Inspection - 2024-08-06_GPO-Building-B_Fire_Alarm.pdf
PDF 1 MB Posted
- Solicitation number
- 040ADV-25-R-0013
- Issued by
-
Government Publishing Office
About this file
This is a fire alarm inspection report conducted on August 6, 2024, for Building B of the Government Publishing Office (GPO) located at 732 North Capitol St. NW in Washington, DC. The inspection was performed by Everon, with inspector Terance Proctor testing the building's fire alarm and life safety systems according to NFPA 72 standards.
The inspection covered 276 total devices, with 274 (99.28%) passing and 2 (0.72%) failing. The failed items included one speaker/strobe on the roof that failed operation and one smoke detector on the 3rd floor elevator that failed annunciation. The inventory included 174 smoke detectors, 19 pull stations, 14 batteries, 12 heat detectors, and various other components like strobes, speakers, and annunciators. Most devices were Edwards brand installed in 2012, though some newer components were installed in 2024, including 9 speaker/strobes and 19 pull stations. The report provided detailed testing documentation for each device, including location, test time/date, and pass/fail status. Additionally, all duct detectors were noted as inoperable, with half being 120V unknown make and half being Siemens, with none tied into the fire alarm system.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UEID: LJLDFKJ2VKP5 | CAGE: 5MB43
Government Publishing Office
732 North Capitol St. NW Building B
Washington, DC 20401 Fire Alarm Inspection
August 6, 2024
Government Publishing Office 732 North Capitol St NW Washington, DC 20401
HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098
(435) 731-9525
Points of Contact
Mason Barrett, President
Mason@HurtVet.com
Dan Vandergriff, Chief Operating Officer
Dan@HurtVet.com
Jason Munoz, Senior Project Manager
Jason@HurtVet.com
Fire Alarm and Life Safety System Inspection Certificate
For
GPO Building B
732 NORTH CAPITOL ST NW
BUILDING B
WASHINGTON, DC 20401
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Date Aug 6, 2024
Building: GPO Building B Company: Everon Contact: Jason Munoz Contact: Terance Proctor
Title: Senior Project Manager Title: Fire Test & Inspect Tech l
Everon 1 Download Date: 09/03/2024
Executive Summary Generated by: BuildingReports.com
Building Information Building: GPO Building B Contact: Jason Munoz
Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548
Address: BUILDING B Fax:
City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865
Country: United States of America Email: Jason@hurtvet.com
Inspection Performed By Company: Everon Inspector: Terance Proctor
Address: 9108 Guilford Road Phone: 301 875-5064
Address: Suite H Fax:
City/State/ZIP Code: Columbia, MD 21046-2629 Mobile: 301 875-5064
Country: United States of America Email: teranceproctor@adt.com
Everon 2 Download Date: 09/03/2024
Inspection Summary
Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %
Control 42 15.22% 42 100.00% 42 100.00% 0 0.00% Indicating 29 10.51% 29 100.00% 28 96.55% 1 3.45% Initiating 205 74.28% 205 100.00% 204 99.51% 1 0.49%
Totals 276 100% 276 100.00% 274 99.28% 2 0.72%
Certification
Company: Everon Building: GPO Building B
Inspector: Terance Proctor Contact: Jason Munoz
Everon 3 Download Date: 09/03/2024
Discrepancy Report
Building: GPO Building B Control Panel: 1
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade No items found during this inspection.
ScanID Location Problem Address Reference
Indicating Speaker/Strobe
000009 Roof Building B Entire Floor Failed Operation 1 NFPA72 14.2.2.2.2
Initiating Smoke Detector
96926351 3rd Building B Elevator 21-22 Failed Annunciation 1-88 20-02-0028
NFPA72 10.10.1;
NFPA72 10.18.1.1.1
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
NFPA72 10.10.1;
NFPA72 10.18.1.1.1
Priority alarms, fire alarms, carbon monoxide alarm signals, supervisory signals, pre-alarm signals, and trouble signals shall be distinctively and descriptively annunciated; Visible annunciation of the location of an operated initiating device shall be by an indicator lamp, alphanumeric display, printout, or other approved means.
Everon 4 Download Date: 09/03/2024
Proposed Solutions Report
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Indicating
Speaker/Strobe
000009 Roof Building B Entire Floor Investigate 757-3A-RS70 T/M
Initiating
Smoke Detector
96926351 3rd Building B Elevator 21-22 See notes/recommenda tions
SIGA-PS T/M
PO #: (none) T/M
Everon 5 Download Date: 09/03/2024
Notes & Recommendations
Building: GPO Building B
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note All duct detector are inoperable. Half 120V, unknown make. The other half is Siemens and per Dan Pruitt none of the duct detectors are tied into Fire Alarm System. Was also told no key to reset operable Siemens duct detectors. Chance AHU will not operate after Shutdown
Building: GPO Building B Control Panel: 1
ScanID Note Device Type Location Comment
Initiating 96926351 2 Smoke Detector 3rd Building B Elevator 21-22 Failed
Annunciation
SMOKE DETECTOR NOT SHOWING THE RIGHT LOCATION
96926355 3 Smoke Detector Roof Building B Elevator Mechanical Room Passed SMOKE DETECTOR 24 AND 25 are not connected to smoke detectors on the elevator
Everon 6 Download Date: 09/03/2024
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed Control
