Inspection - 2024-08-17_GPO-Building-D_Sprinkler.pdf

PDF 1 MB Posted

Attached to
GPO Fire Alarm and Suppression Systems - Test and Certification of Repaired Components
Solicitation number
040ADV-25-R-0013
Issued by

About this file

This is a fire sprinkler inspection report dated August 17, 2024 for Building D of the Government Publishing Office (GPO) located at 732 North Capitol St. NW in Washington, DC, performed by Everon and certified by inspector Jesse Vizzini. The inspection was conducted according to NFPA 25 standards and evaluated 141 total components across five categories: alarms (38), devices (34), pumps (6), sprinklers (1), and valves (62).

The inspection revealed significant maintenance needs, with only 65.91% of inspected items passing. Key issues identified include: expired gauges requiring replacement or calibration, missing hose valve caps throughout the building, leaking casing relief valve in the pump room, damaged piping requiring immediate replacement, out-of-service pressure switches, and three check valves needing 5-year service. The fire pump test showed acceptable performance readings across three test conditions. Several components on the third floor were noted as "Currently shut down for 3rd floor renovations." All discrepancies are documented with specific locations, part numbers, and NFPA code references, with proposed solutions provided for each issue on a time and materials (T/M) basis.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UEID: LJLDFKJ2VKP5 | CAGE: 5MB43

Government Publishing Office

732 North Capitol St. NW Building D

Washington, DC 20401 Fire Sprinkler Inspection

August 17, 2024

Government Publishing Office 732 North Capitol St NW Washington, DC 20401

HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098

(435) 731-9525

Points of Contact

Mason Barrett, President

Mason@HurtVet.com

Dan Vandergriff, Chief Operating Officer

Dan@HurtVet.com

Jason Munoz, Senior Project Manager

Jason@HurtVet.com

Sprinkler Inspection Certificate For

GPO Building D

732 NORTH CAPITOL ST NW

BUILDING D

WASHINGTON, DC 20401

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 17, 2024

Building: GPO Building D Company: Everon Contact: Jason Munoz Contact: Jesse Vizzini

Title: Senior Project Manager Title: Inspector

Everon 1 Download Date: 09/03/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: GPO Building D Contact: Jason Munoz

Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548

Address: BUILDING D Fax:

City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865

Country: United States of America Email: Jason@hurtvet.com

Inspection Performed By Company: Everon Inspector: Jesse Vizzini

Address: 9108 Guilford Road Phone: 202-236-8024

Address: Suite H Fax:

City/State/ZIP Code: Columbia, MD 21046-2629 Mobile:

Country: United States of America Email: jessevizzini@adt.com

Everon 2 Download Date: 09/03/2024

Inspection Summary

Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %

Alarm 38 26.95% 35 92.11% 31 88.57% 4 11.43% Device 34 24.11% 31 91.18% 20 64.52% 11 35.48% Pump 6 4.26% 6 100.00% 4 66.67% 2 33.33% Sprinkler 1 0.71% 1 100.00% 0 0.00% 1 100.00% Valve 62 43.97% 59 95.16% 32 54.24% 27 45.76%

Totals 141 100% 132 93.62% 87 65.91% 45 34.09%

Certification

Company: Everon Building: GPO Building D

Inspector: Jesse Vizzini Contact: Jason Munoz

Signed: Aug 19, 2024 Signed: Aug 19, 2024

Everon 3 Download Date: 09/03/2024

Discrepancy Report

Building: GPO Building D The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Casing Relief Valve 64643493 Basement Pump Room Leaking

Check Valve 64971864 Basement By Column B-G31 Needs 5 Yr. Service NFPA25 13.4.2.1 64971901 Basement Pump Room Needs 5 Yr. Service NFPA25 13.4.2.1 64971902 Basement Pump Room Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 64971750 Basement By Column B-G5 Dry System Leaking NFPA25 13.3.2.2 (5)

Gauge 64971754 Basement By Column B-G5 Dry system air Guage Date Expired NFPA25 13.2.7.2 64971753 Basement By Column B-G5 Dry system water

