This document is a fire sprinkler inspection report conducted by Everon for the Government Publishing Office (GPO) Building B located at 732 North Capitol St. NW in Washington, DC, performed on August 7, 2024 according to NFPA 25 standards.
The inspection identified significant issues requiring attention, with 40.91% of components failing inspection. Of the 110 total items inspected, 45 components failed across various categories including: 37 valves (51.39% failure rate), 5 devices (45.45% failure rate), 2 alarms (8.33% failure rate), and 1 sprinkler component (100% failure rate). Key deficiencies include expired gauges, missing hose valve caps, incorrect inspector's test installations, damaged/worn control valves, and failed waterflow switch tests. The report notes that hose valves have not been exercised in 55 years, with dry rotted gaskets that will cause leaks if operated. The inspection was performed by Jesse Vizzini of Everon and certified by both the inspector and GPO's Senior Project Manager Jason Munoz on August 19, 2024. The report includes detailed testing data, zone mapping, and inventory information for Building B's fire suppression system components.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UEID: LJLDFKJ2VKP5 | CAGE: 5MB43
Government Publishing Office
732 North Capitol St. NW Building B
Washington, DC 20401 Fire Sprinkler Inspection
August 7, 2024
Government Publishing Office 732 North Capitol St NW Washington, DC 20401
HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098
(435) 731-9525
Points of Contact
Mason Barrett, President
Mason@HurtVet.com
Dan Vandergriff, Chief Operating Officer
Dan@HurtVet.com
Jason Munoz, Senior Project Manager
Jason@HurtVet.com
Sprinkler Inspection Certificate For
GPO Building B
732 NORTH CAPITOL ST NW
BUILDING B
WASHINGTON, DC 20401
Tested to NFPA 25 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Date Aug 7, 2024
Building: GPO Building B Company: Everon Contact: Jason Munoz Contact: Jesse Vizzini
Title: Senior Project Manager Title: Inspector
Everon 1 Download Date: 09/03/2024
Executive Summary Generated by: BuildingReports.com
Building Information Building: GPO Building B Contact: Jason Munoz
Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548
Address: BUILDING B Fax:
City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865
Country: United States of America Email: Jason@hurtvet.com
Inspection Performed By Company: Everon Inspector: Jesse Vizzini
Address: 9108 Guilford Road Phone: 202-236-8024
Address: Suite H Fax:
City/State/ZIP Code: Columbia, MD 21046-2629 Mobile:
Country: United States of America Email: jessevizzini@adt.com
Everon 2 Download Date: 09/03/2024
Inspection Summary
Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %
Alarm 24 21.82% 24 100.00% 22 91.67% 2 8.33% Device 11 10.00% 11 100.00% 6 54.55% 5 45.45% Pump 2 1.82% 2 100.00% 2 100.00% 0 0.00% Sprinkler 1 0.91% 1 100.00% 0 0.00% 1 100.00% Valve 72 65.45% 72 100.00% 35 48.61% 37 51.39%
Totals 110 100% 110 100.00
65 59.09% 45 40.91%
Certification
Company: Everon Building: GPO Building B
Inspector: Jesse Vizzini Contact: Jason Munoz
Signed: Aug 19, 2024 Signed: Aug 19, 2024
Everon 3 Download Date: 09/03/2024
Discrepancy Report
Building: GPO Building B The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade No items found during this inspection.
