This solicitation notice seeks proposals for a construction project to build a new 14,557 square foot administration office building at the Whiteriver Indian Hospital campus in Whiteriver, Arizona. The scope of work includes structure demolition, site work, exterior improvements, site utilities, and architectural, structural, mechanical, electrical and low-voltage systems. The period of performance is 335 calendar days from notice to proceed. The construction magnitude is estimated between $5,000,000 to $10,000,000. A site visit is scheduled and offerors must register in the System for Award Management database. The Indian Health Service intends to award a firm fixed price contract through a request for proposal process evaluated with lowest price technically acceptable criteria.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P a g e 1 | 1
JOHNSON SMITTHIPONG & ROSAMOND ASSOCIATES, INC.
5210 E Williams Circle, Suite 600 Tucson, AZ 85711 v:520.547.7904 f:520.547.7905 www.jsrarchinc.com
May 31, 2023
ADDENDUM No. 1 Addendum Letter: AD1
For Bids Due on June 15, 2023
Project Name: Whiteriver Admin Office Building
Project Number: 21-020
This addendum forms a part of the Contract Documents and modifies the original Bid Package dated 11/03/22. The following changes, additions, and deletions shall be made to the following documents: all other conditions shall remain the same.
Instruction to Bidders:
Updates to Bid Submittals:
1. N/A
Addendum To The Drawings:
2. Remove “SHEETS G001, C001, C100, C200, C300, C400, C401, C602, S203, A101, A102, P121, P131, E102, E103, E601, E701” from set and substitute with attached “SHEETS G001, C001, C100, C200, C300, C400, C401, C602, A101, A102, P121, P131, E102, E103, E601, E701, Addendum 1, dated 5/31/23 in lieu thereof.
a. Description – QM trailer removed from site.
Addendum To The Specifications:
3. N/A
Pre-Bid Questions:
4. N/A
General Instructions:
5. N/A
(END OF ADDENDUM)
By: Bill Draper, Project Manager cc: IHS/PHX C.O.; IHS/PHX COR
File encl: List of Issued Drawings: G001, C001, C100, C200, C300, C400, C401, C602, A101, A102, P121, P131, E102, E103, E601, E701
VICINITY MAP
A PORTION OF THE WHITE MOUNTAIN APACHE IHS AREA
SITUATED IN GOVERNMENT LOTS 1 AND 2 OF
SECTION31, TOWNSHIP 6 NORTH, RANGE 23 EAST, PER
THE BLM DEPENDENT RESURVEY AND SURVEY OF
FEBRUARY 4TH 1993 OF THE GILA AND SALT RIVER
MERIDIAN, NAVAJO COUNTY, ARIZONA
PROJECT
LOCATION
TO PINETOP
TO WHITERIVER
NAVAJO DR
H
IG
H W
A Y
PHOENIX
FLAGSTAFF
TUCSON
PROJECT
LOCATION
WHITERIVER
APACHE CIR
t
Z
TR
I
AR
D a
E C ni g
UON A,
.A.S.
VERNON
ROSAMOND
e e
S d:
ET
I AFIC
ON
R E
G I S
TERED ARCH
I T
E C
T
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
1.
.2
/3
/2
:2
:3
A
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
A rc h W
R A d m in
.r v t
12" = 1'-0"
G001
INFORMATION
SHEET
BD
SP
21-020
11/03/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
BLK(G) BLOCK(ING)
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRG BEARING
BRK BRICK
BSMT BASEMENT
BUR BUILT UP ROOFING
C CHANNEL
C/C CENTER TO CENTER
CAB CABINET
CB CHALK BOARD,CATCH BASIN
CEM CEMENT
CG CORNER GUARD
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR(ANCE)
CMP CORRUGATED METAL PIPE
CMTSCOMMENTS
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS OR CONTINUE
CORR CORRIDOR,CORRUGATED
CPT CARPET
CR CLEAN ROOM
CSK COUNTERSINK
CT CERAMIC TILE
CU CUBIC
CU FT CUBIC FOOT (FEET)
CW COLD WATER
D DEPTH
DEMO DEMOLISH, DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DITTO
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DTL DETAIL
DWG DRAWING
DWC DRYWALL CHANNELS (HAT)
E EAST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEC ELECTRIC(AL)
ELEV ELEVATION,ELEVATOR
EMER EMERGENCY
EP EPOXY PAINT
EPS EXPANDED POLYSTYRENE
EQ EQUAL EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
EST ESTIMATE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVAT(E)(ION)
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXT EXTERIOR
EIFS EXT. INSULATION FINISH SYSTEM
F FAHRENHEIT
FA FIRE ALARM
FAB FABRICATE
FD FLOOR DRAIN
FDN FOUNDATION
FE(C) FIRE EXTINGUISHER(CABINET)
FF FINISH FLOOR
FHC FIREHOSE CABINET
FHR FIREHOSE RACK
FIN FINSH(ED)
FL FLOOR
FLA FLASHING
FLEX FLEXIBLE
FLUOR FLUORESCENT
FO FACE OF
FP FIREPROOF
