEMENT. ALL MIX DESIGNS SHALL BE
DESIGNED BY THE CONCRETE PRODUCTION FACILITY IN ACCORDANCE WITH ACI 301
AND SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER PRIOR TO PLACEMENT. MIX
DESIGNS FOR POST-TENSIONING CONCRETE SHALL BE PROPORTIONED SO AS TO
MINIMIZE SHRINKAGE CRACKING.
3. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT THAT SLABS ON
GRADE NEED BE VIBRATED ONLY AROUND UNDER-FLOOR DUCTS, ETC. DO NOT DROP
CONCRETE MORE THAN FIVE FEET WITH OUT THE USE OF TREMIES. REVIBRATE TOPS
OF CAISSONS 15 MINUTES AFTER PLACING CONCRETE. UNLESS APPROVED OTHERWISE
IN WRITING BY THE ARCHITECT, ALL CONCRETE SLABS ON GRADE SHALL BE BOUND BY
CONTROL JOINTS (KEYED OR SAW CUT), AS SHOWN ON THE FOUNDATION PLAN, SUCH
THAT THE ENCLOSED AREA DOES NOT EXCEED 225 SQUARE FEET. KEYED CONTROL
JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING POURING, ALL OTHER JOINTS
MAY BE SAW CUT. CAST CLOSURE POUR AROUND COLUMNS AFTER COLUMN DEAD LOAD
IS APPLIED.
4. PROVIDE SLEEVES FOR ALL UTILITY OPENINGS. DO NOT CUT ANY REINFORCING
AT OPENINGS. CONCRETE WHICH HAS CONTAINED WATER FOR MORE THAN 90 MINUTES
(60 MINUTES IF AIR TEMPERATURE EXCEEDS 85 DEGREES) SHALL NOT BE USED.
RETEMPERING OF CONCRETE AFTER INITIAL SET IS NOT ALLOWED. CURE EXPOSED
CONCRETE PER ACI 301 FOR A MINUMUM OF 7 DAYS.
5. TESTING OF COMPRESSIVE STRENGTH AND SLUMP SHALL CONFORM TO ASTM
C31, C39 AND C143. PROVIDE A MINIMUM OF 3 CYLINDERS FOR EACH DAY'S PLACEMENT
U.N.O. A QUALIFIED TESTING LABORATORY SHALL TEST ONE CYLINDER AT 7 DAYS AND
TWO CYLINDERS AT 28 DAYS, THREE CYLINDERS IF 4”X8” SAMPLES ARE USED.
6. MACRO FIBER - HIGH VOLUME SYNTHETIC FIBER MAY BE SUBSTITUTED AT A RATE
OF 4 POUNDS PER CUBIC YARD OF CONCRETE FOR WELDED WIRE FABRIC IN SLABS ON
GRADE AND SLABS ON METAL DECK. ACCEPTABLE PRODUCTS INCLUDE GRACE STRUX
90/40, PROPEX FIBERMESH 650, EUCLID TUF-STRAND SF, FORTA FERRO.
MASONRY:
1. C.M.U. SHALL CONFORM TO ASTM C90, NORMAL OR MEDIUM WEIGHT, F'm =2,000
PSI AT 28 DAYS, RUNNING BOND, WITH A NET COMPRESSIVE STRENGTH OF 2000
PSI PER ASTM C140.
2. MORTAR SHALL CONFORM TO ASTM C270, TYPE S, 2,000 PSI USING PORTLAND
CEMENT. FINE OR COURSE GROUT PER ASTM C476, 2,000 PSI AT 28 DAYS,
TESTED PER ASTM C1019. GROUT SHALL BE FREE OF CHLORIDE.
GROUT MAY CONTAIN UP TO 18% FLY ASH AT THE APPROVAL OF THE ARCHITECT.
3. SEE DRAWINGS FOR SIZE AND SPACING OF REINFORCING. LAP SPLICE ALL
REINFORCING A MINIMUM OF 40 BAR DIAMETERS FOR GRADE 40 BARS AND 48 BAR
DIAMETERS FOR GRADE 60 BARS. LAP SPLICES SHALL BE 1.3 X LAP LENGTH WHEN
ADJACENT SPLICES ARE SEPARATED BY 3" OR LESS. ALL REINFORCING SHALL BE
ACCURATELY LOCATED PRIOR TO AND DURING GROUTING. TIE ALL VERTICAL
REINFORCING AT 8'-0" VERTICALLY WITH SINGLE WIRE LOOP TIE BY A.A. WIRE
PRODUCTS COMPANY. DOWEL ALL VERTICAL REINFORCING TO FOUNDATION WITH
DOWELS TO MATCH SIZE AND SPACING OF VERTICAL REINFORCING. PROVIDE
BENT BARS TO MATCH HORIZONTAL BOND BEAM REINFORCING AT CORNERS AND
WALL INTERSECTIONS.
4. HORIZONTAL JOINT REINFORCING SHALL BE 9 GAGE LADDER OR TRUSS TYPE
JOINT REINFORCEMENT PER ASTM A82 AT 16" O.C. WITH 12" SPLICES. USE TRUSS
TYPE JOINT REINFORCEMENT IN BRICK OR COMPOSITE WALLS.
