Inspection - 2024-08-17_GPO-Building-C_Sprinkler.pdf

PDF 1 MB Posted

Attached to
GPO Fire Alarm and Suppression Systems - Test and Certification of Repaired Components
Solicitation number
040ADV-25-R-0013
Issued by

About this file

This is a detailed fire sprinkler inspection report performed by Everon for the Government Publishing Office (GPO) Building C located at 732 North Capitol St NW in Washington, DC. The inspection was conducted on August 17, 2024 according to NFPA 25 standards.

The report identifies significant issues requiring attention, including 111 failed/other components (31.36% of total) across 354 inspected items. Key problems include: 8 failed alarm devices, 20 failed devices, 1 failed pump component, 3 failed sprinkler components, and 79 failed valve components. Specific critical issues include leaking control valves, failed annunciation systems, damaged/worn components, missing hose valve caps, and incorrect sprinkler head applications. The inspection included testing of the building's fire pump, which is a Peerless 5AEF11G horizontal split case pump installed in 2012. The report provides comprehensive documentation of each component's location, condition, and recommended solutions, with all repairs noted as Time and Materials (T/M) basis. The inspection was signed off by Jesse Vizzini (Inspector) and Jason Munoz (Senior Project Manager) on August 19, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UEID: LJLDFKJ2VKP5 | CAGE: 5MB43

Government Publishing Office

732 North Capitol St. NW Building C

Washington, DC 20401 Fire Sprinkler Inspection

August 17, 2024

Government Publishing Office 732 North Capitol St NW Washington, DC 20401

HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098

(435) 731-9525

Points of Contact

Mason Barrett, President

Mason@HurtVet.com

Dan Vandergriff, Chief Operating Officer

Dan@HurtVet.com

Jason Munoz, Senior Project Manager

Jason@HurtVet.com

Sprinkler Inspection Certificate For

GPO Building C

732 NORTH CAPITOL ST NW

BUILDING C

WASHINGTON, DC 20401

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 17, 2024

Building: GPO Building C Company: Everon Contact: Jason Munoz Contact: Jesse Vizzini

Title: Senior Project Manager Title: Inspector

Everon 1 Download Date: 09/03/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: GPO Building C Contact: Jason Munoz

Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548

Address: BUILDING C Fax:

City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865

Country: United States of America Email: Jason@hurtvet.com

Inspection Performed By Company: Everon Inspector: Jesse Vizzini

Address: 9108 Guilford Road Phone: 202-236-8024

Address: Suite H Fax:

City/State/ZIP Code: Columbia, MD 21046-2629 Mobile:

Country: United States of America Email: jessevizzini@adt.com

Everon 2 Download Date: 09/03/2024

Inspection Summary

Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %

Alarm 102 28.81% 102 100.00% 94 92.16% 8 7.84% Device 59 16.67% 59 100.00% 39 66.10% 20 33.90% Pump 6 1.69% 6 100.00% 5 83.33% 1 16.67% Sprinkler 4 1.13% 4 100.00% 1 25.00% 3 75.00% Valve 183 51.69% 183 100.00% 104 56.83% 79 43.17%

Totals 354 100% 354 100.00

243 68.64% 111 31.36%

Certification

Company: Everon Building: GPO Building C

Inspector: Jesse Vizzini Contact: Jason Munoz

Signed: Aug 19, 2024 Signed: Aug 19, 2024

Everon 3 Download Date: 09/03/2024

Discrepancy Report

Building: GPO Building C The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Backflow Prevention 96937683 Basement Power Section/Pump Room Needs Annual Service

Casing Relief Valve 96937693 Basement Power Section/Pump Room Leaking

Check Valve 96937659 Basement Outside of Room 25000 Needs 5 Yr. Service NFPA25 13.4.2.1 96937836 Basement Outside of Room 25000 Needs 5 yr. service NFPA25 13.4.2.1 96937692 Basement Power Section/Pump Room Needs 5 Yr. Service NFPA25 13.4.2.1 96937691 Basement Power Section/Pump Room Discharge Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 96937874 Basement Outside Shaft 33 Leaking NFPA25 13.3.2.2 (5) 96937829 Basement Outside Stair 3 (Dry Valve Air

Isolation) Leaking NFPA25 13.3.2.2 (5)

96937675 Basement Power Section/Pump Room Failed annunciation 96937702 Basement Power Section/Pump Room Failed annunciation 96937703 Basement Power Section/Pump Room Failed annunciation 96937704 Basement Power Section/Pump Room Failed annunciation 96937712 Basement Power Section/Pump Room Failed annunciation 96937705 Basement Power Section/Pump Room Test

Header Failed annunciation

96937863 Basement by Shaft 33 (supply) Damaged/Worn NFPA25 13.2.3 96926165 1st Inside Power Brach Leaking NFPA25 13.3.2.2 (5) 87453126 2nd Outside Stair 2 Main Valve Damaged/Worn NFPA25 13.2.3

Drain 87453131 2nd Outside Stair 2 Damaged/Worn NFPA25 4.1.5.1

Gauge 96937859 Basement By Shaft 33 (Dry Valve Air) Date Expired NFPA25 13.2.7.2 96937869 Basement By Shaft 33 (Dry Valve Water) Date Expired NFPA25 13.2.7.2 96937870 Basement By Shaft 33 (QOD Guage) Date Expired NFPA25 13.2.7.2 96937596 Basement Inside Stair 1 (Dry Valve Air) Date Expired NFPA25 13.2.7.2 96937595 Basement Inside Stair 1 (Dry Valve Water) Date Expired NFPA25 13.2.7.2 96937387 Basement Inside of Stair 1 (QOD) Date Expired NFPA25 13.2.7.2 96937606 Basement Outside Shaft 3 (Dry Valve Water) Date Expired NFPA25 13.2.7.2

Everon 4 Download Date: 09/03/2024

96937607 Basement Outside Stair 3 (Dry Valve Air) Date Expired NFPA25 13.2.7.2 96937841 Basement Outside Stair 3 (QOD Guage) Date Expired NFPA25 13.2.7.2 96937688 Basement Outside Stair 4 (Dry Valve) Date Expired NFPA25 13.2.7.2 96937689 Basement Outside Stair 4 (Dry Valve) Date Expired NFPA25 13.2.7.2 96937651 Basement Outside Stair 4 (QOD) Date Expired NFPA25 13.2.7.2 96937708 Basement Power Section/Pump Room Date Expired NFPA25 13.2.7.2 96937709 Basement Power Section/Pump Room Date Expired NFPA25 13.2.7.2 96937713 Basement Power Section/Pump Room Date Expired NFPA25 13.2.7.2 96937700 Basement Power Section/Pump Room Jockey

Controller Date Expired NFPA25 13.2.7.2

96937694 Basement Power Section/Pump Room PRV Date Expired NFPA25 13.2.7.2

Hose Valve 96937648 Basement By BD14 Missing cap 96937843 Basement Outside of Stair 1 Missing cap 96937617 Basement Outside of Stair 3 Missing cap 96937670 Basement Outside of Stair 4 Missing cap 96937850 Basement Stair 2 Missing cap 96937834 Basement Stair 3 Missing cap 96937649 Basement Stair 4 Missing cap 87453144 1st Inside Stair 3 Missing cap 96926203 1st Outside Stair 2 Missing cap 96926173 1st Outside Stair 4 Missing cap 96926177 1st Outside of Oil Storage Missing cap 96926169 1st Outside of Stair 3 Missing cap 96926198 1st by Column 1E13 Missing cap 96926171 1st in Shipping and Recieving Loading Dock Missing cap 87453140 2nd Inside Stair 1 Missing cap 87453128 2nd Inside Stair 2 Missing cap 87453106 2nd Inside Stair 4 Missing cap 87453127 2nd Outside Stair 2 Missing cap 96926218 2nd Outside Stair 3 Missing cap 87453112 2nd Outside Stair 4 Missing cap 87453142 2nd by Column 2B3 Date Expired NFPA25 4.1.4.1 87453141 2nd by Column 2B6 Missing cap 87453123 2nd by Column 2E14 Missing cap 87453143 2nd by Shaft 34 Missing cap 96937751 3rd Inside Stair 2 Missing cap 96937736 3rd Inside Stair 3 Missing cap 96937742 3rd Inside Stair 4 Missing cap 96937749 3rd Outside Stair 2 Missing cap 96937717 3rd Outside Stair 3 Missing cap 96937746 3rd Outside Stair 4 Missing cap 96938307 4th Inside Stair 1 Missing cap 96938300 4th Inside Stair 2 Missing cap 96937793 4th Inside Stair 3 Missing cap 96937921 4th Inside Stair 4 Missing cap 96937805 4th Outside Shaft 34 Damaged/Worn NFPA25 13.6.1.2 –