Guage Date Expired NFPA25 13.2.7.2

64971761 Basement By Column B-G5 QOD Guage Date Expired NFPA25 13.2.7.2 64971847 Basement Dry System By B-G30 QOD Guage Date Expired NFPA25 13.2.7.2 64971851 Basement Dry System By B-G30 air Date Expired NFPA25 13.2.7.2 64971852 Basement Dry System By B-G30 water Date Expired NFPA25 13.2.7.2 64971716 Basement Pump Room Dry system Air Guage Date Expired NFPA25 13.2.7.2 64971717 Basement Pump Room Dry system Water Guage Date Expired NFPA25 13.2.7.2 64971894 Basement Pump Room Fire Pump discharge Date Expired NFPA25 13.2.7.2 64971895 Basement Pump Room Fire Pump suction Date Expired NFPA25 13.2.7.2 64971712 Basement Pump Room QOD Guage Date Expired NFPA25 13.2.7.2

Hose Valve 64971727 Basement By Column B-G25 Missing cap 64971728 Basement By Column B-G25 Missing cap 64971762 Basement Outside Stair 2 Missing cap 64971763 Basement Outside Stair 2 Missing cap 64971729 Basement Pump Room Missing cap 64971730 Basement Pump Room Missing cap 64971874 1st By Column 1G15 Missing cap 64971875 1st By Column 1G15 Missing cap 64971876 1st Outside Stair 1 Missing cap 64971877 1st Outside Stair 1 Missing cap 64971873 1st Outside Stair 2 Missing cap 64971879 1st Outside Stair 2 Missing cap

Everon 4 Download Date: 09/03/2024

ScanID Location Problem Reference

64971781 2nd By Column B-27 Missing cap 64971777 2nd By Column C-8 Improper Position NFPA25 4.1.4.1 64971799 2nd By Column D-16 Missing cap 64971784 2nd By Column D-25 Missing cap 64971785 2nd By Column D-25 Missing cap 64971798 2nd By Offices D-203 Missing cap 64971802 2nd Outside Stair 2 Missing cap 64971803 2nd Outside Stair 2 Missing cap 64971878 3rd By 3A5 Missing cap 64971883 3rd By 3E15 Missing cap 64971872 3rd By 3E24 Missing cap

Jockey Controller 64971896 Basement Pump Room

Piping 64971748 Basement By Column B-G5 Damaged/Worn NFPA25 5.2.2.1

Pressure Switch 000000008 Basement Dry System By B-G30 Out of service 64971723 Basement Pump Room Out of service

Waterflow Switch 0885585 Basement By Column B-G5 Defective NFPA25 4.1.5.1 08552558 Basement Pump Room Dry Defective NFPA25 4.1.5.1

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

NFPA25 13.3.2.2 (5) The valve inspection shall verify that the valves are in the following condition: Free from external leaks NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

NFPA25 4.1.4.1 The property owner or designated representative shall promptly correct or repair deficiencies or impairments that are found while performing the inspection, test, and maintenance required by this standard.

NFPA25 5.2.2.1 Pipe and fittings shall be in good condition and free of mechanical damage, leakage, and corrosion.

NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.