Annunciator 3rd By Room B-104 Annual 12:34:24 PM 07/16/2024 Annunciator 3rd Electrical Shop B-303 Inside Office Annual 8:57:02 AM 07/16/2024 Battery 2nd By Stair 2 Shaft #2 Annual 9:04:19 AM 07/16/2024 Battery 2nd By Stair 2 Shaft #2 Annual 9:04:24 AM 07/16/2024 Battery 3rd By Stair 2 Shaft #2 Annual 8:25:48 AM 07/16/2024 Battery 3rd By Stair 2 Shaft #2 Annual 8:27:46 AM 07/16/2024 Battery 4th By Stair 2 Annual 12:30:24 PM 07/15/2024 Battery 4th By Stair 2 Annual 7:06:24 AM 07/16/2024 Battery 5th By Stair 2 Annual 11:52:24 AM 07/15/2024 Battery 5th By Stair 2 Annual 11:52:58 AM 07/15/2024 Battery 6th By Stair 2 Annual 10:58:13 AM 07/15/2024 Battery 6th By Stair 2 Annual 10:59:01 AM 07/15/2024 Battery 7th By Stair 2 Annual 8:48:51 AM 07/15/2024 Battery 7th By Stair 2 Annual 8:50:00 AM 07/15/2024 Battery 8th By Stair 2 Annual 7:39:43 AM 07/15/2024 Battery 8th By Stair 2 Annual 7:39:49 AM 07/15/2024 Phone Station Basement Building B Stair 1 Annual 10:07:24 AM 07/12/2024 Phone Station Basement Building B Stair 2 Annual 10:21:14 AM 07/12/2024 Phone Station Basement Building B by Oil House and Garage Annual 12:02:35 PM 07/12/2024 Phone Station 1st Building B Stair 1 Annual 10:07:10 AM 07/12/2024 Phone Station 1st Building B Stair 2 Annual 10:20:01 AM 07/12/2024 Phone Station 2nd Building B Stair 1 Annual 10:06:12 AM 07/12/2024 Phone Station 2nd Building B Stair 2 Annual 10:19:32 AM 07/12/2024 Phone Station 3rd Building B Stair 1 Annual 10:05:29 AM 07/12/2024 Phone Station 3rd Building B Stair 2 Annual 10:18:16 AM 07/12/2024 Phone Station 4th Building B Stair 1 Annual 10:04:38 AM 07/12/2024 Phone Station 4th Building B Stair 2 Annual 10:17:54 AM 07/12/2024 Phone Station 5th Building B Stair 1 Annual 10:03:51 AM 07/12/2024 Phone Station 5th Building B Stair 2 Annual 10:14:35 AM 07/12/2024 Phone Station 6th Building B Stair 1 Annual 10:03:17 AM 07/12/2024 Phone Station 6th Building B Stair 2 Annual 10:14:25 AM 07/12/2024 Phone Station 7th Building B Stair 1 Annual 10:02:49 AM 07/12/2024 Phone Station 7th Building B Stair 2 Annual 10:12:51 AM 07/12/2024 Phone Station 8th Building B Stair 1 Annual 10:00:31 AM 07/12/2024 Phone Station 8th Building B Stair 2 Annual 10:11:10 AM 07/12/2024 Power Supply 2nd By Stair 2 Shaft #2 Annual 9:04:40 AM 07/16/2024 Power Supply 3rd By Stair 2 Annual 8:25:10 AM 07/16/2024 Power Supply 4th By Stair 2 Annual 12:30:43 PM 07/15/2024 Power Supply 5th By Stair 2 Annual 11:51:31 AM 07/15/2024
Everon 7 Download Date: 09/03/2024
Power Supply 6th By Stair 2 Annual 10:57:49 AM 07/15/2024 Power Supply 7th By Stair 2 Annual 8:48:38 AM 07/15/2024 Power Supply 8th By Stair 2 Annual 7:38:18 AM 07/15/2024
Indicating Horn/Strobe Basement Building B Floor Annual 12:12:41 PM 08/27/2024 Horn/Strobe 1st Building B Floor Annual 7:06:12 PM 08/27/2024 Horn/Strobe 2nd Building B Floor Annual 7:05:49 PM 08/27/2024 Horn/Strobe 3rd Building B Floor Annual 7:05:28 PM 08/27/2024 Horn/Strobe 4th Building B Floor Annual 7:05:04 PM 08/27/2024 Horn/Strobe 5th Building B Floor Annual 7:04:42 PM 08/27/2024 Horn/Strobe 6th Building B Floor Annual 7:04:16 PM 08/27/2024 Horn/Strobe 7th Building B Floor Annual 7:03:52 PM 08/27/2024 Horn/Strobe 8th Building B Floor Annual 7:00:32 PM 08/27/2024 Speaker Basement Building B Floor Annual 7:08:57 PM 08/27/2024 Speaker/Strobe Basement Building B Floor Annual 12:13:15 PM 08/27/2024 Speaker/Strobe 1st Building B Floor Annual 7:06:00 PM 08/27/2024 Speaker/Strobe 2nd Building B Floor Annual 7:05:36 PM 08/27/2024 Speaker/Strobe 3rd Building B Floor Annual 7:05:14 PM 08/27/2024 Speaker/Strobe 4th Building B Floor Annual 7:04:52 PM 08/27/2024 Speaker/Strobe 5th Building B Floor Annual 7:04:28 PM 08/27/2024 Speaker/Strobe 6th Building B Floor Annual 7:04:02 PM 08/27/2024 Speaker/Strobe 7th Building B Floor Annual 7:00:43 PM 08/27/2024 Speaker/Strobe 8th Building B Floor Annual 7:00:13 PM 08/27/2024 Strobe Basement Building B Floor Annual 12:12:56 PM 08/27/2024 Strobe 1st Building B Floor Annual 7:06:06 PM 08/27/2024 Strobe 2nd Building B Floor Annual 7:05:42 PM 08/27/2024 Strobe 3rd Building B Floor Annual 7:05:21 PM 08/27/2024 Strobe 4th Building B Floor Annual 7:04:58 PM 08/27/2024 Strobe 5th Building B Floor Annual 7:04:35 PM 08/27/2024 Strobe 6th Building B Floor Annual 7:04:08 PM 08/27/2024 Strobe 7th Building B Floor Annual 7:00:52 PM 08/27/2024 Strobe 8th Building B Floor Annual 7:00:23 PM 08/27/2024
Initiating Heat Detector 1st Building B By Blacksmith Shop Annual 12:45:50 PM 07/16/2024 Heat Detector 1st Building B By Blacksmith Shop Annual 12:46:48 PM 07/16/2024 Heat Detector 1st Building B By Garage Annual 12:48:07 PM 07/16/2024 Heat Detector 1st Building B By Garage Annual 12:50:08 PM 07/16/2024 Heat Detector 2nd Building B By Heat Pipe And Sheet Annual 9:22:50 AM 07/16/2024 Heat Detector 2nd Building B By Heat Pipe And Sheet Annual 9:49:43 AM 07/16/2024 Heat Detector 2nd Building B By Heat Pipe And Sheet Annual 9:52:37 AM 07/16/2024 Heat Detector 2nd Building B By Room B214 Annual 9:24:12 AM 07/16/2024 Heat Detector 2nd Building B By Room B214 Annual 9:47:59 AM 07/16/2024 Heat Detector 2nd Building B By Room B214 Annual 9:48:09 AM 07/16/2024 Heat Detector 2nd Building B By Room B227 Annual 9:27:45 AM 07/16/2024 Heat Detector 3rd Building B By Machine Shop Annual 8:35:16 AM 07/16/2024 Pull Station 1st By B115 Annual 11:45:31 AM 07/16/2024 Pull Station 1st By B124 Annual 12:52:00 PM 07/16/2024 Pull Station 1st By B142 Annual 12:55:32 PM 07/16/2024 Pull Station 1st By Stair 2 Annual 11:44:01 AM 07/16/2024
Everon 8 Download Date: 09/03/2024
Pull Station 1st Entrance By B115 Annual 12:17:31 PM 08/27/2024 Pull Station 2nd By Stair 1 Annual 9:58:35 AM 07/16/2024 Pull Station 2nd By Stair 2 Annual 9:02:11 AM 07/16/2024 Pull Station 3rd By Stair 1 Annual 8:47:20 AM 07/16/2024 Pull Station 3rd By Stair 2 Annual 8:23:45 AM 07/16/2024 Pull Station 4th By Stair 1 Annual 10:09:27 AM 07/16/2024 Pull Station 4th By Stair 2 Annual 12:24:58 PM 07/15/2024 Pull Station 5th By Stair 1 Annual 12:14:21 PM 07/15/2024 Pull Station 5th By Stair 2 Annual 11:31:58 AM 07/15/2024 Pull Station 6th By Stair 1 Annual 11:08:01 AM 07/15/2024 Pull Station 6th By Stair 2 Annual 10:55:13 AM 07/15/2024 Pull Station 7th By Stair 1 Annual 9:09:09 AM 07/15/2024 Pull Station 7th By Stair 2 Annual 8:51:47 AM 07/15/2024 Pull Station 8th By Stair 1 Annual 8:34:17 AM 07/15/2024 Pull Station 8th By Stair 2 Annual 7:16:50 AM 07/15/2024 Smoke Detector 1st Building B By Garage Annual 12:55:02 PM 07/16/2024 Smoke Detector 1st Building B By Garage Annual 12:55:47 PM 07/16/2024 Smoke Detector 1st Building B By Men's Room T213 Annual 12:58:08 PM 07/16/2024 Smoke Detector 1st Building B By Room B104 Annual 12:33:07 PM 