13.6.1.5 96938304 4th Outside Stair 2 Missing cap 96937792 4th Outside Stair 3 Missing cap 96937800 4th Outside Stair 4 Missing cap 96938325 5th Inside Stair 1 Missing cap

Everon 5 Download Date: 09/03/2024

96938310 5th Inside Stair 2 Missing cap 96938329 5th Inside Stair 3 Missing cap 96938318 5th Inside Stair 4 Missing cap 96938315 5th Outside Stair 2 Missing cap 96938319 5th Outside Stair 4 Missing cap 96938326 5th by Room C551 Missing cap 96938327 5th by Room C566 Missing cap 96937644 6th Inside Stair 2 Missing cap 96937966 6th Inside Stair 3 Missing cap 96937998 6th Inside Stair 4 Missing cap 96936512 6th Outside Stair 2 Missing cap 96937957 6th Outside Stair 4 Missing cap 96936506 6th by Shaft 36 Missing cap 96938010 7th By Room C702 Missing cap 96937994 7th By Shaft 36 Missing cap 96937987 7th Inside Stair 2 Missing cap 96938011 7th Inside Stair 3 Missing cap 96937993 7th Inside Stair 4 Missing cap 96937903 7th Outside Stair 1 Missing cap 96938007 7th Outside Stair 4 Missing cap 96938028 8th By Room C842 Missing 96937780 8th Inside Stair 4 Missing cap 96938017 Penthouse Inside Stair 1 Missing cap

Piping 96937637 Basement Inside Stair 1 (Dry Valve) Needs 5 Yr. Service NFPA25 14.2.1.1

Pressure Relief 96937706 Basement Power Section/Pump Room PRV Needs 5 Yr. Service

Quick Opening Device 96937666 Basement Outside Stair 4 (Dry Valve) Damaged/Worn NFPA25 4.1.5.1 96937871 Basement by Shaft 33 (Dry Valve) Will not set up

Standard Response 00000012 Basement Power Section Electric room C31 Incorrect Application NFPA25 5.4.1.2 96937643 6th Outside Room C 608 Incorrect Application NFPA25 5.4.1.2

Tamper Switch 96937674 Basement Power Section/Pump Room Failed annunciation 96937684 Basement Power Section/Pump Room Backflow

Valve 1 Failed annunciation

96937681 Basement Power Section/Pump Room Backflow Valve 2

Failed annunciation

96937699 Basement Power Section/Pump Room Main Incoming Valve

Failed annunciation

96937876 Basement behind BD14 Failed annunciation 96937990 7th Outside Stair 2 Failed annunciation 96938014 7th Outside Stair 3 Failed annunciation 96938009 7th Outside Stair 4 Failed annunciation

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

Everon 6 Download Date: 09/03/2024

NFPA25 13.3.2.2 (5) The valve inspection shall verify that the valves are in the following condition: Free from external leaks NFPA25 13.2.3 All system valves shall be protected from physical damage and shall be accessible.

NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.

NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

NFPA25 4.1.4.1 The property owner or designated representative shall promptly correct or repair deficiencies or impairments that are found while performing the inspection, test, and maintenance required by this standard.

NFPA25 13.6.1.2 –

13.6.1.5

Hose valves shall be inspected to ensure that hose caps are in place and not damaged. Hose threads shall be inspected for damage. Valve handles shall be present and not damaged. Gaskets shall be inspected for damage for deterioration.

NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for the purpose of inspecting for the presence of foreign organic and inorganic material.

NFPA25 5.4.1.2 Replacement sprinklers shall have the proper characteristics for the application intended, which include the following: Style, orifice size and K-factor, temperature rating, coating, if any, deflector type, design requirements.

