ITB-2019-0502_CPH_-_C1993_Revised_Drawing_C-7__-_7.29.19.pdf
PDF 812 KB Posted
- Attached to
- PW 1708 Howell Park Water Treatment Plant Rehab
- Solicitation number
- ITB-2019-0502
- Issued by
- Seminole County, Florida
About this file
This document is a site grading plan drawing (Sheet C-7) for the Howell Park Water Treatment Plant Improvements project by the City of Casselberry in Seminole County, Florida. The drawing provides a detailed site layout for a water treatment facility, including ground storage tanks, wells, buildings, chemical rooms, and infrastructure improvements. The plan specifically shows site dimensions, proposed fencing, gate sensor locations, concrete pavement, and various utility line connections including water, sanitary sewer, and drain lines.
The drawing includes technical specifications for pre-cast concrete post and panel fencing, with design requirements such as concrete strength (5000 PSI for panels, 3000 PSI for footings), soil bearing pressures, and fencing manufacturer guidelines. The site plan indicates additive alternate fencing sections, existing site features like power poles and guy wires, and details for gate installations. Specific site elements include a generator, flow meters, storage tanks with cascade aeration, and a grinder pump station, with elevation markers ranging from 90.25 to 91.83 feet. The drawing is part of a bid document set prepared by CPH, Inc., an architecture and engineering firm, and is dated July 29, 2019.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING PUMP SUCTION LINE
NEW RAW WATER LINE
NEW PUMP SUCTION/DISCHARGE LINE
EXISTING TANK FILL LINE (RAW WATER)
EXISTING POTABLE WATER LINE
SITE PIPING LEGEND:
EXISTING RAW WATER LINE
EXISTING STORAGE TANK DRAIN LINE
CHLORINE SOLUTION
ORTHO-POLYPHOSPHATE SOLUTION
NEW FORCE MAIN
NEW WATER SERVICE LINE
NEW SANITARY SERVICE LINE
90.5
90.5
EXISTING SANITARY SEWER GRAVITY LINE
NEW PUMP SUCTION/DISCHARGE LINE
EXISTING TANK FILL LINE (RAW WATER)
EXISTING SANITARY SEWER GRAVITY LINE
N
GRAPHIC SCALE
Scale:
Job No.
Date:
SAB
DEM
RAS
SAB
Checked by:
Approved by:
Designed by:
Drawn by:
D r a w i n g n a m e
C
R
A S
P r o j e c t s C
C u r r e n t P l a n S e t C b a s e d w g
J u l p m r s t o r y
ByNo. Date
2019C
C1993
7/29/2019
1" = 15'
ByNo. Date Revision Revision
1117 E. Robinson St. Orlando, FL 32801
Ph: 407.425.0452
CPH, Inc.
Arch. Lic. No. AA2600926
Landscp. Lic. No. LC0000298
Licenses:
Eng. C.O.A. No. 3215
Survey L.B. No. 7143
Plans Prepared By:
www.cphcorp.com
Architects
Engineers
Environmental
Landscape Architects
M / E / P
Planners
Structural
Surveyors
Offices In:
· Florida
· Puerto Rico
· Connecticut
· Maryland
· Texas
A Full Service A & E Firm
Traffic/Transportation
CITY OF CASSELBERRY
Howell Park WTP Improvements
Seminole County, Florida SCOTT A. BREITENSTEIN
REG NO. 57402
SITE GRADING PLAN
Sheet No.
C-7
B I D
R A
W I N
G
DISTRIBUTION
FLOW METER
0.25 MGD
GROUND STORAGE TANK
W/ CASCADE AERATION
0.50 MGD
GROUND STORAGE TANK
W/ CASCADE AERATION
G E
N E
R A
T O
R
WELL
NO. 1
HSP, ELECTRICAL,
AND OPERATIONS
BUILDING
C H
E M
I C
A L
R O
O M
CL2 BULK
STORAGE
FUEL TANK
S
T
A
T
E
O
GROUND STORAGE
TANK DRAIN LINE
GROUND STORAGE
TANK DRAIN LINE
P
V
C
N
K
A
I
N
A
I
N
HIBISCUS ROAD
91.78
CONCRETE
SLAB EL. 91.75
BUILDING
F.F. 91.83
FLOW METER
WELL NO. 2
BUILDING
F.F. 91.83
91.61
MATCH
EXISTING
2" SCHEDULE 80 PVC SUMP
PUMP DISCHARGE PIPE
6' HIGH CHAIN LINK FENCE
SUMP PUMP DISCHARGE PIPE
OUTLET AND SPLASH PAD
SEE SHEET C-13 FOR DETAIL
D
I P
T A
A
I N
CONCRETE
SPLASH PAD EL. 90.25
SAW CUT EXISTING
ASPHALT PAVEMENT.