07/16/2024 Smoke Detector 1st Building B By Room B104B Annual 12:53:58 PM 07/16/2024 Smoke Detector 1st Building B By Room B104C Annual 12:34:02 PM 07/16/2024 Smoke Detector 1st Building B By Room B104D Annual 12:34:54 PM 07/16/2024 Smoke Detector 1st Building B By Room B104E Annual 12:34:27 PM 07/16/2024 Smoke Detector 1st Building B By Room B104F Annual 12:31:56 PM 07/16/2024 Smoke Detector 1st Building B By Room B104F Annual 12:35:20 PM 07/16/2024 Smoke Detector 1st Building B By Room B114 Annual 12:18:27 PM 07/16/2024 Smoke Detector 1st Building B By Room B157 Annual 12:22:02 PM 07/16/2024 Smoke Detector 1st Building B By Room B157 Annual 12:23:40 PM 07/16/2024 Smoke Detector 1st Building B Elevator 21-22 Annual 7:58:42 AM 08/06/2024 Smoke Detector 1st Building B Hall By Men's Room T212 Annual 12:10:15 PM 07/16/2024 Smoke Detector 1st Building B Hall By Men's Room T212 Annual 12:11:01 PM 07/16/2024 Smoke Detector 2nd Building B By Carpenter Shop Annual 9:38:35 AM 07/16/2024 Smoke Detector 2nd Building B By Carpenter Shop Annual 9:39:02 AM 07/16/2024 Smoke Detector 2nd Building B By Carpenter Shop Annual 9:40:54 AM 07/16/2024 Smoke Detector 2nd Building B By Glue Room Annual 9:40:22 AM 07/16/2024 Smoke Detector 2nd Building B By Hallway Annual 9:36:50 AM 07/16/2024 Smoke Detector 2nd Building B By Hallway Annual 9:42:49 AM 07/16/2024 Smoke Detector 2nd Building B By Men's Room T223 Annual 10:04:21 AM 07/16/2024 Smoke Detector 2nd Building B By Room B202A Annual 9:39:56 AM 07/16/2024 Smoke Detector 2nd Building B By Room B207A Annual 9:42:09 AM 07/16/2024 Smoke Detector 2nd Building B By Room B210 Annual 9:41:23 AM 07/16/2024 Smoke Detector 2nd Building B By Room B218 Annual 9:14:44 AM 07/16/2024 Smoke Detector 2nd Building B By Room B218A Annual 9:27:06 AM 07/16/2024 Smoke Detector 2nd Building B By Room B228 Annual 9:37:45 AM 07/16/2024 Smoke Detector 2nd Building B By Room B228 Annual 10:01:41 AM 07/16/2024 Smoke Detector 2nd Building B By Room B232 Annual 9:39:27 AM 07/16/2024 Smoke Detector 2nd Building B By Room B233 Annual 10:03:07 AM 07/16/2024 Smoke Detector 2nd Building B By Upper Room Annual 9:41:45 AM 07/16/2024 Smoke Detector 2nd Building B Elevator Elevator 21-22 Annual 7:54:38 AM 08/06/2024 Smoke Detector 3rd Building A By Mech Room A342 Annual 8:26:39 AM 07/16/2024
Everon 9 Download Date: 09/03/2024
Smoke Detector 3rd Building B By Electric Shop Annual 8:50:40 AM 07/16/2024 Smoke Detector 3rd Building B By Machine Shop Annual 8:32:33 AM 07/16/2024 Smoke Detector 3rd Building B By Machine Shop Annual 8:47:03 AM 07/16/2024 Smoke Detector 3rd Building B By Machine Shop B-311 Annual 8:45:54 AM 07/16/2024 Smoke Detector 3rd Building B By Machine Shop B312 Annual 8:46:30 AM 07/16/2024 Smoke Detector 3rd Building B By Men's Room T231 Annual 8:47:24 AM 07/16/2024 Smoke Detector 3rd Building B By Room B301 Annual 9:00:20 AM 07/16/2024 Smoke Detector 3rd Building B By Room B301A Annual 8:56:27 AM 07/16/2024 Smoke Detector 3rd Building B By Room B302 Annual 8:59:00 AM 07/16/2024 Smoke Detector 3rd Building B By Room B302A Annual 8:59:23 AM 07/16/2024 Smoke Detector 3rd Building B By Room B305A Annual 8:58:35 AM 07/16/2024 Smoke Detector 3rd Building B By Room B305A Annual 9:04:43 AM 07/16/2024 Smoke Detector 3rd Building B By Room B308 Annual 8:57:31 AM 07/16/2024 Smoke Detector 3rd Building B By Room B318 Annual 8:37:13 AM 07/16/2024 Smoke Detector 3rd Building B By Room B319 Annual 8:59:52 AM 07/16/2024 Smoke Detector 3rd Building B By Room B323 Annual 8:38:33 AM 07/16/2024 Smoke Detector 3rd Building B By Room B323 Annual 8:39:05 AM 07/16/2024 Smoke Detector 3rd Building B By Room B323 Annual 8:39:35 AM 07/16/2024 Smoke Detector 3rd Building B By Room Elevator 21-22 Annual 10:04:12 AM 07/16/2024 Smoke Detector 3rd Building B By Room L232 Annual 9:28:22 AM 07/16/2024 Smoke Detector 4th Building B Bathroom EAST Annual 12:34:14 PM 07/15/2024 Smoke Detector 4th Building B By AOC Breakroom Annual 12:51:32 PM 07/15/2024 Smoke Detector 4th Building B By AOC Column L-4 Annual 1:04:57 PM 07/15/2024 Smoke Detector 4th Building B By AOC East Hallway Annual 12:52:10 PM 07/15/2024 Smoke Detector 4th Building B By AOC East Hallway Annual 12:52:40 PM 07/15/2024 Smoke Detector 4th Building B By AOC Locker Room Annual 1:09:34 PM 07/15/2024 Smoke Detector 4th Building B By AOC Near Column K-4 Annual 1:06:24 PM 07/15/2024 Smoke Detector 4th Building B By AOC Near Column K-6 Annual 1:06:55 PM 07/15/2024 Smoke Detector 4th Building B By AOC Near Column K-8 Annual 1:08:02 PM 07/15/2024 Smoke Detector 4th Building B By AOC Near Spray Area Annual 9:51:47 AM 07/16/2024 Smoke Detector 4th Building B By AOC Room D-405 Annual 1:03:23 PM 07/15/2024 Smoke Detector 4th Building B By AOC Room D-405 Annual 1:03:51 PM 07/15/2024 Smoke Detector 4th Building B By AOC Room D-409 Annual 12:53:12 PM 07/15/2024 Smoke Detector 4th Building B By AOC Room D-409 Annual 1:02:12 PM 07/15/2024 Smoke Detector 4th Building B By AOC Room D-410 Annual 9:40:22 AM 07/16/2024 Smoke Detector 4th Building B By AOC Room D-411 Annual 1:02:56 PM 07/15/2024 Smoke Detector 4th Building B By AOC Spray Prep Room Annual 1:07:32 PM 07/15/2024 Smoke Detector 4th Building B By AOC Storage West Annual 1:05:46 PM 07/15/2024 Smoke Detector 4th Building B Elevator 21-22 Annual 7:54:58 AM 08/06/2024 Smoke Detector 5th Building B By Men's Room T251 Annual 12:22:13 PM 07/15/2024 Smoke Detector 5th Building B By Quality Control Room Annual 12:32:54 PM 07/15/2024 Smoke Detector 5th Building B By Quality Control Room Annual 12:33:34 PM 07/15/2024 Smoke Detector 5th Building B By Room B502 Annual 12:32:08 PM 07/15/2024 Smoke Detector 5th Building B By Room B502B Annual 12:14:58 PM 07/15/2024 Smoke Detector 5th Building B By Room B503 Conference Room Annual 12:31:33 PM 07/15/2024 Smoke Detector 5th Building B By Room B505A Annual 12:31:06 PM 07/15/2024 Smoke Detector 5th Building B By Room B507 Annual 12:30:38 PM 07/15/2024 Smoke Detector 5th Building B By Room B508 Annual 7:28:17 AM 08/06/2024 Smoke Detector 5th Building B By Room B509 Annual 7:28:12 AM 08/06/2024 Smoke Detector 5th Building B By Room B511 Annual 12:29:05 PM 07/15/2024