Everon 7 Download Date: 09/03/2024

Proposed Solutions Report

Building: GPO Building C

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Backflow Prevention

96937683 Basement Power Section/Pump Room Correct G1 FY1109 T/M

Casing Relief Valve

96937693 Basement Power Section/Pump Room Replace 551 T/M

Check Valve

96937659 Basement Outside of Room 25000 5 Year Service

T/M

96937836 Basement Outside of Room 25000 5 Year Service

96937692 Basement Power Section/Pump Room 5 Year Service K0900W T/M

96937691 Basement Power Section/Pump Room Discharge

5 Year Service K0900W T/M

Control Valve

96937874 Basement Outside Shaft 33 Replace

96937829 Basement Outside Stair 3 (Dry Valve Air Isolation)

Replace 200 wog T/M

96937675 Basement Power Section/Pump Room Correct T-104-0 T/M

96937702 Basement Power Section/Pump Room Correct GD-4765-8N T/M

96937703 Basement Power Section/Pump Room Correct GD-4765-8N T/M

96937704 Basement Power Section/Pump Room Correct GD-4765-8N T/M

96937712 Basement Power Section/Pump Room Correct GD-4765-8N T/M

96937705 Basement Power Section/Pump Room Test Header

Correct GD-4765-8N T/M

96937863 Basement by Shaft 33 (supply) Replace

96926165 1st Inside Power Brach Correct

87453126 2nd Outside Stair 2 Main Valve Replace

Drain

87453131 2nd Outside Stair 2 Replace 200 wog T/M

Gauge

96937859 Basement By Shaft 33 (Dry Valve Air) Replace 111.10SP.100 T/M

96937869 Basement By Shaft 33 (Dry Valve Water) Replace 111.10SP.100 T/M

96937870 Basement By Shaft 33 (QOD Guage) Replace 111.10SP.100 T/M

96937596 Basement Inside Stair 1 (Dry Valve Air) Replace 111.10SP.100 T/M

96937595 Basement Inside Stair 1 (Dry Valve Water) Replace 111.10SP.100 T/M

96937387 Basement Inside of Stair 1 (QOD) Replace 111.10SP.100 T/M

96937606 Basement Outside Shaft 3 (Dry Valve Water) Replace 111.10SP.100 T/M

96937607 Basement Outside Stair 3 (Dry Valve Air) Replace 111.10SP.100 T/M

96937841 Basement Outside Stair 3 (QOD Guage) Replace 111.10SP.100 T/M

Everon 8 Download Date: 09/03/2024

96937688 Basement Outside Stair 4 (Dry Valve) Replace 111.10SP.100 T/M

96937689 Basement Outside Stair 4 (Dry Valve) Replace 111.10SP.100 T/M

96937651 Basement Outside Stair 4 (QOD) Replace 111.10SP.100 T/M

96937708 Basement Power Section/Pump Room Replace 111.10SP.100 T/M

96937709 Basement Power Section/Pump Room Replace 111.10SP.100 T/M

96937713 Basement Power Section/Pump Room Replace 111.10SP.100 T/M

96937700 Basement Power Section/Pump Room Jockey Controller

Replace 111.10SP.100 T/M

96937694 Basement Power Section/Pump Room PRV Replace 111.10SP.100 T/M

Hose Valve

96937648 Basement By BD14 Replace 37WL 1.5" T/M

96937843 Basement Outside of Stair 1 Replace 37WL 1.5" T/M

96937617 Basement Outside of Stair 3 Replace 37WL 1.5" T/M

96937670 Basement Outside of Stair 4 Replace 37WL 1.5" T/M

96937850 Basement Stair 2 Replace 37WL 2.5" T/M

96937834 Basement Stair 3 Replace 37WL 2.5" T/M

96937649 Basement Stair 4 Replace 37WL 2.5" T/M

87453144 1st Inside Stair 3 Replace 37WL 2.5" T/M

96926203 1st Outside Stair 2 Correct 37WL 1.5" T/M

96926173 1st Outside Stair 4 Replace 37WL 1.5" T/M

96926177 1st Outside of Oil Storage Replace 37WL 1.5" T/M

96926169 1st Outside of Stair 3 Replace 37WL 1.5" T/M

96926198 1st by Column 1E13 Replace 37WL 1.5" T/M

96926171 1st in Shipping and Recieving Loading Dock Correct 37WL 1.5" T/M

87453140 2nd Inside Stair 1 Replace 37WL 2.5" T/M

87453128 2nd Inside Stair 2 Replace 37WL 2.5" T/M

87453106 2nd Inside Stair 4 Replace 37WL 2.5" T/M

87453127 2nd Outside Stair 2 Replace 37WL 1.5" T/M

96926218 2nd Outside Stair 3 Replace 37WL 1.5" T/M

87453112 2nd Outside Stair 4 Replace 37WL 1.5" T/M

87453142 2nd by Column 2B3 Replace 37WL 2.5" T/M

87453141 2nd by Column 2B6 Replace 37WL 2.5" T/M

87453123 2nd by Column 2E14 Replace 37WL 1.5" T/M

87453143 2nd by Shaft 34 Replace 37WL 1.5" T/M

96937751 3rd Inside Stair 2 Replace 37WL 2.5" T/M

96937736 3rd Inside Stair 3 Replace 37WL 2.5" T/M

96937742 3rd Inside Stair 4 Replace 37WL 2.5" T/M

96937749 3rd Outside Stair 2 Replace 37WL 1.5" T/M

96937717 3rd Outside Stair 3 Replace 37WL 1.5" T/M

96937746 3rd Outside Stair 4 Replace 37WL 1.5" T/M

96938307 4th Inside Stair 1 Replace 37WL 2.5" T/M

96938300 4th Inside Stair 2 Replace 37WL 2.5" T/M

96937793 4th Inside Stair 3 Replace 37WL 2.5" T/M

96937921 4th Inside Stair 4 Replace 37WL 2.5" T/M

96937805 4th Outside Shaft 34 Replace 37WL 1.5" T/M

96938304 4th Outside Stair 2 Replace 37WL 1.5" T/M

96937792 4th Outside Stair 3 Replace 37WL 1.5" T/M

96937800 4th Outside Stair 4 Replace 37WL 1.5" T/M

96938325 5th Inside Stair 1 Replace 37WL 2.5" T/M

96938310 5th Inside Stair 2 Replace 37WL 2.5" T/M

96938329 5th Inside Stair 3 Replace 37WL 2.5" T/M

96938318 5th Inside Stair 4 Replace 37WL 2.5" T/M

Everon 9 Download Date: 09/03/2024

96938315 5th Outside Stair 2 Replace 37WL 1.5" T/M

96938319 5th Outside Stair 4 Replace 37WL 1.5" T/M

96938326 5th by Room C551 Replace 37WL 1.5" T/M

96938327 5th by Room C566 Replace 37WL 1.5" T/M

96937644 6th Inside Stair 2 Replace 37WL 2.5" T/M

96937966 6th Inside Stair 3 Replace 37WL 2.5" T/M

96937998 6th Inside Stair 4 Replace 37WL 2.5" T/M

96936512 6th Outside Stair 2 Replace 37WL 1.5" T/M

96937957 6th Outside Stair 4 Replace 37WL 1.5" T/M

96936506 6th by Shaft 36 Replace 37WL 1.5" T/M

96938010 7th By Room C702 Replace 37WL 1.5" T/M

96937994 7th By Shaft 36 Replace 37WL 1.5" T/M

96937987 7th Inside Stair 2 Replace 37WL 1.5" T/M

96938011 7th Inside Stair 3 Replace 37WL 2.5" T/M

96937993 7th Inside Stair 4 Replace 37WL 1.5" T/M

96937903 7th Outside Stair 1 Replace 37WL 1.5" T/M

96938007 7th Outside Stair 4 Replace 37WL 1.5" T/M

96938028 8th By Room C842 Replace 37WL 1.5" T/M

96937780 8th Inside Stair 4 Replace 37WL 2.5" T/M

96938017 Penthouse Inside Stair 1 Replace 37WL 1.5" T/M

Piping

96937637 Basement Inside Stair 1 (Dry Valve) 5 Year Service

Pressure Relief

96937706 Basement Power Section/Pump Room PRV 5 Year Service 111.10sp.100 T/M

Quick Opening Device

96937666 Basement Outside Stair 4 (Dry Valve) Replace

96937871 Basement by Shaft 33 (Dry Valve) Replace

Standard Response

00000012 Basement Power Section Electric room C31 Replace

96937643 6th Outside Room C 608 Correct

Tamper Switch

96937674 Basement Power Section/Pump Room Correct OSY2 T/M

96937684 Basement Power Section/Pump Room Backflow Valve 1

Correct OSY2 T/M

96937681 Basement Power Section/Pump Room Backflow Valve 2

Correct OSY2 T/M

96937699 Basement Power Section/Pump Room Main Incoming Valve

Correct OSY2 T/M

96937876 Basement behind BD14 Correct OSY2 T/M

96937990 7th Outside Stair 2 Correct OSY2 T/M

96938014 7th Outside Stair 3 Correct OSY2 T/M

96938009 7th Outside Stair 4 Correct OSY2 T/M

PO #: (none) T/M

Everon 10 Download Date: 09/03/2024

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Alternate Power Basement Power Section/Pump Room Annual 11:21:56 AM 07/22/2024 Fire Pump Off Basement Power Section/Pump Room Annual 11:23:15 AM 07/22/2024 Fire Pump Running Basement Power Section/Pump Room Annual 11:22:52 AM 07/22/2024 Pressure Switch 2nd FM200 Behind Printing Machines Annual 12:47:03 PM 07/29/2024 Tamper Switch Basement Outside Stair 4 (hose valves) Annual 12:29:46 PM 07/22/2024 Tamper Switch Basement Outside Stair 4 (basement coverage) Annual 12:30:28 PM 07/22/2024 Tamper Switch Basement Outside Stair 4 (basement Riser) Annual 12:33:26 PM 07/22/2024 Tamper Switch Basement Outside Stair 4 (Dry Valve) Annual 12:33:49 PM 07/22/2024 Tamper Switch Basement by Zone 8 Location 14 Annual 7:03:30 AM 07/23/2024 Tamper Switch Basement by BD14 Annual 7:13:38 AM 07/23/2024 Tamper Switch Basement by Shaft 33 (hose valve riser) Annual 7:49:04 AM 07/23/2024 Tamper Switch Basement by Shaft 33 (Dry System) Annual 8:02:32 AM 07/23/2024 Tamper Switch Basement Outside Shaft 33 Annual 8:04:47 AM 07/23/2024 Tamper Switch Basement by Shaft 33 (supply) Annual 8:14:52 AM 07/23/2024 Tamper Switch Basement Outside Stair 3 Annual 8:22:38 AM 07/23/2024 Tamper Switch Basement Outside of Stair 3 (Dry Valve) Annual 8:32:52 AM 07/23/2024 Tamper Switch Basement Outside of Stair 3 (Hose Valve Riser) Annual 8:41:24 AM 07/23/2024 Tamper Switch Basement Outside of Stair 3 (Vault Area) Annual 8:43:07 AM 07/23/2024 Tamper Switch Basement Outside of Stair 3 (Dry System Air

