2024-08-06_GPO-Building-D_Fire_Alarm.pdf
PDF 1 MB Posted
- Solicitation number
- 040ADV-25-R-0013
- Issued by
-
Government Publishing Office
About this file
This is a fire alarm inspection report dated August 6, 2024, for Building D of the Government Publishing Office (GPO) located at 732 North Capitol St. NW in Washington, DC. The inspection was performed by Everon (contractor) and tested to NFPA 72 standards.
The inspection results show that out of 220 total devices tested, 214 (97.27%) passed and 6 (2.73%) failed. The failed items included one phone station, three pull stations, and two smoke detectors. The inspection covered control devices (59 items), indicating devices (11 items), and initiating devices (150 items). Specific issues identified include damaged/worn components, failed annunciation, and failed operation of certain devices. The report includes detailed documentation of all tested devices, their locations, test times/dates, and auxiliary function testing results. The report also contains a complete inventory of system components, with many devices being newly installed within the past 90 days, including Edwards and EST brand equipment. The 3rd floor was noted as under construction and could not be fully tested.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UEID: LJLDFKJ2VKP5 | CAGE: 5MB43
Government Publishing Office
732 North Capitol St. NW Building D
Washington, DC 20401 Fire Alarm Inspection
August 6, 2024
Government Publishing Office 732 North Capitol St NW Washington, DC 20401
HurtVet Subcontracting 1389 Center Drive Suite 200 Park City, UT 84098
(435) 731-9525
Points of Contact
Mason Barrett, President
Mason@HurtVet.com
Dan Vandergriff, Chief Operating Officer
Dan@HurtVet.com
Jason Munoz, Senior Project Manager
Jason@HurtVet.com
Fire Alarm and Life Safety System Inspection Certificate
For
GPO Building D
732 NORTH CAPITOL ST NW
BUILDING D
WASHINGTON, DC 20401
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Date Aug 6, 2024
Building: GPO Building D Company: Everon Contact: Jason Munoz Contact: Terance Proctor
Title: Senior Project Manager Title: Fire Test & Inspect Tech l
Everon 1 Download Date: 09/03/2024
Executive Summary Generated by: BuildingReports.com
Building Information Building: GPO Building D Contact: Jason Munoz
Address: 732 NORTH CAPITOL ST NW Phone: 225-999-3548
Address: BUILDING D Fax:
City/State/ZIP Code: WASHINGTON, DC 20401 Mobile: 602-679-1865
Country: United States of America Email: Jason@hurtvet.com
Inspection Performed By Company: Everon Inspector: Terance Proctor
Address: 9108 Guilford Road Phone: 301 875-5064
Address: Suite H Fax:
City/State/ZIP Code: Columbia, MD 21046-2629 Mobile: 301 875-5064
Country: United States of America Email: teranceproctor@adt.com
Everon 2 Download Date: 09/03/2024
Inspection Summary
Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %
Control 59 26.82% 59 100.00% 58 98.31% 1 1.69% Indicating 11 5.00% 11 100.00% 11 100.00% 0 0.00% Initiating 150 68.18% 150 100.00% 145 96.67% 5 3.33%
Totals 220 100% 220 100.00% 214 97.27% 6 2.73%
Certification
Company: Everon Building: GPO Building D
Inspector: Terance Proctor Contact: Jason Munoz
Everon 3 Download Date: 09/03/2024
Discrepancy Report
Building: GPO Building D Control Panel: 1
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade No items found during this inspection.
ScanID Location Problem Address Reference
Control Phone Station
96926011 3rd Stair 4 Damaged/Worn 1 NFPA72 14.2.2.2.2
Initiating Pull Station
64971769 2nd Stair 1 Failed Annunciation 1-110 L2D135 NFPA72 10.10.1;
NFPA72 10.18.1.1.1
64971789 2nd Stair 3 Damaged/Worn 1-110 L2D134 NFPA72 14.2.2.2.2 64971832 3rd Stair 3 Damaged/Worn 1-112 L2D134 NFPA72 14.2.2.2.2
Smoke Detector 96926418 2nd Building D By Column 30 Damaged/Worn 1-110
07-02-0020
NFPA72 14.2.2.2.2
96926443 2nd Building D By Room 5D-211 Failed Operation 1 NFPA72 14.2.2.2.2
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
NFPA72 10.10.1;
NFPA72 10.18.1.1.1
Priority alarms, fire alarms, carbon monoxide alarm signals, supervisory signals, pre-alarm signals, and trouble signals shall be distinctively and descriptively annunciated; Visible annunciation of the location of an operated initiating device shall be by an indicator lamp, alphanumeric display, printout, or other approved means.