5. ALL CELLS AND COURSES WITH REINFORCING AND ADDITIONAL CELLS AND
COURSES NOTED ON DRAWINGS SHALL BE GROUTED SOLID. ALL MASONRY
BELOW FINISHED FLOOR OR GRADE SHALL BE GROUTED SOLID. MECHANICALLY
VIBRATE GROUT IN VERTICAL SPACES IMMEDIATELY AFTER POURING AND AGAIN
ABOUT 5 MINUTES LATER. PROVIDE CLEANOUTS IF GROUT POUR HEIGHT
EXCEEDS 5'-4" IN BLOCK WALLS. IF THE MASONRY HAS CURED FOR AT LEAST 4
HOURS, THE GROUT SLUMP IS MAINTAINED BETWEEN 10" AND 11", AND NO
INTERMEDIATE BOND BEAMS ARE PLACED BETWEEN THE TOP AND BOTTOM OF
THE POUR HEIGHT, THEN GROUT MAY BE PLACED IN LIFTS UP TO 12'-8" TALL. STOP
ALL GROUT LIFTS 1-1/2" BELOW THE TOP COURSE OF THE LIFT. PLACE GROUT
LIFTS CONTINUOUS FOR HEIGHT OF LINTELS. DO NOT INTERRUPT GROUTING FOR
MORE THAN ONE HOUR. FOG SPRAY ERECTED CMU EVERY 8 HOURS FOR 48
HOURS FOLLOWING INSTALLATION WHEN TEMPERATURES EXCEED 100 DEGREES
OR WHEN THE TEMPERATURE EXCEEDS 90 DEGREES AND THE WIND SPEED IS
GREATER THAN 8 MPH.
6. ADHERED VENEER SHALL WEIGH LESS THAN 15 PSF. ADHESION DEVELOPED
BETWEEN ADHERED VENEER UNITS AND BACKING SHALL HAVE A SHEAR
TRANSFER STRENGTH OF AT LEAST 50 PSI BASED ON GROSS UNIT SURFACE
AREA.
REINFORCING STEEL:
1. LATEST ACI CODE AND DETAILING MANUAL APPLY.
2. REINFORCING STEEL SHALL CONFORM TO ASTM A615 (Fy = 60 KSI) DEFORMED
BARS FOR ALL REBAR. ALL REINFORCING TO BE WELDED SHALL BE ASTM A706.
WELDED WIRE FABRIC PER ASTM A185, WIRE PER ASTM A82. NO TACK WELDING
OF REINFORCINGBARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH
THE STRUCTURAL ENGINEER.
3. ACCURATELY PLACE OR SUPPORT ALL REINFORCING, INCLUDING WELDED WIRE
FABRIC, WITH GALVANIZED METAL CHAIRS, SPACERS OR HANGERS FOR THE
FOLLOWING CLEAR CONCRETE COVERAGES:
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH --- 3"
EXPOSED TO EARTH OR WEATHER
#6 OR LARGER ----------------------------------------------------------------- 2” #5 AND SMALLER ------------------------------------------------------------- 1 1/2"
ALL OTHER PER LATEST EDITION OF ACI 318.
4. LAP SPLICES, UNLESS NOTED OTHERWISE, SHALL BE CLASS "B" TENSION LAP
SPLICES PER LATEST EDITION OF ACI 318. LAP SPLICES IN CONCRETE COLUMNS
SHALL BE STANDARD COMPRESSION LAP SPLICES. STAGGER SPLICES A MINIMUM
OF ONE LAP LENGTH. LAPS IN WELDED WIRE FABRIC SHALL BE MADE SO THAT
THE OVERLAP, MEASURED BETWEEN OUTERMOST CROSS WIRES OF EACH FABRIC
SHEET, IS NOT LESS THAN THE SPACING OF CROSS WIRES PLUS 2 INCHES.
5. ALL SPLICE LOCATIONS ARE SUBJECT TO APPROVAL BY THE STRUCTURAL
ENGINEER. SPLICED BARS SHALL BE PLACED AT THE SAME EFFECTIVE DEPTH
U.N.O. ALL REINFORCING NOTED AS "CONTINUOUS" SHALL BE FULLY CONTINUOUS
AND SPLICED. PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH
HORIZONTAL BARS AT ALL CORNERS AND INTERSECTIONS PER TYPICAL DETAILS.
6. REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL BARS PER
CRSI SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO
FOUNDATION WITH STANDARD 90 DEGREE HOOKS UNLESS NOTED OTHERWISE.
SKEW HOOKS AS REQUIRED TO MAINTAIN CONCRETE COVER. SECURELY TIE ALL
BARS IN LOCATION BEFORE PLACING CONCRETE. CONCRETE COLUMN DOWEL
EMBEDMENT SHALL BE A STANDARD COMPRESSION DOWEL WITH EMBEDMENT
LENGTH ACCORDING TO THE LATEST EDITION OF ACI 318.
STRUCTURAL STEEL:
1. ALL STEEL CONSTRUCTION SHALL CONFORM WITH THE LATEST AISC
HANDBOOK.ALL STRUCTURAL STEEL W SECTIONS SHALL BE ASTM A992 (Fy = 50 KSI). ALLRECTANGULAR HSS SHALL BE ASTM A500, GRADE B (Fy = 46 KSI). ALL ROUND HSSSHALL BE ASTM A500, GRADE B (Fy = 42 KSI). ALL PIPE STEEL SHALL BEASTM A53, GRADE B (Fy = 35 KSI). ALL OTHER STRUCTURAL SHAPES ANDPLATES SHALL BE ASTM A36 (Fy = 36 KSI). SHOP PAINT ALL STEEL SURFACES
WITHFABRICATOR'S STANDARD RUST-INHIBITING PRIMER EXCEPT AT SURFACES
ENCASEDIN CONCRETE, SURFACES TO RECEIVE FIREPROOFING, OR SURFACES
ENCLOSED WITHINTHE BUILDING FINISHES. BEAMS, COLUMNS AND BRACES SHALL
NOT BE SPLICEDWITHOUT THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER.
2. BOLTS SHALL BE ASTM A307, UNLESS NOTED OTHERWISE. ANCHOR BOLTS SHALL
BEASTM A36 OR A307, GRADE A. ANCHOR RODS SHALL BE ASTM F1554, GRADE
36.THREADED RODS SHALL BE ASTM A36.
