Inspection - 2024-08-17_GPO-Building-A_Sprinkler.pdf

PDF 1 MB Posted

Attached to
GPO Fire Alarm and Suppression Systems - Test and Certification of Repaired Components
Solicitation number
040ADV-25-R-0013
Issued by

About this file

This is a fire sprinkler inspection report conducted on August 17, 2024 by Everon for the Government Publishing Office (GPO) Building A located at 732 North Capitol St NW in Washington, DC. The inspection was performed in accordance with NFPA 25 standards and included testing of 261 total components across five categories: alarms (59 items), devices (25 items), pumps (7 items), sprinklers (7 items), and valves (163 items).

The inspection revealed significant issues requiring attention, with only 61.69% of components passing inspection. Key deficiencies include expired gauges throughout the building, missing hose valve caps, leaking casing relief valve in the basement pump room, failed tamper switches and waterflow switches, and two dry pipe valve systems lacking required inspector's test points. The fire pump testing showed readings at various flow rates (0 GPM at 165 psi, 1008 GPM at 155 psi, and 1512 GPM at 116 psi). The report includes detailed recommendations for repairs and replacements, with most items listed as Time and Materials (T/M) basis work. The inspection was certified by Jesse Vizzini of Everon and Jason Munoz of HurtVet Subcontracting on August 19, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UEID: LJLDFKJ2VKP5 | CAGE: 5MB43

Government Publishing Office

732 North Capitol St. NW Building A

Washington, DC 20401 Fire Sprinkler Inspection

August 17, 2024

Government Publishing Office 732 North Capitol St NW Washington, DC 20401

HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098

(435) 731-9525

Points of Contact

Mason Barrett, President

Mason@HurtVet.com

Dan Vandergriff, Chief Operating Officer

Dan@HurtVet.com

Jason Munoz, Senior Project Manager

Jason@HurtVet.com

Sprinkler Inspection Certificate For

GPO Building A

732 NORTH CAPITOL ST NW

BUILDING A

WASHINGTON, DC 20401

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 17, 2024

Building: GPO Building A Company: Everon Contact: Jason Munoz Contact: Jesse Vizzini

Title: Senior Project Manager Title: Inspector

Everon 1 Download Date: 09/03/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: GPO Building A Contact: Jason Munoz

Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548

Address: BUILDING A Fax:

City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865

Country: United States of America Email: Jason@hurtvet.com

Inspection Performed By Company: Everon Inspector: Jesse Vizzini

Address: 9108 Guilford Road Phone: 202-236-8024

Address: Suite H Fax:

City/State/ZIP Code: Columbia, MD 21046-2629 Mobile:

Country: United States of America Email: jessevizzini@adt.com

Everon 2 Download Date: 09/03/2024

Inspection Summary

Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %

Alarm 59 22.61% 59 100.00% 51 86.44% 8 13.56% Device 25 9.58% 25 100.00% 10 40.00% 15 60.00% Pump 7 2.68% 7 100.00% 6 85.71% 1 14.29% Sprinkler 7 2.68% 7 100.00% 3 42.86% 4 57.14% Valve 163 62.45% 163 100.00% 91 55.83% 72 44.17%

Totals 261 100% 261 100.00

161 61.69% 100 38.31%

Certification

Company: Everon Building: GPO Building A

Inspector: Jesse Vizzini Contact: Jason Munoz

Signed: Aug 19, 2024 Signed: Aug 19, 2024

Everon 3 Download Date: 09/03/2024

Discrepancy Report

Building: GPO Building A The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Casing Relief Valve 619437649 Basement Pump Room Leaking

Check Valve 96937567 Basement Pump Room Discharge Needs 5 Yr. Service NFPA25 13.4.2.1 96937568 Basement Pump Room Discharge Needs 5 Yr. Service NFPA25 13.4.2.1 96937591 Basement Pump Room Standpipe Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 96937565 Basement Pump Room Damaged/Worn NFPA25 13.2.3

Dry Pipe Valve 96937038 3rd Inside Stair 3 Dry System Inspectors test 96937356 8th Outside Stair 2 in sprinkler closet No inspectors test

Gauge 96937569 Basement Pump Room Discharge Guage Date Expired NFPA25 13.2.7.2 96937581 Basement Pump Room Discharge Guage Date Expired NFPA25 13.2.7.2 96937583 Basement inside Room A052 Date Expired NFPA25 13.2.7.2 96937427 3rd Inside Stair 3 Dry System Date Expired NFPA25 13.2.7.2 96937428 3rd Inside Stair 3 Dry System Date Expired NFPA25 13.2.7.2 96937409 4th Inside Stair 2 Pre Action System Date Expired NFPA25 13.2.7.2 96937407 4th Inside Stair 2 Pre Action System Date Expired NFPA25 13.2.7.2 96937408 4th Inside Stair 2 Pre Action System Date Expired NFPA25 13.2.7.2 96937410 4th Inside Stair 2 Pre Action System Date Expired NFPA25 13.2.7.2 96937314 8th Inside Stair 2 Date Expired NFPA25 13.2.7.2 96937317 8th Inside Stair 2 Date Expired NFPA25 13.2.7.2 96937322 8th Inside Stair 4 Date Expired NFPA25 13.2.7.2 96937310 8th Outside Stair 2 in sprinkler closet Date Expired NFPA25 13.2.7.2 96937355 8th Outside Stair 2 in sprinkler closet Date Expired NFPA25 13.2.7.2

Hose Valve 96937510 Basement by Shaft 1 Missing cap 96937515 Basement by Shaft 2 Missing cap 96937516 Basement by Shaft 3 Missing cap 96937517 Basement by Shaft 4 Missing cap 96937504 Basement by Shaft 9 Missing cap 96937721 Basement inside Room 41000 Missing cap

Everon 4 Download Date: 09/03/2024

96937534 1st By Jackson alley Missing cap 96937525 1st In Cage Outside Stair 3 Missing cap 96937535 1st Outside Stair 2 Missing cap 96937523 1st Security post 38 Missing cap 96937556 2nd by Room A257A Missing cap 96937555 2nd by Room A259 Missing cap 96937417 2nd Outside Stair 4 Missing cap 96937549 2nd by A207 Missing cap 96937548 2nd by A211 Missing cap 96937541 2nd by Room 268 Missing cap 96938003 3rd Inside NARA Room Aisle 20 Inaccessible NFPA25 4.1.2 96938002 3rd Inside NARA Room Aisle 33 Inaccessible NFPA25 4.1.2 96938000 3rd Inside NARA Room Aisle 56 Inaccessible NFPA25 4.1.2 96937999 3rd Inside NARA Room Aisle 61 Incompatible NFPA25 4.1.4.1 96937432 3rd Inside Stair 2 Missing cap 96937049 3rd Inside Stair 4 Missing cap 96937449 4th Inside AOC Carpemters Shop Missing cap 96937450 4th Inside AOC Carpemters Shop Missing cap 96937453 4th Inside Room A426 Missing cap 96937452 4th Outside Stair 4 Missing cap 96937454 4th by Column 4E16 Missing cap 96937439 4th by Column 4E5 Missing cap 96937436 4th by Shaft 2 Missing cap 96937448 4th by Shaft 3 Damaged/Worn NFPA25 13.6.1.2 –

13.6.1.5 96937455 4th by Shaft 9 Missing cap 96937728 5th Inside Room A525 Missing cap 96937394 5th by BALER access Leaking NFPA25 13.6.2.1.1;