Everon 4 Download Date: 09/03/2024
Proposed Solutions Report
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Control
Phone Station
96926011 3rd Stair 4 Replace
T/M
Initiating
Pull Station
64971769 2nd Stair 1 Correct Siga-278 T/M
64971789 2nd Stair 3 Replace Siga-278 T/M
64971832 3rd Stair 3 Replace Siga-278 T/M
Smoke Detector
96926418 2nd Building D By Column 30 Replace SIGA-PS T/M
96926443 2nd Building D By Room 5D-211 Replace SIGA-PS T/M
PO #: (none) T/M
Everon 5 Download Date: 09/03/2024
Notes & Recommendations
Building: GPO Building D
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note 3rd Floor under construction. Cannot Test
Building: GPO Building D Control Panel: 1
ScanID Note Device Type Location Comment
Control 96926047 2 Amplifier 2nd Outside Cafeteria Passed
Class 1 and Class 2
Initiating 96926443 3 Smoke Detector 2nd Building D By Room 5D-211 Failed Operation
Old smoke detector not linked to EST system. Didn't report
Everon 6 Download Date: 09/03/2024
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed Control
Amplifier Basement Room D-002 Annual 7:28:28 AM 08/02/2024 Amplifier Basement Room D-002 Annual 7:28:39 AM 08/02/2024 Amplifier Basement Room D-002 Annual 7:28:52 AM 08/02/2024 Amplifier Basement Room D-002 Annual 7:29:11 AM 08/02/2024 Amplifier 1st By Stair 3 Annual 7:48:08 AM 08/05/2024 Amplifier 1st By Stair 3 Annual 7:48:14 AM 08/05/2024 Amplifier 1st By Stair 3 Annual 7:48:24 AM 08/05/2024 Amplifier 1st By Stair 3 Annual 7:48:30 AM 08/05/2024 Amplifier 2nd Outside Cafeteria Annual 12:13:00 PM 07/31/2024 Amplifier 2nd Outside Cafeteria Annual 12:13:37 PM 07/31/2024 Amplifier 2nd Outside Cafeteria Annual 12:13:46 PM 07/31/2024 Amplifier 2nd Room D-231 Annual 8:49:39 AM 08/01/2024 Amplifier 2nd Room D-231 Annual 8:50:17 AM 08/01/2024 Amplifier 2nd Room D-231 Annual 8:50:25 AM 08/01/2024 Battery Basement Room D-002 Annual 7:30:59 AM 08/02/2024 Battery Basement Room D-002 Annual 7:31:35 AM 08/02/2024 Battery Basement Stair 1 Annual 11:24:05 AM 07/31/2024 Battery Basement Stair 1 Annual 11:25:46 AM 07/31/2024 Battery Basement Stair 3 Annual 11:28:47 AM 07/31/2024 Battery Basement Stair 3 Annual 11:29:28 AM 07/31/2024 Battery 1st By Stair 1 Annual 8:03:31 AM 08/05/2024 Battery 1st By Stair 1 Annual 8:03:12 AM 08/28/2024 Battery 1st By Stair 3 Annual 7:49:03 AM 08/05/2024 Battery 1st By Stair 3 Annual 7:49:09 AM 08/05/2024 Battery 1st By Stair 3 Annual 7:50:06 AM 08/05/2024 Battery 1st By Stair 3 Annual 7:50:50 AM 08/05/2024 Battery 2nd By Cafeteria Annual 10:00:07 AM 08/01/2024 Battery 2nd By Cafeteria Annual 10:00:47 AM 08/01/2024 Battery 2nd Outside Cafeteria Annual 12:14:35 PM 07/31/2024 Battery 2nd Outside Cafeteria Annual 12:15:47 PM 07/31/2024 Battery 2nd Room D-231 Annual 8:51:07 AM 08/01/2024 Battery 2nd Room D-231 Annual 8:51:21 AM 08/01/2024 Battery 2nd Stair 3 Annual 12:23:45 PM 07/31/2024 Battery 2nd Stair 3 Annual 12:23:50 PM 07/31/2024 Battery 3rd By Stair 3 Annual 8:14:55 AM 08/02/2024 Battery 3rd By Stair 3 Annual 8:15:17 AM 08/02/2024 Expander Panel Basement Stair 1 Annual 11:23:43 AM 07/31/2024 Expander Panel Basement Stair 3 Annual 11:29:53 AM 07/31/2024 Expander Panel 1st By Stair 1 Annual 8:03:11 AM 08/05/2024
Everon 7 Download Date: 09/03/2024
Expander Panel 1st By Stair 3 Annual 7:49:36 AM 08/05/2024 Expander Panel 2nd By Cafeteria Annual 8:09:53 AM 08/28/2024 Expander Panel 2nd Stair 3 Annual 12:22:01 PM 07/31/2024 Expander Panel 3rd By Stair 3 Annual 8:14:17 AM 08/28/2024 Phone Station Basement Stair 1 Annual 11:20:49 AM 07/31/2024 Phone Station Basement Stair 2 Annual 11:49:27 AM 07/31/2024 Phone Station Basement Stair 3 Annual 11:35:46 AM 07/31/2024 Phone Station Basement Stair 4 Annual 11:31:09 AM 07/31/2024 Phone Station 1st Stair 1 Annual 11:19:46 AM 07/31/2024 Phone Station 1st Stair 2 Annual 11:50:29 AM 07/31/2024 Phone Station 1st Stair 3 Annual 11:36:25 AM 07/31/2024 Phone Station 1st Stair 4 Annual 11:31:52 AM 07/31/2024 Phone Station 2nd Stair 1 Annual 11:19:15 AM 07/31/2024 Phone Station 2nd Stair 2 Annual 11:51:44 AM 07/31/2024 Phone Station 2nd Stair 3 Annual 11:37:04 AM 07/31/2024 Phone Station 2nd Stair 4 Annual 11:32:38 AM 07/31/2024 Phone Station 3rd Stair 1 Annual 11:16:45 AM 07/31/2024 Phone Station 3rd Stair 2 Annual 11:52:43 AM 07/31/2024 Phone Station 3rd Stair 3 Annual 11:37:50 AM 07/31/2024
Indicating Horn/Strobe Basement Building D Floor Annual 8:02:44 AM 08/28/2024 Speaker Sub-Basement Building D Floor Annual 7:36:53 AM 08/28/2024 Speaker Basement Building D Floor Annual 8:02:11 AM 08/28/2024 Speaker 1st Building D Floor Annual 8:08:25 AM 08/28/2024 Speaker 2nd Building D Floor Annual 8:12:41 AM 08/28/2024 Speaker 3rd Building D Floor Annual 8:19:34 AM 08/28/2024 Strobe Sub-Basement Building D Floor Annual 7:36:39 AM 08/28/2024 Strobe Basement Building D Floor Annual 8:02:18 AM 08/28/2024 Strobe 1st Building D Floor Annual 8:09:02 AM 08/28/2024 Strobe 2nd Building D Floor Annual 8:12:16 AM 08/28/2024 Strobe 3rd Building D Floor Annual 8:19:12 AM 08/28/2024