Everon 5 Download Date: 09/03/2024

Proposed Solutions Report

Building: GPO Building D

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Casing Relief Valve

64643493 Basement Pump Room Replace 551 T/M

Check Valve

64971864 Basement By Column B-G31 5 Year Service 717 T/M

64971901 Basement Pump Room 5 Year Service 717 T/M

64971902 Basement Pump Room 5 Year Service 717 T/M

Control Valve

64971750 Basement By Column B-G5 Dry System Replace E311 T/M

Gauge

64971754 Basement By Column B-G5 Dry system air Guage

Replace 111.10SP.100 T/M

64971753 Basement By Column B-G5 Dry system water Guage

Replace 111.10SP.100 T/M

64971761 Basement By Column B-G5 QOD Guage Replace 111.10SP.100 T/M

64971847 Basement Dry System By B-G30 QOD Guage Replace 111.10SP.100 T/M

64971851 Basement Dry System By B-G30 air Replace 111.10SP.100 T/M

64971852 Basement Dry System By B-G30 water Replace 111.10SP.100 T/M

64971716 Basement Pump Room Dry system Air Guage Replace 111.10SP.100 T/M

64971717 Basement Pump Room Dry system Water Guage

Replace 111.10SP.100 T/M

64971894 Basement Pump Room Fire Pump discharge Replace 111.10SP.100 T/M

64971895 Basement Pump Room Fire Pump suction Replace 111.10SP.100 T/M

64971712 Basement Pump Room QOD Guage Replace 111.10SP.100 T/M

Hose Valve

64971727 Basement By Column B-G25 Replace 175 T/M

64971728 Basement By Column B-G25 Replace 175 T/M

64971762 Basement Outside Stair 2 Replace 175 T/M

64971763 Basement Outside Stair 2 Replace 175 T/M

64971729 Basement Pump Room Replace 175 T/M

64971730 Basement Pump Room Replace 175 T/M

64971874 1st By Column 1G15 Replace 175 T/M

64971875 1st By Column 1G15 Replace 175 T/M

64971876 1st Outside Stair 1 Replace 175 T/M

64971877 1st Outside Stair 1 Replace 175 T/M

64971873 1st Outside Stair 2 Replace 175 T/M

64971879 1st Outside Stair 2 Replace 175 T/M

64971781 2nd By Column B-27 Replace 175 T/M

Everon 6 Download Date: 09/03/2024

ScanID Location Solution Model # Cost Fix

64971777 2nd By Column C-8 Correct 175 T/M

64971799 2nd By Column D-16 Replace 175 T/M

64971784 2nd By Column D-25 Replace 175 T/M

64971785 2nd By Column D-25 Replace 175 T/M

64971798 2nd By Offices D-203 Replace 175 T/M

64971802 2nd Outside Stair 2 Replace 175 T/M

64971803 2nd Outside Stair 2 Replace 175 T/M

64971878 3rd By 3A5 Replace 175 T/M

64971883 3rd By 3E15 Replace 175 T/M

64971872 3rd By 3E24 Replace 175 T/M

Jockey Controller

64971896 Basement Pump Room

Z 1464343 T/M

Piping

64971748 Basement By Column B-G5 Replace

T/M

Pressure Switch

000000008 Basement Dry System By B-G30 Replace

64971723 Basement Pump Room Replace

Waterflow Switch

0885585 Basement By Column B-G5 Replace EPS40-2 T/M

08552558 Basement Pump Room Dry Replace EPS40-2 T/M

PO #: (none) T/M

Everon 7 Download Date: 09/03/2024

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Alternate Power Basement Pump Room Annual 7:39:53 AM 08/02/2024 Fire Pump Off Basement Pump Room Annual 7:41:24 AM 08/02/2024 Fire Pump Running Basement Pump Room Annual 7:41:01 AM 08/02/2024 Pressure Switch Basement Pump Room Annual 12:35:03 PM 08/01/2024 Pressure Switch Basement Dry System By B-G30 Annual 8:38:28 AM 08/02/2024 Tamper Switch Basement By Column B-A1 Backflow valve 1 Annual 11:45:48 AM 08/01/2024 Tamper Switch Basement By Column B-A1 Backflow valve 2 Annual 11:46:25 AM 08/01/2024 Tamper Switch Basement By Column B-G5 Isolation Valve Annual 12:24:16 PM 08/01/2024 Tamper Switch Basement Pump Room Dry System Isolation