13.6.2.2.1 96937397 5th by Room A505A Missing cap 96937396 5th by Room A505B Missing cap 96937460 5th by shaft 10 Missing cap 96937398 5th by shaft 2 Missing cap 96937459 5th by shaft 9 Missing cap 96937477 6th Outside Stair 2 Missing cap 96937443 6th by Elevator 7 & 8 Missing cap 96937468 6th by Room A623A Missing cap 96937467 6th by Room A624 Missing cap 96937474 6th by Room A634 Missing cap 96937470 6th by Room A636 Missing cap 96937442 6th by Room A639 Missing cap 96937475 6th by Room A662 Missing cap 96937622 6th by column 6E16 Missing cap 96937623 6th by column 6E21 Missing cap 96937346 7th Outside Stair 4 Missing cap 96937320 7th by Room A720 Missing cap 96937319 7th by Room A750 Missing cap 96937592 8th Inside of Stairs to Roof Missing cap

Inspector's Test 96937499 Basement Inside Stair 3 Incorrect Application NFPA25 4.1.5.1 96937584 Basement for Stair 2 inside Room A052 Incorrect Application NFPA25 4.1.5.1 96937536 1st Inside Stair 2 Incorrect Application NFPA25 4.1.5.1

Everon 5 Download Date: 09/03/2024

96937526 1st Inside Stair 3 Incorrect Application NFPA25 4.1.5.1 96937550 2nd Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96937543 2nd Inside Stair 3 Incorrect Application NFPA25 4.1.5.1 96937420 3rd Inside Stair 3 Dry System Incorrect Application NFPA25 4.1.5.1 96937419 3rd Inside Stair 3 wet System Incorrect Application NFPA25 4.1.5.1 96937411 4th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96937456 4th Inside Stair 3 Incorrect Application NFPA25 4.1.5.1 96937462 5th Inside Stair 2 96937399 5th Inside Stair 3 Incorrect Application NFPA25 4.1.5.1 96937478 6th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96937444 6th Inside Stair 3 Incorrect Application NFPA25 4.1.5.1

Piping 96937594 Basement Pump Room Needs 5 yr. service NFPA25 14.2.1.1

Sprinkler Box 96937561 Basement Pump Room Missing wrench 96937562 Basement Pump Room Missing wrench 96937422 4th Inside Stair 2 Missing head wrenches

Tamper Switch 96937725 Basement Inside Room 41000 Failed Annunciation 96937726 Basement Inside Room A019 Failed annunciation 96937540 1st Inside Stair 2 Failed Test NFPA25 13.3.3.5.2 96937035 3rd Inside Stair 3 Dry System Failed Test NFPA25 13.3.3.5.2

Waterflow Switch 96937531 1st Inside Bailer Room 96937458 4th Inside Stair 3 Failed Flow Test NFPA25 4.1.5.1 96937446 6th Inside Stair 3 Failed Flow Test NFPA25 4.1.5.1 96937329 7th Inside Stair 3 Failed Flow Test NFPA25 4.1.5.1

Supplies 4th floor Pre actio Gauge

96937590 3rd Switch Gear by Capitol Police Storage Date Expired NFPA25 13.2.7.2

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

NFPA25 13.2.3 All system valves shall be protected from physical damage and shall be accessible.

NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

NFPA25 4.1.2 The property owner or designated representative shall provide ready accessibility to components of water-based fire protection systems that require inspection, testing, and maintenance.

NFPA25 4.1.4.1 The property owner or designated representative shall promptly correct or repair deficiencies or impairments that are found while performing the inspection, test, and maintenance required by this standard.

NFPA25 13.6.1.2 –

13.6.1.5

Hose valves shall be inspected to ensure that hose caps are in place and not damaged. Hose threads shall be inspected for damage. Valve handles shall be present and not damaged. Gaskets shall be inspected for damage for deterioration.

NFPA25 13.6.2.1.1;

13.6.2.2.1

Class I and Class III standpipe system hose valves that are difficult to operate or leak shall be repaired or replaced. Hose valves on hose stations attached to sprinkler systems and Class II standpipe systems that are difficult to operate or leak shall be repaired or replaced.

NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.

NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

Everon 6 Download Date: 09/03/2024 the purpose of inspecting for the presence of foreign organic and inorganic material.

NFPA25 13.3.3.5.2 A distinctive signal shall indicate movement from the valve's normal position during either the first two revolutions of a hand wheel or when the stem of the valve has moved one-fifth of the distance from its normal position.