Initiating Duct Detector 2nd AHU 1 Annual 9:17:28 AM 08/01/2024 Duct Detector 2nd AHU 2 By Men Restroom Annual 9:05:06 AM 08/01/2024 Duct Detector 2nd AHU 3 By Room D-231 Annual 8:49:07 AM 08/01/2024 Pull Station Basement By Column 15 Annual 12:54:06 PM 08/01/2024 Pull Station Basement By Stair 1 Annual 11:41:55 AM 08/01/2024 Pull Station Basement By Stair 2 Annual 11:51:16 AM 08/01/2024 Pull Station Basement Stair 3 Annual 7:55:35 AM 08/02/2024 Pull Station Basement Stair 4 Annual 7:46:50 AM 08/02/2024 Pull Station 1st By Column 1D16 Annual 7:54:08 AM 08/05/2024 Pull Station 1st By Stair 1 Annual 7:59:10 AM 08/05/2024 Pull Station 1st By Stair 4 Annual 7:40:40 AM 08/05/2024 Pull Station 1st Loading Dock Annual 7:34:42 AM 08/05/2024 Pull Station 1st Stair 1 Annual 7:38:18 AM 08/01/2024 Pull Station 1st Stair 2 Annual 7:17:33 AM 08/05/2024 Pull Station 2nd Column C-16 Annual 8:02:51 AM 08/01/2024 Pull Station 2nd Stair 2 Annual 7:46:09 AM 08/01/2024 Pull Station 2nd Stair 3 Annual 8:18:04 AM 08/01/2024
Everon 8 Download Date: 09/03/2024
Pull Station 3rd Between Stair 1 And Stair 3 Annual 8:19:48 AM 08/02/2024 Pull Station 3rd Stair 1 Annual 7:38:07 AM 08/01/2024 Pull Station 3rd Stair 2 Annual 8:00:57 AM 08/02/2024 Pull Station 3rd Stair 4 Annual 8:05:42 AM 08/02/2024 Pull Station 3rd Building D By Column A15 Annual 11:22:39 AM 08/02/2024 Smoke Detector Sub-Basement Building D Elevator Lobby 51-52 Annual 7:37:18 AM 08/28/2024 Smoke Detector Basement Building D By Column C15 Annual 7:38:47 AM 08/02/2024 Smoke Detector Basement Building D By Column C18 Annual 11:41:11 AM 08/02/2024 Smoke Detector Basement Building D By Column C2 Annual 11:46:53 AM 08/01/2024 Smoke Detector Basement Building D By Column C20 Annual 7:44:13 AM 08/02/2024 Smoke Detector Basement Building D By Column C22 Annual 11:41:07 AM 08/02/2024 Smoke Detector Basement Building D By Column C24 Annual 7:46:49 AM 08/02/2024 Smoke Detector Basement Building D By Column C26 Annual 12:59:16 PM 08/01/2024 Smoke Detector Basement Building D By Column C4 Annual 11:48:36 AM 08/01/2024 Smoke Detector Basement Building D By Column C6 Annual 11:53:05 AM 08/01/2024 Smoke Detector Basement Building D By Column E13 Annual 12:48:23 PM 08/01/2024 Smoke Detector Basement Building D By Column E4 Annual 12:01:21 PM 08/01/2024 Smoke Detector Basement Building D By Column E9 Annual 12:00:30 PM 08/01/2024 Smoke Detector Basement Building D By Column E9 Annual 12:01:53 PM 08/01/2024 Smoke Detector Basement Building D By Room D002 Annual 7:39:42 AM 08/02/2024 Smoke Detector Basement Building D By Room D006 Annual 7:57:41 AM 08/28/2024 Smoke Detector Basement Building D By Room D009 Annual 12:50:44 PM 08/01/2024 Smoke Detector Basement Building D By Room D011 Annual 12:49:33 PM 08/01/2024 Smoke Detector Basement Building D By Room D024 Column
C28 Annual 12:57:37 PM 08/01/2024
Smoke Detector Basement Building D By Room D025 North Annual 7:41:56 AM 08/02/2024 Smoke Detector Basement Building D By Room D025 South Annual 7:42:51 AM 08/02/2024 Smoke Detector Basement Building D By Room T01 Annual 11:47:57 AM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:37:47 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:38:33 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:39:20 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:40:04 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:40:42 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:41:19 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:42:09 PM 08/01/2024 Smoke Detector Basement Building D By Switch Gear Room Annual 12:43:43 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:28:42 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:29:58 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:30:55 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:31:40 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:32:22 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:33:19 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 12:34:55 PM 08/01/2024 Smoke Detector Basement Building D By Transformer Room Annual 7:52:46 AM 08/28/2024 Smoke Detector Basement Building D Elevator Lobby 51-52 Annual 2:39:03 PM 08/06/2024 Smoke Detector Basement Building D Elevator Lobby 55 Annual 2:59:13 PM 08/06/2024 Smoke Detector Basement Building D Elevator Lobby 56 Annual 2:50:10 PM 08/06/2024 Smoke Detector 1st Building D By Column B18 Annual 11:44:31 AM 08/02/2024 Smoke Detector 1st Building D By Column B20 Annual 11:45:00 AM 08/02/2024 Smoke Detector 1st Building D By Column B22 Annual 11:45:23 AM 08/02/2024
Everon 9 Download Date: 09/03/2024
Smoke Detector 1st Building D By Column B24 Annual 11:45:45 AM 08/02/2024 Smoke Detector 1st Building D By Column B28 Annual 11:43:44 AM 08/02/2024 Smoke Detector 1st Building D By Column B30 Annual 7:34:52 AM 08/05/2024 Smoke Detector 1st Building D By Column C04 Annual 7:20:19 AM 08/05/2024 Smoke Detector 1st Building D By Column D18 Annual 7:21:58 AM 08/05/2024 Smoke Detector 1st Building D By Column D20 Annual 7:20:34 AM 08/05/2024 Smoke Detector 1st Building D By Column D22 Annual 7:24:48 AM 08/05/2024 Smoke Detector 1st Building D By Column D26 Annual 7:30:03 AM 08/05/2024 Smoke Detector 1st Building D By Column E04 Annual 11:52:50 AM 08/02/2024 Smoke Detector 1st Building D By Column E06 Annual 11:51:41 AM 08/02/2024 Smoke Detector 1st Building D By Column E09 Annual 11:52:25 AM 08/02/2024 Smoke Detector 1st Building D By Column E11 Annual 11:49:35 AM 08/02/2024 Smoke Detector 1st Building D By Column E13 Annual 11:50:43 AM 08/02/2024 Smoke Detector 1st Building D By Column E15 Annual 11:50:18 AM 08/02/2024 Smoke Detector 1st Building D By Men's Room T413 Annual 11:54:49 AM 08/02/2024 Smoke Detector 1st Building D By Mourge Offices Annual 7:36:04 AM 08/05/2024 Smoke Detector 1st Building D By Room D130 Annual 8:02:25 AM 08/05/2024 Smoke Detector 1st Building D By Room D156 Annual 8:00:29 AM 08/05/2024 Smoke Detector 1st Building D By Room