Valve Annual 12:44:34 PM 08/01/2024

Tamper Switch Basement Pump Room Backflow Suction Annual 8:15:16 AM 08/02/2024 Tamper Switch Basement Pump Room Backflow Discharge Annual 8:15:35 AM 08/02/2024 Tamper Switch Basement Pump Room Main Supply Valve Annual 8:16:09 AM 08/02/2024 Tamper Switch Basement Dry System By B-G30 Annual 9:22:25 AM 08/02/2024 Tamper Switch Basement Dry System By B-G30 Isolation Valve Annual 9:24:17 AM 08/02/2024 Tamper Switch Basement By Column B-G31 Annual 9:25:45 AM 08/02/2024 Tamper Switch Basement Outaide Stair 3 Annual 9:31:51 AM 08/02/2024 Tamper Switch Basement Pump Room Dry System Annual 9:49:23 AM 08/02/2024 Tamper Switch Basement Pump Room Suction Annual 9:50:21 AM 08/02/2024 Tamper Switch 1st By Column 1G14 Annual 12:45:45 PM 08/02/2024 Tamper Switch 1st By Column 1G6 Annual 12:49:14 PM 08/02/2024 Tamper Switch 1st In Secure Door Annual 7:25:55 AM 08/05/2024 Tamper Switch 2nd By Column E-30 Annual 8:27:36 AM 08/01/2024 Tamper Switch 2nd By Column D-14 Annual 9:23:25 AM 08/01/2024 Tamper Switch 2nd By Column E-6 Annual 9:42:39 AM 08/01/2024 Waterflow Switch Basement By Column B-G5 Isolation Valve Annual 12:23:54 PM 08/01/2024 Waterflow Switch Basement Dry System By B-G30 Annual 9:37:40 AM 08/05/2024 Waterflow Switch 1st By Column 1G14 Annual 12:46:21 PM 08/02/2024 Waterflow Switch 1st By Column 1G6 Annual 12:49:26 PM 08/02/2024 Waterflow Switch 2nd By Column D-14 Annual 9:24:03 AM 08/01/2024 Waterflow Switch 2nd By Column E-30 Annual 9:47:19 AM 08/01/2024 Waterflow Switch 2nd By Column E-6 Annual 12:05:11 PM 08/01/2024 Air Maintenance Device Basement By Column B-G5 Annual 12:04:31 PM 08/01/2024 Air Maintenance Device Basement Pump Room Annual 12:34:17 PM 08/01/2024 Air Maintenance Device Basement Dry System By B-G30 Annual 8:37:39 AM 08/02/2024 Drain Basement By Column B-G5 Annual 12:18:37 PM 08/01/2024 Drain Basement Pump Room Dry System Annual 12:38:07 PM 08/01/2024 Drain Basement Pump Room Annual 12:45:25 PM 08/01/2024 Drain Basement Dry System By B-G30 Annual 9:06:49 AM 08/02/2024 Drain Basement Dry System By B-G30 Isolation Annual 9:09:05 AM 08/02/2024

Everon 8 Download Date: 09/03/2024

Drain Basement By Column B-G5 Annual 12:23:18 PM 08/05/2024 Drain 1st By Column 1G14 Annual 12:43:44 PM 08/02/2024 Drain 1st By Column 1G6 Annual 12:48:49 PM 08/02/2024 Drain 1st In Secure Door Annual 7:27:13 AM 08/05/2024 Drain 2nd By Column B-27 Annual 9:39:57 AM 08/01/2024 Drain 2nd By Column D-8 Annual 9:40:30 AM 08/01/2024 Gauge Basement Pump Room Dry system Air Line

Guage Annual 12:42:34 PM 08/01/2024

Gauge Basement Dry System By B-G30 Air line Annual 9:15:53 AM 08/02/2024 Quick Opening Device Basement By Column B-G5 Annual 12:05:07 PM 08/01/2024 Quick Opening Device Basement Dry System By B-G30 Annual 8:44:05 AM 08/05/2024 Quick Opening Device Basement Pump Room Dry System Annual 9:58:30 AM 08/06/2024 Test Gauge Basement Pump Room Annual 7:51:51 AM 08/02/2024 Controller Basement Pump Room Annual 7:40:15 AM 08/02/2024 Electrical Driver Basement Pump Room Annual 8:07:30 AM 08/02/2024 Jockey Pump Basement Pump Room Annual 8:18:17 AM 08/02/2024 Pump Basement Pump Room Annual 12:52:54 PM 08/17/2024 Backflow Prevention Basement By Column B-A1 Backflow valve 2 Visually Checked 11:51:42 AM 08/01/2024 Backflow Prevention Basement Pump Room Visually Checked 8:13:37 AM 08/02/2024 Control Valve Basement Backup feed by B-A1 Backflow valve

Annual 11:43:51 AM 08/01/2024

Control Valve Basement Backup feed by B-A1 Backflow Valve

Annual 11:44:29 AM 08/01/2024

Control Valve Basement By Column B-G5 Isolation Valve Annual 12:19:36 PM 08/01/2024 Control Valve Basement Pump Room Dry System Annual 12:39:01 PM 08/01/2024 Control Valve Basement Pump Room Dry System Isolation