Everon 7 Download Date: 09/03/2024

Proposed Solutions Report

Building: GPO Building A

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Casing Relief Valve

619437649 Basement Pump Room Replace 551 T/M

Check Valve

96937567 Basement Pump Room Discharge 5 Year Service 717 T/M

96937568 Basement Pump Room Discharge 5 Year Service 717 T/M

96937591 Basement Pump Room Standpipe 5 Year Service 75 T/M

Control Valve

96937565 Basement Pump Room Replace

T/M

Dry Pipe Valve

96937038 3rd Inside Stair 3 Dry System Correct DPV-1 T/M

96937356 8th Outside Stair 2 in sprinkler closet correct

Gauge

96937569 Basement Pump Room Discharge Guage Replace

96937581 Basement Pump Room Discharge Guage Replace

96937583 Basement inside Room A052 Replace 111.10S0.100 T/M

96937427 3rd Inside Stair 3 Dry System Replace 111.10S0.100 T/M

96937428 3rd Inside Stair 3 Dry System Replace 111.10S0.100 T/M

96937409 4th Inside Stair 2 Pre Action System Replace 111.10S0.100 T/M

96937407 4th Inside Stair 2 Pre Action System Replace 111.10S0.100 T/M

96937408 4th Inside Stair 2 Pre Action System Replace 111.10S0.100 T/M

96937410 4th Inside Stair 2 Pre Action System Replace 111.10S0.100 T/M

96937314 8th Inside Stair 2 Replace R1590 T/M

96937317 8th Inside Stair 2 Replace R1590 T/M

96937322 8th Inside Stair 4 Replace R1590 T/M

96937310 8th Outside Stair 2 in sprinkler closet Replace R1590 T/M

96937355 8th Outside Stair 2 in sprinkler closet Replace R1590 T/M

Hose Valve

96937510 Basement by Shaft 1 Replace 1 1/2 T/M

96937515 Basement by Shaft 2 Replace 1 1/2 T/M

96937516 Basement by Shaft 3 Replace 1 1/2 T/M

96937517 Basement by Shaft 4 Replace 1 1/2 T/M

96937504 Basement by Shaft 9 Replace 1 1/2 T/M

96937721 Basement inside Room 41000 Replace 1 1/2 T/M

96937534 1st By Jackson alley Replace 1 1/2 T/M

96937525 1st In Cage Outside Stair 3 Replace 1 1/2 T/M

96937535 1st Outside Stair 2 Replace 1 1/2 T/M

Everon 8 Download Date: 09/03/2024

96937523 1st Security post 38 Replace 1 1/2 T/M

96937556 2nd by Room A257A Replace 1 1/2 T/M

96937555 2nd by Room A259 Replace 1 1/2 T/M

96937417 2nd Outside Stair 4 Replace 1 1/2 T/M

96937549 2nd by A207 Replace 2 1/2 T/M

96937548 2nd by A211 Replace 2 1/2 T/M

96937541 2nd by Room 268 Replace 2 1/2 T/M

96938003 3rd Inside NARA Room Aisle 20 Correct 1 1/2 T/M

96938002 3rd Inside NARA Room Aisle 33 Correct 1 1/2 T/M

96938000 3rd Inside NARA Room Aisle 56 Correct 1 1/2 T/M

96937999 3rd Inside NARA Room Aisle 61 Correct 1 1/2 T/M

96937432 3rd Inside Stair 2 Replace 2 1/2 T/M

96937049 3rd Inside Stair 4 Replace 2 1/2 T/M

96937449 4th Inside AOC Carpemters Shop Replace 1 1/2 T/M

96937450 4th Inside AOC Carpemters Shop Replace 1 1/2 T/M

96937453 4th Inside Room A426 Replace 1 1/2 T/M

96937452 4th Outside Stair 4 Replace 1 1/2 T/M

96937454 4th by Column 4E16 Replace 1 1/2 T/M

96937439 4th by Column 4E5 Replace 1 1/2 T/M

96937436 4th by Shaft 2 Replace 1 1/2 T/M

96937448 4th by Shaft 3 Replace 1 1/2 T/M

96937455 4th by Shaft 9 Replace 1 1/2 T/M

96937728 5th Inside Room A525 Replace 2 1/2 T/M

96937394 5th by BALER access Replace 1 1/2 T/M

96937397 5th by Room A505A Replace 2 1/2 T/M

96937396 5th by Room A505B Replace 2 1/2 T/M

96937460 5th by shaft 10 Replace 2 1/2 T/M

96937398 5th by shaft 2 Replace 2 1/2 T/M

96937459 5th by shaft 9 Replace 2 1/2 T/M

96937477 6th Outside Stair 2 Replace 1 1/2 T/M

96937443 6th by Elevator 7 & 8 Replace 1 1/2 T/M

96937468 6th by Room A623A Replace 1 1/2 T/M

96937467 6th by Room A624 Replace 1 1/2 T/M

96937474 6th by Room A634 Replace 1 1/2 T/M

96937470 6th by Room A636 Replace 1 1/2 T/M

96937442 6th by Room A639 Replace 1 1/2 T/M

96937475 6th by Room A662 Replace 1 1/2 T/M

96937622 6th by column 6E16 Replace 1 1/2 T/M

96937623 6th by column 6E21 Replace 1 1/2 T/M

96937346 7th Outside Stair 4 Replace 1 1/2 T/M

96937320 7th by Room A720 Replace 1 1/2 T/M

96937319 7th by Room A750 Replace 1 1/2 T/M

96937592 8th Inside of Stairs to Roof Replace 1 1/2 T/M

Inspector's Test

96937499 Basement Inside Stair 3 Correct OSY2 T/M

96937584 Basement for Stair 2 inside Room A052 Correct OSY2 T/M

96937536 1st Inside Stair 2 Correct OSY2 T/M

96937526 1st Inside Stair 3 Correct OSY2 T/M

96937550 2nd Inside Stair 2 Correct OSY2 T/M

96937543 2nd Inside Stair 3 Correct OSY2 T/M

96937420 3rd Inside Stair 3 Dry System Correct OSY2 T/M

96937419 3rd Inside Stair 3 wet System Correct OSY2 T/M

Everon 9 Download Date: 09/03/2024

96937411 4th Inside Stair 2 Correct OSY2 T/M

96937456 4th Inside Stair 3 Correct OSY2 T/M

96937462 5th Inside Stair 2

OSY2 T/M

96937399 5th Inside Stair 3 Correct OSY2 T/M

96937478 6th Inside Stair 2 Replace OSY2 T/M

96937444 6th Inside Stair 3 Correct OSY2 T/M

Piping

96937594 Basement Pump Room 5 Year Service 2R97 T/M

Sprinkler Box

96937561 Basement Pump Room Replace

96937562 Basement Pump Room Replace

96937422 4th Inside Stair 2 Replace

Tamper Switch

96937725 Basement Inside Room 41000 Correct 1821 T/M

96937726 Basement Inside Room A019 Correct 1821 T/M

96937540 1st Inside Stair 2 Correct 1821 T/M

96937035 3rd Inside Stair 3 Dry System Replace head wrenches

OSY-2 T/M

Waterflow Switch

96937531 1st Inside Bailer Room

FS43 T/M

96937458 4th Inside Stair 3 Correct WFD40 T/M

96937446 6th Inside Stair 3 Correct WFD40 T/M

96937329 7th Inside Stair 3 Correct WFD40 T/M

Supplies 4th floor Pre actio

Gauge

96937590 3rd Switch Gear by Capitol Police Storage Replace

PO #: (none) T/M

Everon 10 Download Date: 09/03/2024

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Alternate Power Basement Pump Room Annual 7:17:57 AM 07/19/2024 Fire Pump Off Basement Pump Room Annual 7:20:57 AM 07/19/2024 Fire Pump Running Basement Pump Room Annual 7:20:37 AM 07/19/2024 Pressure Switch 4th Inside Stair 2 Pre Action System Annual 8:31:58 AM 07/18/2024 Pressure Switch 4th Inside Stair 2 Pre Action System Annual 8:32:39 AM 07/18/2024 Tamper Switch Basement Outside Stair 4 Annual 12:24:08 PM 07/18/2024 Tamper Switch Basement Inside Stair 2 Annual 12:32:47 PM 07/18/2024 Tamper Switch Basement Outside Stair 4 Annual 12:37:29 PM 07/18/2024 Tamper Switch Basement by Room A055 Annual 12:41:41 PM 07/18/2024 Tamper Switch Basement Inside Stair 3 Annual 12:45:52 PM 07/18/2024 Tamper Switch Basement Outide Stair 3 Annual 12:49:17 PM 07/18/2024 Tamper Switch Basement Pump Room Annual 7:54:28 AM 07/19/2024 Tamper Switch Basement Backflow Discharge Annual 7:56:39 AM 07/19/2024 Tamper Switch Basement Backflow Suction Annual 7:57:21 AM 07/19/2024 Tamper Switch Basement Pump Room Main Incoming Contorl

Valve Annual 8:04:06 AM 07/19/2024

Tamper Switch Basement Pump Room Suction Valve Annual 8:17:34 AM 07/19/2024 Tamper Switch Basement in Room A052 Annual 1:07:48 PM 07/19/2024 Tamper Switch Basement Inside Room 41000 in air Annual 9:39:16 AM 07/22/2024 Tamper Switch Basement Inside Carpenter Shop 2-1013 Hose

Valve Riser shut off Annual 10:01:54 AM 07/22/2024

Tamper Switch 1st Inside Stair 3 Annual 11:59:53 AM 07/18/2024 Tamper Switch 2nd Inside Stair 2 Annual 11:00:53 AM 07/18/2024 Tamper Switch 2nd Inside Stair 3 Annual 11:10:19 AM 07/18/2024 Tamper Switch 3rd Inside Stair 2 Annual 9:05:00 AM 07/18/2024 Tamper Switch 3rd Inside Stair 3 Annual 9:38:13 AM 07/18/2024 Tamper Switch 4th Inside Stair 2 Annual 8:22:08 AM 07/18/2024 Tamper Switch 4th Inside Stair 3 Annual 8:49:07 AM 07/18/2024 Tamper Switch 5th Inside Stair 2 Annual 7:55:54 AM 07/18/2024 Tamper Switch 5th Inside Stair 3 Annual 8:03:08 AM 07/18/2024 Tamper Switch 6th Inside Stair 2 Annual 7:27:36 AM 07/18/2024 Tamper Switch 6th Inside Stair 3 Annual 7:38:33 AM 07/18/2024 Tamper Switch 7th Inside Stair 2 Annual 12:43:47 PM 07/17/2024 Tamper Switch 7th Inside Stair 3 Annual 12:53:37 PM 07/17/2024 Tamper Switch 8th Outside Stair 2 in sprinkler closet dry system Annual 11:59:49 AM 07/17/2024