Everon 10 Download Date: 09/03/2024
Smoke Detector 5th Building B By Room B515 Annual 12:28:38 PM 07/15/2024 Smoke Detector 5th Building B By Room B516 Annual 12:26:16 PM 07/15/2024 Smoke Detector 5th Building B By Room B517 Annual 12:26:48 PM 07/15/2024 Smoke Detector 5th Building B By Room B519 Annual 12:24:58 PM 07/15/2024 Smoke Detector 5th Building B By Room B520 Annual 12:10:33 PM 07/15/2024 Smoke Detector 5th Building B By Room B521 Annual 12:25:25 PM 07/15/2024 Smoke Detector 5th Building B By Room B522 Annual 12:21:06 PM 07/15/2024 Smoke Detector 5th Building B By Room B523 Annual 12:24:37 PM 07/15/2024 Smoke Detector 5th Building B By Room B524 Annual 12:24:08 PM 07/15/2024 Smoke Detector 5th Building B By Room B531 Annual 11:53:59 AM 07/15/2024 Smoke Detector 5th Building B By Room B532 Annual 12:29:32 PM 07/15/2024 Smoke Detector 5th Building B By Room B538 Annual 12:17:11 PM 07/15/2024 Smoke Detector 5th Building B By Room B539 Annual 12:16:36 PM 07/15/2024 Smoke Detector 5th Building B By Room B541 Annual 12:19:59 PM 07/15/2024 Smoke Detector 5th Building B By Room B544 Annual 11:36:35 AM 07/15/2024 Smoke Detector 5th Building B Elevator 21-22 Annual 7:54:48 AM 08/06/2024 Smoke Detector 6th Building B By Inner Office B610 Annual 11:20:04 AM 07/15/2024 Smoke Detector 6th Building B By Room A612 Mechnical Room Annual 11:02:13 AM 07/15/2024 Smoke Detector 6th Building B By Room A612 Mechnical Room Annual 11:03:22 AM 07/15/2024 Smoke Detector 6th Building B By Room B601 Annual 11:34:56 AM 07/15/2024 Smoke Detector 6th Building B By Room B603 Annual 11:33:04 AM 07/15/2024 Smoke Detector 6th Building B By Room B604 Annual 11:34:02 AM 07/15/2024 Smoke Detector 6th Building B By Room B604A Annual 11:34:29 AM 07/15/2024 Smoke Detector 6th Building B By Room B611 Annual 11:21:15 AM 07/15/2024 Smoke Detector 6th Building B By Room B612 Annual 11:30:55 AM 07/15/2024 Smoke Detector 6th Building B By Room B612 Annual 11:35:18 AM 07/15/2024 Smoke Detector 6th Building B By Room B613 Annual 11:20:47 AM 07/15/2024 Smoke Detector 6th Building B By Room B616 Annual 11:05:39 AM 07/15/2024 Smoke Detector 6th Building B By Room B625 Annual 11:21:41 AM 07/15/2024 Smoke Detector 6th Building B By Room B625 Annual 11:22:09 AM 07/15/2024 Smoke Detector 6th Building B By Room B625 Annual 11:22:43 AM 07/15/2024 Smoke Detector 6th Building B By Room B625 Annual 11:32:02 AM 07/15/2024 Smoke Detector 6th Building B By Room B625 Inner Office Annual 11:33:31 AM 07/15/2024 Smoke Detector 6th Building B By Room B626 Annual 11:23:13 AM 07/15/2024 Smoke Detector 6th Building B By Room B627 Annual 11:24:49 AM 07/15/2024 Smoke Detector 6th Building B By Room B629 Annual 11:24:28 AM 07/15/2024 Smoke Detector 6th Building B By Room B630 Annual 11:23:57 AM 07/15/2024 Smoke Detector 6th Building B By Women's Room T261 Annual 11:06:58 AM 07/15/2024 Smoke Detector 6th Building B Elevator 21-22 Annual 7:50:21 AM 08/06/2024 Smoke Detector 7th Building B By B708C Conference Room Annual 9:36:48 AM 07/15/2024 Smoke Detector 7th Building B By Hall Room B704 Annual 8:55:06 AM 07/15/2024 Smoke Detector 7th Building B By Room B701 Annual 9:39:34 AM 07/15/2024 Smoke Detector 7th Building B By Room B701A Annual 9:38:45 AM 07/15/2024 Smoke Detector 7th Building B By Room B701B Annual 9:38:13 AM 07/15/2024 Smoke Detector 7th Building B By Room B701C Annual 9:41:45 AM 07/15/2024 Smoke Detector 7th Building B By Room B706 Annual 9:33:12 AM 07/15/2024 Smoke Detector 7th Building B By Room B706 Annual 9:33:42 AM 07/15/2024 Smoke Detector 7th Building B By Room B706 Annual 10:09:33 AM 07/16/2024 Smoke Detector 7th Building B By Room B706 Inner Office Annual 9:34:11 AM 07/15/2024 Smoke Detector 7th Building B By Room B706 Inner Office Annual 9:34:46 AM 07/15/2024
Everon 11 Download Date: 09/03/2024
Smoke Detector 7th Building B By Room B706 Inner Office Annual 9:35:51 AM 07/15/2024 Smoke Detector 7th Building B By Room B707 Annual 9:37:40 AM 07/15/2024 Smoke Detector 7th Building B By Room B708A Annual 9:42:47 AM 07/15/2024 Smoke Detector 7th Building B By Room B708B Annual 9:36:19 AM 07/15/2024 Smoke Detector 7th Building B By Room B709 Annual 9:10:27 AM 07/15/2024 Smoke Detector 7th Building B By Room B709 Annual 9:31:32 AM 07/15/2024 Smoke Detector 7th Building B By Room B709A Annual 9:43:16 AM 07/15/2024 Smoke Detector 7th Building B By Room B709B Annual 9:43:45 AM 07/15/2024 Smoke Detector 7th Building B By Room B709D Annual 9:30:53 AM 07/15/2024 Smoke Detector 7th Building B By Room B709F Annual 9:14:12 AM 07/15/2024 Smoke Detector 7th Building B By Room B711 Annual 9:06:58 AM 07/15/2024 Smoke Detector 7th Building B By Room B711 Annual 9:08:17 AM 07/15/2024 Smoke Detector 7th Building B By Room B712 Annual 9:44:14 AM 07/15/2024 Smoke Detector 7th Building B By Women's Room T271 Annual 9:40:16 AM 07/15/2024 Smoke Detector 7th Building B Elevator 21-22 Annual 7:50:05 AM 08/06/2024 Smoke Detector 8th Building B By Men's Room T282 Annual 7:58:56 AM 07/15/2024 Smoke Detector 8th Building B By Room B801 Annual 8:39:22 AM 07/15/2024 Smoke Detector 8th Building B By Room B802 Annual 8:40:43 AM 07/15/2024 Smoke Detector 8th Building B By Room B802A Annual 8:41:39 AM 07/15/2024 Smoke Detector 8th Building B By Room B802B Annual 8:41:10 AM 07/15/2024 Smoke Detector 8th Building B By Room B806 Annual 8:30:22 AM 07/15/2024 Smoke Detector 8th Building B By Room B806 Annual 8:31:59 AM 07/15/2024 Smoke Detector 8th Building B By Room B806A Annual 8:34:10 AM 07/15/2024 Smoke Detector 8th Building B By Room B807 Annual 8:00:21 AM 07/15/2024 Smoke Detector 8th Building B By Room B809 Annual 7:46:50 AM 07/15/2024 Smoke Detector 8th Building B By Room B810 Annual 7:56:04 AM 07/15/2024 Smoke Detector 8th Building B By Room B810 Storage Annual 8:43:23 AM 07/15/2024 Smoke Detector 8th Building B By Room B812 Annual 8:45:41 AM 07/15/2024 Smoke Detector 8th Building B By Room B828 Annual 8:01:07 AM 07/15/2024 Smoke Detector 8th Building B By Room B832 Annual 7:54:52 AM 07/15/2024 Smoke Detector 8th Building B By Women's Room T281 Annual 7:59:44 AM 07/15/2024 Smoke Detector 8th Building B Elevator 21-22 Annual 7:36:58 AM 08/06/2024 Smoke Detector Roof Building B By B904 Fan Room Annual 7:28:47 AM 07/15/2024 Smoke Detector Roof Building B By Room B907 Annual 7:29:17 AM 07/15/2024 Smoke Detector Roof Building B By Room B909A Annual 7:28:15 AM 07/15/2024 Smoke Detector Roof Building B Elevator Room B901 Annual 8:08:47 AM 08/06/2024 Smoke Detector Roof Building B Elevator Mechanical Room Annual 8:14:47 AM 08/06/2024 Smoke Detector Roof Building B Elevator 21-22 Mechanical