FR FIRE RETARDANT
FRP FIBER REINFORCED PLASTIC
FT FOOT,FEET
FTG FOOTING
FUR FURRED(ING)
FUT FUTURE
GA GAGE,(GUAGE)
GALV GALVANIZED
GC GENERAL CONTRACT(OR)
GD GRADE
GL GLASS, GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
H(T) HEIGHT
HB HOSE BIBB
HC HOLLOW CORE
HDBD HARDBOARD
HD HEAVY DUTY
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HORZ HORIZONTAL
HP HIGH POINT
HR HOUR
HVAC HEATING/VENTILATING/ AIR
CONDITIONING
HW HOT WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCH(ES)
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JC JANITORS CLOSET
JST JOIST
JT JOINT
KD KNOCKED DOWN
KIT KITCHEN
KO KNOCK OUT
KP KICK PLATE
L LENGTH,LONG
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LF LINEAL FEET
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LT LIGHT
LTWT LIGHTWEIGHT
LVR LOUVER
MAS MASONRY
MAX MAXIMUM
MATL MATERIAL
MED MEDIUM
MECH MECHANICAL
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MM MILLIMETER
MIN MINIMUM
MISC MISCELLANOUS
MO MASONRY OPENING
MOD MODULAR
MOV MOVABLE
MTD MOUNTED
MWP METAL WALL PANEL (SYSTEM)
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENTS
NTS NOT TO SCALE
NO NUMBER
OA OVERALL
OC ON CENTER(S)
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD,OPPOSITE HAND
OPG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
P PAINT(ED)
PAR PARALLEL
PART PARTITION
PART BD PARTICLE BOARD
PC PIECE
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PREFAB PERFORATE(D)
PERIM PERIMETER
PERP PERPENDICULAR
PF PREFABRICATED
PJ PANEL JOINT
PL PLASTER,PLATE,PROPERTY LINE
PLBG PLUMBING
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAL FOOT
PNL PANEL
PO POWER OPERATED
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTD PAPER TOWEL DISPENSER
PTR PAPER TOWEL RECEPTOR
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
PLWD PLYWOOD
QT QUARRY TILE
QTR QUARTER
QTY QUANTITY
(R) RECESSED
R RADIUS,RISER ROUND
RA RETURN AIR
RB RESILIENT BASE
RCP REINFORCED CONCRETE PIPE,
REFLECTED CEILING PLAN
RD ROOF DRAIN
RE(F) REFERENCE
RELO RELOCATION
REPL REPLACE
RES RESILIENT
REV REVISION(S),REVISED
RF RIGID FIBERGLASS
RFG ROOFING
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RRF ROLLED RUBBER FLOORING
REQ'D REQUIRED
RWL RAINWATER LEADER
S SEALED, SOUTH
(S) SURFACE MOUNTED
SC SOLID CORE, SEALED CONCRETE
SCHED SCHEDULE
SECT SECTION
SD STORM DRAIN
SDG SIDING
SF SQUARE FEET
SHT SHEET
SHWR SHOWER
SIM SIMILAR
SL SHEET LINOLEUM
SM SHEET METAL
SP SOUNDPROOF
SPECS SPECIFICATIONS
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SERVICE SINK
SST STAINLESS STEEL
STD STANDARD ST STEEL, STREET
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SV SEAMLESS VINYL
SW SWITCH
SWR SEWER
SYM SYMMETRY(ICAL)
T THICKNESS, TEE
TD TRENCH DRAIN
T&G TONGUE AND GROOVE
TB TACKBOARD TEL TELEPHONE
TEMP TEMPERATURE,TEMPORARY
TERR TERRAZZO
THK THICK(NESS)
TO TOP OF
TOC TOP OF CONCRETE
TOIL TOILET
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TV TELEVISION
TYP TYPICAL
U URINAL
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VNR VENEER
VPL VENEER PLASTER
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDTH, WIDE, WEST
W/ WITH
W/O WITHOUT
W/W WALL TO WALL
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WALL HUNG, WATER HEATER
WI WROUGHT IRON
WM WIRE MESH
WP WATERPROOFING
WR WATER REPELLENT
WS WEATHERSTRIP
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
ABBREVIATIONS PROJECT DIRECTORY
CODE DATA & STANDARDS
1. ALL DIMENSIONS GIVEN ARE TO FACE OF STUD AND TO FACE OF STEM WALL.
EXCEPTIONS AS INDICATED ON THE DOCUMENTS.
2. LARGE SCALE DETAILS AND PLANS TAKE PRECEDENCE OVER SMALL SCALE
DRAWINGS.
3. CIVIL DRAWINGS FINISH FLOOR DATUM ELEVATION EQUALS ARCHITECTURAL
ELEVATION OF 0'=0" FOR EACH BUILDING INDEPENDANT OF OTHER BUILDINGS.
4. COORDINATE AND VERIFY ALL DIMENSIONS, OPENINGS AND CONDITIONS WITH
CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL AND ALL OTHER PERTINENT
DRAWINGS AND TRADES PRIOR TO CONSTRUCTION. NOTIFY ARCHITECT OF
DISCREPANCIES PRIOR TO FABRICATION AND INSTALLATION.
5. FIRE RATINGS SHALL BE MAINTAINED AT FIRE RATED PARTITIONS BY A U.L.
ASSEMBLY AT GAPS AND VOIDS CREATED BY PENETRATIONS, STRUCTURAL
MEMBERS AND INTERSECTIONS WITH ADJACENT SURFACES.
6. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE CODES
AND REGULATIONS.