Tamper Switch 8th Outside Stair 2 in sprinkler closet wet system

Annual 12:02:09 PM 07/17/2024

Tamper Switch 8th Outside Stair 3 Annual 12:19:13 PM 07/17/2024 Waterflow Switch Basement Inside Stair 2 Annual 12:33:22 PM 07/18/2024

Everon 11 Download Date: 09/03/2024

Waterflow Switch Basement Inside Stair 3 Annual 12:46:49 PM 07/18/2024 Waterflow Switch Basement Inside Room 41000 Annual 9:53:03 AM 07/22/2024 Waterflow Switch 1st Inside Stair 2 Annual 11:28:50 AM 07/18/2024 Waterflow Switch 1st Inside Stair 3 Annual 12:00:52 PM 07/18/2024 Waterflow Switch 2nd Inside Stair 2 Annual 11:01:18 AM 07/18/2024 Waterflow Switch 2nd Inside Stair 3 Annual 11:10:57 AM 07/18/2024 Waterflow Switch 3rd Inside Stair 2 Annual 9:05:25 AM 07/18/2024 Waterflow Switch 3rd Inside Stair 3 Annual 9:39:13 AM 07/18/2024 Waterflow Switch 4th Inside Stair 2 Annual 8:24:33 AM 07/18/2024 Waterflow Switch 5th Inside Stair 2 Annual 7:56:47 AM 07/18/2024 Waterflow Switch 5th Inside Stair 3 Annual 8:10:11 AM 07/18/2024 Waterflow Switch 6th Inside Stair 2 Annual 7:28:47 AM 07/18/2024 Waterflow Switch 7th Inside Stair 2 Annual 12:45:23 PM 07/17/2024 Waterflow Switch 8th Outside Stair 2 in sprinkler closet Annual 11:57:59 AM 07/17/2024 Waterflow Switch 8th Outside Stair 3 Annual 12:20:30 PM 07/17/2024 Air Maintenance Device 3rd Inside Stair 3 Dry System Annual 9:32:53 AM 07/18/2024 Air Maintenance Device 3rd Switch Gear bz Capitol Police Storage Annual 12:40:14 PM 07/19/2024 Air Maintenance Device 8th Outside Stair 2 in sprinkler closet Annual 11:49:40 AM 07/17/2024 Drain Basement Pump Room Bypass Drain Annual 8:23:30 AM 07/19/2024 Drain Basement Pump Room Test Header Drain Annual 8:24:44 AM 07/19/2024 Drain 3rd Inside Stair 3 Dry System Annual 9:35:36 AM 07/18/2024 Drain 4th Inside Stair 2 Pre Action System Annual 8:33:15 AM 07/18/2024 Drain 8th Outside Stair 2 in sprinkler closet Annual 11:55:33 AM 07/17/2024 Quick Opening Device 3rd Inside Stair 3 Dry System Annual 9:31:37 AM 07/18/2024 Controller Basement Pump Room Annual 7:18:12 AM 07/19/2024 Electrical Driver Basement Pump Room Jockey Pump Valve Annual 7:50:36 AM 07/19/2024 Jockey Controller Basement Pump Room Annual 7:59:24 AM 07/19/2024 Jockey Pump Basement Pump Room Jockey Pump Valve Annual 7:44:16 AM 07/19/2024 Pump Basement Pump Room Annual 12:47:18 PM 08/17/2024 Sprinkler Box Spares Basement Pump Room Annual 8:05:44 AM 07/19/2024 Sprinkler Box Spares Basement Pump Room Annual 8:08:06 AM 07/19/2024 Sprinkler Box Spares 4th Inside Stair 2 Annual 8:40:11 AM 07/18/2024 Backflow Prevention Basement Pump Room Visually Checked 8:00:59 AM 07/19/2024 Control Valve Basement Outside Stair 4 Annual 12:23:27 PM 07/18/2024 Control Valve Basement Inside Stair 2 Annual 12:33:01 PM 07/18/2024 Control Valve Basement by Shaft 1 Annual 12:36:52 PM 07/18/2024 Control Valve Basement by Room A055 Annual 12:41:32 PM 07/18/2024 Control Valve Basement Inside Stair 3 Annual 12:46:28 PM 07/18/2024 Control Valve Basement Outside Stair 3 Annual 12:47:55 PM 07/18/2024 Control Valve Basement Pump Room Test Header Annual 7:23:27 AM 07/19/2024 Control Valve Basement Pump Room Suction Valve Annual 7:41:27 AM 07/19/2024 Control Valve Basement Pump Room Jockey Pump Valve Annual 7:49:39 AM 07/19/2024 Control Valve Basement Pump Room Backflow Discharge Annual 7:55:23 AM 07/19/2024 Control Valve Basement Pump Room Main Incoming Control

Valve Annual 8:02:18 AM 07/19/2024

Control Valve Basement Pump Room Backflow Suction Annual 8:11:10 AM 07/19/2024 Control Valve Basement Pump Room Jockey Pump Valve Annual 11:10:56 AM 07/19/2024 Control Valve Basement Pump Room Bypass 2 Annual 11:12:00 AM 07/19/2024 Control Valve Basement Pump Room Bypass 1 Annual 11:13:06 AM 07/19/2024 Control Valve Basement Pump Room Discharge Annual 11:16:25 AM 07/19/2024 Control Valve Basement in Room A052 Annual 1:07:00 PM 07/19/2024 Control Valve Basement Inside Room A019 Annual 9:23:28 AM 07/22/2024

Everon 12 Download Date: 09/03/2024

Control Valve Basement Inside Room 41000 Annual 9:29:36 AM 07/22/2024 Control Valve Basement Inside Room 41000 in air Annual 9:52:30 AM 07/22/2024 Control Valve Basement Carpenter Shop 2-1013 Hose Valve

Riser Shut off Annual 10:01:03 AM 07/22/2024

Control Valve 1st Inside Stair 2 Annual 11:28:39 AM 07/18/2024 Control Valve 1st Inside Stair 3 Annual 12:00:22 PM 07/18/2024 Control Valve 2nd Inside Stair 2 Annual 11:01:08 AM 07/18/2024 Control Valve 2nd Inside Stair 3 Annual 11:10:43 AM 07/18/2024 Control Valve 3rd Inside Stair 2 Annual 9:05:15 AM 07/18/2024 Control Valve 3rd Inside Stair 3 Dry System Annual 9:36:27 AM 07/18/2024 Control Valve 3rd Inside Stair 3 Annual 9:38:00 AM 07/18/2024 Control Valve 4th Inside Stair 2 Annual 8:23:27 AM 07/18/2024 Control Valve 4th Inside Stair 2 Pre Action System Annual 8:36:16 AM 07/18/2024 Control Valve 4th Inside Stair 3 Annual 8:49:58 AM 07/18/2024 Control Valve 5th Inside Stair 2 Annual 7:56:34 AM 07/18/2024 Control Valve 5th Inside Stair 3 Annual 8:09:59 AM 07/18/2024 Control Valve 6th Inside Stair 2 Annual 7:27:45 AM 07/18/2024 Control Valve 6th Inside Stair 3 Annual 7:38:45 AM 07/18/2024 Control Valve 7th Inside Stair 2 Annual 12:44:48 PM 07/17/2024 Control Valve 7th Inside Stair 3 Annual 12:54:31 PM 07/17/2024 Control Valve 8th Outside Stair 2 in sprinkler closet wet system Annual 12:01:40 PM 07/17/2024