3. ALL WELDING PER LATEST AMERICAN WELDING SOCIETY STANDARDS. ALL
WELDINGSHALL BE PERFORMED BY WELDERS HOLDING VALID CERTIFICATES AND
HAVING CURRENTEXPERIENCE IN THE TYPE OF WELD SHOWN ON THE DRAWINGS
OR NOTES. CERTIFICATESSHALL BE THOSE ISSUED BY AN ACCEPTED TESTING
AGENCY. ALL WELDING DONE BYE70 SERIES LOW HYDROGEN RODS UNLESS
NOTED OTHERWISE. FOR GRADE 60REINFORCING BARS, USE E80 SERIES. THESE
DRAWINGS DO NOT DISTINGUISH BETWEENSHOP AND FIELD WELDS; THE
CONTRACTOR MAY SHOP WELD OR FIELD WELD AT HISDISCRETION. SHOP WELDS
AND FIELD WELDS SHALL BE SHOWN ON THE SHOP DRAWINGSSUBMITTED FOR
REVIEW.
4. NON-SHRINK GROUT SHALL BE 5,000 PSI, FIVE STAR, SIKA 212 OR EQUIVALENT.
INSTALL NON-SHRINK GROUT UNDER BEARING PLATES BEFORE FRAMING MEMBER
IS INSTALLED. AT COLUMNS, INSTALL NON-SHRINK GROUT UNDER BASEPLATES
AFTER COLUMN HAS BEEN PLUMBED BUT PRIOR TO FLOOR OR ROOF
INSTALLATION.
LOW VELOCITY POWDER ACTUATED FASTENERS (P.A.F.):
1. LOW VELOCITY P.A.F. SHALL BE SIMPSON PDPAWL FASTENERS WITH A MINIMUM
SHANK DIAMETER OF .157" INSTALLED AND COMPLYING WITH ICC ES REPORT NO.
2138.
POST-INSTALLED ANCHORS:
1. EPOXY BOLTS OR DOWELS SHALL BE A THREADED ROD OR REINFORCING STEEL
INSTALLED WITH THE ONE OF THE FOLLOWING APPROVED PRODUCTS SATISFYING
CRACKED CONCRETE REQUIREMENTS IN ACCORDANCE WITH ACI APPENDIX D.
SIMPSON "SET-3G" ICC REPORT ESR-4057
DEWALT "PURE110+" ICC REPORT ESR-3298
DEWALT “AC200+” ICC REPORT ESR-4027
2. EXPANSION BOLTS FOR CONCRETE SHALL BE ONE OF THE FOLLOWING APPROVED
PRODUCTS SATISFYING CRACKED CONCRETE REQUIREMENTS IN ACCORDANCE WITH
ACI APPENDIX D.
HILTI "KWIK BOLT TZ" ICC REPORT ESR-1917
HILTI "HDA UNDERCUT ANCHOR" ICC REPORT ESR-1546
HILTI "HSL-3 HD EXPANSION ANCHOR" ICC REPORT ESR-1545
SIMPSON "STRONG BOLT 2 WEDGE ANCHOR" ICC REPORT ESR-3037
SIMPSON "TORQ-CUT" ICC REPORT ESR-2705
DEWALT “POWER-STUD+SD1 WEDGE ANCHOR” ICC REPORT ESR-2818
DEWALT “POWER-STUD+SD2 WEDGE ANCHOR” ICC REPORT ESR-2502
DEWALT “ATOMIC+UNDERCUT ANCHOR” ICC REPORT ESR-3067
DEWALT “POWER-BOLT+ EXPANSION ANCHOR” ICC REPORT ESR-3260
3. SCREW BOLTS FOR CONCRETE SHALL BE ONE OF THE FOLLOWING APPROVED
PRODUCTS SATISFYING CRACKED CONCRETE REQUIREMENTS IN ACCORDANCE
WITH ACI APPENDIX D.
SIMPSON "TITEN HD" ICC REPORT ESR-2713
DEWALT “SCREW-BOLT+” ICC REPORT ESR-3889
4. THE CONTRACTOR MAY NOT USE SUBSTITUTES FOR EPOXY OR EXPANSION
ANCHORS WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER.
5. FOR MINIMUM EMBEDMENT LENGTH SEE DETAILS. INSTALL ALL BOLTS AS
OUTLINED IN MANUFACTURER'S SPECIFICATIONS, UTILIZING PROPER SIZE AND
TYPE OF DRILL, CLEANING HOLE, DRIVING AND TIGHTENING BOLT.