MATCH NEW CONCRETE
PAVEMENT TO EXISTING
91.41
MATCH
EXISTING
PROTECT EXISTING 6" A.C. PIPE
TANK DRAIN DURING CONSTRUCTION
x
R E
D U
C E
R
A
I
N
8" D.I.P. TANK
DRAIN LINE
TANK
DRAIN LINE
91.78
91.70 TOP
OF CURB
DISTRIBUTION
FLOW METER
0.25 MGD
GROUND STORAGE
TANK
0.50 MGD
GROUND STORAGE TANK
G E
N E
R A
T O
R
W E
L L
O
HSP, ELECTRICAL,
AND OPERATIONS
BUILDING
C H
E M
I C
A L
R O
O M
CL2 BULK
STORAGE
FUEL TANK
6'
18.27' 30'
14'6.5'
40.45'
6'
9.1'
16'
10.45'
21.56'
7.5'
SITE DIMENSION LAYOUT AND GATE SENSOR DETECTOR LOOP LOCATIONS
35.33'
23.5'
6" THICK CONCRETE PAVEMENT
SEE SHEET C-15 FOR DETAIL
CONCRETE SIDEWALK
CONCRETE SLAB
6"x18" CONCRETE CURB
AND GRAVEL - SEE
SHEET C-15 FOR DETAIL
EXISTING 8' HIGH, MOTORIZED ROLL
GATE TO REMAIN. CONTRACTOR TO
REMOVE AND REINSTALL ROLL GATE,
GATE POST, AND GATE MOTOR AS
NECESSARY FOR BUILDING CONSTRUCTION
NOTES:
1. SOD ALL DISTURBED AREAS WITHIN CONSTRUCTION SITE.
2. THE SECURITY OF THE WATER TREATMENT PLANT IS TO
BE MAINTAINED AT ALL TIMES DURING THE REMOVAL OF
EXISTING FENCING AND INSTALLATION OF NEW PRE-CAST
CONCRETE POST AND PANEL FENCING AND DURING SITE
CONSTRUCTION.
BOLLARD SEE
FLOOR PLAN
BOLLARD SEE
FLOOR PLAN
GRINDER PUMP
STATION
TOP EL. 91.75
EXISTING POWER POLE
EXISTING GUY WIRES
EXISTING CHAIN LINK
FENCE TO REMAIN
EXISTING GUY WIRE
EXISTING POWER POLE
8' HIGH, PRE-CAST CONCRETE POST AND
PANEL FENCE. SEE DETAIL THIS SHEET
8' HIGH, PRE-CAST CONCRETE POST AND
PANEL FENCE. SEE DETAIL THIS SHEET
ADDITIVE ALTERNATE
8' HIGH, PRE-CAST CONCRETE
POST AND PANEL FENCE.
SEE DETAIL THIS SHEET
ADDITIVE ALTERNATE
REMOVE EXISTING SHRUBS AND
VEGETATION AS NECESSARY
FOR FENCE INSTALLATION
ADDITIVE ALTERNATE
REMOVE EXISTING TREES AS NECESSARY
FOR INSTALLATION OF PRE-CAST CONCRETE
POST AND PANEL FENCE. APPROVAL BY THE
CITY REQUIRED PRIOR TO TREE REMOVAL
DESIGN REQUIREMENTS:
1. PRE-CAST CONCRETE PANEL AND POST TO BE 5000 PSI.
2. FENCE POST CONCRETE FOOTING TO BE 3000 PSI.
3. PRE-CAST CONCRETE POST TO HAVE DECORATIVE PIER CAP.
4. MINIMUM SOIL LATERAL BEARING ALLOWABLE = 150 PSF/FT. OF
DEPTH BELOW GRADE.