Control Valve 8th Outside Stair 3 Annual 12:18:23 PM 07/17/2024 Control Valve 8th Outside Stair 2 in sprinkler closet dry system Annual 8:41:37 AM 08/07/2024

Hose Valve Basement Inside stair 4 Annual 12:23:07 PM 07/18/2024 Hose Valve Basement Inside Stair 2 Annual 12:31:39 PM 07/18/2024 Hose Valve Basement by Shaft 10 Annual 12:39:38 PM 07/18/2024 Hose Valve 1st Inside Stair 2 Annual 11:29:34 AM 07/18/2024 Hose Valve 1st Stair 1 Annual 11:44:23 AM 07/18/2024 Hose Valve 1st inside BALER ROOM Annual 11:45:19 AM 07/18/2024 Hose Valve 1st Inside Stair 3 Annual 12:01:05 PM 07/18/2024 Hose Valve 1st Mail Room Loading Dock Annual 12:09:40 PM 07/18/2024 Hose Valve 1st Inside stair 4 Annual 12:14:15 PM 07/18/2024 Hose Valve 1st by Room A140 Annual 12:15:30 PM 07/18/2024 Hose Valve 2nd Inside Stair 4 Annual 10:54:45 AM 07/18/2024 Hose Valve 2nd Inside Stair 2 Annual 11:01:29 AM 07/18/2024 Hose Valve 2nd Inside Stair 3 Annual 11:14:54 AM 07/18/2024 Hose Valve 2nd by Room 214 Annual 11:21:05 AM 07/18/2024 Hose Valve 3rd Inside Stair 3 Annual 8:26:20 AM 07/18/2024 Hose Valve 3rd Inside Stair 1 Annual 9:25:50 AM 07/18/2024 Hose Valve 3rd Inside Stair 3 Annual 9:40:55 AM 07/18/2024 Hose Valve 3rd Capital Police Storage Annual 9:54:31 AM 07/18/2024 Hose Valve 3rd Inside NARA Room Aisle 7 Annual 9:46:39 AM 07/25/2024 Hose Valve 3rd Inside NARA Room Aisle 45 Annual 9:50:23 AM 07/25/2024 Hose Valve 4th by Shaft 1 Annual 8:43:20 AM 07/18/2024 Hose Valve 4th inside Stair 1 Annual 8:44:07 AM 07/18/2024 Hose Valve 4th Inside Stair 3 Annual 8:50:39 AM 07/18/2024 Hose Valve 4th Inside Stair 4 Annual 8:56:13 AM 07/18/2024 Hose Valve 4th by Column 4C24 Annual 12:26:18 PM 07/19/2024 Hose Valve 5th Inside Stair 2 Annual 7:57:01 AM 07/18/2024 Hose Valve 5th Inside Stair 1 Annual 7:58:50 AM 07/18/2024

Everon 13 Download Date: 09/03/2024

Hose Valve 5th Inside Stair 3 Annual 8:10:28 AM 07/18/2024 Hose Valve 5th Inside Stair 4 Annual 8:15:34 AM 07/18/2024 Hose Valve 6th Inside Stair 2 Annual 7:30:18 AM 07/18/2024 Hose Valve 6th Inside Stair 1 Annual 7:34:25 AM 07/18/2024 Hose Valve 6th Inside Stair 3 Annual 7:39:10 AM 07/18/2024 Hose Valve 6th inside Stair 4 Annual 7:51:04 AM 07/18/2024 Hose Valve 7th Inside Stair 4 Annual 12:37:47 PM 07/17/2024 Hose Valve 7th Inside Stair 2 Annual 12:49:26 PM 07/17/2024 Hose Valve 7th Inside Stair 1 Annual 12:50:02 PM 07/17/2024 Hose Valve 7th Inside Stair 3 Annual 12:57:15 PM 07/17/2024 Hose Valve 8th Inside Stair 2 Annual 12:11:57 PM 07/17/2024 Hose Valve 8th Outside of Stair 3 by doors Annual 12:17:24 PM 07/17/2024 Hose Valve 8th Outside of Stair 3 Annual 12:17:57 PM 07/17/2024 Hose Valve 8th Inside Stair 4 Annual 12:33:30 PM 07/17/2024 Hose Valve 8th by Room A857 Annual 12:35:37 PM 07/17/2024 Hose Valve 8th by Vending Machines Annual 12:35:40 PM 07/17/2024 Hose Valve 8th Outside of Stairs to Roof Annual 9:04:25 AM 07/19/2024 Inspector's Test 3rd Inside Stair 2 Annual 9:07:58 AM 07/18/2024 Inspector's Test 7th Inside Stair 2 Annual 12:46:40 PM 07/17/2024 Inspector's Test 7th Inside Stair 3 Annual 12:54:54 PM 07/17/2024 Inspector's Test 8th Outside Stair 2 in sprinkler closet wet system Annual 12:02:34 PM 07/17/2024

Inspector's Test 8th Inside Stair 3 Annual 12:30:15 PM 07/17/2024 Preaction Valve 4th Inside Stair 2 Pre Action System Annual 8:35:16 AM 07/18/2024

Supplies 4th floor Pre actio Nitrogen System 3rd Switch Gear by Capitol Police Storage Annual 12:44:15 PM 07/19/2024 Air Compressor 3rd Switch Gear by Capitol Police Storage Annual 12:49:16 PM 07/19/2024

Failed/Other Tamper Switch Basement Inside Room 41000 Annual 9:41:53 AM 07/22/2024 Tamper Switch Basement Inside Room A019 Annual 9:42:34 AM 07/22/2024 Tamper Switch 1st Inside Stair 2 Annual 11:35:21 AM 07/18/2024 Tamper Switch 3rd Inside Stair 3 Dry System Annual 9:51:42 AM 07/18/2024 Waterflow Switch 1st Inside Bailer Room Annual 11:59:31 AM 07/18/2024 Waterflow Switch 4th Inside Stair 3 Annual 8:52:21 AM 07/18/2024 Waterflow Switch 6th Inside Stair 3 Annual 7:44:37 AM 07/18/2024 Waterflow Switch 7th Inside Stair 3 Annual 12:58:56 PM 07/17/2024 Gauge Basement Pump Room Discharge Guage Annual 7:36:51 AM 07/19/2024 Gauge Basement Pump Room Discharge Guage Annual 7:38:41 AM 07/19/2024 Gauge Basement inside Room A052 Annual 1:11:44 PM 07/19/2024 Gauge 3rd Inside Stair 3 Dry System Annual 9:34:04 AM 07/18/2024 Gauge 3rd Inside Stair 3 Dry System Annual 9:34:22 AM 07/18/2024 Gauge 4th Inside Stair 2 Pre Action System Annual 8:30:09 AM 07/18/2024 Gauge 4th Inside Stair 2 Pre Action System Annual 8:30:31 AM 07/18/2024 Gauge 4th Inside Stair 2 Pre Action System Annual 8:31:17 AM 07/18/2024 Gauge 4th Inside Stair 2 Pre Action System Annual 10:36:17 AM 08/07/2024 Gauge 8th Outside Stair 2 in sprinkler closet Annual 11:54:17 AM 07/17/2024 Gauge 8th Outside Stair 2 in sprinkler closet Annual 12:01:23 PM 07/17/2024 Gauge 8th Inside Stair 2 Annual 12:11:45 PM 07/17/2024 Gauge 8th Inside Stair 2 Annual 12:15:59 PM 07/17/2024 Gauge 8th Inside Stair 4 Annual 12:34:34 PM 07/17/2024 Casing Relief Valve Basement Pump Room Annual 12:25:49 PM 08/17/2024