Isolation) Annual 8:48:01 AM 07/23/2024

Tamper Switch Basement Outside of Room 25000 Annual 9:00:28 AM 07/23/2024 Tamper Switch Basement By Room C-302 Annual 9:23:17 AM 07/23/2024 Tamper Switch Basement By Room C-302 (4") Annual 9:24:04 AM 07/23/2024 Tamper Switch Basement Outside of Stair 1 Annual 9:34:47 AM 07/23/2024 Tamper Switch Basement Outside of Stair 1 Annual 9:34:54 AM 07/23/2024 Tamper Switch Basement Inside Stair 1 (Dry Valve) Annual 9:35:36 AM 07/23/2024 Tamper Switch Basement Inside Cleaning Cage Annual 9:44:28 AM 07/23/2024 Tamper Switch 1st Outside Stair 2 Annual 9:17:34 AM 07/30/2024 Tamper Switch 1st Outside Stair 4 Annual 9:47:33 AM 07/30/2024 Tamper Switch 1st Inside Power Branch Annual 11:52:54 AM 07/30/2024 Tamper Switch 1st Inside Stair 1 main lobby Annual 12:39:59 PM 07/30/2024 Tamper Switch 1st Inside Stair 1 stairway heads Annual 12:48:41 PM 07/30/2024 Tamper Switch 2nd Outside Stair 3 Isolation Valve Annual 12:14:34 PM 07/29/2024 Tamper Switch 2nd Outside Stair 3 Main Valve Annual 12:15:23 PM 07/29/2024 Tamper Switch 2nd FM200 Behind Printing Machines Annual 12:44:04 PM 07/29/2024 Tamper Switch 2nd Outside Stair 4 Isolation Valve Annual 12:53:25 PM 07/29/2024 Tamper Switch 2nd Outside Stair 4 Main Valve Annual 12:54:48 PM 07/29/2024 Tamper Switch 2nd Outside Stair 2 Isolation Valve Annual 7:13:21 AM 07/30/2024 Tamper Switch 2nd Outside Stair 2 Main Valve Annual 7:24:16 AM 07/30/2024 Tamper Switch 2nd Outside Stair 1 Isolation Valve Annual 7:39:02 AM 07/30/2024

Everon 11 Download Date: 09/03/2024

Tamper Switch 2nd Outside Stair 1 Main Valve Annual 7:41:39 AM 07/30/2024 Tamper Switch 3rd Outside Stair 3 Annual 8:49:03 AM 07/29/2024 Tamper Switch 3rd Outside Stair 4 Annual 9:01:02 AM 07/29/2024 Tamper Switch 3rd Outside Stair 2 Annual 9:20:48 AM 07/29/2024 Tamper Switch 3rd Outside Stair 1 Annual 9:29:23 AM 07/29/2024 Tamper Switch 4th Outside Stair 1 Main Control Annual 11:07:29 AM 07/26/2024 Tamper Switch 4th Outside Stair 1 Isolation Control Annual 11:09:16 AM 07/26/2024 Tamper Switch 4th Outside Stair 2 closet Annual 11:18:17 AM 07/26/2024 Tamper Switch 4th Outside Stair 2 Annual 11:19:25 AM 07/26/2024 Tamper Switch 4th Outside Stair 3 Isolation valve Annual 11:40:18 AM 07/26/2024 Tamper Switch 4th Outside Stair 3 Main Control Annual 11:42:18 AM 07/26/2024 Tamper Switch 4th Outside Stair 4 Isolation Valve Annual 11:51:05 AM 07/26/2024 Tamper Switch 4th Outside Stair 4 Main Valve Annual 11:52:20 AM 07/26/2024 Tamper Switch 5th Outside Stair 1 Annual 7:07:07 AM 07/26/2024 Tamper Switch 5th Inside Room C543 Annual 8:19:07 AM 07/26/2024 Tamper Switch 5th Room Just Outside Stair 4 Annual 8:44:00 AM 07/26/2024 Tamper Switch 5th Outside Stair 2 Annual 9:16:01 AM 07/26/2024 Tamper Switch 6th Outside Stair 1 Annual 8:38:04 AM 07/25/2024 Tamper Switch 6th Outside Stair 2 closet Annual 8:59:11 AM 07/25/2024 Tamper Switch 6th Outside Stair 2 Annual 9:00:58 AM 07/25/2024 Tamper Switch 6th Outside Stair 3 Main Control Annual 11:26:36 AM 07/25/2024 Tamper Switch 6th Outside Stair 3 Isolation Control Annual 11:31:48 AM 07/25/2024 Tamper Switch 6th Outside Stair 4 Annual 11:50:58 AM 07/25/2024 Tamper Switch 6th Outside Stair 4 above ceiling Annual 11:53:16 AM 07/25/2024 Tamper Switch 7th Outside Stair 1 Annual 8:19:26 AM 07/25/2024 Tamper Switch 7th Inside Stair 1 Annual 8:21:12 AM 07/25/2024 Tamper Switch 7th Inside Stair 1 Annual 8:27:40 AM 07/25/2024 Tamper Switch 8th Inside Stair 4 Annual 12:25:20 PM 07/23/2024 Tamper Switch 8th Inside Stair 4 Annual 12:26:17 PM 07/23/2024 Tamper Switch 8th Inside Stair 2 Annual 12:36:33 PM 07/23/2024 Tamper Switch 8th Inside Stair 3 Annual 7:59:09 AM 07/24/2024 Tamper Switch 8th Inside Stair 3 Annual 8:03:49 AM 07/24/2024 Waterflow Switch Basement Outside Stair 4 (Dry System) Annual 12:39:04 PM 07/22/2024 Waterflow Switch Basement Outside Stair 3 (1st Floor Coverage) Annual 8:35:35 AM 07/23/2024 Waterflow Switch Basement Outside Stair 3 (Basement Coverage) Annual 8:37:30 AM 07/23/2024 Waterflow Switch Basement Outside Stair 3 (Vault Area) Annual 8:44:23 AM 07/23/2024 Waterflow Switch Basement By Room C-302 Annual 9:26:11 AM 07/23/2024 Waterflow Switch Basement Inside Stair 1 (Dry Valve Air) Annual 9:39:16 AM 07/23/2024 Waterflow Switch 1st Outside Stair 4 Annual 9:51:34 AM 07/30/2024 Waterflow Switch 1st Inside Stair 1 Annual 12:40:16 PM 07/30/2024 Waterflow Switch 2nd Outside Stair 3 Annual 12:20:37 PM 07/29/2024 Waterflow Switch 2nd Outside Stair 4 Annual 12:52:41 PM 07/29/2024 Waterflow Switch 2nd Outside Stair 2 Annual 7:24:27 AM 07/30/2024 Waterflow Switch 2nd Outside Stair 1 Annual 7:40:56 AM 07/30/2024 Waterflow Switch 4th Outside Stair 1 Annual 11:08:36 AM 07/26/2024 Waterflow Switch 4th Outside Stair 2 closet Annual 11:18:28 AM 07/26/2024 Waterflow Switch 4th Outside Stair 3 Annual 11:40:54 AM 07/26/2024 Waterflow Switch 4th Outside Stair 4 Annual 11:58:24 AM 07/26/2024 Waterflow Switch 6th Outside Stair 1 Annual 8:37:07 AM 07/25/2024 Waterflow Switch 6th Outside Stair 2 closet Annual 8:58:46 AM 07/25/2024 Waterflow Switch 6th Outside Stair 3 Annual 11:33:36 AM 07/25/2024 Waterflow Switch 6th Outside Stair 4 Annual 11:55:33 AM 07/25/2024

