ITB_FAC260128_275_Ton_Air-Cooled_Chiller_Replacement_-_Addendum_3.pdf

PDF 120 KB Posted

Attached to
275-Ton Air-Cooled Chiller Replacement
Solicitation number
ITB# FAC/260128
Issued by
Marion County, Orlando City, Florida

About this file

This is Addendum #3 to Solicitation ITB# FAC/260128 issued by the City of Ocala, Florida, dated November 20, 2025, addressing the 275-Ton Air-Cooled Chiller Replacement project at City Hall and the Customer Service Center. The solicitation requires a licensed mechanical contractor in Florida with a minimum of five years of experience to supply and install a new 275-ton air-cooled chiller system to replace an existing 247-ton unit. A mandatory pre-bid meeting was held on November 10, 2025, at City Hall in Ocala, and an optional site visit was scheduled for November 21, 2025, from 10:00 AM to 11:00 AM. Follow-up questions must be submitted through ProRFx no later than November 24, 2025, by 5:00 PM.

Addendum #3 clarifies three critical technical specifications through questions and answers. The City confirmed it is upgrading to a 275-ton chiller rather than performing a like-for-like replacement of the current 247-ton unit, and current pump ratings of 2.5 GPM per ton will be maintained with existing pumps. The addendum further specifies that bidders proposing alternate chiller manufacturers other than the existing York brand must upload detailed specifications for the proposed equipment in Section 3.5 of the bid submission for City review and approval.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum # 3

Date: November 20, 2025

To: All bidders who attended the Mandatory Pre-Bid Meeting

From: Caley Conard, Buyer

Solicitation Number: ITB# FAC/260128

Solicitation Title: 275-Ton Air-Cooled Chiller Replacement

SECTION 1. QUESTIONS AND ANSWERS

1.1 QUESTION: The current chiller is 200 tons, and the pump is rated at 500gpm or 2.5gpm/ton. Do you want to keep the same 2.5gpm/ton for the new pumps? If not, can we please receive the GPM the

275-ton chiller needs?

ANSWER: Maintain current pump ratings to match existing pump not being replaced

1.2 QUESTION: The model and serial number provided equates to a 247-ton chiller. Please confirm you are requesting a 247-ton chiller for like for like replacement and not an upgrade to 275 tons.

ANSWER: We are upgrading to 275-ton chiller

1.3 QUESTION: Regarding the selection of a new chiller manufacturer to replace the existing York brand, how may we submit the chosen chiller information for your review and approval?

ANSWER: Upload the alternate manufacturer specifications in the section labeled:

3.5 SPECIFICATIONS

Upload detailed specifications for the proposed equipment [HERE]

SECTION 1. QUESTIONS AND ANSWERS