Room B905A Annual 7:29:25 AM 08/06/2024
Failed/Other Indicating
Speaker/Strobe Roof Building B Entire Floor Annual 7:03:35 PM 08/27/2024
Initiating Smoke Detector 3rd Building B Elevator 21-22 Annual 7:56:03 AM 08/06/2024
Everon 12 Download Date: 09/03/2024
Service Summary
Building: GPO Building B
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Smoke Detector Annual 1
Speaker/Strobe Annual 1
Total 2
Passed
Annunciator Annual 2
Battery Annual 14
Heat Detector Annual 12
Horn/Strobe Annual 9
Phone Station Annual 19
Power Supply Annual 7
Pull Station Annual 19
Smoke Detector Annual 173
Speaker/Strobe Annual 9
Speaker Annual 1
Strobe Annual 9
Total 274
Grand Total 276
Everon 13 Download Date: 09/03/2024
Auxiliary Functions Testing
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Smoke Compartment 1st Building B By Garage Passed 96937115
Smoke Compartment 1st Building B By Garage Passed 96937114
Smoke Compartment 1st Building B By Men's Room T213 Passed 96937116
Smoke Compartment 1st Building B By Room B104B Passed 96937104
Smoke Compartment 1st Building B By Room B104C Passed 96937105
Smoke Compartment 1st Building B By Room B104D Passed 96937107
Smoke Compartment 1st Building B By Room B104E Passed 96937106
Smoke Compartment 1st Building B By Room B104F Passed 96937109
Smoke Compartment 1st Building B By Room B104F Passed 96937108
Smoke Compartment 1st Building B By Room B114 Passed 96937100
Smoke Compartment 1st Building B By Room B157 Passed 96937102
Elevator Recall 1st Building B Elevator 21-22 Passed 96926353
Smoke Compartment 1st Building B Hall By Men's Room T212 Passed 96937098
Smoke Compartment 1st Building B Hall By Men's Room T212 Passed 96937099
Smoke Compartment 2nd Building B By Carpenter Shop Passed 96937281
Smoke Compartment 2nd Building B By Carpenter Shop Passed 96937282
Smoke Compartment 2nd Building B By Carpenter Shop Passed 96937286
Smoke Compartment 2nd Building B By Glue Room Passed 96937285
Smoke Compartment 2nd Building B By Hallway Passed 96937291
Smoke Compartment 2nd Building B By Hallway Passed 96937290
Smoke Compartment 2nd Building B By Men's Room T223 Passed 96937097
Smoke Compartment 2nd Building B By Room B202A Passed 96937284
Smoke Compartment 2nd Building B By Room B207A Passed 96937289
Smoke Compartment 2nd Building B By Room B210 Passed 96937287
Smoke Compartment 2nd Building B By Room B218 Passed 96937272
Smoke Compartment 2nd Building B By Room B218A Passed 96937273
Smoke Compartment 2nd Building B By Room B228 Passed 96937279
Smoke Compartment 2nd Building B By Room B228 Passed 96937280
Smoke Compartment 2nd Building B By Room B232 Passed 96937283
Smoke Compartment 2nd Building B By Room B233 Passed 96937296
Elevator Recall 2nd Building B Elevator Elevator 21-22 Passed 96926352
Smoke Compartment 3rd Building A By Mech Room A342 Passed 96937083
Smoke Compartment 3rd Building B By Electric Shop Passed 96937264
Smoke Compartment 3rd Building B By Machine Shop Passed 96937095
Smoke Compartment 3rd Building B By Machine Shop Passed 96937259
Smoke Compartment 3rd Building B By Machine Shop B-311 Passed 96937257
Smoke Compartment 3rd Building B By Machine Shop B312 Passed 96937258
Smoke Compartment 3rd Building B By Men's Room T231 Passed 96937260
Everon 14 Download Date: 09/03/2024
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Smoke Compartment 3rd Building B By Room B301 Passed 96937269
Smoke Compartment 3rd Building B By Room B301A Passed 96937270
Smoke Compartment 3rd Building B By Room B302 Passed 96937266
Smoke Compartment 3rd Building B By Room B302A Passed 96937267
Smoke Compartment 3rd Building B By Room B305A Passed 96937265
Smoke Compartment 3rd Building B By Room B305A Passed 96937271
Smoke Compartment 3rd Building B By Room B308 Passed 96937262
Smoke Compartment 3rd Building B By Room B318 Passed 96937091
Smoke Compartment 3rd Building B By Room B319 Passed 96937268
Smoke Compartment 3rd Building B By Room B323 Passed 96937092
Smoke Compartment 3rd Building B By Room B323 Passed 96937093
Smoke Compartment 3rd Building B By Room B323 Passed 96937094
Smoke Compartment 3rd Building B By Room Elevator 21-22 Passed 96937263
Smoke Compartment 3rd Building B By Room L232 Passed 96937261
Smoke Compartment 4th Building B Bathroom EAST Passed 96937071
Smoke Compartment 4th Building B By AOC Breakroom Passed 96937072
Smoke Compartment 4th Building B By AOC Column L-4 Passed 96937082
Smoke Compartment 4th Building B By AOC East Hallway Passed 96937074
Smoke Compartment 4th Building B By AOC East Hallway Passed 96937075
Smoke Compartment 4th Building B By AOC Locker Room Passed 96937073
Smoke Compartment 4th Building B By AOC Near Column K-4 Passed 96937085
Smoke Compartment 4th Building B By AOC Near Column K-6 Passed 96937086
Smoke Compartment 4th Building B By AOC Near Column K-8 Passed 96937088
Smoke Compartment 4th Building B By AOC Near Spray Area Passed 96937089
Smoke Compartment 4th Building B By AOC Room D-405 Passed 96937079
Smoke Compartment 4th Building B By AOC Room D-405 Passed 96937080
Smoke Compartment 4th Building B By AOC Room D-409 Passed 96937076
Smoke Compartment 4th Building B By AOC Room D-409 Passed 96937077
Smoke Compartment 4th Building B By AOC Room D-410 Passed 96937081
Smoke Compartment 4th Building B By AOC Room D-411 Passed 96937078