Everon 12 Download Date: 09/03/2024

Waterflow Switch 7th Inside Stair 1 Annual 8:22:04 AM 07/25/2024 Waterflow Switch 8th Inside Stair 4 Annual 12:23:32 PM 07/23/2024 Waterflow Switch 8th Inside Stair 3 Annual 8:30:05 AM 07/24/2024 Air Maintenance Device Basement by Shaft 33 (Dry Valve) Annual 7:54:17 AM 07/23/2024 Air Maintenance Device Basement Outside Stair 3 (Dry Valve) Annual 8:28:21 AM 07/23/2024 Air Maintenance Device Basement Inside Stair 1 (Dry Valve) Annual 9:42:07 AM 07/23/2024 Drain Basement by Shaft 33 (Dry Valve) Annual 8:00:16 AM 07/23/2024 Drain Basement Outside Shaft 33 Annual 8:05:11 AM 07/23/2024 Drain Basement Outside Stair 3 (Dry Valve) Annual 8:31:01 AM 07/23/2024 Drain Basement Outside Stair 3 (Basement Coverage ) Annual 8:37:57 AM 07/23/2024 Drain Basement Outside Stair 1 Annual 9:28:58 AM 07/23/2024 Drain Basement Inside Stair 1 (Dry Valve) Annual 9:36:51 AM 07/23/2024 Drain 1st Outside Stair 2 Annual 9:17:49 AM 07/30/2024 Drain 1st Outside Stair 4 Annual 9:47:46 AM 07/30/2024 Drain 1st Inside Power Branch Annual 11:52:30 AM 07/30/2024 Drain 2nd Outside Stair 3 Annual 12:14:14 PM 07/29/2024 Drain 2nd Outside Stair 4 Annual 12:53:57 PM 07/29/2024 Drain 2nd Outside Stair 1 Annual 7:40:43 AM 07/30/2024 Drain 3rd Outside Stair 3 Annual 8:48:28 AM 07/29/2024 Drain 3rd Outside Stair 4 Annual 9:00:24 AM 07/29/2024 Drain 3rd Outside Stair 2 Annual 9:22:17 AM 07/29/2024 Drain 3rd Outside Stair 1 Annual 9:29:12 AM 07/29/2024 Drain 4th Outside Stair 1 Annual 11:09:45 AM 07/26/2024 Drain 4th Outside Stair 2 Annual 11:19:43 AM 07/26/2024 Drain 4th Outside Stair 3 Annual 11:40:43 AM 07/26/2024 Drain 4th Outside Stair 4 Annual 11:51:18 AM 07/26/2024 Drain 5th Outside Stair 1 Annual 7:07:18 AM 07/26/2024 Drain 5th Inside Room C543 Annual 8:19:26 AM 07/26/2024 Drain 5th Outside Stair 2 Annual 9:16:31 AM 07/26/2024 Drain 6th Outside Stair 1 Annual 8:39:00 AM 07/25/2024 Drain 6th Outside Stair 2 Annual 9:00:30 AM 07/25/2024 Drain 6th Outside Stair 4 above ceiling Annual 11:53:26 AM 07/25/2024 Drain 7th Outside Stair 3 Annual 11:53:03 AM 07/24/2024 Drain 7th Outside Stair 2 Annual 12:40:55 PM 07/24/2024 Drain 7th Outside Stair 1 Annual 8:18:19 AM 07/25/2024 Drain 7th Inside Stair 1 Annual 8:21:36 AM 07/25/2024 Drain 8th Inside Stair 4 Annual 12:24:01 PM 07/23/2024 Drain 8th Outside Stair 2 Annual 12:34:47 PM 07/23/2024 Drain 8th Inside Stair 3 Annual 7:56:55 AM 07/24/2024 Quick Opening Device Basement Outside Stair 3 (Dry Valve) Annual 8:25:46 AM 07/23/2024 Quick Opening Device Basement Inside of Stair 1 (Dry Valve) Annual 8:30:18 AM 08/08/2024 Test Gauge Basement Power Section/Pump Room Annual 11:41:25 AM 07/22/2024 Controller Basement Power Section/Pump Room Annual 11:22:11 AM 07/22/2024 Electrical Driver Basement Power Section/Pump Room Annual 11:47:26 AM 07/22/2024 Jockey Controller Basement Power Section/Pump Room Annual 12:07:44 PM 07/22/2024 Jockey Pump Basement Power Section/Pump Room Annual 11:42:58 AM 07/22/2024 Pump Basement Power Section/Pump Room Annual 12:57:26 PM 08/17/2024 Standard Response 4th Inside Stair 1 Annual 8:57:20 AM 07/31/2024 Control Valve Basement Power Section/Pump Room Annual 11:34:12 AM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 11:37:00 AM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 12:07:01 PM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 12:10:38 PM 07/22/2024

Everon 13 Download Date: 09/03/2024

Control Valve Basement Power Section/Pump Room Backflow

Valve 1 Annual 12:13:04 PM 07/22/2024

Control Valve Basement Power Section/Pump Room Backflow Valve 2

Annual 12:13:30 PM 07/22/2024

Control Valve Basement Outside Stair 4 (basement coverage) Annual 12:31:16 PM 07/22/2024 Control Valve Basement Outside Stair 4 (Riser) Annual 12:32:35 PM 07/22/2024 Control Valve Basement Outside Stair 4 (Dry Valve) Annual 12:34:10 PM 07/22/2024 Control Valve Basement by BD14 Annual 12:46:09 PM 07/22/2024 Control Valve Basement by Zone 8 Location 14 Annual 7:05:15 AM 07/23/2024 Control Valve Basement behind BD14 Annual 7:18:36 AM 07/23/2024 Control Valve Basement by Shaft 33 (hose valve riser) Annual 7:50:28 AM 07/23/2024 Control Valve Basement by Shaft 33 (Dry Valve) Annual 8:09:56 AM 07/23/2024 Control Valve Basement Outside Stair 3 Annual 8:20:38 AM 07/23/2024 Control Valve Basement Outaide of Stair 3 (Hose Valve Riser) Annual 8:40:49 AM 07/23/2024 Control Valve Basement Outaide of Stair 3 (Vault Area) Annual 8:43:37 AM 07/23/2024 Control Valve Basement Outaide of Stair 3 (Dry Valve) Annual 8:49:24 AM 07/23/2024 Control Valve Basement Outaide of Room 25000 Annual 8:59:14 AM 07/23/2024 Control Valve Basement By Room C-302 Annual 9:24:48 AM 07/23/2024 Control Valve Basement By Room C-302 Annual 9:25:20 AM 07/23/2024 Control Valve Basement Outside of Stair 1 Annual 9:28:10 AM 07/23/2024 Control Valve Basement Outside of Stair 1 Annual 9:28:46 AM 07/23/2024 Control Valve Basement Inside Stair 1 (Dry Valve) Annual 9:36:06 AM 07/23/2024 Control Valve Basement Inside Cleaning Cage Annual 9:44:51 AM 07/23/2024 Control Valve 1st Outside Stair 2 Annual 9:17:16 AM 07/30/2024 Control Valve 1st Outside Stair 4 hose valve isolation Annual 9:46:12 AM 07/30/2024 Control Valve 1st Outside Stair 4 Annual 9:47:17 AM 07/30/2024 Control Valve 1st Inside Stair 1 stairway heads Annual 12:36:44 PM 07/30/2024 Control Valve 1st Inside Stair 1 main lobby Annual 12:39:15 PM 07/30/2024 Control Valve 2nd Outside Stair 3 Isolation Valve Annual 12:14:44 PM 07/29/2024 Control Valve 2nd Outside Stair 3 Main Valve Annual 12:15:38 PM 07/29/2024 Control Valve 2nd FM200 Behind Printing Machines Annual 12:46:45 PM 07/29/2024 Control Valve 2nd Outside Stair 4 Main Valve Annual 12:53:10 PM 07/29/2024 Control Valve 2nd Outside Stair 4 Isolation Valve Annual 12:53:37 PM 07/29/2024 Control Valve 2nd Outside Stair 2 Isolation Valve Annual 7:13:45 AM 07/30/2024 Control Valve 2nd Outside Stair 1 Main Valve Annual 7:38:19 AM 07/30/2024 Control Valve 2nd Outside Stair 1 Isolation Valve Annual 7:39:38 AM 07/30/2024 Control Valve 3rd Outside Stair 3 Annual 8:48:50 AM 07/29/2024 Control Valve 3rd Outside Stair 4 Annual 9:00:41 AM 07/29/2024 Control Valve 3rd Outside Stair 2 Annual 9:22:07 AM 07/29/2024 Control Valve 3rd Outside Stair 1 Annual 9:29:34 AM 07/29/2024 Control Valve 4th Outside Stair 1 Main Control Annual 11:08:01 AM 07/26/2024 Control Valve 4th Outside Stair 1 Isolation Control Annual 11:08:58 AM 07/26/2024 Control Valve 4th Outside Stair 2 closet Annual 11:18:02 AM 07/26/2024 Control Valve 4th Outside Stair 2 Annual 11:19:00 AM 07/26/2024 Control Valve 4th Outside Stair 3 Isolation Valve Annual 11:40:31 AM 07/26/2024 Control Valve 4th Outside Stair 3 Main Control Annual 11:41:59 AM 07/26/2024 Control Valve 4th Outside Stair 4 Isolation Valve Annual 11:50:47 AM 07/26/2024 Control Valve 4th Outside Stair 4 Main Valve Annual 11:52:01 AM 07/26/2024 Control Valve 5th Outside Stair 1 Annual 7:06:49 AM 07/26/2024 Control Valve 5th Inside Room C543 Annual 8:18:36 AM 07/26/2024 Control Valve 5th Room Just Outside Stair 4 Annual 8:44:29 AM 07/26/2024 Control Valve 5th Room Just Outside Stair 4 Annual 8:44:52 AM 07/26/2024