Everon 14 Download Date: 09/03/2024

Piping Basement Pump Room Annual 11:17:23 AM 07/19/2024 Sprinkler Box Basement Pump Room Annual 8:05:36 AM 07/19/2024 Sprinkler Box Basement Pump Room Annual 8:07:59 AM 07/19/2024 Sprinkler Box 4th Inside Stair 2 Annual 8:40:02 AM 07/18/2024 Check Valve Basement Pump Room Discharge Annual 7:25:06 AM 07/19/2024 Check Valve Basement Pump Room Discharge Annual 7:49:04 AM 07/19/2024 Check Valve Basement Pump Room Standpipe Annual 11:21:29 AM 07/19/2024 Control Valve Basement Pump Room Annual 8:15:43 AM 07/19/2024 Dry Pipe Valve 3rd Inside Stair 3 Dry System Annual 12:17:14 PM 08/07/2024 Dry Pipe Valve 8th Outside Stair 2 in sprinkler closet Annual 9:38:37 AM 08/07/2024 Hose Valve Basement by Shaft 4 Annual 12:29:43 PM 07/18/2024 Hose Valve Basement by Shaft 3 Annual 12:30:31 PM 07/18/2024 Hose Valve Basement by Shaft 2 Annual 12:31:35 PM 07/18/2024 Hose Valve Basement by Shaft 1 Annual 12:36:25 PM 07/18/2024 Hose Valve Basement by Shaft 9 Annual 12:45:31 PM 07/18/2024 Hose Valve Basement inside Room 41000 Annual 9:38:53 AM 07/22/2024 Hose Valve 1st Outside Stair 2 Annual 11:38:50 AM 07/18/2024 Hose Valve 1st By Jackson alley Annual 11:45:07 AM 07/18/2024 Hose Valve 1st In Cage Outside Stair 3 Annual 12:09:03 PM 07/18/2024 Hose Valve 1st Security post 38 Annual 12:13:57 PM 07/18/2024 Hose Valve 2nd Outside Stair 4 Annual 10:55:46 AM 07/18/2024 Hose Valve 2nd by Room A257A Annual 10:58:57 AM 07/18/2024 Hose Valve 2nd by Room A259 Annual 11:00:02 AM 07/18/2024 Hose Valve 2nd by A207 Annual 11:08:15 AM 07/18/2024 Hose Valve 2nd by A211 Annual 11:08:41 AM 07/18/2024 Hose Valve 2nd by Room 268 Annual 11:25:57 AM 07/18/2024 Hose Valve 3rd Inside Stair 2 Annual 9:06:09 AM 07/18/2024 Hose Valve 3rd Inside Stair 4 Annual 10:03:09 AM 07/18/2024 Hose Valve 3rd Inside NARA Room Aisle 20 Annual 9:48:42 AM 07/25/2024 Hose Valve 3rd Inside NARA Room Aisle 33 Annual 9:50:13 AM 07/25/2024 Hose Valve 3rd Inside NARA Room Aisle 56 Annual 9:51:19 AM 07/25/2024 Hose Valve 3rd Inside NARA Room Aisle 61 Annual 9:53:06 AM 07/25/2024 Hose Valve 4th by Column 4E5 Annual 8:47:24 AM 07/18/2024 Hose Valve 4th by Shaft 9 Annual 8:47:58 AM 07/18/2024 Hose Valve 4th by Column 4E16 Annual 8:53:30 AM 07/18/2024 Hose Valve 4th Inside Room A426 Annual 8:54:23 AM 07/18/2024 Hose Valve 4th Outside Stair 4 Annual 8:55:56 AM 07/18/2024 Hose Valve 4th Inside AOC Carpemters Shop Annual 8:58:12 AM 07/18/2024 Hose Valve 4th Inside AOC Carpemters Shop Annual 9:01:52 AM 07/18/2024 Hose Valve 4th by Shaft 3 Annual 9:03:00 AM 07/18/2024 Hose Valve 4th by Shaft 2 Annual 9:03:48 AM 07/18/2024 Hose Valve 5th by shaft 10 Annual 8:01:26 AM 07/18/2024 Hose Valve 5th by shaft 9 Annual 8:02:49 AM 07/18/2024 Hose Valve 5th by shaft 2 Annual 8:13:25 AM 07/18/2024 Hose Valve 5th by Room A505A Annual 8:14:30 AM 07/18/2024 Hose Valve 5th by Room A505B Annual 8:15:23 AM 07/18/2024 Hose Valve 5th by BALER access Annual 8:10:34 AM 07/22/2024 Hose Valve 5th Inside Room A525 Annual 8:21:22 AM 07/22/2024 Hose Valve 6th by Room A662 Annual 7:37:02 AM 07/18/2024 Hose Valve 6th by Room A634 Annual 7:37:29 AM 07/18/2024 Hose Valve 6th Outside Stair 2 Annual 7:38:19 AM 07/18/2024 Hose Valve 6th by Room A639 Annual 7:48:41 AM 07/18/2024

Everon 15 Download Date: 09/03/2024

Hose Valve 6th by Elevator 7 & 8 Annual 7:49:45 AM 07/18/2024 Hose Valve 6th by Room A636 Annual 7:50:50 AM 07/18/2024 Hose Valve 6th by Room A623A Annual 7:52:17 AM 07/18/2024 Hose Valve 6th by Room A624 Annual 7:53:34 AM 07/18/2024 Hose Valve 6th by column 6E21 Annual 11:36:10 AM 07/19/2024 Hose Valve 6th by column 6E16 Annual 11:36:58 AM 07/19/2024 Hose Valve 7th Outside Stair 4 Annual 12:40:22 PM 07/17/2024 Hose Valve 7th by Room A750 Annual 12:40:56 PM 07/17/2024 Hose Valve 7th by Room A720 Annual 12:43:30 PM 07/17/2024 Hose Valve 8th Inside of Stairs to Roof Annual 9:06:44 AM 07/19/2024 Inspector's Test Basement Inside Stair 3 Annual 12:52:52 PM 07/18/2024 Inspector's Test Basement for Stair 2 inside Room A052 Annual 1:09:53 PM 07/19/2024 Inspector's Test 1st Inside Stair 2 Annual 11:31:24 AM 07/18/2024 Inspector's Test 1st Inside Stair 3 Annual 12:02:21 PM 07/18/2024 Inspector's Test 2nd Inside Stair 2 Annual 11:02:22 AM 07/18/2024 Inspector's Test 2nd Inside Stair 3 Annual 11:15:27 AM 07/18/2024 Inspector's Test 3rd Inside Stair 3 wet System Annual 9:41:55 AM 07/18/2024 Inspector's Test 3rd Inside Stair 3 Dry System Annual 9:42:35 AM 07/18/2024 Inspector's Test 4th Inside Stair 2 Annual 8:27:15 AM 07/18/2024 Inspector's Test 4th Inside Stair 3 Annual 8:51:19 AM 07/18/2024 Inspector's Test 5th Inside Stair 2 Annual 7:57:19 AM 07/18/2024 Inspector's Test 5th Inside Stair 3 Annual 8:11:00 AM 07/18/2024 Inspector's Test 6th Inside Stair 2 Annual 7:30:59 AM 07/18/2024 Inspector's Test 6th Inside Stair 3 Annual 7:39:52 AM 07/18/2024

Supplies 4th floor Pre actio Gauge 3rd Switch Gear by Capitol Police Storage Annual 12:52:13 PM 07/19/2024

Everon 16 Download Date: 09/03/2024

Fire Pump Testing

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Pump

Manufacturer Model Number Location Install Date ScanID Peerless Basement Pump Room 07/17/2015 96937491

Serial Number Type Orientation Aligned? Water Supply Impeller Size 50008289 Pump Primary Horizontal Split

Case Yes Municipal

Fire Pump Tests

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water Temperature

Other 08/17/2024 165 60 0 3289

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

154 154 152 474 465 472

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 155 48 1008 3587

152 154 152 474 474 472

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 116 35 1512 3608

152 152 152 474 466 468

Fire Pump Rating

Amps Volts

Net Pressure Gallons Per Minute

Rotations Per Minute A B C A-B B-C A-C

98 0

85 1000

65 1500

Everon 17 Download Date: 09/03/2024

Everon 18 Download Date: 09/03/2024

Inventory & Warranty Report

Building: GPO Building A

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Air Compressor Pump 0.38% 1

Air Maintenance Device Device 1.15% 3

Alternate Power Alarm 0.38% 1

Backflow Prevention Valve 0.38% 1

Casing Relief Valve Pump 0.38% 1

Check Valve Valve 1.15% 3

Control Valve Valve 15.71% 41

Controller Pump 0.38% 1

Drain Device 1.92% 5

Dry Pipe Valve Valve 0.77% 2

Electrical Driver Pump 0.38% 1

Fire Pump Off Alarm 0.38% 1

Fire Pump Running Alarm 0.38% 1

Gauge Device 5.75% 15

Hose Valve Valve 36.78% 96

Inspector's Test Valve 7.28% 19

Jockey Controller Pump 0.38% 1

Jockey Pump Pump 0.38% 1

Nitrogen System Device 0.38% 1

Piping Sprinkler 0.38% 1

Preaction Valve Valve 0.38% 1

Pressure Switch Alarm 0.77% 2

Pump Pump 0.38% 1

Quick Opening Device Device 0.38% 1

Sprinkler Box Sprinkler 1.15% 3

Sprinkler Box Spares Sprinkler 1.15% 3

Tamper Switch Alarm 13.03% 34

Waterflow Switch Alarm 7.66% 20

Device Type

Qt y Model # Type Description Install Date

New (under 90 days)

Gauge 2

System Pressure

07/19/2024

Air Maintenance Device 1

Pressure Reducing

07/17/2024

In Service - 5 Years to 10 Years

Sprinkler Box Spares 1 F1FR56 QR

07/17/2018

Casing Relief Valve 1 551

07/17/2015

Check Valve 1 75 Grooved

Pump 1

Pump Primary

Alternate Power 1 GPU-460/75/3/60

Supervisory 07/17/2015

Controller 1 GPU-460/75/3/60

Automatic 07/17/2015

Fire Pump Off 1 GPU-460/75/3/60

Fire Pump Running 1 GPU-460/75/3/60

Everon 19 Download Date: 09/03/2024

Check Valve 1 717

Check Valve 1 717 Grooved

Control Valve 2 705 Butterfly

In Service - 10 Years to 15 Years

Control Valve 1 1846 OS&Y Main Control 07/17/2010

Tamper Switch 1 OSY-2 Lever Supervisory 07/17/2010

Drain 1

Main

07/17/2010

Gauge 1 111.10S0.100 Air Pressure

Gauge 1 111.10S0.100 System Pressure

Dry Pipe Valve 1 DPV-1 Flanged

In Service - 25 Years or Older

Sprinkler Box Spares 1 F950 Pendant

07/17/1982

Sprinkler Box Spares 1 F950 Upright

07/17/1982

Sprinkler Box 3

07/17/1979

Control Valve 1 S 145 RW OS&Y Suction 07/17/1979

Electrical Driver 1

Hose Valve 1 2 1/2

Control Valve 1

OS&Y

Control Valve 21 1821 OS&Y Main Control 07/17/1979

Control Valve 3 200 woq OS&Y Main Control 07/17/1979

Control Valve 2 WFD40 OS&Y Main Control 07/17/1979

Jockey Pump 1 T41E BF Automatic

Waterflow Switch 1 FS43 Vane Alarm 07/17/1979

Control Valve 1 1821 OS&Y Main Control 07/17/1979

Tamper Switch 24 1821 Lever Supervisory 07/17/1979

Control Valve 1 1848 OS&Y Main Control 07/17/1979

Control Valve 1 C515 OS&Y

Tamper Switch 1 C515 Lever Supervisory 07/17/1979

Pressure Switch 1 PS10-2 Pressure Switch Alarm 07/17/1979

Pressure Switch 1 PS15-2 High Low

Tamper Switch 3 OSYSU-2 Lever Supervisory 07/17/1979

Air Maintenance Device 1

Pressure Reducing

Inspector's Test 19 OSY2

Tamper Switch 3 OSY2 Lever Supervisory 07/17/1979

Tamper Switch 2 OsY2 Lever

Waterflow Switch 19 WFD40 Vane Alarm 07/17/1979

Jockey Controller 1 JP3-480/0.75/3/6

Drain 2 2R97 Auxiliary

Piping 1 2R97 Steel

Quick Opening Device 1 ACC-1

Gauge 5 R1590 Air Pressure

Drain 1

Main

Control Valve 1 705 Butterfly

Control Valve 2 705 OS&Y Suction 07/17/1979

Control Valve 1 728 Butterfly Discharge 07/17/1979

Control Valve 1 728 Butterfly Suction 07/17/1979

Drain 1 PS10-2 Main

Preaction Valve 1 769N Double Interlock

Dry Pipe Valve 1

Flanged

Gauge 2 111.10S0.100 Air Pressure

Gauge 3 111.10S0.100 System Pressure

Everon 20 Download Date: 09/03/2024

Air Maintenance Device 1 AMD-1 Pressure Reducing

Control Valve 2 C515 OS&Y

Backflow Prevention 1 350AST Double Check Detecto

Hose Valve 53 1 1/2

Hose Valve 3 2 1/12

Hose Valve 39 2 1/2

Supplies 4th floor Pre actio

Air Compressor 1 L20033A Automatic Tankless 07/17/1979

Gauge 1

System Pressure

Nitrogen System 1 FPS-500

Everon 21 Download Date: 09/03/2024

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.