Valve Annual 12:45:04 PM 08/01/2024

Control Valve Basement Pump Room Annual 7:41:48 AM 08/02/2024 Control Valve Basement Pump Room Jockey Pump Suction Annual 7:44:19 AM 08/02/2024 Control Valve Basement Pump Room bypass 2 Annual 7:49:01 AM 08/02/2024 Control Valve Basement Pump Room bypass 1 Annual 7:49:10 AM 08/02/2024 Control Valve Basement Pump Room Flow guage Discharge Annual 7:54:32 AM 08/02/2024 Control Valve Basement Pump Room Jockey Pump Discharge Annual 7:55:21 AM 08/02/2024 Control Valve Basement Pump Room Test Header Annual 7:56:55 AM 08/02/2024 Control Valve Basement Pump Room Discharge Valve Annual 7:58:33 AM 08/02/2024 Control Valve Basement Pump Room Flow Guage Suction Annual 8:00:28 AM 08/02/2024 Control Valve Basement Pump Room Backflow Discharge

Valve Annual 8:14:03 AM 08/02/2024

Control Valve Basement Pump Room Backflow Suction Valve Annual 8:15:00 AM 08/02/2024 Control Valve Basement Pump Room Main Supply Valve Annual 8:16:47 AM 08/02/2024 Control Valve Basement Dry System By B-G30 Isolation Valve Annual 9:08:23 AM 08/02/2024 Control Valve Basement By Column B-G31 Annual 9:17:06 AM 08/02/2024 Control Valve Basement Outaide Stair 3 Annual 9:31:22 AM 08/02/2024 Control Valve 1st By Column 1G14 Annual 12:46:12 PM 08/02/2024 Control Valve 1st By Column 1G6 Annual 12:49:02 PM 08/02/2024 Control Valve 1st In Secure Door Annual 7:26:56 AM 08/05/2024 Control Valve 2nd By Column E-30 Annual 8:30:10 AM 08/01/2024 Control Valve 2nd By Column D-14 Annual 9:23:46 AM 08/01/2024 Control Valve 2nd By Column E-6 Annual 9:42:17 AM 08/01/2024 Dry Pipe Valve Basement By Column B-G5 Annual 12:08:21 PM 08/01/2024 Dry Pipe Valve Basement Pump Room Annual 12:37:45 PM 08/01/2024 Dry Pipe Valve Basement Dry System By B-G30 Annual 8:44:28 AM 08/05/2024

Everon 9 Download Date: 09/03/2024

Hose Valve Basement Pump Room Annual 8:10:15 AM 08/02/2024

Failed/Other Pressure Switch Basement Dry System By B-G30 Annual 9:39:23 AM 08/05/2024 Pressure Switch Basement Pump Room Annual 12:48:22 PM 08/05/2024 Waterflow Switch Basement By Column B-G5 Annual 12:26:04 PM 08/05/2024 Waterflow Switch Basement Pump Room Dry Annual 12:50:10 PM 08/05/2024 Gauge Basement By Column B-G5 QOD Guage Annual 12:02:58 PM 08/01/2024 Gauge Basement By Column B-G5 Dry system air