Smoke Compartment 4th Building B By AOC Spray Prep Room Passed 96937087
Smoke Compartment 4th Building B By AOC Storage West Passed 96937084
Elevator Recall 4th Building B Elevator 21-22 Passed 96926350
Smoke Compartment 5th Building B By Men's Room T251 Passed 96937070
Smoke Compartment 5th Building B By Quality Control Room Passed 96937067
Smoke Compartment 5th Building B By Quality Control Room Passed 96937068
Smoke Compartment 5th Building B By Room B502 Passed 96937065
Smoke Compartment 5th Building B By Room B502B Passed 96937066
Smoke Compartment 5th Building B By Room B503 Conference Room
Passed 96937064
Smoke Compartment 5th Building B By Room B505A Passed 96937062
Smoke Compartment 5th Building B By Room B507 Passed 96937063
Smoke Compartment 5th Building B By Room B508 Passed 96937061
Smoke Compartment 5th Building B By Room B509 Passed 96937057
Smoke Compartment 5th Building B By Room B511 Passed 96937059
Smoke Compartment 5th Building B By Room B515 Passed 96937058
Smoke Compartment 5th Building B By Room B516 Passed 96936834
Everon 15 Download Date: 09/03/2024
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Smoke Compartment 5th Building B By Room B517 Passed 96936835
Smoke Compartment 5th Building B By Room B519 Passed 96936832
Smoke Compartment 5th Building B By Room B520 Passed 96936826
Smoke Compartment 5th Building B By Room B521 Passed 96936833
Smoke Compartment 5th Building B By Room B522 Passed 96936829
Smoke Compartment 5th Building B By Room B524 Passed 96936830
Smoke Compartment 5th Building B By Room B531 Passed 96936825
Smoke Compartment 5th Building B By Room B532 Passed 96937060
Smoke Compartment 5th Building B By Room B538 Passed 96936828
Smoke Compartment 5th Building B By Room B539 Passed 96936827
Smoke Compartment 5th Building B By Room B541 Passed 96937069
Smoke Compartment 5th Building B By Room B544 Passed 96936824
Elevator Recall 5th Building B Elevator 21-22 Passed 96926349
Smoke Compartment 6th Building B By Inner Office B610 Passed 96936806
Smoke Compartment 6th Building B By Room A612 Mechnical
Passed 96936803
Smoke Compartment 6th Building B By Room A612 Mechnical
Passed 96936802
Smoke Compartment 6th Building B By Room B601 Passed 96936821
Smoke Compartment 6th Building B By Room B603 Passed 96936818
Smoke Compartment 6th Building B By Room B604 Passed 96936819
Smoke Compartment 6th Building B By Room B604A Passed 96936820
Smoke Compartment 6th Building B By Room B611 Passed 96936808
Smoke Compartment 6th Building B By Room B612 Passed 96936823
Smoke Compartment 6th Building B By Room B612 Passed 96936822
Smoke Compartment 6th Building B By Room B613 Passed 96936807
Smoke Compartment 6th Building B By Room B616 Passed 96936805
Smoke Compartment 6th Building B By Room B625 Passed 96936809
Smoke Compartment 6th Building B By Room B625 Passed 96936810
Smoke Compartment 6th Building B By Room B625 Passed 96936811
Smoke Compartment 6th Building B By Room B625 Passed 96936816
Smoke Compartment 6th Building B By Room B625 Inner Office Passed 96936817
Smoke Compartment 6th Building B By Room B626 Passed 96936812
Smoke Compartment 6th Building B By Room B627 Passed 96936815
Smoke Compartment 6th Building B By Room B629 Passed 96936814
Smoke Compartment 6th Building B By Room B630 Passed 96936813
Smoke Compartment 6th Building B By Women's Room T261 Passed 96936804
Elevator Recall 6th Building B Elevator 21-22 Passed 96926348
Smoke Compartment 7th Building B By B708C Conference Room Passed 96936791
Smoke Compartment 7th Building B By Hall Room B704 Passed 96936777
Smoke Compartment 7th Building B By Room B701A Passed 96936794
Smoke Compartment 7th Building B By Room B701B Passed 96936793
Smoke Compartment 7th Building B By Room B701C Passed 96936796
Smoke Compartment 7th Building B By Room B706 Passed 96936785
Smoke Compartment 7th Building B By Room B706 Passed 96936788
Smoke Compartment 7th Building B By Room B706 Inner Office Passed 96936786
Smoke Compartment 7th Building B By Room B706 Inner Office Passed 96936787
Everon 16 Download Date: 09/03/2024
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Smoke Compartment 7th Building B By Room B706 Inner Office Passed 96936789
Smoke Compartment 7th Building B By Room B707 Passed 96936792
Smoke Compartment 7th Building B By Room B708A Passed 96936797
Smoke Compartment 7th Building B By Room B708B Passed 96936790
Smoke Compartment 7th Building B By Room B709 Passed 96936780
Smoke Compartment 7th Building B By Room B709 Passed 96936781
Smoke Compartment 7th Building B By Room B709A Passed 96936798
Smoke Compartment 7th Building B By Room B709B Passed 96936799
Smoke Compartment 7th Building B By Room B709D Passed 96936782
Smoke Compartment 7th Building B By Room B711 Passed 96936778
Smoke Compartment 7th Building B By Room B711 Passed 96936779
Smoke Compartment 7th Building B By Room B712 Passed 96936800
Smoke Compartment 7th Building B By Women's Room T271 Passed 96936801
Elevator Recall 7th Building B Elevator 21-22 Passed 96926347
Smoke Compartment 8th Building B By Men's Room T282 Passed 96936764
Smoke Compartment 8th Building B By Room B801 Passed 96936774
Smoke Compartment 8th Building B By Room B802 Passed 96936771
Smoke Compartment 8th Building B By Room B802A Passed 96936773
Smoke Compartment 8th Building B By Room B806 Passed 96936768
Smoke Compartment 8th Building B By Room B806A Passed 96936770
Smoke Compartment 8th Building B By Room B807 Passed 96936766
Smoke Compartment 8th Building B By Room B809 Passed 96936761
Smoke Compartment 8th Building B By Room B810 Passed 96936763
Smoke Compartment 8th Building B By Room B810 Storage Passed 96936775
Smoke Compartment 8th Building B By Room B812 Passed 96936776
Smoke Compartment 8th Building B By Room B828 Passed 96936767
Smoke Compartment 8th Building B By Room B832 Passed 96936762
Smoke Compartment 8th Building B By Women's Room T281 Passed 96936765
Elevator Recall 8th Building B Elevator 21-22 Passed 96926346
Smoke Compartment Roof Building B By B904 Fan Room Passed 96936759
Smoke Compartment Roof Building B By Room B907 Passed 96936760