6. SPECIAL INSPECTION OF ALL POST-INSTALLED ANCHORS IS REQUIRED.
ROUGH CARPENTRY AND WOOD STRUCTURAL PANELS:
1. ALL FRAMING PER IBC CHAPTER 23. FRAMING LUMBER SHALL COMPLY WITH THE
2015 EDITION OF THE NATIONAL DESIGN SPECIFICATION. MAXIMUM MOISTURE
CONTENT SHALLNOT EXCEED 19%. ALL SAWN LUMBER SHALL BE STAMPED WITH
THE GRADE MARK OF ANAPPROVED LUMBER GRADING AGENCY. ALL SAWN
LUMBER SHALL BE DOUGLAS FIR-LARCHWITH THE FOLLOWING MINIMUM
PROPERTIES:
WOOD TYPE
JOISTS 2 X 4 --------------------- D.F. #2
2 X 6 OR LARGER ------------- D.F. #2
BEAMS, LEDGERS AND TOP PLATES
WIDTH 4" OR LESS ------------- D.F. #2
WIDTH GREATER THAN 4" --------- D.F. #1
STUDS, PLATES AND BLOCKING
2 X 4 --------------------- D.F. #2
2 X 6 OR LARGER ------------- D.F. #2
POSTS
4 X 4 --------------------- D.F. #2
4 X 6 OR LARGER ------------- D.F. #2
6 X 6 OR LARGER ------------- D.F. #1
2. ALL WOOD STRUCTURAL PANELS SHALL CONFORM TO DOC PS-1 OR PS-2
STANDARDS,SHALL HAVE AN EXTERIOR OR EXPOSURE 1 CLASSIFICATION AND
SHALL BEAR THESTAMP OF AN APPROVED TESTING AGENCY. WHERE PLYWOOD
IS USED, LAY UP PLYWOODWITH FACE GRAIN PERPENDICULAR TO SUPPORTS AND
STAGGER JOINTS. ON ROOFS WHERE PLYWOOD IS LAID UP WITH FACE GRAIN
PARALLEL TO SUPPORTS, USE A MINIMUMOF 5-PLY PLYWOOD. AT SHEARWALLS,
PROVIDE 2X BLOCKING AT ALL UNSUPPORTED EDGES. ALL NAILING, COMMON
NAILS. WHERE SCREWS ARE INDICATED FOR WOOD TO WOOD ATTACHMENTS,
USE WOOD SCREWS. ALL WOOD STRUCTURAL PANELS SHALL BE OF THE
FOLLOWING NOMINAL THICKNESS, SPAN/INDEX RATIO AND SHALL BE ATTACHED
ASFOLLOWS UNLESS NOTED OTHERWISE:
SPAN/INDEX EDGE INTERMEDIATE
USE THICKNESS RATIO ATTACHMENT ATTACHMENT
ROOF 1/2" 32/16 8d AT 6" O.C. 8d AT 12" O.C.
SHEAR 3/8" 24/0 8d @ 6" O.C. 8d @ 12" O.C.
WALL U.N.O. U.N.O.
3. DO NOT NOTCH, DRILL OR SPLICE JOISTS, BEAMS OR LOAD BEARING STUDS
WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER THRU THE
ARCHITECT. DOUBLE UPFLOOR JOISTS AND BLOCKING UNDER PARTITIONS.
DOUBLE UP JOISTS BELOWMECHANICAL EQUIPMENT. PROVIDE 2" SOLID BLOCKING
AT MIDSPAN AND AT SUPPORTSOF ALL JOISTS.
4. STUD WALLS SHALL BE 2 X 6 AT 16" O.C. U.N.O. ON PLANS. BOTTOM PLATE
ANCHORSAT CONCRETE FOUNDATIONS SHALL BE SIMPSON MASA CLIPS AT 6'-0"
O.C. MAXIMUM U.N.O. ANCHORS SHALL BE PLACED AT ALL JAMBS,
CORNERS,INTERSECTIONS AND ENDS OF WALLS. ALL LUMBER ON CONCRETE OR
MASONRYFOUNDATIONS SHALL BE PRESSURE TREATED WOOD STAMPED BY AN
APPROVED AGENCY.
5. DOUBLE UP STUDS AT JAMBS AND AS REQUIRED UNDER BEAMS IN BEARING
WALLS.EVERY OTHER STUD OF WOOD FRAME BEARING WALL SHALL HAVE A
SIMPSON H3 ANCHORTOP AND BOTTOM, EXCEPT AT THOSE WALLS WHERE
PLYWOOD SHEATHING IS NAILEDDIRECTLY TO THE TOP AND BOTTOM PLATES.
PROVIDE 2 X SOLID BLOCKING AT MID-HEIGHT OF BEARING STUD WALLS.
6. ALL NAILING NOT NOTED SHALL BE ACCORDING TO TABLE 2304.9.1 OF THE
INTERNATIONAL BUILDING CODE. ALL NAILS SHALL BE WITH COMMON NAILS.
WOOD CONNECTORS SHALL BE AS MANUFACTURED BY SIMPSON STRONG-TIE
COMPANY, INC. OROTHER MANUFACTURER WITH CURRENT AND EQUIVALENT
I.C.B.O. APPROVAL. ALL NAILHOLES IN CONNECTORS SHALL BE FILLED WITH NAIL
OF THE LARGEST SIZE INDICATEDIN THE MANUFACTURER'S CATALOG U.N.O.
7. ALL FABRICATION SHALL BE PERFORMED ON THE PREMISES OF A
FABRICATORREGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT
SPECIAL INSPECTION.
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
CREATING ELEGANT SOLUTIONS
STRUCTURAL ENGINEERS
SCHNEIDER
435 East 9th Street | Tucson, AZ 85705 | 520.512.8183 | www.sastructural.com
121083Project Number:
UNLESS THIS DRAWING IS SIGNED AND SEALED BY A LICENSED STRUCTURAL ENGINEER, IT IS A
PRELIMINARY DESIGN AND SHALL NOT BE USED FOR CONSTRUCTION.
As Indicated
/1 /2
:0 :0
A
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
S tr c W
R A d m in
.r v t
S101
G.S.N.
DNG
SRK
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
No. Date Description
/01
/22
Th is
E le ct ro ni c
Si gn at ur e H as B ee n
Au th or iz ed B y M e Th is N ov em be r 0
1, GLUED-LAMINATED BEAMS (GLULAM):
1. GLUED-LAMINATED BEAMS SHALL BE DOUGLAS FIR LARCH WITH THE FOLLOWING
MINIMUM PROPERTIES: Fb = 2,400 PSI, Fv = 265 PSI, Fc (PERPENDICULAR) = 650 PSI, E = 1,800,000 PSI. BEAMS CANTILEVERING OVER SUPPORTS SHALL HAVE THE
SPECIFIED MINIMUM PROPERTIES TOP AND BOTTOM.
2. CAMBER AS SHOWN ON DRAWINGS. IF NO CAMBER IS SPECIFIED, PROVIDE
STANDARD CAMBER USING A RADIUS OF 3500 FEET.
3. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE. FABRICATION
AND HANDLING PER LATEST AITC AND WCLA STANDARDS. BEAMS SHALL BEAR
GRADE STAMP AND AITC STAMP AND CERTIFICATE. APPEARANCE GRADE BEAMS
SHALL BE USED IF INDICATED ON ARCHITECTURAL DRAWINGS.
PREFABRICATED WOOD TRUSSES:
1. THE TRUSS MANUFACTURER SHALL BE RESPONSIBLE FOR THE COMPLETE
DESIGN, FABRICATION AND ERECTION PROCEDURES OF ALL TRUSSES, BRIDGING
AND/OR BLOCKING PANELS, HANGERS, BRACING, ETC. FOR A COMPLETE
INSTALLATION OF THE TRUSSSYSTEM. TRUSS CONFIGURATIONS ARE AS SHOWN
ON THE DRAWINGS. ALL BRACING ANDBRIDGING SIZES AND SPACINGS BY TRUSS
MANUFACTURER IN ACCORDANCE WITH THELATEST RECOMMENDATIONS OF THE
TRUSS PLATE INSTITUTE.
2. TRUSSES SHALL BE DESIGNED AND FABRICATED IN ACCORDANCE WITH IBC
CHAPTER 23TO SUPPORT SELF WEIGHT PLUS LIVE LOAD, SUPERIMPOSED DEAD
LOADS, AND LATERALLOADS STATED IN THE GENERAL STRUCTURAL NOTES OR
LOCATED ON PLANS. ROOF TRUSSESSHALL BE DESIGNED TO ACCOMMODATE A
FUTURE MECHANICAL LOAD OF 300 POUNDS ATANY LOCATION. THE UNIFORM
LOADS DO NOT INCLUDE SPECIAL OR ADDITIONAL LOADSNOTED ON THE PLANS OR
DETAILS. THE ROOF LOAD DURATION FACTOR IS 1.25.
3. FOR ROOF TRUSSES, LIMIT TOTAL LOAD DEFLECTIONS TO SPAN/240 AT SIMPLE
SPANS U.N.O. LIMIT LIVE LOAD DEFLECTIONS TO SPAN/360 AT SIMPLE SPANS
U.N.O.
4. ADDITIONAL TRUSSES SHALL BE SUPPLIED AS REQUIRED TO SUPPORT
MECHANICAL EQUIPMENT.
5. ALL CONNECTORS SHALL HAVE CURRENT ICC APPROVAL. ALL TRUSS TO TRUSS
CONNECTORS SHALL BE DESIGNED BY THE TRUSS MANUFACTURER. MULTIPLE
TRUSSMEMBERS SHALL BE FASTENED TOGETHER TO ALLOW TRANSFER OF
SHEAR AND TENSIONFORCES (MINIMUM 200 PLF) AT PLYWOOD SHEATHING JOINTS
AND TO PREVENT CROSSGRAIN BENDING OF TOP CHORDS. ATTACHMENT SHALL
BE A CONTINUOUS 20 GAGE METALPLATE OR OTHER APPROVED MEANS. METHOD
OF ATTACHMENT SHALL BE INDICATED ONSHOP DRAWINGS FOR REVIEW.
6. TRUSS MEMBER PERMANENT BRACING. WHERE PERMANENT BRACING OF TRUSS
MEMBERSIS REQUIRED ON THE TRUSS DESIGN DRAWINGS, IT SHALL BE
ACCOMPLISHED BY THE FOLLOWING METHOD: THE TRUSSES SHALL BE DESIGNED
SO THAT THE BUCKLING OF ANY INDIVIDUAL TRUSS MEMBER CAN BE RESISTED
INTERNALLY BY THE STRUCTURE (E.G. BUCKLING MEMBER T-BRACING, L-BRACING,
ETC.) OF THE INDIVIDUAL TRUSS. THE TRUSS INDIVIDUAL MEMBER BUCKLING
REINFORCEMENT SHALL BE INSTALLED AS SHOWN ON THE TRUSS DESIGN
DRAWING OR ON SUPPLEMENTAL TRUSS MEMBER BUCKLING REINFORCEMENT
DIAGRAMS PROVIDED BY THE TRUSS DESIGNER.
7. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, ERECTION DRAWINGS AND
DESIGN CALCULATIONS SEALED BY A REGISTERED ENGINEER FOR REVIEW PRIOR
TOMANUFACTURE. CALCULATIONS AND SHOP DRAWINGS SHALL SHOW ANY
SPECIAL DETAILSREQUIRED AT BEARING POINTS.
8. ALL FABRICATION SHALL BE PERFORMED ON THE PREMISES OF A
FABRICATORREGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT
SPECIAL INSPECTION.
SHOP DRAWINGS AND PRODUCT DATA SUBMITTALS:
1. SUBMIT SHOP DRAWINGS AND/OR PRODUCT DATA FOR ALL ITEMS DEFINED BY THE
STRUCTURAL DRAWINGS AND SPECIFICATIONS, AS WELL AS STRUCTURAL ITEMS
DEFINED BY THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS, PRIOR TO
FABRICATION AND/OR CONSTRUCTION IN THE FIELD.
2. PROVIDE SUBMITTALS IN A TIMELY MANNER TO ALLOW FIVE WORKING DAYS FOR
THE ENGINEER'S REVIEW. FOR HARD COPY SUBMITTALS, PROVIDE NO MORE THAN
FOUR SETS FOR REVIEW (ONE COPY TO BE RETAINED BY THE ENGINEER). FOR
ELECTRONIC SUBMITTALS, PROVIDE PDF FILES ONLY. ALL SUBMITTALS WITH A
REQUESTED REVIEW TIME OF LESS THAN FIVE WORKING DAYS MAY BE RETURNED
WITHOUT REVIEW AT THE ENGINEER’S DISCRETION.
3. CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE AS SHOP
DRAWINGS. THE MANUFACTURER OR FABRICATOR SHALL CLOUD ANY CHANGES,
SUBSTITUTIONS, AND/OR DEVIATIONS FROM THE CONTRACT DOCUMENTS. ANY
CHANGES, SUBSTITUTIONS, AND/OR DEVIATIONS THAT ARE NOT CLOUDED OR
FLAGGED SHALL NOT BE CONSIDERED ALLOWED AFTER THE ENGINEER'S REVIEW,
UNLESS NOTED ACCORDINGLY BY THE ENGINEER.
4. THE CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL TO
THE ENGINEER. CLEARLY INDICATE ITEMS NOT IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. VERIFY DIMENSIONS WITH THE ARCHITECT.
5. THE ENGINEER'S REVIEW IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN
OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR CORRECTNESS AND
COMPLETENESS SHALL REST WITH THE CONTRACTOR. SHOP DRAWINGS WILL BE
RETURNED FOR RESUBMITTAL IF SIGNIFICANT ERRORS ARE FOUND DURING
REVIEW
6. THE SHOP DRAWINGS DO NOT REPLACE THE CONTRACT DOCUMENTS. SHOP
DRAWINGS PROCESSED BY THE ENGINEER SHALL NOT BE CONSIDERED CHANGE
ORDERS. ITEMS THAT ARE OMITTED OR SHOWN INCORRECTLY AND THAT ARE NOT
FLAGGED BY THE ENGINEER ARE NOT TO BE CONSIDERED CHANGES TO
CONTRACT DOCUMENTS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
CONSTRUCT ITEMS ACCORDING TO THE CONTRACT DOCUMENTS. SHOULD A
DISCREPANCY EXIST BETWEEN THE PROCESSED SHOP DRAWINGS AND THE
CONTRACT DOCUMENTS, THE CONTRACT DOCUMENTS SHALL GOVERN.
7. THE ENGINEER RESERVES THE RIGHT TO MAKE CHANGES TO THE CONTRACT
DOCUMENTS, AT ANY TIME BEFORE OR AFTER SHOP DRAWING REVIEW.
8. THE ADEQUACY OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY OTHERS
RESTS WITH THE DESIGNING OR SUBMITTING PARTY.
DEFERRED SUBMITTALS (PER 2018 IBC 107.3.4.1):
1. FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
APPLICATION AND WHICH ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
WITHIN A SPECIFIED PERIOD.
2. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE PRIOR APPROVAL OF THE
BUILDING OFFICIAL. THE ARCHITECT OR ENGINEER OF RECORD SHALL LIST THE
DEFERRED SUBMITTALS ON THE PLANS AND THE CONTRACTOR SHALL SUBMIT
THE DEFERRED SUBMITTAL DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
3. SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED
TO THE ARCHITECT OR ENGINEER OF RECORD A MINIMUM OF 30 DAYS PRIOR TO
FABRICATION. THE DOCUMENTS SHALL BE REVIEWED FOR GENERAL
CONFORMANCE WITH THE DRAWINGS. A COPY OF THE DEFERRED SUBMITTAL
DOCUMENTS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL WITH A NOTATION
INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED.
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN
AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
DEFERRED SUBMITTAL ITEMS:
WOOD TRUSSES
SPECIAL INSPECTIONS AND TESTING:
1. THE OWNER (OR REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
ACTINGAS THE OWNER'S AGENT) SHALL EMPLOY ONE OR MORE SPECIAL
INSPECTORS TOPROVIDE INSPECTION AND TESTING DURING CONSTRUCTION OF
THE TYPES OF WORKREQUIRING SPECIAL INSPECTION AS INDICATED ON THE
DRAWINGS.
2. EACH SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL
DEMONSTRATECOMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL
AND STRUCTURALENGINEER OF RECORD, FOR INSPECTION OF THE PARTICULAR
TYPE OF CONSTRUCTIONOR OPERATION REQUIRING SPECIAL INSPECTION.
3. THE CONTRACTOR SHALL CONVENE A MEETING WITH THE SPECIAL INSPECTION
AGENCY(AGENCIES), THE BUILDING OFFICIAL, THE ARCHITECT, AND THE
STRUCTURAL ENGINEEROF RECORD TO REVIEW INSPECTION REQUIREMENTS AND
PROCEDURES, PRIOR TOCOMMENCING WITH CONSTRUCTION.
4. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR:
A. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR
CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS.B) THE
SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE
BUILDING OFFICIAL, AND TO THE ENGINEER OR ARCHITECT OF RECORD.
REPORTS SHALL INDICATE THAT WORK INSPECTED WAS DONE IN
CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS.
DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, TO THE
ENGINEER OR ARCHITECT OF RECORD AND THE BUILDING OFFICIAL. IT IS
EXPECTED THAT REPORTS WILL BE SUBMITTED ON A WEEKLY BASIS AT A
MINIMUM.C) UPON COMPLETION OF THE ASSIGNED WORK, THE SPECIAL
INSPECTOR SHALL COMPLETE AND SIGN THE APPROPRIATE FORMS
CERTIFYING THAT, TO THE BEST OF HIS KNOWLEDGE, THE WORK IS IN
CONFORMANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS, AND
THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE.
ABBREVIATIONS
A.B.C.
A.F.F.
ALT
A.B.
B.F.F.
B.O.B.
B.O.D.
B.O.F.
B.O.S.
BOT
BRG
C.I.P.
C.F.S.
C.L.
CLR
CONC.
CONC. C.J.
C.M.U.
CONN.
CONT.
D.L.
DIA.
DN
DWG (S)
(E) E.F.
E.O.S.
EQ
EQUIP.
EXP. BOLT
E.J.
E.W.
FDN
F.F.E.
GA
GALV
G.S.N.