Guage Annual 12:06:35 PM 08/01/2024

Gauge Basement By Column B-G5 Dry system water Guage

Annual 12:07:34 PM 08/01/2024

Gauge Basement Pump Room QOD Guage Annual 12:33:27 PM 08/01/2024 Gauge Basement Pump Room Dry system Air Guage Annual 12:36:45 PM 08/01/2024 Gauge Basement Pump Room Dry system Water Guage Annual 12:37:21 PM 08/01/2024 Gauge Basement Pump Room Fire Pump discharge Annual 8:11:22 AM 08/02/2024 Gauge Basement Pump Room Fire Pump suction Annual 8:11:50 AM 08/02/2024 Gauge Basement Dry System By B-G30 air Annual 8:40:42 AM 08/02/2024 Gauge Basement Dry System By B-G30 water Annual 9:03:13 AM 08/02/2024 Gauge Basement Dry System By B-G30 QOD Guage Annual 8:43:53 AM 08/05/2024 Casing Relief Valve Basement Pump Room Annual 12:24:38 PM 08/17/2024 Jockey Controller Basement Pump Room Annual 9:50:16 AM 08/02/2024 Piping Basement By Column B-G5 Annual 12:25:09 PM 08/05/2024 Check Valve Basement Pump Room Annual 7:50:55 AM 08/02/2024 Check Valve Basement Pump Room Annual 7:53:04 AM 08/02/2024 Check Valve Basement By Column B-G31 Annual 9:18:57 AM 08/02/2024 Control Valve Basement By Column B-G5 Dry System Annual 12:24:56 PM 08/05/2024 Hose Valve Basement Outside Stair 2 Annual 11:54:26 AM 08/01/2024 Hose Valve Basement Outside Stair 2 Annual 12:00:20 PM 08/01/2024 Hose Valve Basement By Column B-G25 Annual 1:02:31 PM 08/01/2024 Hose Valve Basement By Column B-G25 Annual 1:04:04 PM 08/01/2024 Hose Valve Basement Pump Room Annual 1:04:36 PM 08/01/2024 Hose Valve Basement Pump Room Annual 1:05:19 PM 08/01/2024 Hose Valve 1st Outside Stair 2 Annual 12:24:47 PM 08/02/2024 Hose Valve 1st Outside Stair 2 Annual 12:28:14 PM 08/02/2024 Hose Valve 1st Outside Stair 1 Annual 12:34:32 PM 08/02/2024 Hose Valve 1st Outside Stair 1 Annual 12:35:21 PM 08/02/2024 Hose Valve 1st By Column 1G15 Annual 12:41:43 PM 08/02/2024 Hose Valve 1st By Column 1G15 Annual 12:42:37 PM 08/02/2024 Hose Valve 2nd Outside Stair 2 Annual 7:47:07 AM 08/01/2024 Hose Valve 2nd Outside Stair 2 Annual 7:52:55 AM 08/01/2024 Hose Valve 2nd By Column C-8 Annual 7:54:13 AM 08/01/2024 Hose Valve 2nd By Column B-27 Annual 8:26:19 AM 08/01/2024 Hose Valve 2nd By Column D-25 Annual 8:42:26 AM 08/01/2024 Hose Valve 2nd By Column D-25 Annual 8:43:08 AM 08/01/2024 Hose Valve 2nd By Column D-16 Annual 9:16:25 AM 08/01/2024 Hose Valve 2nd By Offices D-203 Annual 9:38:55 AM 08/01/2024 Hose Valve 3rd By 3E15 Annual 11:14:54 AM 08/02/2024 Hose Valve 3rd By 3E24 Annual 11:16:35 AM 08/02/2024 Hose Valve 3rd By 3A5 Annual 11:23:21 AM 08/02/2024

Untested Tamper Switch 3rd By Column 3E5

Everon 10 Download Date: 09/03/2024

Tamper Switch 3rd By Column 3E14 Tamper Switch 3rd By Column 3E28 Drain 3rd By Column 3E5 Drain 3rd By Column 3E14 Drain 3rd By Column 3E28 Control Valve 3rd By Column 3E5 Control Valve 3rd By Column 3E14 Control Valve 3rd By Column 3E28

Everon 11 Download Date: 09/03/2024

Fire Pump Testing

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Pump

Manufacturer Model Number Location Install Date ScanID Peerless Pump 6AEF14 Basement Pump Room 08/01/2003 64971844

Serial Number Type Orientation Aligned? Water Supply Impeller Size Pump Primary 45 Yes Municipal 11.13

Fire Pump Tests

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water Temperature

Other 08/17/2024 118 62 0 1790

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

25 27 28 496 497 498

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 95 44 1008 1754

45 45 47 495 495 496

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 65 22 1512 1767

56 56 57 494 497 494

Fire Pump Rating

Amps Volts

Net Pressure Gallons Per Minute

Rotations Per Minute A B C A-B B-C A-C

56 0

50 1000

43 1500

Everon 12 Download Date: 09/03/2024

Everon 13 Download Date: 09/03/2024

Inventory & Warranty Report

Building: GPO Building D

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Air Maintenance Device Device 2.13% 3

Alternate Power Alarm 0.71% 1

Backflow Prevention Valve 1.42% 2

Casing Relief Valve Pump 0.71% 1

Check Valve Valve 2.13% 3

Control Valve Valve 21.28% 30

Controller Pump 0.71% 1

Drain Device 9.93% 14

Dry Pipe Valve Valve 2.13% 3

Electrical Driver Pump 0.71% 1

Fire Pump Off Alarm 0.71% 1

Fire Pump Running Alarm 0.71% 1

Gauge Device 9.22% 13

Hose Valve Valve 17.02% 24

Jockey Controller Pump 0.71% 1

Jockey Pump Pump 0.71% 1

Piping Sprinkler 0.71% 1

Pressure Switch Alarm 2.84% 4

Pump Pump 0.71% 1

Quick Opening Device Device 2.13% 3

Tamper Switch Alarm 15.60% 22

Test Gauge Device 0.71% 1

Waterflow Switch Alarm 6.38% 9

Device Type

Qt y Model # Type Description Install Date

New (under 90 days)

Hose Valve 14 175

08/01/2024

Hose Valve 10 175

Pressure Switch 1

Low Supervisory 08/01/2024

Pressure Switch 1

Low Air Supervisory 08/01/2024

Waterflow Switch 1

Pressure Switch Alarm 08/01/2024

Control Valve 1

OS&Y Suction 08/01/2024

Control Valve 2 175

Control Valve 9 175 OS&Y

Tamper Switch 1 OSYU-2 Lever

Waterflow Switch 1 VSR-1

Waterflow Switch 1 VSR-1 Vane

Waterflow Switch 4 VSR-1 Vane Alarm 08/01/2024

Pressure Switch 2 EPS40-2 Waterflow Alarm 08/01/2024

Tamper Switch 6 OSY2 Lever

Tamper Switch 10 OSY2 Lever Supervisory 08/01/2024

Tamper Switch 1 PSP1 Lever Supervisory 08/01/2024

Everon 14 Download Date: 09/03/2024

Tamper Switch 2 osy2 Lever

Tamper Switch 2 psp1 Lever

Quick Opening Device 3

Alternate Power 1 Z 150608

Controller 1 Z 150608

Automatic 08/01/2024

Fire Pump Off 1 Z 150608

Supervisory 08/01/2024

Fire Pump Running 1 Z 150608

Supervisory 08/01/2024

Jockey Controller 1 Z 1464343

Drain 11

Auxiliary

Check Valve 2 717 Grooved

Control Valve 8 728 Butterfly

Test Gauge 1 717

Gauge 4 111.10SP.100 Quick Opening Device

Backflow Prevention 1 350AST Double Check Detecto

Backflow Prevention 1 350 Double Check Detecto

Air Maintenance Device 3 D27254 Pressure Reducing

In Service - 5 Years to 10 Years

Gauge 2 111.10SP.100 Supply Pressure

08/01/2015

In Service - 15 Years to 25 Years

Piping 1

Steel

08/01/2003

Jockey Pump 1

Automatic

Casing Relief Valve 1 551

Electrical Driver 1 PVF324TTDTP4038

CDL

Control Valve 5 E311 OS&Y

Pump 1 6AEF14 Pump Primary

Waterflow Switch 2 EPS40-2 Pressure Switch Alarm 08/01/2003

Dry Pipe Valve 3 DPV-1 Flanged

Drain 3 200 wog Main

Gauge 1 111.10SP.100 Air Pressure

Gauge 6 111.10SP.100 Supply Pressure

Control Valve 5 MDL48 OS&Y

In Service - 25 Years or Older

Check Valve 1 717 Flanged

08/01/1990

Everon 15 Download Date: 09/03/2024

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.