OWNER
INDIAN HEALTH SERVICE
DIVISION OF FACILITIES ENGINEERING
- PHOENIX AREA
TWO RENAISSANCE SQUARE
40 N. CENTRAL AVE., SUITE 720
PHOENIX, AZ 85004
CONTACT: VERNON CLASHIN
PHONE: (602) 364-5062
CIVIL ENGINEER
DOWL ENGINEERS
4686 E. VAN BUREN STREET, SUITE 175
PHOENIX, AZ 85008
CONTACT: ERIN O'BRIEN
PHONE: (480) 753-0800
STRUCTURAL ENGINEER
SCHNEIDER STRUCTURAL ENGINEERS, INC
435 E. 9TH ST.
TUCSON, AZ 85705
CONTACT: RON SCHNEIDER
PHONE: (520) 512-8183
ARCHITECT
JOHNSON SMITTHIPONG & ROSAMOND
5120 E. WILLIAMS CIR, SUITE 600
TUCSON, AZ 85711
CONTACT: BILL DRAPER
PHONE: (520) 547-7904
ELECTRICAL/MECHANICAL
ENGINEERING
TME/BERNARD
2990 N SWAN RD., SUITE 227
TUCSON, AZ 85712
CONTACT: JACOB CLARK
PHONE: (520) 323-2381
INTERIOR DESIGN
AVIAR DESIGN
7650 E. BROADWAY BLVD, SUITE 212
TUCSON, AZ 85710
CONTACT: KATHRYN VICKERS
PHONE: (520) 216-5509
OCCUPANCY B
CONSTRUCTION TYPE VB
SEISMIC ZONE REFER TO STRUCTURAL
SPRINKLERS FULLY SPRINKLERED
GENERAL ARCHITECTURAL NOTES
PROJECT LOCATION
INTERNATIONAL BUILDING CODE 2018
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL MECHANICAL CODE
2017 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2019 A/E DESIGN GUIDE
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
2018 INTERNATIONAL FIRE CODE
2018 NFPA 101 - LIFE SAFETY CODE
2019 NFPA 72
2019 NFPA 13
N
SHEET INDEX
Sht No Sheet Name
GENERAL
G000 COVER SHEET
G001 INFORMATION SHEET
G101 CODE SHEET
CIVIL
C001 COVER SHEET
C002 NOTES SHEET
C100 DEMOLITION PLAN
C200 SITE PLAN
C300 GRADING & DRAINAGE PLAN
C400 SANITARY SEWER PLAN & PROFILE
C401 WATER PLAN
C500 DETAILS
C501 DETAILS
C502 MAG STANDARD DETAILS
C503 MAG STANDARD DETAILS
C504 MAG AND CITY OF PHOENIX DETAILS
C600 STORMWATER MANAGEMENT PLAN COVER
C601 STORMWATER MANAGMENT PLAN DETAILS
C602 STORMWATER MANAGMENT PLAN
STRUCTURAL
S101 G.S.N.
S102 G.S.N. & I.O.D.
S103 SPECIAL INSPECTIONS CHART
S104 TYPICAL DETAILS
S105 TYPICAL DETAILS
S106 TYPICAL DETAILS
S107 SCHEDULES
S201 FOUNDATION PLAN
S202 ROOF FRAMING PLAN
S203 ADDENDUM 1 - SHEET REMOVED
S301 FOUNDATION DETAILS
S401 FRAMING DETAILS
S402 FRAMING DETAILS
S403 FRAMING DETAILS
ARCHITECTURAL
A001 WALL TYPES & MOUNTING HEIGHTS
A101 SITE PLAN EXISTING
A102 REFERENCE SITE PLAN NEW
A121 FLOOR PLAN
A131 DIMENSION PLAN
A141 REFLECTED CEILING PLAN
A151 ROOF PLAN
A201 EXTERIOR ELEVATIONS
A202 INTERIOR ELEVATIONS
A301 BUILDING SECTIONS
A401 ENLARGED PLANS
A501 EXTERIOR DETAILS
A502 INTERIOR DETAILS
A503 MILLWORK DETAILS
A504 DOOR DETAILS
A505 WINDOW DETAILS
A601 ROOM FINISH SCHEDULES
A602 DOOR & WINDOW SCHEDULE
A603 SIGNAGE FLOOR PLAN
A604 SIGNAGE SCHEDULE
INTERIORS
I001 FURNITURE PLAN
I002 MODULAR FURNITURE ELECTRICAL PLAN
I003 PANEL PLAN
FIRE PROTECTION
F001 GENERAL NOTES - FIRE PROTECTION
F101 FIRST FLOOR PLAN -FIRE PROTECTION
F501 DETAILS - FIRE PROTECTION
F502 DETAILS - FIRE PROTECTION
SHEET INDEX
Sht No Sheet Name
PLUMBING
P001 LEGENDS, DETAILS AND SCHEDULES -
PLUMBING
P101 PLUMBING SITE PLAN
P121 FIRST FLOOR PLAN - PLUMBING DOMESTIC
P131 FIRST FLOOR PLAN - PLUMBING SANITARY
P501 RISERS - PLUMBING
MECHANICAL
M001 GENERAL NOTES & LEGEND
M111 FIRST FLOOR PLAN - HVAC DUCTWORK
M112 FIRST FLOOR PLAN - HVAC ZONES
M113 ROOF HVAC PLAN
M601 SCHEDULES - HVAC
ELECTRICAL
E001 SCHEDULES, LEGENDS & GENERAL NOTES
E002 EQUIPMENT CONNECTION SCHEDULES
E101 SITE PLAN - DEMOLITION
E102 SITE PLAN
E103 SITE PLAN - SSB BUILDING
E121 LIGHTING PLAN
E131 POWER PLAN - NORTH
E132 POWER PLAN - SOUTH
E141 MECHANICAL POWER PLAN
E142 ROOF POWER PLAN
E151 FIRE ALARM PLAN
E161 SYSTEMS PLAN
E401 ENLARGED PLANS
E601 PANEL SCHEDULES
E602 PANEL SCHEDULES
E701 ONE-LINE DIAGRAM
2018 IECC SUMMARY: TABLE C402.1.2 - CLIMATE ZONE 5
INSULATON ENTIRELY ABOVE ROOF DECK: R-30ci rigid insulation WOOD FRAME WALL: R-18 wall cavity + R-3.8ci rigid insulation SLAB ON GRADE: R-10 for 24" below; vertical & horizontal combined
No. Date Description
1 5/31/23 Addendum 1
EXISTING SSB BUILDING
02 01
02 01
02 01
02 02 02 03 02 04 02 05
02 06
02 01
02 07
APACHE CIRCLE
A P
A C
H E
C
IR
C L E
N A
V A
J O
D R
IV
E
EXISTING
METAL BUILDING
02 08
02 09
02 10
02 08
02 11 t
Z
TR
I
AR
D a
E C ni g
UON A,
.A.S.
VERNON
ROSAMOND
e e
S d:
ET
I AFIC
ON
R E
G I S
TERED ARCH
I T
E C
T
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
1.
.2
/3
/2
:2
:2
A
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
A rc h W
R A d m in
.r v t
1" = 50'-0"
A101
SITE PLAN
EXISTING
BD
SY
21-020
11/03/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
1" = 50'-0"A1 REFERENCE SITE PLAN - EXISTING
KEYNOTES
Key # Keynote Text
02 01 EXISTING PARKING LOT.