ScanID Location Problem Reference
Control Valve 96937013 8th Outside Stair 2 dry system Damaged/Worn NFPA25 13.2.3
Dry Pipe Valve 96937028 8th Outside Stair 2
Gauge 96936983 1st Inside Stair 2 Date Expired NFPA25 13.2.7.2 96936984 1st Inside Stair 2 Date Expired NFPA25 13.2.7.2 96937040 8th Inside Stair 1 Date Expired NFPA25 13.2.7.2 96937009 8th Outside Stair 2 Dry System Date Expired NFPA25 13.2.7.2 96937010 8th Outside Stair 2 dry system Date Expired NFPA25 13.2.7.2
Hose Valve 96937307 Basement Outside Stair 1 Missing cap 96937382 Basement Outside Stair 2 Missing cap 96937381 Basement Storage Room Missing cap 96937298 1st GPO Outside Storage Missing cap 96936978 1st Outside Stair 1 Missing cap 96936979 1st Outside Stair 2 Missing cap 96936961 1st Rear of B142 Shop Missing cap 96937299 1st GPO outside storage middle o 96936974 2nd Outside of Stair 1 Missing cap 96936459 3rd Machine shop by column 3M13 Missing cap 96936964 3rd Outside Freight Elevator Missing cap 96936456 3rd Outside of Stair 1 Missing cap 96936975 3rd Outside of Stair 2 Missing cap 96936457 3rd Outside of bathroom T231 Incorrect Application NFPA25 4.1.4.1 96936862 4th Outside Stair 1 Requires Maintenance NFPA25 13.6.3 96936863 4th Outside Stair 2 Missing cap 96936991 5th Outside Stair 1 Missing cap 96936993 5th Outside Stair 2 Missing cap 96936988 6th Outside Stair 1 Missing cap 96936987 6th Outside Stair 2 Missing cap 96937039 7th Inside Stair 1 Missing cap 96937054 7th Inside Stair 2 Missing cap 96937358 7th Outside Stair 1 Missing cap 96937056 7th Outside Stair 2 Missing cap
Everon 4 Download Date: 09/03/2024
ScanID Location Problem Reference
96937006 8th Outside Stair 2 dry system Damaged/Worn NFPA25 13.6.1.2 – 13.6.1.5
96937030 Roof Inside Room B907 Defective NFPA25 4.1.4.1
Inspector's Test 96937383 Basement Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936966 1st Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936488 2nd Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936491 3rd Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936990 4th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936998 5th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96937004 6th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1 96936501 7th Inside Stair 2 Damaged/Worn NFPA25 13.2.3 96936511 8th Inside Stair 2 Incorrect Application NFPA25 4.1.5.1
Standard Response 96937014 Penthouse
Waterflow Switch 96936489 2nd Inside Stair 2 Failed Flow Test NFPA25 4.1.5.1 96936994 5th Inside Stair 2 Failed Flow Test NFPA25 4.1.5.1
Code References NFPA25 13.2.3 All system valves shall be protected from physical damage and shall be accessible.
NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.
NFPA25 4.1.4.1 The property owner or designated representative shall promptly correct or repair deficiencies or impairments that are found while performing the inspection, test, and maintenance required by this standard.
NFPA25 13.6.3 Hose valves that do not operate smoothly or open fully shall be lubricated, repaired or replaced.
NFPA25 13.6.1.2 –
13.6.1.5