Address Device Type Location Type ScanID

Control Panel 1 Zone/Address: ZN

Tamper Switch Basement Outaide Stair 3 Lever 64971884 Tamper Switch Basement Pump Room Backflow Discharge Lever 64971889 Tamper Switch Basement Pump Room Backflow Suction Lever 64971888 Tamper Switch Basement Pump Room Dry System Isolation

Valve Lever 64971724

Tamper Switch Basement Pump Room Main Supply Valve Lever 64971885

Zone/Address: ZN105 L002D0129 Tamper Switch Basement Pump Room Dry System Lever 64971720 L002D0131 Control Valve Basement By Column B-G5 Dry System OS&Y 64971750

Zone/Address: ZN106 L002D0131 Tamper Switch Basement By Column B-G31 Lever 64971862 L002D0131 Tamper Switch Basement Dry System By B-G30 Lever 64971855 L002D0131 Tamper Switch Basement Dry System By B-G30 Isolation

Valve Lever 64971857

Zone/Address: Zn106 L002D0126 Waterflow Switch Basement Dry System By B-G30 Pressure Switch 64971860 L002D0126 Pressure Switch Basement Dry System By B-G30 Low 000000008

Zone/Address: Zn107 L002D0131 Tamper Switch 1st By Column 1G14 Lever 64972097 L002D0131 Tamper Switch 1st By Column 1G6 Lever 64971982 L002D0131 Waterflow Switch 1st By Column 1G6 Vane 64971981 L002D0131 Tamper Switch 1st In Secure Door Lever 64971913

Zone/Address: Zn109 L002D0131 Tamper Switch 2nd By Column D-14 Lever 64971789 L002D0131 Tamper Switch 2nd By Column E-6 Lever 64971797 L002D0131 Tamper Switch 3rd By Column 3E14 Lever 64971869 L002D0131 Tamper Switch 3rd By Column 3E28 Lever 64971882 L002D0131 Tamper Switch 3rd By Column 3E5 Lever 64971867

Zone/Address: Zn110 L002D0131 Tamper Switch Basement By Column B-A1 Backflow valve 1 Lever 64971792 L002D0131 Tamper Switch Basement By Column B-A1 Backflow valve 2 Lever 64971765 L002D0131 Control Valve Basement Pump Room Discharge Valve Butterfly 64971906 L002D0131 Control Valve Basement Pump Room Flow Guage Suction Butterfly 64971905 L002D0131 Control Valve Basement Pump Room Flow guage

Butterfly 64971900

Everon 16 Download Date: 09/03/2024

L002D0131 Control Valve Basement Pump Room Jockey Pump

Butterfly 64971907

L002D0131 Control Valve Basement Pump Room Jockey Pump Suction Butterfly 64971897 L002D0131 Tamper Switch Basement Pump Room Suction Lever 64971898 L002D0131 Control Valve Basement Pump Room Test Header Butterfly 64971892 L002D0131 Control Valve Basement Pump Room bypass 1 Butterfly 64971904 L002D0131 Control Valve Basement Pump Room bypass 2 Butterfly 64971903 L002D0131 Tamper Switch 2nd By Column E-30 Lever 64971783

Everon 17 Download Date: 09/03/2024

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID 1 Casing Relief Valve Basement Pump Room Leaking 64643493

Found closed all the way before pump test. Opened to preform test. Valve leaks by when pump is not running. Replace.

2 Control Valve Basement By Column B-G31 Passed 64971863 Backup supply

3 Piping Basement By Column B-G5 Damaged/Worn 64971748 Section in picture needs to be replaced ASAP. also due for 5 year internal inspection

4 Pressure Switch Basement Dry System By B-G30 Out of service 000000008 Replace with new high Low air device.

5 Pressure Switch Basement Pump Room Out of service 64971723 Replace with new high Low air device.

6 Hose Valve 2nd By Column C-8 Improper Position 64971777 Spin down

7 Control Valve 3rd By Column 3E5 64971866 Currently shut down for 3rd floor renovations.

8 Control Valve 3rd By Column 3E14 64971870 Currently shut down for 3rd floor renovations.

9 Control Valve 3rd By Column 3E28 64971881 Currently shut down for 3rd floor renovations.

10 Drain 3rd By Column 3E5 64971868 Currently shut down for 3rd floor renovations.

11 Tamper Switch 3rd By Column 3E5 64971867 Currently shut down for 3rd floor renovations.

12 Tamper Switch 3rd By Column 3E14 64971869 Currently shut down for 3rd floor renovations.

13 Tamper Switch 3rd By Column 3E28 64971882 Currently shut down for 3rd floor renovations.

File details come from the government source that posted it. Updated .