Everon 14 Download Date: 09/03/2024

Control Valve 5th Outside Stair 2 Annual 9:15:27 AM 07/26/2024 Control Valve 6th Outside Stair 1 Annual 8:38:30 AM 07/25/2024 Control Valve 6th Outside Stair 2 closet Annual 8:59:32 AM 07/25/2024 Control Valve 6th Outside Stair 2 Annual 9:00:46 AM 07/25/2024 Control Valve 6th Outside Stair 3 Main Control Annual 11:27:59 AM 07/25/2024 Control Valve 6th Outside Stair 3 Isolation Control Annual 11:30:49 AM 07/25/2024 Control Valve 6th Outside Stair 4 Annual 11:38:30 AM 07/25/2024 Control Valve 6th Outside Stair 4 above ceiling Annual 11:53:05 AM 07/25/2024 Control Valve 7th Outside Stair 3 Annual 11:54:58 AM 07/24/2024 Control Valve 7th Outside Stair 4 Annual 12:15:52 PM 07/24/2024 Control Valve 7th Outside Stair 2 Annual 12:40:24 PM 07/24/2024 Control Valve 7th Outside Stair 1 Annual 8:17:27 AM 07/25/2024 Control Valve 7th Inside Stair 1 Annual 8:20:37 AM 07/25/2024 Control Valve 7th Inside Stair 1 Annual 8:20:50 AM 07/25/2024 Control Valve 8th Inside Stair 4 Annual 12:20:49 PM 07/23/2024 Control Valve 8th Inside Stair 4 Annual 12:23:14 PM 07/23/2024 Control Valve 8th Outside of Stair 2 Annual 12:36:19 PM 07/23/2024 Control Valve 8th Inside Stair 3 Annual 7:57:14 AM 07/24/2024 Control Valve 8th Inside Stair 3 Annual 7:57:25 AM 07/24/2024 Dry Pipe Valve Basement Outside Stair 4 (Dry Valve) Annual 12:34:41 PM 07/22/2024 Dry Pipe Valve Basement by Shaft 33 (Dry Valve) Annual 8:01:32 AM 07/23/2024 Dry Pipe Valve Basement Outside of Stair 3 (Dry Valve) Annual 8:31:57 AM 07/23/2024 Dry Pipe Valve Basement Inside Stair 1 (Dry Valve) Annual 8:30:09 AM 08/08/2024 Hose Valve Basement Stair 1 Annual 9:22:02 AM 07/23/2024 Hose Valve 1st Inside Stair 2 Annual 9:15:27 AM 07/30/2024 Hose Valve 1st Inside Stair 4 Annual 9:45:45 AM 07/30/2024 Hose Valve 1st Inside Stair 1 Annual 12:36:09 PM 07/30/2024 Hose Valve 2nd Outside Stair 1 Annual 7:38:00 AM 07/30/2024 Hose Valve 2nd Inside Stair 3 Annual 12:27:55 PM 07/30/2024 Hose Valve 3rd by Column 3E 13 Annual 9:10:18 AM 07/29/2024 Hose Valve 3rd Inside Stair 1 Annual 9:28:19 AM 07/29/2024 Hose Valve 3rd Outside Stair 1 Annual 9:28:56 AM 07/29/2024 Hose Valve 4th Outside Stair 1 Annual 11:02:44 AM 07/26/2024 Hose Valve 5th Outside Stair 1 Annual 7:05:17 AM 07/26/2024 Hose Valve 6th Inside Stair 1 Annual 8:39:27 AM 07/25/2024 Hose Valve 6th Outside Stair 1 Annual 8:44:35 AM 07/25/2024 Hose Valve 6th Outside Stair 3 Annual 11:28:32 AM 07/25/2024 Hose Valve 7th Outside Stair 3 Annual 11:52:36 AM 07/24/2024 Hose Valve 7th Inside Stair 1 Annual 8:19:44 AM 07/25/2024 Hose Valve 8th Outide Stair 4 Annual 12:28:14 PM 07/23/2024 Hose Valve 8th By Room C-825 Annual 12:29:02 PM 07/23/2024 Hose Valve 8th Outside Stair 2 Annual 12:35:17 PM 07/23/2024 Hose Valve 8th Inside Stair 2 Annual 12:35:36 PM 07/23/2024 Hose Valve 8th Outside Stair 1 Annual 1:00:27 PM 07/23/2024 Hose Valve 8th Inside Stair 1 Annual 1:01:47 PM 07/23/2024 Hose Valve 8th Outside Stair 3 Annual 7:56:25 AM 07/24/2024 Hose Valve 8th Inside Stair 3 Annual 7:56:41 AM 07/24/2024 Hose Valve Penthouse Outside Stair 3 Annual 8:48:53 AM 07/24/2024 Hose Valve Penthouse Inside Stair 3 Annual 8:49:27 AM 07/24/2024 Hose Valve Penthouse Inside Stair 1 Annual 8:58:44 AM 07/24/2024

Failed/Other

Everon 15 Download Date: 09/03/2024

Tamper Switch Basement Power Section/Pump Room Annual 11:38:14 AM 07/22/2024 Tamper Switch Basement Power Section/Pump Room Main

Incoming Valve Annual 12:11:35 PM 07/22/2024

Tamper Switch Basement Power Section/Pump Room Backflow Valve 1

Annual 12:12:20 PM 07/22/2024

Tamper Switch Basement Power Section/Pump Room Backflow Valve 2

Annual 12:12:46 PM 07/22/2024

Tamper Switch Basement behind BD14 Annual 7:27:45 AM 07/23/2024 Tamper Switch 7th Outside Stair 3 Annual 11:56:41 AM 07/24/2024 Tamper Switch 7th Outside Stair 4 Annual 12:19:38 PM 07/24/2024 Tamper Switch 7th Outside Stair 2 Annual 12:44:29 PM 07/24/2024 Drain 2nd Outside Stair 2 Annual 7:28:21 AM 07/30/2024 Gauge Basement Power Section/Pump Room Annual 11:26:11 AM 07/22/2024 Gauge Basement Power Section/Pump Room Annual 11:46:25 AM 07/22/2024 Gauge Basement Power Section/Pump Room Annual 11:46:45 AM 07/22/2024 Gauge Basement Power Section/Pump Room PRV Annual 11:54:03 AM 07/22/2024 Gauge Basement Power Section/Pump Room Jockey

Controller Annual 12:09:15 PM 07/22/2024

Gauge Basement Outside Stair 4 (Dry Valve) Annual 12:36:20 PM 07/22/2024 Gauge Basement Outside Stair 4 (Dry Valve) Annual 12:36:52 PM 07/22/2024 Gauge Basement Outside Stair 4 (QOD) Annual 12:38:22 PM 07/22/2024 Gauge Basement By Shaft 33 (QOD Guage) Annual 7:58:36 AM 07/23/2024 Gauge Basement By Shaft 33 (Dry Valve Air) Annual 7:59:31 AM 07/23/2024 Gauge Basement By Shaft 33 (Dry Valve Water) Annual 8:00:03 AM 07/23/2024 Gauge Basement Outside Stair 3 (QOD Guage) Annual 8:27:27 AM 07/23/2024 Gauge Basement Outside Stair 3 (Dry Valve Air) Annual 8:29:25 AM 07/23/2024 Gauge Basement Outside Shaft 3 (Dry Valve Water) Annual 8:30:15 AM 07/23/2024 Gauge Basement Inside Stair 1 (Dry Valve Water) Annual 9:38:17 AM 07/23/2024 Gauge Basement Inside Stair 1 (Dry Valve Air) Annual 9:39:04 AM 07/23/2024 Gauge Basement Inside of Stair 1 (QOD) Annual 9:41:01 AM 07/23/2024 Quick Opening Device Basement by Shaft 33 (Dry Valve) Annual 9:26:13 AM 08/08/2024 Quick Opening Device Basement Outside Stair 4 (Dry Valve) Annual 10:21:17 AM 08/08/2024 Casing Relief Valve Basement Power Section/Pump Room Annual 12:21:08 PM 08/17/2024 Piping Basement Inside Stair 1 (Dry Valve) Annual 9:42:57 AM 07/23/2024 Standard Response Basement Power Section Electric room C31 Annual 10:16:57 AM 07/23/2024 Standard Response 6th Outside Room C 608 Annual 9:03:32 AM 07/25/2024 Backflow Prevention Basement Power Section/Pump Room Visually Checked 12:15:10 PM 07/22/2024 Check Valve Basement Power Section/Pump Room Annual 11:41:04 AM 07/22/2024 Check Valve Basement Power Section/Pump Room Discharge Annual 12:06:33 PM 07/22/2024 Check Valve Basement Outside of Room 25000 Annual 9:03:19 AM 07/23/2024 Check Valve Basement Outside of Room 25000 Annual 9:46:18 AM 07/23/2024 Control Valve Basement Power Section/Pump Room Annual 11:33:36 AM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 11:39:07 AM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 12:03:25 PM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 12:04:35 PM 07/22/2024 Control Valve Basement Power Section/Pump Room Annual 12:05:19 PM 07/22/2024 Control Valve Basement Power Section/Pump Room Test