Hose valves shall be inspected to ensure that hose caps are in place and not damaged. Hose threads shall be inspected for damage. Valve handles shall be present and not damaged. Gaskets shall be inspected for damage for deterioration.
NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.
Everon 5 Download Date: 09/03/2024
Proposed Solutions Report
Building: GPO Building B
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Control Valve
96937013 8th Outside Stair 2 dry system Replace 250W T/M
Dry Pipe Valve
96937028 8th Outside Stair 2
DPV-1 T/M
Gauge
96936983 1st Inside Stair 2 Replace 35-W100-02L-
XUL
T/M
96936984 1st Inside Stair 2 Replace 35-W100-02L-
XUL
T/M
96937040 8th Inside Stair 1 Replace 35-W100-02L-
XUL
T/M
96937009 8th Outside Stair 2 Dry System Replace 35-W100-02L-
XUL
T/M
96937010 8th Outside Stair 2 dry system Replace 35-W100-02L-
XUL
T/M
Hose Valve
96937307 Basement Outside Stair 1 Replace 1 1/2 T/M
96937382 Basement Outside Stair 2 Replace 1 1/2 T/M
96937381 Basement Storage Room Replace 1 1/2 T/M
96937298 1st GPO Outside Storage Replace 1 1/2 T/M
96936978 1st Outside Stair 1 Replace 1 1/2 T/M
96936979 1st Outside Stair 2 Replace 1 1/2 T/M
96936961 1st Rear of B142 Shop Replace 1 1/2 T/M
96937299 1st GPO outside storage middle o
1 1/2 T/M
96936974 2nd Outside of Stair 1 Replace 1 1/2 T/M
96936459 3rd Machine shop by column 3M13 Replace 1 1/2 T/M
96936964 3rd Outside Freight Elevator Replace 1 1/2 T/M
96936456 3rd Outside of Stair 1
1 1/2 T/M
96936975 3rd Outside of Stair 2 Replace 1 1/2 T/M
96936457 3rd Outside of bathroom T231 Correct 1 1/2 T/M
96936862 4th Outside Stair 1 Correct 1 1/2 T/M
96936863 4th Outside Stair 2 Replace 1 1/2 T/M
96936991 5th Outside Stair 1 Replace 1 1/2 T/M
96936993 5th Outside Stair 2 Replace 1 1/2 T/M
96936988 6th Outside Stair 1 Replace 1 1/2 T/M
96936987 6th Outside Stair 2 Replace 1 1/2 T/M
96937039 7th Inside Stair 1 Replace 2 1/2 T/M
Everon 6 Download Date: 09/03/2024
ScanID Location Solution Model # Cost Fix
96937054 7th Inside Stair 2 Replace 2 1/2 T/M
96937358 7th Outside Stair 1 Replace 1 1/2 T/M
96937056 7th Outside Stair 2 Replace 1 1/2 T/M
96937006 8th Outside Stair 2 dry system Replace 250Wa T/M
96937030 Roof Inside Room B907 Replace 300 1 1/2 T/M
Inspector's Test
96937383 Basement Inside Stair 2 Correct
T/M
96936966 1st Inside Stair 2 Correct
96936488 2nd Inside Stair 2 Correct
96936491 3rd Inside Stair 2 Correct
96936990 4th Inside Stair 2 Correct
96936998 5th Inside Stair 2 Correct
96937004 6th Inside Stair 2 Correct
96936501 7th Inside Stair 2 Replace
96936511 8th Inside Stair 2 Replace
Standard Response
96937014 Penthouse
Waterflow Switch
96936489 2nd Inside Stair 2 Correct WFD40 T/M
96936994 5th Inside Stair 2 Adjust/Test WFD40 T/M
PO #: (none) T/M
Everon 7 Download Date: 09/03/2024
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed Tamper Switch Basement Inside Stair 2 8" Annual 7:42:04 AM 07/17/2024 Tamper Switch Basement Inside Stair 2 4" Annual 7:44:53 AM 07/17/2024 Tamper Switch Basement Outside Elevator Pit 21&22 Hose valve Riser stair 1 Annual 8:49:46 AM 07/17/2024