GLB (GLULAM)
HORIZ.
I.B.C.
I.C.C.
I.C.F.
K (KIP)
L.L.
LBS
L.L.H.
L.L.V.
MFR ('S)
M.C.J.
MECH.
(N) N/A N.I.C.
N.F.S.
N.T.
O.C.
OPP
P.A.F.
P.C.
PCF
PLF
PREFAB
P.S.F.
P.S.I.
REINF.
SCH
SIM
S.I.P.
S.L.R.S.
SP
STD
T&B T.L.
T.O.B.
T.O.C.
T.O.D.
T.O.F.
T.O.L.
T.O.M.
T.O.PL.
T.O.S.
T.O.W.
TYP
U.N.O.
VERT.
W.S.P.
W.W.F.
W/ (W/O)
AGGREGATE BASE COURSE
ABOVE FINISHED FLOOR
ALTERNATE
ANCHOR BOLT
BELOW FINISHED FLOOR
BOTTOM OF BEAM
BOTTOM OF DECK
BOTTOM OF FOOTING
BOTTOM OF STEEL
BOTTOM
BEARING
CAST IN PLACE
COLD FORMED STEEL
CENTERLINE
CLEAR
CONCRETE
CONCRETE CONTROL JOINT
CONCRETE MASONRY UNIT
CONNECTION
CONTINUOUS
DEAD LOAD
DIAMETER
DOWN
DRAWING(S)
EXISTING
EACH FACE
EDGE OF SLAB
EQUAL
EQUIPMENT
EXPANSION BOLT
EXPANSION JOINT
EACH WAY
FOUNDATION
FINISHED FLOOR ELEVATION
GAGE
GALVANIZED
GENERAL STRUCTURAL NOTES
GLUED-LAMINATED BEAM
HORIZONTAL
INTERNATIONAL BUILDING CODE
INTERNATIONAL CODE COUNCIL
INSULATED CONCRETE FORM
1000 POUNDS
LIVE LOAD
POUNDS
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MANUFACTURER('S)
MASONRY CONTROL JOINT
MECHANICAL
NEW
NOT APPLICABLE
NOT IN CONTRACT
NON-FROST SUSCEPTIBLE
NOT TO SCALE
ON CENTER
OPPOSITE (MIRRORED)
POWDER ACTUATED FASTENER
PRECAST CONCRETE
POUNDS PER CUBIC FOOT
POUNDS PER LINEAR FOOT
PREFABRICATED
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
REINFORCING
SCHEDULE
SIMILAR
STRUCTURAL INSULATED PANEL
SEISMIC LOAD RESISTING SYSTEM
SPACES
STANDARD
TOP AND BOTTOM
TOTAL LOAD
TOP OF BEAM
TOP OF CONCRETE
TOP OF DECK
TOP OF FOOTING
TOP OF LEDGER
TOP OF MASONRY
TOP OF PLATE
TOP OF STEEL
TOP OF WALL
TYPICAL
UNLESS NOTED OTHERWISE.
VERTICAL
WOOD STRUCTURAL PANEL
WELDED WIRE FABRIC
WITH (WITHOUT)
PLAN LEGEND
SW
SYMBOL DESCRIPTION REMARKS
DETAIL CUTS ON PLANS
KEYNOTE
8" MASONRY WALL U.N.O.
CONCRETE WALL U.N.O.
SHEAR WALL
SLAB DEPRESSION/
CHANGE IN ELEVATION
REVISION SYMBOL
OPENING
MECHANICAL EQUIPMENT
SEE PLANS FOR LOCATION, SIZE AND
TYPE
VERIFY DEPTH WITH ARCHITECTURAL
DRAWINGS
HOLDOWN ANCHOR
SEE PLANS AND SCHEDULES FOR
SIZE AND LOCATIONS
RIGID (MOMENT) CONNECTION
STEEL STUD WALL U.N.O.
WOOD STUD WALL U.N.O. SEE PLANS AND SCHEDULES FOR SIZE
SEE PLANS AND SCHEDULES FOR SIZE
MASONRY CONTROL JOINT
12" MASONRY WALL U.N.O.
INTERPRETATION OF DRAWINGS
SEE PLANS AND SCHEDULES FOR SIZE
AND REINFORCING
VERIFY SIZE AND LOCATION WITH
ARCHITECTURAL AND/OR MECHANICAL
DRAWINGS
M.C.J.
H
FOUNDATION DETAILS ARE 100
SERIES NUMBERS.
FRAMING DETAILS ARE 200 SERIES
NUMBERS.
BRACED FRAME DETAILS ARE 300
SERIES NUMBERS.
STAIR FRAMING DETAILS ARE 400
SERIES NUMBERS.
SEE PLANS FOR LOCATION. IF NO
SYMBOL INDICATED, SINGLE ROW OF
BOLTS OCCURS
NUMBER OF ROWS OF BOLTS
AT BEAM TO COLUMN OR
BEAM TO BEAM CONNECTION
CIRCULAR OR RECTANGULAR
OPENING IN BEAM WEB (SIZE)
SEE TYPICAL DETAIL U.N.O.
(-2 1/2")
TOP OF STEEL ELEVATION
RELATIVE TO BOTTOM OF
DECK ELEVATION
(15")
POINT OF SUPPORT/SHORING
SIMPLE BEAM SPLICE
CONNECTION
SEE PLANS AND SCHEDULES FOR SIZE
AND REINFORCING
SEE PLANS AND SCHEDULES FOR SIZE
AND REINFORCING
SEE PLANS FOR LOCATION
ELEVATION TARGET
QUANTITY OF HEADED STUDS
ON COMPOSITE STEEL BEAM
SEE G.S.N. AND TYPICAL DETAILS FOR
PLACEMENT
(24)
100'-0"
DIRECTION OF SLOPE
VERIFY DEPTH WITH ARCHITECTURAL
AND/OR MECHANICAL DRAWINGS
DROPPED BEAM
FLUSH BEAM
B (D)
B (F)
(15") c=1/2" BEAM CAMBER
BRACED FRAME MEMBERS SEE PLANS FOR LOCATION
PANEL JOINT SEE PLANS FOR LOCATION
P.J.