Address Device Type Location Type ScanID

Control Panel 1 Zone/Address: Z42

L002D0388 Tamper Switch Basement Outside Stair 4 Lever 96937509 L002D0390 Tamper Switch Basement Inside Carpenter Shop 2-1013

Hose Valve Riser shut off Lever 96937686

Zone/Address: Z43 L002D0387 Tamper Switch Basement Backflow Discharge Lever 96937571 L002D0387 Tamper Switch Basement Backflow Suction Lever 96937572 L002D0387 Tamper Switch Basement Inside Stair 3 Lever 96937503 L002D0387 Tamper Switch Basement Pump Room Suction Valve Lever 96937580 L002D0387 Tamper Switch Basement by Room A055 Lever 96937505 L002D0391 Tamper Switch Basement Inside Room 41000 in air Lever 96937720 L002D0391 Tamper Switch Basement Inside Room A019 Lever 96937726 L002D0392 Tamper Switch Basement Outide Stair 3 Lever 96937498

Zone/Address: Z44 L002D0388 Tamper Switch Basement Inside Stair 2 Lever 96937514 L002D0388 Tamper Switch Basement Outside Stair 4 Lever 96937519

Zone/Address: Z45 L002D0395 Tamper Switch Basement Inside Room 41000 Lever 96937725

Zone/Address: Z47 L002D0385 Tamper Switch 1st Inside Stair 3 Lever 96937530

Zone/Address: Z50 L002D0143 Tamper Switch 1st Inside Stair 2 Lever 96937540 L002D0143 Tamper Switch 2nd Inside Stair 2 Lever 96937554

Zone/Address: Z51 L002D0152 Tamper Switch 2nd Inside Stair 3 Lever 96937547

Zone/Address: Z54 L002D0141 Tamper Switch 3rd Inside Stair 2 Lever 96937435

Zone/Address: Z55 L002D0150 Tamper Switch 3rd Inside Stair 3 Lever 96937034

Zone/Address: Z58 L002D0139 Tamper Switch 4th Inside Stair 2 Lever 96937393

Zone/Address: Z59 L002D0148 Tamper Switch 4th Inside Stair 3 Lever 96937438

Everon 22 Download Date: 09/03/2024

Zone/Address: Z62 L004D0387 Tamper Switch 5th Inside Stair 2 Lever 96937466

Zone/Address: Z63 L004D0387 Tamper Switch 5th Inside Stair 3 Lever 96937403

Zone/Address: Z66 L004D0385 Tamper Switch 7th Inside Stair 2 Lever 96937323

Zone/Address: Z67 L004D0385 Tamper Switch 6th Inside Stair 3 Lever 96937473

Zone/Address: Z70 L004D0143 Tamper Switch 6th Inside Stair 2 Lever 96937482

Zone/Address: Z71 L004D0140 Tamper Switch 7th Inside Stair 3 Lever 96937327

Zone/Address: ZN42 L002D0386 Waterflow Switch Basement Inside Stair 2 Vane 96937512 L002D0389 Tamper Switch Basement in Room A052 Lever 96937585

Zone/Address: ZN43 L002D0387 Waterflow Switch Basement Inside Stair 3 Vane 96937501 L002D0387 Waterflow Switch 7th Inside Stair 3 Vane 96937329

Zone/Address: ZN44 L002D0393 Control Valve Basement Pump Room Backflow Suction OS&Y 96937485 L002D0393 Control Valve Basement in Room A052 OS&Y 96937586

Zone/Address: ZN46 L002D0383 Waterflow Switch 1st Inside Bailer Room Vane 96937531 L002D0383 Waterflow Switch 1st Inside Stair 2 Vane 96937538 L002D0383 Waterflow Switch 1st Inside Stair 3 Vane 96937528

Zone/Address: ZN50 L002D0142 Waterflow Switch 2nd Inside Stair 2 Vane 96937552

Zone/Address: ZN51 L002D0151 Waterflow Switch 2nd Inside Stair 3 Vane 96937545

Zone/Address: ZN54 L002D0140 Waterflow Switch 3rd Inside Stair 2 Vane 96937433

Zone/Address: ZN55 L002D Tamper Switch 3rd Inside Stair 3 Dry System Lever 96937035 L002D0149 Waterflow Switch 3rd Inside Stair 3 Vane 96937032

Zone/Address: ZN58 L002D0138 Waterflow Switch 4th Inside Stair 2 Vane 96937413 L002D174 Pressure Switch 4th Inside Stair 2 Pre Action System High Low 96937406 L002D0175 Control Valve 4th Inside Stair 2 Pre Action System Butterfly 96937423

Zone/Address: ZN59 L002D0147 Waterflow Switch 4th Inside Stair 3 Vane 96937458

Zone/Address: ZN62 L002D0386 Waterflow Switch 6th Inside Stair 2 Vane 96937480

Everon 23 Download Date: 09/03/2024

Zone/Address: ZN63 L004D0386 Waterflow Switch 5th Inside Stair 3 Vane 96937401

Zone/Address: ZN66 L004D038 Waterflow Switch 6th Inside Stair 3 Vane 96937446 L004D0384 Waterflow Switch 5th Inside Stair 2 Vane 96937464

Zone/Address: ZN70 L004D0142 Waterflow Switch 7th Inside Stair 2 Vane 96937325

Zone/Address: ZN74 L004D0140 Waterflow Switch 8th Outside Stair 2 in sprinkler closet Vane 96937353 L004D0141 Tamper Switch 8th Outside Stair 2 in sprinkler closet wet system Lever 96937312

Zone/Address: ZN75 L004D0137 Waterflow Switch 8th Outside Stair 3 Vane 96937348 L004D0138 Tamper Switch 8th Outside Stair 3 Lever 96937349

Zone/Address: ZN84 L004D0141 Tamper Switch 8th Outside Stair 2 in sprinkler closet dry system Lever 96937351

Zone/Address: Zn43 L002D0387 Control Valve Basement Pump Room Jockey Pump Valve Butterfly 96937579

Zone/Address: Zn44 L002D0391 Control Valve Basement Pump Room Bypass 1 OS&Y 96937577 L002D0393 Tamper Switch Basement Pump Room Lever 96937566 L002D0393 Control Valve Basement Pump Room Backflow Discharge OS&Y 96937486

Control Panel 7 Zone/Address: ZN43

L002D0391 Control Valve Basement Pump Room Bypass 2 OS&Y 96937578

Control Panel 11 Zone/Address: ZN44

L002D0391 Control Valve Basement Pump Room Discharge Butterfly 96937575

Everon 24 Download Date: 09/03/2024

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID 1 Casing Relief Valve Basement Pump Room Leaking 619437649

Found closed all the way before pump test. Opened to preform test. Valve leaks by when pump is not running. Replace.

2 Check Valve Basement Pump Room Discharge Needs 5 Yr.

Service

96937567

Due for 5 year internal inspection.

3 Piping Basement Pump Room Needs 5 yr.

service 96937594

Due for 5 year internal inspection.

Areas of piping in pictures that are rusted and corroded I recommend replacing before a major issue occurs

4 Tamper Switch Basement Inside Room 41000 Failed Annunciation

96937725

Came to panel A004 5 Tamper Switch Basement Inside Room A019 Failed annunciation 96937726

Came to panel as A009 6 Tamper Switch 1st Inside Stair 2 Failed Test 96937540

Did not send supervisory to panel 7 Dry Pipe Valve 3rd Inside Stair 3 Dry System Inspectors test 96937038

Need to add inspectors test at furthest point of system.

8 Hose Valve 3rd Inside NARA Room Aisle 61 Incompatible 96937999

Female hose valve with no adapter, it's just plugged.

9 Tamper Switch 3rd Inside Stair 3 Dry System Failed Test 96937035

Device did not send signal to panel. Even when finger tested 10 Waterflow Switch 4th Inside Stair 3 Failed Flow Test 96937458

Did not go into alarm in time 11 Hose Valve 5th by BALER access Leaking 96937394

Leaks when opened 12 Waterflow Switch 7th Inside Stair 3 Failed Flow Test 96937329

Did not go into alarm within 90 seconds 13 Dry Pipe Valve 8th Outside Stair 2 in sprinkler closet No inspectors test 96937356

Add inspectors test at furthest part of system.