Tamper Switch Basement Outside Elevator Pit 21&22 Hose valve Riser stair 2
Annual 8:50:41 AM 07/17/2024
Tamper Switch Basement Outside Paint Shop B035 Annual 8:52:05 AM 07/17/2024 Tamper Switch 1st Inside Stair 2 Annual 11:44:21 AM 07/16/2024 Tamper Switch 1st Inside Stair 2 Dry System Annual 11:54:12 AM 07/16/2024 Tamper Switch 2nd Inside Stair 2 Annual 9:02:51 AM 07/16/2024 Tamper Switch 3rd Inside Stair 2 Annual 8:02:19 AM 07/16/2024 Tamper Switch 4th Inside Stair 2 Annual 12:27:44 PM 07/15/2024 Tamper Switch 5th Inside Stair 2 Annual 11:34:59 AM 07/15/2024 Tamper Switch 6th Inside Stair 2 Annual 10:58:51 AM 07/15/2024 Tamper Switch 7th Inside Stair 2 Annual 8:56:13 AM 07/15/2024 Tamper Switch 8th Outside Stair 2 dry system Annual 7:49:48 AM 07/15/2024 Tamper Switch 8th Outside Shaft 2 Annual 7:20:54 AM 07/16/2024 Waterflow Switch Basement Inside Stair 2 Annual 7:47:32 AM 07/17/2024 Waterflow Switch 1st Inside Stair 2 Annual 11:42:54 AM 07/16/2024 Waterflow Switch 3rd Inside Stair 2 Annual 8:02:49 AM 07/16/2024 Waterflow Switch 4th Inside Stair 2 Annual 12:27:57 PM 07/15/2024 Waterflow Switch 6th Inside Stair 2 Annual 10:59:07 AM 07/15/2024 Waterflow Switch 7th Inside Stair 2 Annual 8:57:17 AM 07/15/2024 Waterflow Switch 8th Inside Stair 2 Annual 7:14:10 AM 07/16/2024 Air Maintenance Device 1st Outside Stair 2 Annual 12:00:21 PM 07/16/2024 Air Maintenance Device 8th Outside Stair 2 Annual 7:40:48 AM 07/15/2024 Drain 1st Inside Stair 2 Dry System Annual 11:55:24 AM 07/16/2024 Drain 8th Outside Stair 2 dry system Annual 7:45:58 AM 07/15/2024 Quick Opening Device 1st Inside Stair 2 Annual 12:01:39 PM 07/16/2024 Quick Opening Device 8th Outside Stair 2 Annual 7:41:19 AM 07/15/2024 Air Compressor 1st Inside Stair 2 Air for system is run off of house air. Air line goes from 8th floor down shaft 2 all the way to the basement in Buildin
Annual 7:46:57 AM 07/22/2024
Air Compressor 8th Outside Stair 2 Air for system is run off of house air. Air line goes from 8th floor down shaft 2 all the way to the basement in Buildin
Annual 7:43:52 AM 07/22/2024
Control Valve Basement Inside Stair 2 Annual 7:41:19 AM 07/17/2024 Control Valve Basement Inside Stair 2 Annual 7:45:40 AM 07/17/2024 Control Valve Basement Outside Elevator Pit 21 & 22 Hose valve Riser stair 2 Annual 8:47:25 AM 07/17/2024
Everon 8 Download Date: 09/03/2024
Control Valve Basement Outside Elevator Pit 21 & 22 Hose
Valves Riser stair 1 Annual 8:48:32 AM 07/17/2024
Control Valve Basement Outside Paint Shop B035 Annual 8:52:33 AM 07/17/2024 Control Valve 1st Inside Stair 2 Annual 11:44:37 AM 07/16/2024 Control Valve 1st Inside Stair 2 Dry System Annual 11:50:44 AM 07/16/2024 Control Valve 2nd Inside Stair 2 Annual 9:02:39 AM 07/16/2024 Control Valve 3rd Inside Stair 2 Annual 8:02:35 AM 07/16/2024 Control Valve 4th Inside Stair 2 Annual 12:27:20 PM 07/15/2024 Control Valve 5th Inside Stair 2 Annual 11:34:43 AM 07/15/2024 Control Valve 6th Inside Stair 2 Annual 10:58:14 AM 07/15/2024 Control Valve 7th Inside Stair 2 Annual 8:54:51 AM 07/15/2024 Control Valve 8th Outside Shaft 