D156 Annual 8:03:22 AM 08/05/2024 Smoke Detector 1st Building D By Room L123 North Annual 7:33:30 AM 08/05/2024 Smoke Detector 1st Building D By Room L123 South Annual 7:36:32 AM 08/05/2024 Smoke Detector 1st Building D By Room T12 Annual 7:40:35 AM 08/05/2024 Smoke Detector 1st Building D By Women's Room T411 Annual 7:20:19 AM 08/05/2024 Smoke Detector 1st Building D Elevator Lobby 51-52 Annual 2:38:35 PM 08/06/2024 Smoke Detector 1st Building D Elevator Lobby 55 Annual 2:49:36 PM 08/06/2024 Smoke Detector 1st Building D Elevator Lobby 56 Annual 2:44:46 PM 08/06/2024 Smoke Detector 2nd Building D By Column 11 Annual 8:04:46 AM 08/01/2024 Smoke Detector 2nd Building D By Column 14 Annual 7:59:08 AM 08/01/2024 Smoke Detector 2nd Building D By Column 14 Annual 9:26:56 AM 08/01/2024 Smoke Detector 2nd Building D By Column 16 Annual 8:01:49 AM 08/01/2024 Smoke Detector 2nd Building D By Column 18 Annual 8:06:38 AM 08/01/2024 Smoke Detector 2nd Building D By Column 20 Annual 8:08:27 AM 08/01/2024 Smoke Detector 2nd Building D By Column 22 Annual 8:13:21 AM 08/01/2024 Smoke Detector 2nd Building D By Column 24 Annual 8:14:56 AM 08/01/2024 Smoke Detector 2nd Building D By Column 27 Annual 8:22:57 AM 08/01/2024 Smoke Detector 2nd Building D By Column 28 Annual 8:27:08 AM 08/01/2024 Smoke Detector 2nd Building D By Column 30 Annual 8:34:00 AM 08/01/2024 Smoke Detector 2nd Building D By Column 30 Annual 8:55:42 AM 08/01/2024 Smoke Detector 2nd Building D By Column 9 Annual 7:56:36 AM 08/01/2024 Smoke Detector 2nd Building D By Column D07 Annual 9:49:21 AM 08/01/2024 Smoke Detector 2nd Building D By Column D09 Annual 9:36:36 AM 08/01/2024 Smoke Detector 2nd Building D By Column D11 Annual 9:37:27 AM 08/01/2024 Smoke Detector 2nd Building D By Column D13 Annual 9:34:17 AM 08/01/2024 Smoke Detector 2nd Building D By Column E06 Annual 9:42:02 AM 08/01/2024 Smoke Detector 2nd Building D By Column E09 Annual 9:39:02 AM 08/01/2024 Smoke Detector 2nd Building D By Column E11 Annual 9:31:24 AM 08/01/2024 Smoke Detector 2nd Building D By Column E13 Annual 9:28:25 AM 08/01/2024 Smoke Detector 2nd Building D By Column E13 Annual 9:30:21 AM 08/01/2024 Smoke Detector 2nd Building D By Column E17 Annual 9:15:26 AM 08/01/2024 Smoke Detector 2nd Building D By Column E19 Annual 9:13:41 AM 08/01/2024
Everon 10 Download Date: 09/03/2024
Smoke Detector 2nd Building D By Column E21 Annual 9:12:26 AM 08/01/2024 Smoke Detector 2nd Building D By Column E23 Annual 9:04:15 AM 08/01/2024 Smoke Detector 2nd Building D By Column E23 Annual 8:55:33 AM 08/28/2024 Smoke Detector 2nd Building D By Column E25 Annual 8:58:59 AM 08/01/2024 Smoke Detector 2nd Building D By Column E28 Annual 8:54:20 AM 08/01/2024 Smoke Detector 2nd Building D By Column E30 Annual 8:32:30 AM 08/01/2024 Smoke Detector 2nd Building D By Lunch Room Annual 8:00:32 AM 08/01/2024 Smoke Detector 2nd Building D By Lunch Room Annual 8:00:59 AM 08/01/2024 Smoke Detector 2nd Building D By Men's Locker Room T23 Annual 9:03:14 AM 08/01/2024 Smoke Detector 2nd Building D By Men's Locker Room T24 Annual 8:21:12 AM 08/01/2024 Smoke Detector 2nd Building D By Men's Room T21 Annual 8:03:13 AM 08/01/2024 Smoke Detector 2nd Building D By Room D207 Annual 8:09:22 AM 08/01/2024 Smoke Detector 2nd Building D By Room D211 Annual 8:01:21 AM 08/01/2024 Smoke Detector 2nd Building D By Room D219 Annual 8:48:35 AM 08/01/2024 Smoke Detector 2nd Building D By Room D222A Annual 8:02:50 AM 08/01/2024 Smoke Detector 2nd Building D By Room D231 Annual 8:49:42 AM 08/01/2024 Smoke Detector 2nd Building D By Room D232 Annual 8:36:04 AM 08/01/2024 Smoke Detector 2nd Building D By Women's Room T25 Annual 8:03:39 AM 08/01/2024 Smoke Detector 2nd Building D Elevator Lobby 51-52 Annual 8:11:44 AM 08/28/2024 Smoke Detector 2nd Building D Elevator Lobby 55 Annual 2:49:58 PM 08/06/2024 Smoke Detector 2nd Building D Elevator Lobby 56 Annual 2:43:50 PM 08/06/2024 Smoke Detector 3rd Building D EMR 51-52 Annual 2:40:34 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Hoistway 55 Annual 2:59:03 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 51-52 Annual 2:35:39 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 51-52 Annual 2:36:10 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 51-52 Annual 2:41:19 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 55 Annual 2:46:01 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 56 Annual 2:41:40 PM 08/06/2024 Smoke Detector 3rd Building D Elevator Machine Room 56 Annual 2:43:25 PM 08/06/2024
Failed/Other Control
Phone Station 3rd Stair 4 Annual 11:33:57 AM 07/31/2024
Initiating Pull Station 2nd Stair 1 Annual 9:57:48 AM 08/01/2024 Pull Station 2nd Stair 3 Annual 8:58:32 AM 08/01/2024 Pull Station 3rd Stair 3 Annual 8:11:33 AM 08/02/2024 Smoke Detector 2nd Building D By Column 30 Annual 8:50:59 AM 08/28/2024 Smoke Detector 2nd Building D By Room 5D-211 Annual 9:03:03 AM 08/28/2024
Everon 11 Download Date: 09/03/2024
Service Summary
Building: GPO Building D
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Phone Station Annual 1
Pull Station Annual 3
Smoke Detector Annual 2
Total 6
Passed
Amplifier Annual 14
Battery Annual 22
Duct Detector Annual 3
Expander Panel Annual 7
Horn/Strobe Annual 1
Phone Station Annual 15
Pull Station Annual 19
Smoke Detector Annual 123
Speaker Annual 5
Strobe Annual 5
Total 214
Grand Total 220
Everon 12 Download Date: 09/03/2024
Auxiliary Functions Testing
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Duct Detector