02 02 EXISTING QM BUILDING TO BE REMOVED AND
DEMOLISHED.
02 03 EXISTING HR TO BE REMOVED AND DEMOLISHED.
02 04 EXISTING TRAINING CENTER TO BE REMOVED
AND DEMOLISHED.
02 05 EXISTING PRC TO BE REMOVED AND
DEMOLISHED.
02 06 EXISTING ABANDONED UNIT TO BE REMOVED AND
DEMOLISHED.
02 07 EXISTING DROP OFF LANE.
02 08 EXISTING ADA PARKING.
02 09 EXISTING DIRT ROAD.
02 10 NEED UTILITY HOOKUP.
02 11 EXISTING FIRE HYDRANT, REFERENCE CIVIL.
GENERAL NOTES
A REFER TO CIVIL DEMOLITION DRWGS.
EXISTING SSB BUILDING
NEW ADMINISTRATION
BUILDING
32 02
32 02
32 02
32 04
32 04
32 03
32 06
02 09
32 15
03 21
04 03
4' - 0"
3' - 8"
CONCRETE
FOOTING
4X4 TUBE STEEL
POST, PAINTED
C L
C L
GRAPHICS PER
HEALTH CENTER
SIGNAGE
STANDARDS
1' - 0"
ALUMINUM PANEL
WITH 3/4"
ALUMINUM LIP
FRAME
t
Z
TR
I
AR
D a
E C ni g
UON A,
.A.S.
VERNON
ROSAMOND
e e
S d:
ET
I AFIC
ON
R E
G I S
TERED ARCH
I T
E C
T
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
1.
.2
/3
/2
:2
:2
A
M
A u to d e s k D o c s /2
-0
W h it e ri v e r A d m in v
/2
-0
A rc h W
R A d m in
.r v t
As indicated
A102
REFERENCE SITE
PLAN NEW
BD
SY
21-020
11/03/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
1" = 20'-0"A1 REFERENCE SITE PLAN - NEW
KEYNOTES
Key # Keynote Text
02 09 EXISTING DIRT ROAD.
03 21 CAST IN PLACE CONCRETE STAIR, REF CIVIL.
04 03 SITE WALL - ADHERED STONE MASONRY VENEER
ON CMU WITH WEEPS AT 32" O.C.
32 02 NEW CONCRETE SIDEWALK.
32 03 NEW FDC LOCATION WITH BOLLARDS.
32 04 NEW FIRETRUCK ACCESS LANE, REF CIVIL.
32 06 EXISTING PATIENT DROP-OFF.
32 15 FREE STANDING SIGNAGE, FOR DETAIL SEE THIS
SHEET.
GENERAL NOTES
A VERIFY ALL UTILITY LOCATIONS AND STUBS PRIOR
TO EXCAVATION.
1/2" = 1'-0"A5 BUILDING SIGNAGE
F
E
D
C
B
ER/LR
HUMAN
RESOURCES
DIRECTOR
PIV
PAYROLL
FILE / COPIER
PURCHASED
REFERRED CARE
CONSULTATION
PRC DIRECTOR
LOBBY
ENTRY
CONFERENCE
CONFERENCE
CONF. STORAGE
104A
WOMEN
MEN
DATA CL.
HSKG
PREVENTATIVE
MEDICINE
COPY/STOR.
ASST. DIRECTOR
DIRECTOR
OFFICE
EXAM
CORRIDOR
ADMIN
ADMIN
STOR.
173MECH
WOMENS
MENS
STAFF BRK
TRAINING RM 2
SECURE STOR.
140A
CORRIDOR
C O
R R
ID
O
R
TRAINING RM 1
STAFF DEV
A/V 141A
COPIER
UTILIZATION
REVIEW
DIRECTOR
COMPLIANCE
OFFICER
QUALITY MGMT
INFECTION
CONTROL
EMPLOYEE
HEALTH
NURSE
SPECIALIST
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
CORRIDOR
STOR FILES
CORRIDOR
CORRIDOR
HWRP-1
3" CW
3" CW
3/4" HW/R
1 1/4" HW
RPZ-1
1 1/4" HW
1 1/4" HW
HWRP-1
1" HW
3/4" HW/R
S-1
WC-1
WC-2
WC-2
WC-2
WC-2WC-1
UR-1
L-1L-1
L-1
L-1
L-1
L-1
UR-1
EWC-1
EWC-1
R
IM
S U
-1
TMV-1
3" CW
SS-1
3/4" HW 3" CW
3/4" HW
3/4" HW/R
3/4" HW/R
1 1/4" HW
3/4" HW/R
3" CW
3/4" HW/R
S-2
HB-1
HB-1
HB-1
HB-1
3"FS-1
2"FD-1
2"FD-1
2" FD-1
2" FD-1
1 1/4" HW
1" CW 3/4" CW
1/2" HW
1/2" HW
2" CW
1 1/2" CW
3/4" CW 1/2" HW
WHA-1
WHA-1
WHA-1
WHA-1
WHA-1
WHA-1
WHA-1
1/2" CW
3" CW
3/4" CW
WHA-1
2 1/2" CW
2" CW
3/4" CW
WH-1
1 1/4" CW
1 1/2" CW
3/4" HW
2 1/2" CW
3/4" CW
3/4" CW
3/4" CW
1/8" = 1'-0"1 PLUMBING FLOOR PLAN - PLUMBING DOMESTIC
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:2 :2
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
1/8" = 1'-0"
P121
FIRST FLOOR
PLAN - PLUMBING
DOMESTIC
Checker
Author
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
GENERAL NOTES:
A. REFERENCE PLUMBING FIXTURE SCHEDULE ON P0.02 FOR SIZE
OF BRANCH PIPE TO INDIVIDUAL FIXTURES.
No. Date Description
1 5/31/23 Addendum 1
R e g is te re d anoisseforP l
)l a ci na hc e M( re eni gnE
ARIZONA U.S.
A.
54000
MARK A.