2 Annual 7:20:15 AM 07/16/2024 Dry Pipe Valve 1st Inside Stair 2 Annual 11:59:06 AM 07/16/2024 Hose Valve Basement Inside Stair 2 Annual 7:40:31 AM 07/17/2024 Hose Valve Basement Inside Storage Room Annual 8:34:22 AM 07/17/2024 Hose Valve Basement Inside Stair 1 Annual 8:40:20 AM 07/17/2024 Hose Valve 1st Inside Stair 2 Annual 11:45:29 AM 07/16/2024 Hose Valve 1st Inside of Stair 1 Annual 12:39:13 PM 07/16/2024 Hose Valve 2nd Inside Stair 2 Annual 9:03:04 AM 07/16/2024 Hose Valve 2nd Inside of Stair 1 Annual 9:30:51 AM 07/16/2024 Hose Valve 2nd GPO outside storage rear of ao QOD ilasaza Annual 7:31:19 AM 07/17/2024 Hose Valve 3rd Inside Stair 2 Annual 8:03:03 AM 07/16/2024 Hose Valve 3rd Machine shop by eye wash station Annual 8:32:27 AM 07/16/2024 Hose Valve 3rd Inside of Stair 1 Annual 8:46:18 AM 07/16/2024 Hose Valve 4th Inside Stair 2 Annual 12:26:45 PM 07/15/2024 Hose Valve 4th Inside Stair 1 Annual 12:42:51 PM 07/15/2024 Hose Valve 5th Inside Stair 2 Annual 11:33:32 AM 07/15/2024 Hose Valve 5th Inside Stair 1 Annual 12:14:32 PM 07/15/2024 Hose Valve 6th Inside Stair 2 Annual 10:57:20 AM 07/15/2024 Hose Valve 6th Inside Stair 1 Annual 11:05:52 AM 07/15/2024 Hose Valve 8th Outside Stair 1 Annual 8:35:21 AM 07/15/2024 Hose Valve 8th Inside Stair 1 Annual 8:39:24 AM 07/15/2024 Hose Valve 8th Inside Stair 2 Annual 9:00:14 AM 07/15/2024
Failed/Other Waterflow Switch 2nd Inside Stair 2 Annual 9:08:12 AM 07/16/2024 Waterflow Switch 5th Inside Stair 2 Annual 7:57:01 AM 07/16/2024 Gauge 1st Inside Stair 2 Annual 11:56:29 AM 07/16/2024 Gauge 1st Inside Stair 2 Annual 11:58:16 AM 07/16/2024 Gauge 8th Outside Stair 2 Dry System Annual 7:44:45 AM 07/15/2024 Gauge 8th Outside Stair 2 dry system Annual 7:45:33 AM 07/15/2024 Gauge 8th Inside Stair 1 Annual 8:40:43 AM 07/15/2024 Standard Response Penthouse Annual 7:22:28 AM 07/15/2024 Control Valve 8th Outside Stair 2 dry system Annual 7:54:12 AM 07/22/2024 Dry Pipe Valve 8th Outside Stair 2 Annual 8:41:14 AM 08/07/2024 Hose Valve Basement Outside Stair 2 Annual 8:10:59 AM 07/17/2024 Hose Valve Basement Storage Room Annual 8:21:21 AM 07/17/2024 Hose Valve Basement Outside Stair 1 Annual 8:42:01 AM 07/17/2024 Hose Valve 1st Outside Stair 2 Annual 12:07:28 PM 07/16/2024 Hose Valve 1st Outside Stair 1 Annual 12:33:29 PM 07/16/2024 Hose Valve 1st Rear of B142 Shop Annual 1:01:42 PM 07/16/2024 Hose Valve 1st GPO Outside Storage Annual 7:21:41 AM 07/17/2024
Everon 9 Download Date: 09/03/2024
Hose Valve 1st GPO outside storage middle o Annual 7:27:38 AM 07/17/2024 Hose Valve 2nd Outside of Stair 1 Annual 9:30:36 AM 07/16/2024 Hose Valve 3rd Outside Freight Elevator Annual 8:13:34 AM 07/16/2024 Hose Valve 3rd Machine shop by column 3M13 Annual 8:32:12 AM 07/16/2024 Hose Valve 3rd Outside of bathroom T231 Annual 8:44:28 AM 07/16/2024 Hose Valve 3rd Outside of Stair 1 Annual 8:45:53 AM 07/16/2024 Hose Valve 3rd Outside of Stair 2 Annual 9:20:54 AM 07/16/2024 Hose Valve 4th Outside Stair 2 Annual 12:30:34 PM 07/15/2024 Hose Valve 4th Outside Stair 1 Annual 12:41:51 PM 07/15/2024 Hose Valve 5th