Smoke Compartment Roof Building B By Room B909A Passed 96936758
Elevator Recall 3rd Building B Elevator 21-22 Failed Annunciation
96926351
Everon 17 Download Date: 09/03/2024
Battery & Power Supply Testing
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated Ah
Rated Volts
Pre Test
Post Test
Min Ah
Tested Ah
Passed Sealed Lead Acid 2nd By Stair 2 Shaft #2 7 12
Sealed Lead Acid 2nd By Stair 2 Shaft #2 7 12
Sealed Lead Acid 3rd By Stair 2 Shaft #2 7 12
Sealed Lead Acid 3rd By Stair 2 Shaft #2 7 12
Sealed Lead Acid 4th By Stair 2 7 12
Sealed Lead Acid 4th By Stair 2 7 12
Sealed Lead Acid 5th By Stair 2 7 12
Sealed Lead Acid 5th By Stair 2 7 12
Sealed Lead Acid 6th By Stair 2 7 12
Sealed Lead Acid 6th By Stair 2 7 12
Sealed Lead Acid 7th By Stair 2 7 12
Sealed Lead Acid 7th By Stair 2 7 12
Sealed Lead Acid 8th By Stair 2 7 12
Sealed Lead Acid 8th By Stair 2 7 12
Power Supply Protection Type Location Rated Ah Rated Volts Charging Voltage
Passed Breaker 2nd By Stair 2 Shaft #2 3 120
Breaker 3rd By Stair 2 3 120
Breaker 4th By Stair 2 3 120
Breaker 5th By Stair 2 3 120
Breaker 6th By Stair 2 3 120
Breaker 7th By Stair 2 3 120
Breaker 8th By Stair 2 3 120
Everon 18 Download Date: 09/03/2024
Inventory & Warranty Report
Building: GPO Building B Control Panel: 1
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Annunciator Control 0.72% 2
Battery Control 5.07% 14
Heat Detector Initiating 4.35% 12
Horn/Strobe Indicating 3.26% 9
Phone Station Control 6.88% 19
Power Supply Control 2.54% 7
Pull Station Initiating 6.88% 19
Smoke Detector Initiating 63.04% 174
Speaker Indicating 0.36% 1
Speaker/Strobe Indicating 3.62% 10
Strobe Indicating 3.26% 9
Type Qty Model # Description Install Date
New (under 90 days)
Edwards
Speaker/Strobe 9 GCHFRF-S7VMC
08/08/2024
EST
Annunciator 2
LED List 07/15/2024
Pull Station 19 SIGA-278 Dual Action 07/15/2024
Edwards
Power Supply 7 8570
07/15/2024
Phone Station 19
07/12/2024
In Service - 1 Year to 2 Years
Power-Sonic
Battery 2 PS-1270 F1 Sealed Lead Acid 08/01/2023
Battery 10 PS-1270 F1 Sealed Lead Acid 11/01/2022
In Service - 3 Years to 5 Years
Power-Sonic
Battery 2 PS-1270 F1 Sealed Lead Acid 08/02/2021
In Service - 10 Years to 15 Years
Edwards
Heat Detector 11 SIGA-HRS Combination 01/30/2012
Heat Detector 1 SIGA-PS Rate-of-Rise 01/30/2012
Horn/Strobe 9 EG1RF-CVM
01/30/2012
Smoke Detector 174 SIGA-PS Photoelectric 01/30/2012
Speaker 1 5552-15W-R Cone Type 01/30/2012
Speaker/Strobe 1 757-3A-RS70
Everon 19 Download Date: 09/03/2024
Strobe 9 CS405-7A-T
Everon 20 Download Date: 09/03/2024
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Zone/Circuit: 69 15-04-0251 Smoke Detector 6th Building B By Room A612 Mechnical
Room Photoelectric 96936802
15-04-0257 Smoke Detector 6th Building B By Room A612 Mechnical Room
Photoelectric 96936803
Zone/Circuit: 84 20-02-0286 Smoke Detector 1st Building B Hall By Men's Room T212 Photoelectric 96937098 20-02-0288 Smoke Detector 1st Building B By Room B114 Photoelectric 96937100 20-02-0289 Smoke Detector 1st Building B By Room B157 Photoelectric 96937101 20-02-0290 Smoke Detector 1st Building B By Room B104F Photoelectric 96937109 20-02-0291 Smoke Detector 1st Building B By Room B104 Photoelectric 96937103 20-02-0292 Smoke Detector 1st Building B By Room B157 Photoelectric 96937102 20-02-0293 Smoke Detector 1st Building B Hall By Men's Room T212 Photoelectric 96937099 20-02-0294 Smoke Detector 1st Building B By Room B104D Photoelectric 96937107 20-02-0295 Smoke Detector 1st Building B By Room B104B Photoelectric 96937104 20-02-0296 Smoke Detector 1st Building B By Room B104C Photoelectric 96937105 20-02-0297 Smoke Detector 1st Building B By Room B104F Photoelectric 96937108 20-02-0316 Smoke Detector 1st Building B By Room B104E Photoelectric 96937106 20-02-0319 Smoke Detector 1st Building B Elevator 21-22 Photoelectric 96926353
Zone/Circuit: 85 20-02-0298 Heat Detector 1st Building B By Blacksmith Shop Combination 96937110 20-02-0299 Smoke Detector 1st Building B By Men's Room T213 Photoelectric 96937116 20-02-0301 Heat Detector 1st Building B By Blacksmith Shop Combination 96937111
Zone/Circuit: 86 20-02-0001 Smoke Detector 2nd Building B By Hallway Photoelectric 96937290 20-02-0003 Smoke Detector 2nd Building B By Room B218A Photoelectric 96937273 20-02-0004 Smoke Detector 2nd Building B By Room B218 Photoelectric 96937272 20-02-0005 Smoke Detector 2nd Building B By Men's Room T223 Photoelectric 96937097 20-02-0006 Smoke Detector 2nd Building B By Hallway Photoelectric 96937291 20-02-0008 Smoke Detector 2nd Building B By Room B233 Photoelectric 96937296
Zone/Circuit: 87 20-02-0009 Heat Detector 2nd Building B By Heat Pipe And Sheet Combination 96937090 20-02-0009 Heat Detector 2nd Building B By Heat Pipe And Sheet Combination 96937276 20-02-0010 Heat Detector 2nd Building B By Heat Pipe And Sheet Combination 96937277 20-02-0011 Smoke Detector 2nd Building B By Upper Room Photoelectric 96937288 20-02-0012 Heat Detector 2nd Building B By Room B214 Combination 96937275 20-02-0012 Heat Detector 2nd Building B By Room B214 Combination 96937292 20-02-0013 Smoke Detector 2nd Building B By Room B228 Photoelectric 96937279 20-02-0014 Smoke Detector 2nd Building B By Glue Room Photoelectric 96937285
Everon 21 Download Date: 09/03/2024
20-02-0015 Smoke Detector 2nd Building B By Room B228 Photoelectric 96937280 20-02-0016 Heat Detector 2nd Building B By Room B214 Combination 96937278 20-02-0018 Smoke Detector 2nd Building B By Room B202A Photoelectric 96937284 20-02-0019 Smoke Detector 2nd Building B By Room B207A Photoelectric 96937289 20-02-0020 Heat Detector 2nd Building B By Room B227 Combination 96937274 20-02-0021 Smoke Detector 2nd Building B By Room B232 Photoelectric 96937283 20-02-0023 Smoke Detector 2nd Building B By Room B210 Photoelectric 96937287 20-02-0024 Smoke Detector 2nd Building B By Carpenter Shop Photoelectric 96937282 20-02-0025 Smoke Detector 2nd Building B By Carpenter Shop Photoelectric 96937286 20-02-0058 Smoke Detector 2nd Building B By Carpenter Shop Photoelectric 96937281 20-02-0062 Smoke Detector 2nd Building B Elevator Elevator 21-22 Photoelectric 96926352