AHU Shutdown 2nd AHU 1 Passed 64971778
AHU Shutdown 2nd AHU 2 By Men Restroom Passed 64971800
AHU Shutdown 2nd AHU 3 By Room D-231 Passed 64971775
Smoke Detector
Elevator Recall Sub-Basement Building D Elevator Lobby 51-52
Passed 96926396
Smoke Compartment Basement Building D By Column C15 Passed 96926474
Smoke Compartment Basement Building D By Column C18 Passed 96926477
Smoke Compartment Basement Building D By Column C2 Passed 96926445
Smoke Compartment Basement Building D By Column C20 Passed 96926478
Smoke Compartment Basement Building D By Column C22 Passed 96926479
Smoke Compartment Basement Building D By Column C24 Passed 96926480
Smoke Compartment Basement Building D By Column C26 Passed 96926472
Smoke Compartment Basement Building D By Column C4 Passed 96926446
Smoke Compartment Basement Building D By Column C6 Passed 96926447
Smoke Compartment Basement Building D By Column E13 Passed 96926467
Smoke Compartment Basement Building D By Column E4 Passed 96926448
Smoke Compartment Basement Building D By Room D002 Passed 96926473
Smoke Compartment Basement Building D By Room D006 Passed 96926470
Smoke Compartment Basement Building D By Room D011 Passed 96926468
Smoke Compartment Basement Building D By Room D024 Column C28
Passed 96926471
Smoke Compartment Basement Building D By Room D025 North Passed 96926476
Smoke Compartment Basement Building D By Room D025 South Passed 96926475
Smoke Compartment Basement Building D By Room T01 Passed 96926444
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926459
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926460
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926461
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926462
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926463
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926464
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926465
Smoke Compartment Basement Building D By Switch Gear Room Passed 96926466
Smoke Compartment Basement Building D By Transformer Room Passed 96926451
Smoke Compartment Basement Building D By Transformer Room Passed 96926452
Smoke Compartment Basement Building D By Transformer Room Passed 96926453
Smoke Compartment Basement Building D By Transformer Room Passed 96926454
Smoke Compartment Basement Building D By Transformer Room Passed 96926455
Everon 13 Download Date: 09/03/2024
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Smoke Compartment Basement Building D By Transformer Room Passed 96926456
Smoke Compartment Basement Building D By Transformer Room Passed 96926458
Smoke Compartment Basement Building D By Transformer Room Passed 96926457
Elevator Recall Basement Building D Elevator Lobby 51-52 Passed 96926395
Elevator Recall Basement Building D Elevator Lobby 55 Passed 96926667
Elevator Recall Basement Building D Elevator Lobby 56 Passed 96926663
Smoke Compartment 1st Building D By Column B18 Passed 96926482
Smoke Compartment 1st Building D By Column B20 Passed 96926483
Smoke Compartment 1st Building D By Column B22 Passed 96926484
Smoke Compartment 1st Building D By Column B24 Passed 96926485
Smoke Compartment 1st Building D By Column B28 Passed 96926486
Smoke Compartment 1st Building D By Column B30 Passed 96926503
Smoke Compartment 1st Building D By Column C04 Passed 96926495
Smoke Compartment 1st Building D By Column D18 Passed 96926497
Smoke Compartment 1st Building D By Column D20 Passed 96926496
Smoke Compartment 1st Building D By Column D22 Passed 96926498
Smoke Compartment 1st Building D By Column D26 Passed 96926499
Smoke Compartment 1st Building D By Column E04 Passed 96926492
Smoke Compartment 1st Building D By Column E06 Passed 96926491
Smoke Compartment 1st Building D By Column E09 Passed 96926490
Smoke Compartment 1st Building D By Column E11 Passed 96926489
Smoke Compartment 1st Building D By Column E13 Passed 96926488
Smoke Compartment 1st Building D By Column E15 Passed 96926487
Smoke Compartment 1st Building D By Men's Room T413 Passed 96926494
Smoke Compartment 1st Building D By Mourge Offices Passed 96926500
Smoke Compartment 1st Building D By Room D130 Passed 96926507
Smoke Compartment 1st Building D By Room D156 Passed 96926505
Smoke Compartment 1st Building D By Room D156 Passed 96926506
Smoke Compartment 1st Building D By Room L123 North Passed 96926502
Smoke Compartment 1st Building D By Room L123 South Passed 96926501
Smoke Compartment 1st Building D By Room T12 Passed 96926504
Smoke Compartment 1st Building D By Women's Room T411 Passed 96926493
Elevator Recall 1st Building D Elevator Lobby 51-52 Passed 96926394
Elevator Recall 1st Building D Elevator Lobby 55 Passed 96926666
Elevator Recall 1st Building D Elevator Lobby 56 Passed 96926662
Smoke Compartment 2nd Building D By Column 11 Passed 96926407
Smoke Compartment 2nd Building D By Column 14 Passed 96926408
Smoke Compartment 2nd Building D By Column 14 Passed 96926434
Smoke Compartment 2nd Building D By Column 16 Passed 96926409
Smoke Compartment 2nd Building D By Column 18 Passed 96926410
Smoke Compartment 2nd Building D By Column 20 Passed 96926411
Smoke Compartment 2nd Building D By Column 22 Passed 96926413
Smoke Compartment 2nd Building D By Column 24 Passed 96926414
Smoke Compartment 2nd Building D By Column 27 Passed 96926416
Smoke Compartment 2nd Building D By Column 28 Passed 96926417
Smoke Compartment 2nd Building D By Column 30 Passed 96926419
Smoke Compartment 2nd Building D By Column 30 Passed 96926425
Everon 14 Download Date: 09/03/2024