Outside Stair 2 Annual 11:37:10 AM 07/15/2024 Hose Valve 5th Outside Stair 1 Annual 12:15:22 PM 07/15/2024 Hose Valve 6th Outside Stair 2 Annual 11:02:53 AM 07/15/2024 Hose Valve 6th Outside Stair 1 Annual 11:07:23 AM 07/15/2024 Hose Valve 7th Outside Stair 2 Annual 8:50:16 AM 07/15/2024 Hose Valve 7th Inside Stair 2 Annual 8:54:41 AM 07/15/2024 Hose Valve 7th Inside Stair 1 Annual 9:27:02 AM 07/15/2024 Hose Valve 7th Outside Stair 1 Annual 11:31:36 AM 07/17/2024 Hose Valve 8th Outside Stair 2 dry system Annual 8:02:51 AM 07/15/2024 Hose Valve Roof Inside Room B907 Annual 12:30:27 PM 07/15/2024 Inspector's Test Basement Inside Stair 2 Annual 7:50:35 AM 07/17/2024 Inspector's Test 1st Inside Stair 2 Annual 11:46:46 AM 07/16/2024 Inspector's Test 2nd Inside Stair 2 Annual 9:07:23 AM 07/16/2024 Inspector's Test 3rd Inside Stair 2 Annual 8:08:19 AM 07/16/2024 Inspector's Test 4th Inside Stair 2 Annual 7:56:10 AM 07/16/2024 Inspector's Test 5th Inside Stair 2 Annual 7:53:50 AM 07/16/2024 Inspector's Test 6th Inside Stair 2 Annual 7:52:32 AM 07/16/2024 Inspector's Test 7th Inside Stair 2 Annual 7:52:17 AM 07/16/2024 Inspector's Test 8th Inside Stair 2 Annual 7:52:10 AM 07/16/2024
Everon 10 Download Date: 09/03/2024
Inventory & Warranty Report
Building: GPO Building B
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Air Compressor Pump 1.82% 2
Air Maintenance Device Device 1.82% 2
Control Valve Valve 13.64% 15
Drain Device 1.82% 2
Dry Pipe Valve Valve 1.82% 2
Gauge Device 4.55% 5
Hose Valve Valve 41.82% 46
Inspector's Test Valve 8.18% 9
Quick Opening Device Device 1.82% 2
Standard Response Sprinkler 0.91% 1
Tamper Switch Alarm 13.64% 15
Waterflow Switch Alarm 8.18% 9
Device Type
Qt y Model # Type Description Install Date
New (under 90 days)
Standard Response 1
07/15/2024
In Service - 5 Years to 10 Years
Gauge 2 35-W100-02L-XU L
Supply Pressure
07/15/2015
Air Compressor 1
Air Compressor 1
Automatic
Dry Pipe Valve 2 DPV-1 Flanged
In Service - 15 Years to 25 Years
Hose Valve 1
07/15/2009
Inspector's Test 9
Gauge 1 35-W100-02L-XU
Air Pressure
Gauge 1 35-W100-02L-XU
Supply Pressure
Control Valve 1 250W OS&Y Isolation 07/15/2009
Control Valve 1 250W OS&Y Main Control 07/15/2009
Hose Valve 1 1 1/2
Hose Valve 1 250Wa
Tamper Switch 15 OSY2 Lever Supervisory 07/15/2009
Waterflow Switch 9 WFD40 Vane Alarm 07/15/2009
Quick Opening Device 2 ACC-1
Drain 2 126 WSP Main
In Service - 25 Years or Older
Gauge 1 35-W100-02L-XU Supply Pressure
07/15/1983
Everon 11 Download Date: 09/03/2024
Hose Valve 2 300 1 1/2
07/15/1980
Hose Valve 1 300 2 1/2
Hose Valve 23 1 1/2
Hose Valve 16 2 1/2
Control Valve 3 10240 Gate Isolation 07/15/1980
Control Valve 7 10240 OS&Y Isolation 07/15/1980
Control Valve 2 10240 OS&Y Isolation 07/15/1980
Hose Valve 1 1 1/2
Air Maintenance Device 2 4ZK96 Pressure Reducing
Control Valve 1 95-5 OS&Y Isolation 07/15/1980
Everon 12 Download Date: 09/03/2024
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location and description are included for your reference. For more information on the device, use the link provided under ScanID.