Zone/Circuit: 88 20-02-0027 Smoke Detector 3rd Building B By Men's Room T231 Photoelectric 96937260 20-02-0028 Smoke Detector 3rd Building B Elevator 21-22 Photoelectric 96926351 20-02-0029 Smoke Detector 3rd Building B By Room B323 Photoelectric 96937092 20-02-0030 Smoke Detector 3rd Building B By Room L232 Photoelectric 96937261 20-02-0031 Smoke Detector 3rd Building B By Room B318 Photoelectric 96937091 20-02-0033 Smoke Detector 3rd Building B By Room B323 Photoelectric 96937093 20-02-0034 Smoke Detector 3rd Building B By Room B308 Photoelectric 96937262 20-02-0035 Smoke Detector 3rd Building B By Room B323 Photoelectric 96937094
Zone/Circuit: 89 20-02-0022 Smoke Detector 3rd Building B By Room Elevator 21-22 Photoelectric 96937263 20-02-0037 Smoke Detector 3rd Building B By Room B319 Photoelectric 96937268 20-02-0038 Smoke Detector 3rd Building B By Machine Shop B312 Photoelectric 96937258 20-02-0039 Smoke Detector 3rd Building B By Machine Shop Photoelectric 96937259 20-02-0040 Smoke Detector 3rd Building B By Machine Shop Photoelectric 96937095 20-02-0041 Smoke Detector 3rd Building B By Room B301A Photoelectric 96937270 20-02-0042 Smoke Detector 3rd Building B By Room B305A Photoelectric 96937265 20-02-0042 Smoke Detector 3rd Building B By Room B305A Photoelectric 96937271 20-02-0043 Smoke Detector 3rd Building B By Room B301 Photoelectric 96937269 20-02-0044 Smoke Detector 3rd Building B By Room B302 Photoelectric 96937266 20-02-0045 Smoke Detector 3rd Building B By Electric Shop Photoelectric 96937264 20-02-0047 Smoke Detector 3rd Building B By Room B302A Photoelectric 96937267 20-02-0082 Smoke Detector 3rd Building B By Machine Shop B-311 Photoelectric 96937257
Zone/Circuit: 90 20-02-0053 Smoke Detector 4th Building B By AOC Room D-411 Photoelectric 96937078 20-02-0054 Smoke Detector 4th Building B By AOC Room D-405 Photoelectric 96937079 20-02-0055 Smoke Detector 4th Building B By AOC East Hallway Photoelectric 96937075 20-02-0057 Smoke Detector 4th Building B By AOC Room D-410 Photoelectric 96937081 20-02-0060 Smoke Detector 4th Building B By AOC Room D-409 Photoelectric 96937076 20-02-0061 Smoke Detector 4th Building B By AOC Room D-409 Photoelectric 96937077 20-02-0075 Smoke Detector 4th Building B Bathroom EAST Photoelectric 96937071 20-02-0075 Smoke Detector 4th Building B By AOC Breakroom Photoelectric 96937072 20-02-0079 Smoke Detector 4th Building B By AOC Room D-405 Photoelectric 96937080
Zone/Circuit: 91 20-02-0051 Smoke Detector 4th Building B By AOC Storage West Photoelectric 96937084 20-02-0063 Smoke Detector 4th Building B Elevator 21-22 Photoelectric 96926350 20-02-0065 Smoke Detector 4th Building B By AOC Spray Prep Room Photoelectric 96937087 20-02-0067 Smoke Detector 4th Building B By AOC Near Spray Area Photoelectric 96937089 20-02-0068 Smoke Detector 4th Building B By AOC Near Column K-8 Photoelectric 96937088 20-02-0070 Smoke Detector 4th Building B By AOC Near Column K-6 Photoelectric 96937086
Everon 22 Download Date: 09/03/2024
20-02-0072 Smoke Detector 4th Building B By AOC Near Column K-4 Photoelectric 96937085 20-02-0073 Smoke Detector 4th Building B By AOC Column L-4 Photoelectric 96937082 20-02-0074 Smoke Detector 4th Building B By AOC East Hallway Photoelectric 96937074 20-02-0077 Smoke Detector 4th Building B By AOC Locker Room Photoelectric 96937073
Zone/Circuit: 92 20-04-0253 Smoke Detector 5th Building B By Room B544 Photoelectric 96936824 20-04-0256 Smoke Detector 5th Building B By Men's Room T251 Photoelectric 96937070 20-04-0257 Smoke Detector 5th Building B By Room B531 Photoelectric 96936825 20-04-0258 Smoke Detector 5th Building B By Quality Control Room Photoelectric 96937067 20-04-0259 Smoke Detector 5th Building B By Room B532 Photoelectric 96937060 20-04-0260 Smoke Detector 5th Building B By Room B520 Photoelectric 96936826 20-04-0262 Smoke Detector 5th Building B By Quality Control Room Photoelectric 96937068 20-04-0264 Smoke Detector 5th Building B By Room B541 Photoelectric 96937069 20-04-0278 Smoke Detector 5th Building B By Room B539 Photoelectric 96936827
Zone/Circuit: 93 20-04-0251 Smoke Detector 5th Building B By Room B515 Photoelectric 96937058 20-04-0252 Smoke Detector 5th Building B By Room B508 Photoelectric 96937061 20-04-0254 Smoke Detector 5th Building B Elevator 21-22 Photoelectric 96926349 20-04-0265 Smoke Detector 5th Building B By Room B511 Photoelectric 96937059 20-04-0266 Smoke Detector 5th Building B By Room B538 Photoelectric 96936828 20-04-0267 Smoke Detector 5th Building B By Room B503 Conference
Room Photoelectric 96937064
20-04-0268 Smoke Detector 5th Building B By Room B524 Photoelectric 96936830 20-04-0269 Smoke Detector 5th Building B By Room B523 Photoelectric 96936831 20-04-0270 Smoke Detector 5th Building B By Room B505A Photoelectric 96937062 20-04-0271 Smoke Detector 5th Building B By Room B507 Photoelectric 96937063 20-04-0272 Smoke Detector 5th Building B By Room B521 Photoelectric 96936833 20-04-0273 Smoke Detector 5th Building B By Room B522 Photoelectric 96936829 20-04-0274 Smoke Detector 5th Building B By Room B519 Photoelectric 96936832 20-04-0275 Smoke Detector 5th Building B By Room B517 Photoelectric 96936835 20-04-0276 Smoke Detector 5th Building B By Room B502 Photoelectric 96937065 20-04-0277 Smoke Detector 5th Building B By Room B516 Photoelectric 96936834 20-04-0279 Smoke Detector 5th Building B By Room B509 Photoelectric 96937057 20-04-0280 Smoke Detector 5th Building B By Room B502B Photoelectric 96937066
Zone/Circuit: 94 20-04-0282 Smoke Detector 6th Building B By Room B612 Photoelectric 96936822 20-04-0283 Smoke Detector 6th Building B By Room B627 Photoelectric 96936815 20-04-0284 Smoke Detector 6th Building B By Women's Room T261 Photoelectric 96936804 20-04-0285 Smoke Detector 6th Building B By Room B625 Photoelectric 96936816 20-04-0286…
This is the start of the file's text. The full file is on GovTribe.