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Smoke Compartment 2nd Building D By Column 9 Passed 96926406
Smoke Compartment 2nd Building D By Column D07 Passed 96926442
Smoke Compartment 2nd Building D By Column D09 Passed 96926439
Smoke Compartment 2nd Building D By Column D11 Passed 96926438
Smoke Compartment 2nd Building D By Column D13 Passed 96926437
Smoke Compartment 2nd Building D By Column E06 Passed 96926441
Smoke Compartment 2nd Building D By Column E09 Passed 96926440
Smoke Compartment 2nd Building D By Column E11 Passed 96926436
Smoke Compartment 2nd Building D By Column E13 Passed 96926433
Smoke Compartment 2nd Building D By Column E13 Passed 96926435
Smoke Compartment 2nd Building D By Column E19 Passed 96926431
Smoke Compartment 2nd Building D By Column E21 Passed 96926430
Smoke Compartment 2nd Building D By Column E23 Passed 96926427
Smoke Compartment 2nd Building D By Column E23 Passed 96926429
Smoke Compartment 2nd Building D By Column E25 Passed 96926426
Smoke Compartment 2nd Building D By Column E28 Passed 96926424
Smoke Compartment 2nd Building D By Column E30 Passed 96926420
Smoke Compartment 2nd Building D By Lunch Room Passed 96926400
Smoke Compartment 2nd Building D By Lunch Room Passed 96926401
Smoke Compartment 2nd Building D By Men's Locker Room T23 Passed 96926428
Smoke Compartment 2nd Building D By Men's Locker Room T24 Passed 96926415
Smoke Compartment 2nd Building D By Men's Room T21 Passed 96926405
Smoke Compartment 2nd Building D By Room D207 Passed 96926412
Smoke Compartment 2nd Building D By Room D211 Passed 96926402
Smoke Compartment 2nd Building D By Room D219 Passed 96926423
Smoke Compartment 2nd Building D By Room D222A Passed 96926403
Smoke Compartment 2nd Building D By Room D231 Passed 96926422
Smoke Compartment 2nd Building D By Room D232 Passed 96926421
Smoke Compartment 2nd Building D By Women's Room T25 Passed 96926404
Elevator Recall 2nd Building D Elevator Lobby 51-52 Passed 96926393
Elevator Recall 2nd Building D Elevator Lobby 55 Passed 96926665
Elevator Recall 2nd Building D Elevator Lobby 56 Passed 96926661
Elevator Recall 3rd Building D Elevator Hoistway 55 Passed 96926668
Elevator Recall 3rd Building D Elevator Machine Room 51-52 Passed 96926391
Elevator Recall 3rd Building D Elevator Machine Room 51-52 Passed 96926392
Elevator Recall 3rd Building D Elevator Machine Room 51-52 Passed 96926398
Elevator Recall 3rd Building D Elevator Machine Room 55 Passed 96926664
Elevator Recall 3rd Building D Elevator Machine Room 56 Passed 96926399
Elevator Recall 3rd Building D Elevator Machine Room 56 Passed 96926660
Smoke Detector
Smoke Compartment 2nd Building D By Column 30 Damaged/Worn 96926418
Smoke Compartment 2nd Building D By Room 5D-211 Failed Operation 96926443
Everon 15 Download Date: 09/03/2024
Battery & Power Supply Testing
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated Ah
Rated Volts
Pre Test
Post Test
Min Ah
Tested Ah
Passed Sealed Lead Acid Basement Room D-002 40 12
Sealed Lead Acid Basement Room D-002 40 12
Sealed Lead Acid Basement Stair 1 18 12
Sealed Lead Acid Basement Stair 1 18 12
Sealed Lead Acid Basement Stair 3 18 12
Sealed Lead Acid Basement Stair 3 18 12
Sealed Lead Acid 1st By Stair 1 18 12
Sealed Lead Acid 1st By Stair 1 18 12
Sealed Lead Acid 1st By Stair 3 40 12
Sealed Lead Acid 1st By Stair 3 40 12
Sealed Lead Acid 1st By Stair 3 18 12
Sealed Lead Acid 1st By Stair 3 18 12
Sealed Lead Acid 2nd By Cafeteria 18 12
Sealed Lead Acid 2nd By Cafeteria 18 12
Sealed Lead Acid 2nd Outside Cafeteria 40 12
Sealed Lead Acid 2nd Outside Cafeteria 40 12
Sealed Lead Acid 2nd Room D-231 40 12
Sealed Lead Acid 2nd Room D-231 40 12
Sealed Lead Acid 2nd Stair 3 18 12
Sealed Lead Acid 2nd Stair 3 18 12
Sealed Lead Acid 3rd By Stair 3 18 12
Sealed Lead Acid 3rd By Stair 3 18 12
Everon 16 Download Date: 09/03/2024
Inventory & Warranty Report
Building: GPO Building D Control Panel: 1
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Amplifier Control 6.36% 14
Battery Control 10.00% 22
Duct Detector Initiating 1.36% 3
Expander Panel Control 3.18% 7
Horn/Strobe Indicating 0.45% 1
Phone Station Control 7.27% 16
Pull Station Initiating 10.00% 22
Smoke Detector Initiating 56.82% 125
Speaker Indicating 2.27% 5
Strobe Indicating 2.27% 5
Type Qty Model # Description Install Date
New (under 90 days)
Edwards
Horn/Strobe 1 EG1RF-CVM
08/08/2024
Speaker 5 5552-15W-R Cone Type 08/08/2024
Strobe 5 CS405-7A-T
08/08/2024
Smoke Detector 5 SIGA-PS
08/01/2024
Smoke Detector 120 SIGA-PS Photoelectric 08/01/2024
Phone Station 16
07/31/2024
Est
Amplifier 14 1B3250 Bulk 07/31/2024
Est 3
Expander Panel 7 3-CPU
07/31/2024
In Service - 1 Year to 2 Years
Power-Sonic
Battery 8 PS-12400 NB Sealed Lead Acid 07/03/2023
In Service - 2 Years to 3 Years
Est
Duct Detector 3 Siga-278 Photoelectric 02/01/2022
Pull Station 2 Siga- Dual Action 02/01/2022
Pull Station 20 Siga-278 Dual Action 02/01/2022
Power-Sonic
Battery 10 PS-1218 NB Sealed Lead Acid 02/01/2022
Battery 4 PS-1218 NB Sealed Lead Acid 01/03/2022
Everon 17 Download Date: 09/03/2024
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Zone/Circuit: 105 02-02-0001 Smoke Detector Basement Building D By Room D002 Photoelectric 96926473 02-02-0002 Smoke Detector Basement Building D By Column E4 Photoelectric 96926448 02-02-0004 Smoke Detector Basement Building D By Column E9 96926449 02-02-0005 Smoke Detector Basement Building D By Column E9 96926450 02-02-0006 Smoke Detector Basement Building D By Room D006 Photoelectric 96926470 02-02-0007 Smoke Detector Basement Building D By Room D009 96926469 02-02-0008 Smoke Detector Basement Building D By Room D011 Photoelectric 96926468 02-02-0009 Smoke Detector Basement Building D By Column E13 Photoelectric 96926467 02-02-0011 Smoke Detector Basement Building D By Column C15 Photoelectric 96926474 02-02-0013 Smoke Detector Basement Building D By Switch Gear