ALVAREZ
D
ATE
SIGNED___
.O
NETACIFITREC
E x p i r e s 1 2 / 3 1 /
/3
/ 2
F
E
D
C
B
ER/LR
HUMAN
RESOURCES
DIRECTOR
PIV
PAYROLL
FILE / COPIER
PURCHASED
REFERRED CARE
CONSULTATION
PRC DIRECTOR
LOBBY
ENTRY
CONFERENCE
CONFERENCE
CONF. STORAGE
104A
WOMEN
MEN
DATA CL.
HSKG
PREVENTATIVE
MEDICINE
COPY/STOR.
ASST. DIRECTOR
DIRECTOR
OFFICE
EXAM
CORRIDOR
ADMIN
ADMIN
STOR.
MECH
WOMENS
MENS
STAFF BRK
TRAINING RM 2
SECURE STOR.
140A
CORRIDOR
C O
R R
ID
O
R
TRAINING RM 1
STAFF DEV
A/V 141A
COPIER
UTILIZATION
REVIEW
DIRECTOR
COMPLIANCE
OFFICER
QUALITY MGMT
INFECTION
CONTROL
EMPLOYEE
HEALTH
NURSE
SPECIALIST
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
ADMIN
CORRIDOR
STOR FILES
CORRIDOR
COTG
DCOTG
4" WCO-1
S-1
WC-1WC-2
WC-2
WC-2
WC-2WC-1
UR-1
L-1L-1
L-1
L-1L-1
L-1
UR-1
EWC-1
EWC-1
2"FD-1
2"FD-1
2" FD-1
2" FD-1
R
IM
S U
-1
SS-1
S-2
HB-1
HB-1
HB-1
HB-1
3"FS-1
2" SS
2" SS
4" WCO-1
4" SS
4" SS
4" SS
4" SS
4" SS
2" SS
2" V
2" V
2 1/2" V
2" V
2 1/2" VTR
2" V 2 1/2" V
2" V
2 1/2" VTR
3" SS
2" VTR
3" WCO
2" WCO
2" WCO
2" WCO
4" WCO
4" WCO
4" WCO
4" WCO
WH-1
1/8" = 1'-0"1 FIRST FLOOR PLAN - PLUMBING SANITARY
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:2 :0
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
1/8" = 1'-0"
P131
FIRST FLOOR
PLAN - PLUMBING
SANITARY
Checker
Author
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
2" WCO
GENERAL NOTES:
A. WALL CLEANOUT FOR SERVICE SINK TO BE ABOVE ALL SINK
TRIM.
B. WALL CLEANOUT FOR TOILET TO BE ABOVE FLUSH VALVE.
C. ALL PLUMBING VENTS THROUGH ROOF TO DISCHARGE A MINIMUM OF 15 FEET
AWAY FROM ROOFTOP UNITS.
No. Date Description
1 5/31/23 Addendum 1
R e g is te re d anoisseforP l
)l a ci na hc e M( re eni gnE
ARIZONA U.S.
A.
54000
MARK A.
ALVAREZ
D
ATE
SIGNED___
.O
NETACIFITREC
E x p i r e s 1 2 / 3 1 /
/3
/ 2
D
D
S
F
P
S
S
S
S
W
D
F
F
E
E
E
F O
E
E
E
E
EXISTING SPECIALITY
SERVICE BUILDING
NEW ADMINISTRATION
OFFICE BUILDING
FO
FO
FO
SES-MOB
H2E
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:1 :2
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
1" = 20'-0"
E102
SITE PLAN
JSC
RMW
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
KEYED NOTES:
1. EXISTING INCOMING UNDERGROUND NAVOAPACHE ELECTRICAL UTILITY
PRIMARY.
2. EXISTING NAVOAPACHE ELECTRICAL UTILITY PAD MOUNTED TRANSFORMER.
3. PROVIDE 4-#600KCMIL, 1-#2G, 3 1/2" AND (1)3 1/2"C SPARE WITH PULL WIRE
UNDERGROUND FROM EXISTING SPECIALTY SERVICE BUILDING MAIN
DISTRIBUTION PANEL 'MDP' IN ELECTRICAL ROOM 002 TO DISTRIBUTION PANEL
'SES-MOB'. REFER TO ONE LINE DIAGRAM AND PANEL SCHEDULES FOR
ADDITIONAL DETAILS AND REQUIREMENTS.
4. NOT USED.
5. NOT USED.
6. NOT USED.
7. NOT USED.
8. EXISTING UNDERGROUND FIBER OPTIC CABLING DUCTBANK. PROVIDE (1) 12
STRAND MULTI-MODE OM4MM FIBER BACKBONE OSP RATED CABLES IN
(1)1 1/4" INNER DUCT. PROVIDE (1) 25 PAIR CAT6A CABLE WITHIN (1)1 1/4"
INNERDUCT AND (1) SPARE 1 1/4" INNERDUCT WITH PULL WIRE. PROVIDE
FIBER OPTIC CABLING AND CAT6A CABLING FROM EXISTING SPECIALTY
SERVICES MDF PATCH PANEL.
9. EXISTING UNDERGROUND FIBER OPTIC VAULT TO REMAIN.
10. EXISTING (2)4"C UNDERGROUND EMPTY FIBER OPTIC DUCTBANK CONDUITS,
CUT BACK, DURING SITE DEMOLITION. EXTEND EXISTING (2)4"C TO PLYWOOD
TERMINAL BOARDS WITHIN DATA CLOSET 142. PROVIDE (1) 12 STRAND FIBER
OPTIC CABLING AND CAT6A CABLING PER KEYED NOTE 2 WITHIN (2) 1 1/4"
INNERDUCTS WITHIN (1) 4"C. REMAINING (1) 4"C WITH PULL WIRE TO REMAIN
EMPTY AS A SPARE CONDUIT.