Header Annual 12:05:50 PM 07/22/2024

Control Valve Basement Outside Shaft 33 Annual 8:09:11 AM 07/23/2024 Control Valve Basement by Shaft 33 (supply) Annual 8:16:03 AM 07/23/2024 Control Valve Basement Outside Stair 3 (Dry Valve Air

Isolation) Annual 8:48:24 AM 07/23/2024

Everon 16 Download Date: 09/03/2024

Control Valve 1st Inside Power Brach Annual 11:59:42 AM 07/30/2024 Control Valve 2nd Outside Stair 2 Main Valve Annual 7:31:12 AM 07/30/2024 Hose Valve Basement Stair 3 Annual 8:57:18 AM 07/23/2024 Hose Valve Basement Outside of Stair 3 Annual 8:59:02 AM 07/23/2024 Hose Valve Basement Stair 4 Annual 9:03:58 AM 07/23/2024 Hose Valve Basement Outside of Stair 4 Annual 9:05:17 AM 07/23/2024 Hose Valve Basement By BD14 Annual 9:05:44 AM 07/23/2024 Hose Valve Basement Stair 2 Annual 9:07:49 AM 07/23/2024 Hose Valve Basement Outside of Stair 1 Annual 9:21:13 AM 07/23/2024 Hose Valve 1st Outside Stair 2 Annual 9:17:03 AM 07/30/2024 Hose Valve 1st by Column 1E13 Annual 9:45:00 AM 07/30/2024 Hose Valve 1st Outside Stair 4 Annual 9:45:37 AM 07/30/2024 Hose Valve 1st Outside of Oil Storage Annual 10:01:02 AM 07/30/2024 Hose Valve 1st in Shipping and Recieving Loading Dock Annual 11:45:10 AM 07/30/2024 Hose Valve 1st Outside of Stair 3 Annual 11:51:47 AM 07/30/2024 Hose Valve 1st Inside Stair 3 Annual 12:26:06 PM 07/30/2024 Hose Valve 2nd Outside Stair 3 Annual 12:12:40 PM 07/29/2024 Hose Valve 2nd Inside Stair 4 Annual 12:50:59 PM 07/29/2024 Hose Valve 2nd Outside Stair 4 Annual 12:52:23 PM 07/29/2024 Hose Valve 2nd by Column 2E14 Annual 7:08:53 AM 07/30/2024 Hose Valve 2nd Outside Stair 2 Annual 7:23:25 AM 07/30/2024 Hose Valve 2nd Inside Stair 2 Annual 7:36:53 AM 07/30/2024 Hose Valve 2nd Inside Stair 1 Annual 7:37:43 AM 07/30/2024 Hose Valve 2nd by Column 2B6 Annual 8:03:45 AM 07/30/2024 Hose Valve 2nd by Column 2B3 Annual 8:04:17 AM 07/30/2024 Hose Valve 2nd by Shaft 34 Annual 8:06:09 AM 07/30/2024 Hose Valve 3rd Inside Stair 3 Annual 8:47:01 AM 07/29/2024 Hose Valve 3rd Outside Stair 3 Annual 8:48:08 AM 07/29/2024 Hose Valve 3rd Inside Stair 4 Annual 8:59:20 AM 07/29/2024 Hose Valve 3rd Outside Stair 4 Annual 9:00:07 AM 07/29/2024 Hose Valve 3rd Outside Stair 2 Annual 9:23:09 AM 07/29/2024 Hose Valve 3rd Inside Stair 2 Annual 9:23:55 AM 07/29/2024 Hose Valve 4th Inside Stair 1 Annual 11:02:32 AM 07/26/2024 Hose Valve 4th Inside Stair 2 Annual 11:17:21 AM 07/26/2024 Hose Valve 4th Outside Stair 2 Annual 11:17:46 AM 07/26/2024 Hose Valve 4th Outside Shaft 34 Annual 11:37:16 AM 07/26/2024 Hose Valve 4th Outside Stair 3 Annual 11:47:01 AM 07/26/2024 Hose Valve 4th Inside Stair 3 Annual 11:47:26 AM 07/26/2024 Hose Valve 4th Outside Stair 4 Annual 11:50:37 AM 07/26/2024 Hose Valve 4th Inside Stair 4 Annual 11:53:32 AM 07/26/2024 Hose Valve 5th Inside Stair 1 Annual 7:05:59 AM 07/26/2024 Hose Valve 5th by Room C551 Annual 7:25:04 AM 07/26/2024 Hose Valve 5th by Room C566 Annual 7:27:57 AM 07/26/2024 Hose Valve 5th Inside Stair 3 Annual 7:30:29 AM 07/26/2024 Hose Valve 5th Inside Stair 4 Annual 8:42:22 AM 07/26/2024 Hose Valve 5th Outside Stair 4 Annual 8:42:53 AM 07/26/2024 Hose Valve 5th Inside Stair 2 Annual 9:14:25 AM 07/26/2024 Hose Valve 5th Outside Stair 2 Annual 9:15:12 AM 07/26/2024 Hose Valve 6th by Shaft 36 Annual 8:57:22 AM 07/25/2024 Hose Valve 6th Inside Stair 2 Annual 8:57:53 AM 07/25/2024 Hose Valve 6th Outside Stair 2 Annual 8:58:24 AM 07/25/2024 Hose Valve 6th Inside Stair 3 Annual 11:28:23 AM 07/25/2024

Everon 17 Download Date: 09/03/2024

Hose Valve 6th Outside Stair 4 Annual 11:40:22 AM 07/25/2024 Hose Valve 6th Inside Stair 4 Annual 11:40:49 AM 07/25/2024 Hose Valve 7th Inside Stair 3 Annual 11:52:25 AM 07/24/2024 Hose Valve 7th By Room C702 Annual 12:11:42 PM 07/24/2024 Hose Valve 7th Outside Stair 4 Annual 12:17:04 PM 07/24/2024 Hose Valve 7th Inside Stair 4 Annual 12:17:38 PM 07/24/2024 Hose Valve 7th By Shaft 36 Annual 12:24:30 PM 07/24/2024 Hose Valve 7th Inside Stair 2 Annual 12:39:51 PM 07/24/2024 Hose Valve 7th Outside Stair 1 Annual 8:17:12 AM 07/25/2024 Hose Valve 8th Inside Stair 4 Annual 12:27:50 PM 07/23/2024 Hose Valve 8th By Room C842 Annual 7:53:30 AM 07/24/2024 Hose Valve Penthouse Inside Stair 1 Annual 8:59:08 AM 07/24/2024 Pressure Relief Basement Power Section/Pump Room PRV Annual 11:56:14 AM 07/22/2024

Everon 18 Download Date: 09/03/2024

Fire Pump Testing

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Pump

Manufacturer Model Number Location Install Date ScanID Peerless 5AEF11G Basement Power Section/Pump

Room 07/22/2012 96937707

Serial Number Type Orientation Aligned? Water Supply Impeller Size Pump Primary Horizontal Split

Case Yes Municipal 9.76

Fire Pump Tests

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water Temperature

Other 08/17/2024 160 62 0 1892

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

43 39 42 482 483 482

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 140 54 1008 1759

81 76 74 477 478 477

Discharge Device Date

Disch.

psi

Suct.