Room Photoelectric 96926459
02-02-0014 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926461
02-02-0015 Smoke Detector Basement Building D By Column C6 Photoelectric 96926447 02-02-0016 Smoke Detector Basement Building D By Column C4 Photoelectric 96926446 02-02-0017 Smoke Detector Basement Building D By Column C2 Photoelectric 96926445 02-02-0018 Smoke Detector Basement Building D By Room T01 Photoelectric 96926444 02-02-0019 Smoke Detector Basement Building D By Switch Gear
Room Photoelectric 96926462
02-02-0020 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926463
02-02-0021 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926464
02-02-0022 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926465
02-02-0023 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926466
02-02-0024 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926452
02-02-0025 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926453
02-02-0026 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926454
02-02-0027 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926455
02-02-0028 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926456
02-02-0029 Smoke Detector Basement Building D By Transformer Room
Photoelectric 96926457
02-02-0030 Smoke Detector Basement Building D By Transformer Photoelectric 96926458
Everon 18 Download Date: 09/03/2024
Room 02-02-0031 Smoke Detector Basement Building D By Transformer
Room Photoelectric 96926451
02-02-0061 Smoke Detector Basement Building D By Switch Gear Room
Photoelectric 96926460
L2D003 Smoke Detector Sub-Basement Building D Elevator Lobby 51-52
Photoelectric 96926396
L2D032 Smoke Detector Basement Building D Elevator Lobby 51-52
Photoelectric 96926395
L2D134 Pull Station Basement By Column 15 Dual Action 64971709 L2D135 Pull Station Basement By Stair 2 Dual Action 64971710 L2D136 Pull Station Basement By Stair 1 Dual Action 64971711
Zone/Circuit: 106 09-02-0003 Smoke Detector Basement Building D By Room D025
North Photoelectric 96926476
09-02-0004 Smoke Detector Basement Building D By Room D025 South
Photoelectric 96926475
09-02-0005 Smoke Detector Basement Building D By Room D024 Column C28
Photoelectric 96926471
09-02-0006 Smoke Detector Basement Building D By Column C26 Photoelectric 96926472 09-02-0007 Smoke Detector Basement Building D By Column C24 Photoelectric 96926480 09-02-0008 Smoke Detector Basement Building D By Column C22 Photoelectric 96926479 09-02-0009 Smoke Detector Basement Building D By Column C20 Photoelectric 96926478 09-02-0010 Smoke Detector Basement Building D By Column C18 Photoelectric 96926477
L2D015 Smoke Detector Basement Building D Elevator Lobby 56 Photoelectric 96926663 L2D019 Smoke Detector Basement Building D Elevator Lobby 55 Photoelectric 96926667 L2D125 Pull Station Basement Stair 4 Dual Action 64971836 L2D134 Pull Station Basement Stair 3 Dual Action 64971835
Zone/Circuit: 107 03-02-0001 Smoke Detector 1st Building D By Column E04 Photoelectric 96926492 03-02-0002 Smoke Detector 1st Building D By Column E06 Photoelectric 96926491 03-02-0003 Smoke Detector 1st Building D By Column E09 Photoelectric 96926490 03-02-0004 Smoke Detector 1st Building D By Column E11 Photoelectric 96926489 03-02-0005 Smoke Detector 1st Building D By Column E13 Photoelectric 96926488 03-02-0006 Smoke Detector 1st Building D By Column E15 Photoelectric 96926487 03-02-0007 Smoke Detector 1st Building D By Room D130 Photoelectric 96926507 03-02-0012 Smoke Detector 1st Building D By Column C04 Photoelectric 96926495 03-02-0013 Smoke Detector 1st Building D By Men's Room T413 Photoelectric 96926494 03-02-0014 Smoke Detector 1st Building D By Women's Room T411 Photoelectric 96926493 03-02-0015 Smoke Detector 1st Building D By Room D156 Photoelectric 96926506 03-02-0016 Smoke Detector 1st Building D By Room D156 Photoelectric 96926505
L2D017 Smoke Detector 1st Building D Elevator Lobby 51-52 Photoelectric 96926394 L2D135 Pull Station 1st By Stair 1 Dual Action 64971967
Zone/Circuit: 108 08-02-0001 Smoke Detector 1st Building D By Column D26 Photoelectric 96926499 08-02-0002 Smoke Detector 1st Building D By Mourge Offices Photoelectric 96926500 08-02-0004 Smoke Detector 1st Building D By Room L123 North Photoelectric 96926502 08-02-0005 Smoke Detector 1st Building D By Room L123 South Photoelectric 96926501 08-02-0006 Smoke Detector 1st Building D By Column B30 Photoelectric 96926503 08-02-0007 Smoke Detector 1st Building D By Column B28 Photoelectric 96926486 08-02-0009 Smoke Detector 1st Building D By Column B24 Photoelectric 96926485 08-02-0010 Smoke Detector 1st Building D By Room T12 Photoelectric 96926504
Everon 19 Download Date: 09/03/2024
08-02-0011 Smoke Detector 1st Building D By Column B22 Photoelectric 96926484 08-02-0013 Smoke Detector 1st Building D By Column B20 Photoelectric 96926483 08-02-0014 Smoke Detector 1st Building D By Column B18 Photoelectric 96926482 08-02-0015 Smoke Detector 1st Building D By Column D18 Photoelectric 96926497 08-02-0016 Smoke Detector 1st Building D By Column D20 Photoelectric 96926496 08-02-0017 Smoke Detector 1st Building D By Column D22 Photoelectric 96926498