11. EXISTING FIBER OPTIC CABLING DUCTBANK TO WHITERIVER INDIAN HOSPITAL.
12. NOT USED.
13. EXISTING SITE LIGHTING POLE LIGHT TO REMAIN.
14. NOT USED.
15. NOT USED.
16. PROVIDE 4-#8, 1-#10G, 1"C UNDERGROUND FROM EXISTING SPECIALTY
SERVICE BUILDING PANEL 'H1E' LOCATED WITHIN ELECTRICAL ROOM FM115
ON THE FIRST FLOOR ADJACENT TO COLUMN E3 TO PANEL 'H2E'. REFER TO
ONE LINE DIAGRAM AND PANEL SCHEDULES FOR ADDITIONAL DETAILS AND
REQUIREMENTS.
17. EXTEND CONDUIT AND LIGHTING BRANCH CIRCUIT AS REQUIRED OUTSIDE OF
THE NEW ADMINSTRATION OFFICE BUILDING FOOTPRINT AND RECONNECT.
GENERAL NOTES:
A. ALL NEW UNDERGROUND CONDUITS TO HAVE DETECTABLE WARNING TAPE
ABOVE EACH CONDUIT.
R e g is te re d anoisseforP l
)l a ci rt ce lE re eni gnE
ARIZONA U.S.
A.
64509
JACOB S.
CLARK
D
ATE
SIGNED___
.O
NETACIFITRE
C
/ 0
E x p i r e s 0 9 / 3 0 /
No. Date Description
1 5/31/23 Addendum 1
1" = 20'-0"1 SITE PLAN
CT-1
STAIR
MDF
MECHANICAL
ELECTRICAL
MED GAS
TANK STORAGE FIRE RISER
CORRIDOR
PT GYM
IRM OFFICE
LOBBY
TREATMENT
MODALITY
TREATMENT
DIR OFFICE
OPEN OFFICE
CONFERENCE
EXAM
EXAM
EXAM
EXAM
PEDS
STORAGE
W STAFF TOILET
PAT TOILET
M STAFF TOILET
IRM OFFICE
STAFF TOILET
BIOMED
HALL
HALL
HALL
HALL
FAPS ATS
MDP
TBA
LBA
HBA
ATS-E
6 43
AREA OF WORK
AREA OF WORK
A B C D E F
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:0 :0
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
1/8" = 1'-0"
E103
SITE PLAN - SSB
BUILDING
Checker
Author
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
1/8" = 1'-0"A2 SSB BUILDING GROUND FLOOR POWER TAP PLAN
GENERAL NOTES:
A. CONTRACTOR TO COORDINATE ALL FIBER OPTIC CABLING AND CAT6A
CABLING TERMINATIONS WITH WHITERIVER SERVICE UNIT.
KEYED NOTES:
1. PROVIDE 4-#600KCMIL, 1-#2G WITHIN (1) 3 1/2"C AND (1) 3 1/2"C SPARE WITH
PULL WIRE FROM EXISTING 'MDP' TO SES-MOB'.
2. NOT USED.
3. EXISTING UNDERGROUND FIBER OPTIC CABLING DUCT BANK TO EXISTING
FIBER OPTIC VAULT.
4. PROVIDE (1) 12 STRAND MULTI-MODE OM4MM FIBER OPTIC BACKBONE OSP
RATED WITHIN (1) EMPTY 1 1/4" INNERDUCT AND (1) 25 PAIR CAT6A TSP WITHIN
(1) EMPTY 1 1/4" INNERDUCT TO DATA CLOSET 142 WITHIN ADMINISTRATION
OFFICE BUILDING.
5. NOT USED.
6. TERMINATE FIBER OPTIC CABLING AND 25 PAIR CAT6A CABLE TO
ADMINISTRATION OFFICE BUILDING TO NEW PATCH PANELS WITHIN EXISTING
MDF ROOM.
7. PROVIDE 4-#8, 1-#10G, 1"C TO PANEL 'H2E' WITHIN ADMINISTRATION OFFICE
BUILDING.
8. PROVIDED 4-#8, 1-#10G, 1"C UP TO EXISTING PANEL 'H1E' IN EXISTING
ELECTRICAL ROOM ON FIRST FLOOR.
R e g is te re d anoisseforP l
)l a ci rt ce lE re eni gnE
ARIZONA U.S.
A.
64509
JACOB S.
CLARK
D
ATE
SIGNED___
.O
NETACIFITRE
C
/ 3
E x p i r e s 0 9 / 3 0 /
No. Date Description
1 5/31/23 Addendum 1
* ESTIMATED LOAD.