5. MINIMUM ALLOWABLE SOIL BEARING PRESSURE = 2000 PSI.
6. DIMENSIONS MAY BE REDUCED TO FIT PROJECT REQUIREMENTS.
7. GROUT BETWEEN POST AND FOOTING TO BE 2500 PSI.
8. FENCE MANUFACTURER TO BE FLORIDA WALL CONCEPTS OR
APPROVED EQUAL. MANUFACTURER TO SUBMIT SIGNED AND
SEALED STRUCTURAL DRAWINGS MEETING BUILDING PERMIT
AND WIND LOAD REQUIREMENTS.
1'-8"
2'-0" DIA.
12'-0"
10" 10"
WALL TOP VIEW
WALL FRONT VIEW
COLUMN TOP VIEW
COLUMN FRONT VIEW
VERTICAL REBAR
HORIZONTAL TIES
(2) TIES AT BASE OF WALL
REBAR 'L' DOWEL
VERTICAL REBAR
HORIZONTAL TIES
3" MIN. CLEARANCE
LOOPED REBAR
1'-2"
REBAR CENTERED IN
PERIMETER OF PANEL WIDTH.
3" MIN. CLEARANCE ALL AROUND
PERIMETER REBAR THRU
LOOP INSERTS (TYP.)
(2) COIL LOOP INSERTS
WITH 1/2" RECESS
(2) COIL LOOP INSERTS WITH 1/2" RECESS
SECTION A-A
PRE-CAST CONCRETE POST AND PANEL FENCE
HAIR PIN
THRU INSERT
GROUT SURFACE
AS REQUIRED
(3) TIES AT TOP OF FOOTER
10'-4"
12'-0"
10" 10" 10'-4"
DECORATIVE PANEL FACE
AA
AA
1'-8"
DETECTOR LOOP REPLACEMENT NOTE:
CONTRACTOR TO REMOVE EXISTING DETECTOR
LOOPS AND INSTALL NEW DETECTOR LOOPS IN
CONCRETE ACCESS DRIVE. CONTRACTOR TO
CONNECT NEW DETECTOR LOOPS/SENSORS
TO EXISTING GATE SYSTEM EQUIPMENT.
SEE SHEET C-15 FOR DETECTOR LOOP DETAIL
EXISTING DETECTOR LOOPS FOR
GATE SENSORS LOCATED UNDER
EXISTING ASPHALT PAVEMENT
NOTES:
1. TRUSS BARS ARE REQUIRED FOR EACH GATE SECTION AND
THE FIRST SPAN ON EACH SIDE OF A CORNER POST ONLY.
2. PROVIDE CHAIN AND LOCK FOR SECURING GATE.
3. FENCING AND POSTS SHALL BE BLACK, VINYL CLAD.
FENCE DETAIL
DOUBLE SWING GATE DETAIL
#9 GALV CLIPS
2'-MAX SPACING
POST CAP
3" POST
CORNER SCH. 40
FINISHED
GRADE
STRETCHER BARS
2" MESH FABRIC
BLACK VINYL
COATED
3/8" ROUND
TRUSS BARS
TURNBUCKLE
#9 TIE WIRES
12" OC
" LINE POST
SCH. 40
TENSION WIRE
2500 PSI
CONCRETE
3" GATE POST
SCH. 40 (TYP)
GATE CORNER
3/8" ADJ
TRUSS RODS
" GATE FRAME
SCH. 40
2500 PSI
CONCRETE
10'-0" TO CENTER (MAX)
" TOP RAIL
SCH. 20 (TYP)
6"
12"
2"
6' 0" 6' 0"
12"
6"
6"
12"
FINISHED GRADE
BOX OUT (TYP)
NOT TO SCALE
CHAIN LINK FENCE AND DOUBLE SWING GATE
CAUTION!
EXISTING TANK DRAIN
TRANSITIONS FROM 6" PVC TO
6" A.C. PIPE. FIELD VERIFY
EXACT LOCATION AND DEPTH.
PROTECT EXISTING A.C. PIPE
DURING CONSTRUCTION
1 7-29-19 SABREVISED PER ADDENDUM NO. 5
6' HIGH x 12' WIDE SWING
GATE WITH BOXOUT
(6' DOUBLE PANELS)
File details come from the government source that posted it. Updated .