Address Device Type Location Type ScanID
Control Panel 1 Zone/Address: Z82
L002D0147 Control Valve Basement Inside Stair 2 OS&Y 96937302 L002D0147 Control Valve Basement Outside Elevator Pit 21 & 22
Hose Valves Riser stair 1 Gate 96937376
L002D0147 Control Valve Basement Outside Elevator Pit 21 & 22 Hose valve Riser stair 2
Gate 96937378
L002D0147 Control Valve Basement Outside Paint Shop B035 Gate 96937374 L002D0185 Waterflow Switch Basement Inside Stair 2 Vane 96937303 L002D0186 Tamper Switch Basement Inside Stair 2 4" Lever 96937301 L002D0186 Tamper Switch Basement Inside Stair 2 8" Lever 96937304 L002D0186 Tamper Switch Basement Outside Elevator Pit 21&22 Hose valve Riser stair 1 Lever 96937377
L002D0186 Tamper Switch Basement Outside Elevator Pit 21&22 Hose valve Riser stair 2
Lever 96937375
L002D0186 Tamper Switch Basement Outside Paint Shop B035 Lever 96937373
Zone/Address: Z84 L002D0187 Waterflow Switch 1st Inside Stair 2 Vane 96936969 L002D0188 Tamper Switch 1st Inside Stair 2 Lever 96936968 L002D0188 Tamper Switch 1st Inside Stair 2 Dry System Lever 96936985
Zone/Address: Z86 L002D0191 Waterflow Switch 2nd Inside Stair 2 Vane 96936489 L002D0192 Tamper Switch 2nd Inside Stair 2 Lever 96936490
Zone/Address: Z88 L002D0193 Waterflow Switch 3rd Inside Stair 2 Vane 96936492 L002D0194 Tamper Switch 3rd Inside Stair 2 Lever 96936494
Zone/Address: Z90 L002D0195 Waterflow Switch 4th Inside Stair 2 Vane 96936864 L002D0196 Tamper Switch 4th Inside Stair 2 Lever 96936865
Zone/Address: Z92 L002D0198 Tamper Switch 5th Inside Stair 2 Lever 96936996
Zone/Address: Z94 L002D0199 Waterflow Switch 6th Inside Stair 2 Vane 96937005
Zone/Address: Z96 L002D0202 Tamper Switch 7th Inside Stair 2 Lever 96937052 Waterflow Switch 5th Inside Stair 2 Vane 96936994
Everon 13 Download Date: 09/03/2024
Tamper Switch 6th Inside Stair 2 Lever 96937003
Zone/Address: Z98 L002D0201 Waterflow Switch 7th Inside Stair 2 Vane 96937051 L002D0203 Waterflow Switch 8th Inside Stair 2 Vane 96936510 L02D0204 Tamper Switch 8th Outside Shaft 2 Lever 96936508 L02D0204 Control Valve 8th Outside Stair 2 dry system OS&Y 96937013 L02D0204 Tamper Switch 8th Outside Stair 2 dry system Lever 96937012
Everon 14 Download Date: 09/03/2024
Notes & Recommendations
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.
General Note Hose Valves have not been annually exercised in 55 years. Gaskets are dry rotted and will cause leaks if opened. Recommend replacement.
Note Device Type Location Comment ScanID 2 Inspector's Test Basement Inside Stair 2 Incorrect
Application 96937383
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
3 Inspector's Test 1st Inside Stair 2 Incorrect Application
96936966
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
4 Inspector's Test 2nd Inside Stair 2 Incorrect Application
96936488
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
5 Waterflow Switch 2nd Inside Stair 2 Failed Flow Test 96936489 Did not go into alarm in time
6 Inspector's Test 3rd Inside Stair 2 Incorrect Application
96936491
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
7 Hose Valve 4th Outside Stair 1 Requires Maintenance
96936862
Need pipe wrench to remove cap. Also improper cap. Replace.
8 Inspector's Test 4th Inside Stair 2 Incorrect
Application 96936990
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
9 Inspector's Test 5th Inside Stair 2 Incorrect Application
96936998
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
10 Waterflow Switch 5th Inside Stair 2 Failed Flow Test 96936994 Alarm did not come in while flowing
11 Inspector's Test 6th Inside Stair 2 Incorrect Application
96937004
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
12 Inspector's Test 7th Inside Stair 2 Damaged/Worn 96936501 They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
Everon 15 Download Date: 09/03/2024
13 Dry Pipe Valve 8th Outside Stair 2 96937028 No inspectors test found. Must add one for a proper full trip test. Partial trip performed.
14 Hose Valve 8th Outside Stair 2 dry system Damaged/Worn 96937006 Channel locks are required to fully close the valve and stop from leaking. Recommend replacement.
15 Inspector's Test 8th Inside Stair 2 Incorrect Application
96936511
They have two 1" valves installed for a drain and inspectors test. The sprinkler heads are 1/2" so they need a 1/2" orifice to flow through.
16 Standard Response Penthouse 96937014 2 heads inside paint shop to be replaced. 1 pendant, 1 upright
17 Hose Valve Roof Inside Room B907 Defective 96937030 Valves have not been annually exercised. Seals are dry rotted and cause leakes when open. Recommend replacement. Also missing cap.