CONTROL JOINT SEE PLANS FOR LOCATIONC.J.
TWO-SIDED SHEAR WALL
SEE PLANS FOR LOCATION, SIZE AND
TYPE
SW
SW
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
CREATING ELEGANT SOLUTIONS
STRUCTURAL ENGINEERS
SCHNEIDER
435 East 9th Street | Tucson, AZ 85705 | 520.512.8183 | www.sastructural.com
121083Project Number:
UNLESS THIS DRAWING IS SIGNED AND SEALED BY A LICENSED STRUCTURAL ENGINEER, IT IS A
PRELIMINARY DESIGN AND SHALL NOT BE USED FOR CONSTRUCTION.
As Indicated
/1 /2
:0 :0
A
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
S tr c W
R A d m in
.r v t
S102
G.S.N. AND I.O.D.
DNG
SRK
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
No. Date Description
/01
/22
Th is
E le ct ro ni c
Si gn at ur e H as B ee n
Au th or iz ed B y M e Th is N ov em be r 0
1, VERIFY MATERIALS BELOW SHALLOW
1705.6
GEOTECHNICAL
REPORT
x
BY THE GEOTECHNICAL ENGINEER
FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING
SYSTEM OR MATERIAL
INSPECTION
REMARKSIBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCY
CONTINUOUS PERIODIC
x
CAPACITY
VERIFY ExCAVATIONS ARE ExTENDED
TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL
PERFORM CLASSIFICATION AND
TESTING OF COMPACTED
FILL MATERIAL
VERIFY USE OF PROPER MATERIALS,
DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL
PRIOR TO PLACEMENT OF
COMPACTED FILL, INSPECT
SUBGRADE AND VERIFY THAT SITE
HAS BEEN PREPARED PROPERLY
x x x
NO CONCRETE SPECIAL INSPECTIONS ARE REQUIRED. CONCRETE TESTING IS REQUIRED, REFERENCE REQUIRED TESTING TABLE 3.
SYSTEM OR MATERIAL
INSPECTION
REMARKSIBC CODE CODE OR STANDARD FREQUENCY
REFERENCE CONTINUOUS PERIODICREFERENCE
FABRICATED SYSTEMS AND ELEMENTS 1704.2 x
SPECIAL INSPECTIONS APPLY TO VERIFICATION OF
DETAILED FABRICATION AND QUALITY CONTROL
PROCEDURES, INCLUDING REVIEW FOR
CODE REQUIREMENTS. SPECIAL INSPECTIONS ARE
NOT REQUIRED FOR WORK DONE ON THE PREMISES
OF A FABRICATOR REGISTERED AND APPROVED TO
PERFORM SUCH WORK WITHOUT SPECIAL
COMPLETENESS AND ADEQUACY RELATIVE TO THE
INSPECTION. APPROVED FABRICATORS, UPON
COMPLETION OF COMPONENT MANUFACTURING,
SHALL SUBMIT A CERTIFICATE OF COMPLIANCE
TO THE BUILDING OFFICIAL STATING THAT THE WORK
WAS PERFORMED IN ACCORDANCE WITH THE
APPROVED CONSTRUCTION DOCUMENTS.
INSTALLATION IN HARDENED
CONCRETE AND COMPLETED
MASONRY
1703.4.2 1704.13.3
ICC EVALUATION
REPORT
SPECIAL INSPECTIONS APPLY TO ANCHOR PRODUCT
NAME, TYPE, AND DIMENSIONS, HOLE DIMENSIONS,
COMPLIANCE WITH DRILL BIT REQUIREMENTS,
CLEANLINESS OF THE HOLE AND ANCHOR, ADHESIVE
ExPIRATION DATE, ANCHOR/ADHESIVE INSTALLATION, ANCHOR EMBEDMENT, AND TIGHTENING TORQUE x
REFERENCE CONTINUOUS PERIODIC
FILL IN-PLACE DENSITY OR
PREPARED SUBGRADE DENSITY
1705.6
VARIES; MINIMUM PER
IBC APPENDIx J107.5 x BY THE GEOTECHNICAL ENGINEER
MATERIAL VERIFICATION
VARIES;
CLASSIFICATION AND
TESTING OF
CONTROLLED FILL
MATERIALS
x BY THE GEOTECHNICAL ENGINEER
CONCRETE STRENGTH
1704.4
ASTM C39
EACH 150 CY NOT LESS
THAN ONE TEST EACH
5000 SF OF SLAB OR
FABRICATE SPECIMENS AT TIME FRESH
CONCRETE IS PLACED
CONCRETE SLUMP ASTM C143
CONCRETE AIR CONTENT ASTM C231
CONCRETE TEMPERATURE ASTM C1064
1905.6
WALL PLACED EACH DAY
REFERENCE
SYSTEM OR MATERIAL
INSPECTION
REMARKSIBC CODE CODE OR STANDARD FREQUENCY
1. SOILS
TABLE 1: REQUIRED GEOTECHNICAL SPECIAL INSPECTIONS
2. CONCRETE
TABLE 2: REQUIRED STRUCTURAL SPECIAL INSPECTIONS
1. FABRICATORS
3. POST-INSTALLED ANCHORS
TABLE 3: REQUIRED TESTING FOR SPECIAL INSPECTIONS
1. GEOTECHNICAL
2. CONCRETE
890-IBC18
891.4A
894-IBC18
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
CREATING ELEGANT SOLUTIONS
STRUCTURAL…