Notes:
Total Est. Demand Current: 761 A
Total Conn. Current: 761 A
Total Est. Demand: 632687 VA
Total Conn. Load: 632687 VA
POWER, OTHER 111075 VA 100.00% 111075 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 761 A
Total Conn. Load: 632687 VA
11 ROOFTOP UNIT RTU-1 3 100 A 0 A 62250 VA FD35K
10 SPACE - PROVISIONS 3 100 A 0 A 0 VA FD35K
9 PANEL HBA 3 200 A 200 A 138900 VA FD35K
8 PANEL HIA 3 200 A 200 A 124400 VA FD35K
7 AUTOMATIC TRANSFER SWITCH ATS-E 3 40 A 40 A 3400 VA FD35K
6 SPACE - PROVISIONS 3 100 A 0 A 0 VA FD35K
5 SPACE 1 -- -- --
4 TRANSFORMER TBA / PANEL LBA AND PANEL LIA 3 225 A 225 A 111400 VA FD35K
3 ADMINISTRATION OFFICE BUILDING SES-MOB 3 600 A 400 A 192337 VA L630H
2 INCOMING UTILITY MAIN 3 800 A 800 A 0 VA
1 INCOMING GENERATOR MAIN 3 800 A 800 A 0 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
EXISTING EATON POW-R-LINE
Notes:
Enclosure: NEMA 1 MCB Rating: 800 A
Mounting: FLOOR Wires: 4 Mains Rating: 800 A
Supply From: Phases: 3 Mains Type: MCB
Location: Volts: 480/277 Wye A.I.C. Rating: 35,000
Switchboard: MDP R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:0 :0
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
E601
PANEL
SCHEDULES
JSC
RMW
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
SITE
NAVOPACHE TRANSFORMER
Total Est. Demand Current: 5 A
Total Conn. Current: 5 A
Total Est. Demand: 4153 VA
Total Conn. Load: 4153 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 9 A 3 A 3 A
Total Load: 2576 VA 837 VA 740 VA
11 SPARE 20 1 0 -- 1 -- SPACE 12
9 SPARE 20 1 0 -- 1 -- SPACE 10
7 SPARE 20 1 0 -- 1 -- SPACE 8
5 LTS 20 1 740 0 -- -- -- 6
3 LTS 20 1 660 177 -- -- -- 4
1 LTS 20 1 1340 1236 3 30 PANEL AOB-H2E* 2
CKT Circuit Description Trip
(A) Poles "A" PHASE (VA)
"B" PHASE
(VA) "C" PHASE (VA) Poles
Trip
(A) Circuit Description CKT
*PROVIDE NEW MATCHING CIRCUIT BREAKER
Notes: EXISTING EMERGENCY PANEL
Enclosure: NEMA 1
Mounting: SURFACE Wires: 4 MCB Rating: 100 A
Supply From: Phases: 3 Bus Rating: 100 A
Location: Volts: 480/277 Wye A.I.C. Rating: 10,000
Branch Panel: H1E
Total Est. Demand Current: 10 A
Total Conn. Current: 10 A
Total Est. Demand: 8271 VA
Total Conn. Load: 8271 VA
POWER, OTHER 6858 VA 100.00% 6858 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 12 A 10 A 8 A
Total Load: 3222 VA 2793 VA 2256 VA
17 SPACE -- 1 -- 2256 -- -- -- 18
15 SPACE -- 1 -- 2616 -- -- -- 16
13 SPACE -- 1 -- 1986 3 30 TRANSFORMER T-AOB-L2E 14
11 SPACE -- 1 -- -- 1 -- SPACE 12
9 SPACE -- 1 -- -- 1 -- SPACE 10
7 SPACE -- 1 -- -- 1 -- SPACE 8
5 LTS- MOB EXTERIOR 20 1 0 0 -- -- -- 6
3 LTS- MOB INTERIOR 20 1 177 0 -- -- -- 4
1 LTS- MOB INTERIOR CORRIDOR 20 1 1236 0 3 30 INCOMING MAIN (BRANCH MOUNTED) 2
CKT Circuit Description Trip
(A) Poles "A" PHASE (VA)
"B" PHASE
(VA) "C" PHASE (VA) Poles
Trip
(A) Circuit Description CKT
SQUARE D NQ OR APPROVED EQUAL
Notes:
Enclosure: NEMA 1
Mounting: SURFACE Wires: 4 MCB Rating: 30A
Supply From: Phases: 3 Bus Rating: 125 A
Location: ELEC 187 Volts: 480/277 Wye A.I.C. Rating: 18,000
Branch Panel: AOB-H2E
SSB 1ST FLOOR ELECT RM FM115
ATS-E
EXISTING PANEL H1E
EXISTING DISTRIBUTION PANEL EXISTING PANELBOARD
NEW PANELBOARD
Total Est. Demand Current: 19 A
Total Conn. Current: 19 A
Total Est. Demand: 6858 VA
Total Conn. Load: 6858 VA
POWER, OTHER 6858 VA 100.00% 6858 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 17 A 22 A 19 A
Total Load: 1986 VA 2616 VA 2256 VA
29 SPARE 20 1 0 -- 1 -- SPACE 30
27 SPARE 20 1 0 -- 1 -- SPACE 28
25 SPARE 20 1 0 -- 1 -- SPACE 26
23 SPARE 20 1 0 -- 1 -- SPACE 24
21 SPARE 20 1 0 -- 1 -- SPACE 22
19 SPARE 20 1 0 -- 1 -- SPACE 20
17 SPARE 20 1 0 -- 1 -- SPACE 18
15 PWR- ACCESS CONTROL PANEL 20 1 180 -- 1 -- SPACE 16
13 PWR- FACP 20 1 180 -- 1 -- SPACE 14
11 PWR- DOORS LOBBY 102 20 1 600 -- 1 -- SPACE 12
9 PWR- DOORS MEN 106, WOMEN 107 20 1 1656 -- 1 -- SPACE 10
7 PWR- DOORS MEN 138, WOMENS 137 20 1 1656 -- 1 -- SPACE 8
5 PWR- DOORS ENTRY 101 20 1 1656 -- 1 -- SPACE 6
3 PWR- DOORS CORRIDOR 135 20 1 780 -- 1 -- SPACE 4
1 PWR- DOORS CORRIDOR 136 20 1 150 -- 1 -- SPACE 2
CKT Circuit Description Trip
(A) Poles "A" PHASE (VA)
"B" PHASE
(VA) "C" PHASE (VA) Poles
Trip
(A) Circuit Description CKT
Notes:
Enclosure: NEMA 1
Mounting: SURFACE Wires: 4 MCB Rating: 60 A
Supply From: T-AOB-L2E Phases: 3 Bus Rating: 100 A
Location: ELEC 187 Volts: 120/208 Wye A.I.C. Rating: 100
Branch Panel: AOB-L2E
NEW PANELBOARD
R e g is te re d anoisseforP l
)l a ci rt ce lE re eni gnE
ARIZONA U.S.
A.
64509
JACOB S.