L2D003 Smoke Detector 1st Building D Elevator Lobby 56 Photoelectric 96926662 L2D018 Smoke Detector 1st Building D Elevator Lobby 55 Photoelectric 96926666 L2D135 Pull Station 1st Loading Dock Dual Action 64971979 L2D136 Pull Station 1st By Stair 4 Dual Action 64971978 L2D136 Pull Station 1st Stair 2 Dual Action 64971980 L2D137 Pull Station 1st By Column 1D16 Dual Action 64971968
Zone/Circuit: 109 04-02-0001 Smoke Detector 2nd Building D By Lunch Room Photoelectric 96926400 04-02-0002 Smoke Detector 2nd Building D By Lunch Room Photoelectric 96926401 04-02-0004 Smoke Detector 2nd Building D By Room D211 Photoelectric 96926402 04-02-0005 Smoke Detector 2nd Building D By Room D222A Photoelectric 96926403 04-02-0007 Smoke Detector 2nd Building D By Women's Room T25 Photoelectric 96926404 04-02-0008 Smoke Detector 2nd Building D By Men's Room T21 Photoelectric 96926405 04-02-0009 Smoke Detector 2nd Building D By Column D07 Photoelectric 96926442 04-02-0010 Smoke Detector 2nd Building D By Column E06 Photoelectric 96926441 04-02-0012 Smoke Detector 2nd Building D By Column E09 Photoelectric 96926440 04-02-0013 Smoke Detector 2nd Building D By Column E11 Photoelectric 96926436 04-02-0014 Smoke Detector 2nd Building D By Column E13 Photoelectric 96926435 04-02-0016 Smoke Detector 2nd Building D By Column D13 Photoelectric 96926437 04-02-0017 Smoke Detector 2nd Building D By Column D11 Photoelectric 96926438 04-02-0018 Smoke Detector 2nd Building D By Column D09 Photoelectric 96926439 04-02-0019 Smoke Detector 2nd Building D By Column 9 Photoelectric 96926406 04-02-0020 Smoke Detector 2nd Building D By Column 11 Photoelectric 96926407 04-02-0021 Smoke Detector 2nd Building D By Column 14 Photoelectric 96926408 04-02-0022 Smoke Detector 2nd Building D By Column E13 Photoelectric 96926433 04-02-0023 Smoke Detector 2nd Building D By Column 14 Photoelectric 96926434
L2D024 Smoke Detector 2nd Building D Elevator Lobby 51-52 Photoelectric 96926393 L2D134 Pull Station 2nd Stair 2 Dual Action 64971776 L2D136 Pull Station 1st Stair 1 Dual Action 64971804
Zone/Circuit: 110 01-02-0006 Smoke Detector 2nd Building D By Column 24 Photoelectric 96926414 07-02-0001 Smoke Detector 2nd Building D By Column E17 96926432 07-02-0002 Smoke Detector 2nd Building D By Column E19 Photoelectric 96926431 07-02-0003 Smoke Detector 2nd Building D By Column E21 Photoelectric 96926430 07-02-0004 Smoke Detector 2nd Building D By Column E23 Photoelectric 96926429 07-02-0005 Smoke Detector 2nd Building D By Men's Locker Room
T23 Photoelectric 96926428
07-02-0007 Smoke Detector 2nd Building D By Column 22 Photoelectric 96926413 07-02-0009 Smoke Detector 2nd Building D By Room D207 Photoelectric 96926412 07-02-0010 Smoke Detector 2nd Building D By Column 20 Photoelectric 96926411 07-02-0011 Smoke Detector 2nd Building D By Column 18 Photoelectric 96926410 07-02-0012 Smoke Detector 2nd Building D By Column 16 Photoelectric 96926409 07-02-0013 Smoke Detector 2nd Building D By Column E23 Photoelectric 96926427 07-02-0014 Smoke Detector 2nd Building D By Column E25 Photoelectric 96926426 07-02-0015 Smoke Detector 2nd Building D By Room D219 Photoelectric 96926423 07-02-0016 Smoke Detector 2nd Building D By Room D231 Photoelectric 96926422
Everon 20 Download Date: 09/03/2024
07-02-0017 Smoke Detector 2nd Building D By Column E28 Photoelectric 96926424 07-02-0018 Smoke Detector 2nd Building D By Room D232 Photoelectric 96926421 07-02-0019 Smoke Detector 2nd Building D By Column 30 Photoelectric 96926425 07-02-0020 Smoke Detector 2nd Building D By Column 30 Photoelectric 96926418 07-02-0021 Smoke Detector 2nd Building D By Column 28 Photoelectric 96926417 07-02-0022 Smoke Detector 2nd Building D By Column 27 Photoelectric 96926416 07-02-0023 Smoke Detector 2nd Building D By Men's Locker Room
T24 Photoelectric 96926415
07-02-0024 Smoke Detector 2nd Building D By Column E30 Photoelectric 96926420 07-02-0025 Smoke Detector 2nd Building D By Column 30 Photoelectric 96926419
L2D026 Duct Detector 2nd AHU 2 By Men Restroom Photoelectric 64971800 L2D027 Duct Detector 2nd AHU 1 Photoelectric 64971778 L2D028 Duct Detector 2nd AHU 3 By Room D-231 Photoelectric 64971775 L2D029 Smoke Detector 2nd Building D Elevator Lobby 56 Photoelectric 96926661 L2D030 Smoke Detector 2nd Building D Elevator Lobby 55 Photoelectric 96926665 L2D134 Pull Station 2nd Stair 3 Dual Action 64971789 L2D135 Pull Station 2nd Stair 1 Dual Action 64971769 L2D135 Pull Station 2nd Stair 3 Dual Action 64971779 L2D136 Pull Station 2nd Column C-16 Dual Action 64971801
Zone/Circuit: 111 L2D015 Smoke Detector 3rd Building D Elevator Machine Room
51-52 Photoelectric 96926392
L2D019 Smoke Detector 3rd Building D Elevator Machine Room 51-52
Photoelectric 96926391
L2D021 Smoke Detector 3rd Building D Elevator Machine Room 51-52
Photoelectric 96926398
L2D022 Smoke Detector 3rd Building D EMR 51-52 96926397 L2D126 Pull Station 3rd Stair 1 Dual Action 64971805 L2D127 Pull Station 3rd Stair 2 Dual Action 64971834 L2D138 Pull Station 3rd Between Stair 1 And Stair 3 Dual Action 64971828
Zone/Circuit: 112 L2D001 Smoke Detector 3rd Building D Elevator Machine Room
Photoelectric 96926664
L2D002 Smoke Detector 3rd Building D Elevator Machine Room
Photoelectric 96926660
L2D021 Smoke Detector 3rd Building D Elevator Machine Room
Photoelectric 96926399
L2D022 Smoke Detector 3rd Building D Elevator Hoistway 55 Photoelectric 96926668 L2D134 Pull Station 3rd Stair 3 Dual Action 64971832 L2D135 Pull Station 3rd Stair 4 Dual Action 64971833