psi GPM RPM Oil Pressure

Water

Other 08/17/2024 105 40 1512 1727

88 82 85 477 477 478

Fire Pump Rating

Amps Volts

Net Pressure Gallons Per Minute

Rotations Per Minute A B C A-B B-C A-C

98 0

86 1000

65 1500

Everon 19 Download Date: 09/03/2024

Everon 20 Download Date: 09/03/2024

Inventory & Warranty Report

Building: GPO Building C

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Air Maintenance Device Device 0.85% 3

Alternate Power Alarm 0.28% 1

Backflow Prevention Valve 0.28% 1

Casing Relief Valve Pump 0.28% 1

Check Valve Valve 1.13% 4

Control Valve Valve 23.73% 84

Controller Pump 0.28% 1

Drain Device 9.60% 34

Dry Pipe Valve Valve 1.13% 4

Electrical Driver Pump 0.28% 1

Fire Pump Off Alarm 0.28% 1

Fire Pump Running Alarm 0.28% 1

Gauge Device 4.80% 17

Hose Valve Valve 25.14% 89

Jockey Controller Pump 0.28% 1

Jockey Pump Pump 0.28% 1

Piping Sprinkler 0.28% 1

Pressure Relief Valve 0.28% 1

Pressure Switch Alarm 0.28% 1

Pump Pump 0.28% 1

Quick Opening Device Device 1.13% 4

Standard Response Sprinkler 0.85% 3

Tamper Switch Alarm 21.19% 75

Test Gauge Device 0.28% 1

Waterflow Switch Alarm 6.50% 23

Device Type

Qt y Model # Type Description Install Date

In Service - 3 Years to 5 Years

Alternate Power 1 7ANG1051

Supervisory 07/22/2020

Controller 1 7ANG1051

07/22/2020

Fire Pump Off 1 7ANG1051

Fire Pump Running 1 7ANG1051

In Service - 10 Years to 15 Years

Check Valve 2

Flanged

07/22/2012

Piping 1

Steel

Standard Response 3

Control Valve 1 2004 Ball Main Control 07/22/2012

Hose Valve 52 37WL 1.5"

Hose Valve 37 37WL 2.5"

Jockey Pump 1 84Z04053 Automatic

Casing Relief Valve 1 551

Everon 21 Download Date: 09/03/2024

Pressure Relief 1 111.10sp.100 Main - Fire Pump

Test Gauge 1 6"-1000G

Pressure Switch 1 3PDT

Alarm 07/22/2012

Check Valve 2 K0900W Grooved

Control Valve 58

OS&Y Isolation 07/22/2012

Control Valve 1

OS&Y Main Control 07/22/2012

Control Valve 2 200 wog OS&Y Isolation 07/22/2012

Control Valve 3 250W OS&Y Main Control 07/22/2012

Control Valve 1 250W OS&Y Suction 07/22/2012

Control Valve 3 GD-4765-8N Butterfly Bypass 07/22/2012

Control Valve 2 GD-4765-8N Butterfly Discharge 07/22/2012

Control Valve 10 GD-4765-8N OS&Y Isolation 07/22/2012

Control Valve 1 T-104-0 Butterfly Bypass 07/22/2012

Control Valve 2 T-104-0 Butterfly Drain valve 07/22/2012

Pump 1 5AEF11G Pump Primary

Waterflow Switch 1 PS10-2 Pressure Switch Alarm 07/22/2012

Waterflow Switch 6 VSR-F Vane Alarm 07/22/2012

Drain 1 200 wog Auxiliary

Drain 2 200 wog Low Point

Drain 31 200 wog Main

Air Maintenance Device 3 4zk96 Pressure Reducing

Tamper Switch 74 OSY2 Lever Supervisory 07/22/2012

Waterflow Switch 1

Waterflow Switch 1

Vane Alarm 07/22/2012

Waterflow Switch 2 WFD60 Vane Alarm 07/22/2012

Waterflow Switch 12 WFD60 Vane Alarm 07/22/2012

Dry Pipe Valve 1 dpv1

Quick Opening Device 1

Jockey Controller 1 JP3-208/0.75/3/6

Gauge 4 111.10SP.100

Dry Pipe Valve 2 DPV-1 Flanged

Dry Pipe Valve 1 DPV-1v Flanged

Quick Opening Device 3

Electrical Driver 1 125360P3GFP404T S

Gauge 8 111.10SP.100 Air Pressure

Gauge 1 111.10SP.100 Supply Pressure

Gauge 4 111.10SP.100 System Pressure

Backflow Prevention 1 G1 FY1109 Double Check

Tamper Switch 1 RBVS Ball Valve Supervisory 07/22/2012

Everon 22 Download Date: 09/03/2024

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.

Address Device Type Location Type ScanID

Control Panel 1 Zone/Address: Z03

L002D0419 Tamper Switch Basement Outside of Stair 3 (Dry System Air Isolation)

Lever 96937855

Zone/Address: Z05 L002D0423 Tamper Switch 1st Inside Stair 1 stairway heads Lever 87453156

Zone/Address: Z06 L002D0424 Tamper Switch 1st Outside Stair 2 Lever 96926200

Zone/Address: Z07 L002D0426 Tamper Switch 1st Inside Power Branch Lever 96926166 L002D0426 Tamper Switch 1st Inside Stair 1 main lobby Lever 87453153

Zone/Address: Z08 L002D0429 Tamper Switch 1st Outside Stair 4 Lever 96926184

Zone/Address: Z09 L002D0431 Tamper Switch 2nd Outside Stair 1 Main Valve Lever 87453132

Zone/Address: Z10 L002D0433 Tamper Switch 2nd Outside Stair 1 Isolation Valve Lever 87453135 L002D0433 Tamper Switch 2nd Outside Stair 2 Isolation Valve Lever 87453129 L002D0433 Tamper Switch 2nd Outside Stair 2 Main Valve Lever 87453125

Zone/Address: Z11 L002D0435 Tamper Switch 2nd Outside Stair 3 Isolation Valve Lever 96926226 L002D0435 Tamper Switch 2nd Outside Stair 3 Main Valve Lever 96926220

Zone/Address: Z12 L002D0437 Tamper Switch 2nd Outside Stair 4 Isolation Valve Lever 87453108 L002D0437 Tamper Switch 2nd Outside Stair 4 Main Valve Lever 96926208

Zone/Address: Z13 L002D0438 Tamper Switch 3rd Outside Stair 1 Lever 96937758

Zone/Address: Z14 L002D0439 Tamper Switch 4th Outside Stair 2 Lever 96938302

Zone/Address: Z15 L002D0425 Tamper Switch 3rd Outside Stair 2 Lever 96937752 L002D0425 Tamper Switch 3rd Outside Stair 3 Lever 96937716

Zone/Address: Z16

Everon 23 Download Date: 09/03/2024

L002D0427 Tamper Switch 3rd Outside Stair 4 Lever 96937743

Zone/Address: Z17 L002D0447 Tamper Switch 4th Outside Stair 1 Isolation Control Lever 96937928 L002D0447 Tamper Switch 4th Outside Stair 1 Main Control Lever 96937932

Zone/Address: Z18 L002D0449 Tamper Switch 4th Outside Stair 2 closet Lever 96938306

Zone/Address: Z19 L002D0415 Tamper Switch Basement By Room C-302 Lever 96937653 L002D0415 Tamper Switch Basement By Room C-302 (4") Lever 96937632 L002D0415 Tamper Switch Basement Inside Cleaning Cage Lever 96937661 L002D0415 Tamper Switch Basement Inside Stair 1 (Dry Valve) Lever 96937391 L002D0415 Tamper Switch Basement Outside of Stair 1 Lever 96937846 L002D0415 Tamper Switch Basement Outside of Stair 1 Lever 96937849 L002D0417 Tamper Switch Basement Outside Shaft 33 Lever 96937868 L002D0417 Tamper Switch Basement Outside Stair 3 Lever 96937858 L002D0417 Tamper Switch Basement by Shaft 33 (supply) Lever 96937862 L002D0419 Tamper Switch Basement Outside of Room 25000 Lever 96937835 L002D0419 Tamper Switch Basement Outside of Stair 3 (Dry Valve) Lever 96937603 L002D0419 Tamper Switch Basement Outside of Stair 3 (Hose…