CLARK
D
ATE
SIGNED___
.O
NETACIFITRE
C
/ 3
E x p i r e s 0 9 / 3 0 /
No. Date Description
M
CTS
E
TVSS
N
G
1 2 800/3 800/3
#2/0
200A 3P
HIA
RM 115
4-#3/0 1-#6G 2"C
#2/0
225A 3P
LBA
RM 115
4-#3/0 1-#4G 2"C
4-500KCMIL
1-#3G 3 1/2"C
#1/0
TBA
150KVA
480V 120/208V
200A
150A
100A 3P
RTU-1
3-#3 1-#8G 1"C
200A 3P
HBA
RM 002
4-#3/0 1-#6G 2"C
600A/3P
400AT
40A 3P
HIE
4-#8 1-#10G 3/4"C
4-#8 1-#10G 3/4"C
N E
L
ATS-E
40A 3P
4-#8 1-#10G
1"PVC
SPECIALTY SERVICE CLINIC
EXISTING MAIN DISTRIBUTION PANEL (MDP)
277/480V, 3⌀, 4W, 800A, 35KAIC,
SERVICE ENTRANCE RATED
(2) 4-600KCMIL
1-#1/0G
3 1/2"PVC
E
G
40A 3P
LSI
800A 3P
LSI
GENERATOR
500KW/625KVA
277/480-3⌀-4W
400AF/
400AT
150AF/
100AT
150AF/
150AT
DISTRIBUTION
PANEL
SES-AOB
4-#600KCMIL
1-#2G 3 1/2"C
(1) 3 1/2"C SPARE
NAVOPACHE
ELECTRIC UTILITY
PAD MOUNTED
TRANSFORMER
INCOMING NAVOPACHE
ELECTRIC UTILITY
PRIMARY CONDUCTORS
IN (3) 2"C
NAVOPACHE
ELECTRIC UTILITY
SECONDARY
CONDUCTORS IN
(2) 4"C RM 002
RM 187
NOTE:
SCREENED (LIGHT) INDICATES EXISTING
COMPONENTS. BOLD (DARK) INDICATES
NEW COMPONENTS OR NEW SCOPE
REQUIREMENTS.
PANEL
AOB-H1
1-#1/0G
TRANSFORMER AOB-L1
112.5KVA
480-120/208V-3PH-4W
PANEL
AOB-L1
PANEL
AOB-L2
225A /3P
400A /3P
4-#600KCMIL
1-#1/0G 3 1/2"C
4-#4/0 1-#4G
2 1/2"C
3-#1/0 1-#6G
1 1/2"C
4-#2 1-#8G
1 1/2"C
RM 187
RM 187
RM
RM 187
L1A (L)
L1A (R)
4-#3/0 1-#6G
2"C
4-#8 1-#10G 1"C
AOB-H2E
MODULAR
BLDGS
MDP
4-#4/0 1-#2G 2"C
(2) 3-500KCMIL
1-#2/0G
3"C
#2/0
TMA
167KVA
480V 120/240V
AOB-L2E
4-6 1-#10G 1"C
#10G
T-AOB-L2E
15KVA
480V 120/208V
3-#10 1-#10G 1"C
R
VI
H
P
S
N I
D
C E
I
A
A N
HE TL H
S
E
E
H
N M
E
A R
P
T O
F T
C D
SU
S
A
E
TAE L
&H
N V
I S
E R
U M
A H
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Sheet Number:
Sheet Title:
Checked By:
Drawn By:
Scale:
Project No:
Issue Date:
Consultants:
JOHNSON SMITTHIPONG &
ROSAMOND ASSOCIATES, INC.
5210 E Williams Cir Ste 600 Tucson, AZ 85711
(520) 547-7904 www.jsrarchinc.com
U. S.
DEPARTMENT OF
HEALTH AND
HUMAN SERVICES
INDIAN HEALTH SERVICE
PHOENIX AREA OFFICE
/3
/2
:0 :1
P
M
A u to d e s k D o c s /2
-0
W h it e ri v e r
A d m in v
/2
-0
M E
P W
R M
O B
.r v t
NTS
E701
ONE-LINE
DIAGRAM
Checker
Author
21-020
11/3/2022
FINAL CD
WHITERIVER
ADMINISTRATION
OFFICE BUILDING
200 W HOSPITAL DR
WHITERIVER, AZ 85941
HHSI102201800007I
NTSB1 ONE-LINE DIAGRAM
GENERAL NOTES:
A. UPON THE REMOVAL OF THE EXISTING TRAILERS CONTRACTOR TO PROVIDE A
DEMAND RECORDING METER FOR 30 DAYS ON THE INCOMING FEEDER TO
EXISTING MAIN DISTRIBUTION PANEL 'MDP'. RECORDING METER TO BE SET FOR
RECORDING ON ONE MINUTE INTERVALS. UPON COMPLETION CONTRACTOR TO
DOWNLOAD RECORDING AND ISSUE A REPORT TO OWNER, ARCHITECT AND
ENGINEER FOR REVIEW AND RECORD.
KEYED NOTES:
1. EXISTING 600AF/400AT LSI TO REMAIN AND RE-UTILIZED TO SOURCE NEW
ADMINISTRATION OFFICE BUILDING SERVICE ENTRANCE "SES-AOB".
2. NOT USED.
3. REMOVE EXISTING FEEDER CONDUCTORS AND ABANDON EXISTING CONDUIT
IN PLACE.
4. REMOVE EXISTING TRANSFORMER, GROUND AND CONCRETE PAD.
5. REMOVE EXISTING FEEDER CONDUCTORS AND UNDERGROUND CONDUITS.
6. REMOVE EXISTING DISTRIBUTION PANEL, CONCRETE PAD, FEEDER
CONDUCTORS AND UNDERGROUND CONDUITS TO REMOVED EXISTING
TRAILERS.
R e g is te re d anoisseforP l
)l a ci rt ce lE re eni gnE
ARIZONA U.S.
A.
64509
JACOB S.
CLARK
D
ATE
SIGNED___
.O
NETACIFITRE
C
/ 3
E x p i r e s 0 9 / 3 0 /
No. Date Description
1 5/31/23 Addendum 1
| Addendum 1 |
| G001 - INFORMATION SHEET |
| C001 |
| C100 |
| C200 |
| C300 |
| C400 |
| C401 |
| C602 |
| A101 - SITE PLAN EXISTING |
| A102 - REFERENCE SITE PLAN NEW |
| P121 |
| P131 |
| E102 - SITE PLAN |
| E103 - SITE PLAN - SSB BUILDING |
| E601 - PANEL SCHEDULES |
| E701 - ONE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .