Technical Design Guideline 17180

View the file

Other files for this federal contract opportunity

Other files attached to MDC Guaynabo - Upgrade Control Center, newest first.
File Type Posted
Bid Results.pdf PDF
Amendment 5.pdf PDF
Amendment 4.pdf PDF
Final Questions and Answers.pdf PDF
17100.pdf PDF
17200.pdf PDF
17260.pdf PDF
Amendment 3.pdf PDF
17020.pdf PDF
17050.pdf PDF
17040.pdf PDF
scan0020.pdf PDF
MDC Guaynabo - Upgrade Control Center Site Visit Meeting Minutes.pdf PDF
17300.pdf PDF
17220.pdf PDF
Amendment 1.pdf PDF
17165.pdf PDF
17120.pdf PDF
17900.pdf PDF
C - Attachment 1 —
E - Attachment 3 —
F - Attachment 4 —
A - Cover Letter.pdf PDF
B - Solicitation.pdf PDF
D - Attachment 2 —
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FBOP TECHNICAL DESIGN GUIDELINES ISSUE DATE: SEPTEMBER 29, 2005

SENSITIVE - LOU

DOOR CONTROL SYSTEMS 17180-1

SECTION 17180 - DOOR CONTROL SYSTEMS

PART 1 - GENERAL

1.1

SUMMARY

A.

This section covers the door control system as shown on the drawings or as required to support the systems defined in these specifications. The work under this section consists of furnishing materials and equipment, performing labor and services necessary for the installation of the door control system required for the security electronics, communications, and fire alarm system.

B.

Related Work Specified Elsewhere: Refer to all other Division 17 specification sections and drawings, and to the specifications and drawings under the General

Construction Contract to ascertain the extent of work included.

1.2

SUBMITTALS

A.

Since the Division 17 systems must be reviewed by the Contracting Officer as a system, no individual, specific submittal shall be made for this section.

Submittals shall be packaged in groups and shall be made in accordance with the General Provisions (Section 17000) of these specifications.

B.

When making the submittal as required by Section 17000, include this additional information.

1.

Submit hardwired relay interlock wiring diagrams, where applicable.

2.

Submit wiring diagram of door relay interface boards, if utilized.

1.3

REFERENCES AND/OR CODES:

A.

National Electrical Code

1.4

COORDINATION:

A.

Coordinate with specific hardware used by Division 8 and Division 11 for security hardware and builders hardware to ensure that the specified hardware can perform the functions and operations required by this section, Section 17100 and Section 17170. Provide written notification to the Contracting Officer of any discrepancy between the Division 17 requirements and the Division 8 and

Division 11 electric door hardware requirements.

B.

Coordinate with Division 8 and Division 11 to ensure that a fully open signal is provided at all sliding doors and gates.

1.5

SYSTEMS DESCRIPTION:

A.

Door control system shall be controlled by the Central Control Programmable

Logic Controller which shall accept the various inputs from systems being interfaced with door control, cause operation as described in this Section and

DOOR CONTROL SYSTEMS 17180-2

elsewhere in the documents and provide outputs to the various systems.

Electrically operated doors are listed in the schedule in this Section. This schedule indicates the type of door hardware and the electrical interlocks.

B.

Definitions: The following definitions of functions or indications shall apply to the descriptions contained herein.

1.

"Secure" The door is closed and locked. This is effected by monitoring the deadlock switch and the door position switch.

2.

"Open" The door is not "Secure".

3.

"Fully Open" The door is in the fully open position and is not "Secure".

This is effected by monitoring the a dedicated limit switch in the sliding door hardware.

4.

"Locked" The status of a locking device when the roller bolt is retracted and the latch bolt is fully extended. The device will not be locked until the door is closed.

5.

"Unlocked" The status of a locking device when the latch bolt is partially or fully retracted.

6.

"Lock" Control power is applied to or removed from, the locking device as required to effect a "locked" mode. The nature of the locking signal or sequence is determined by the specific locking device.

7.

"Unlock" Control power is applied to the locking device to place the device in an "unlocked" mode. Control may be by momentary or continuous application of power as dictated by the locking device.

8.

"Interlock" Interlocked doors will be electrically controlled so that only a single door in the interlock group can be opened at one time.

C.

Door Control System Functional Description:

1.

The control and monitoring functions of all electrically operated and or monitored doors and gates shall be initiated or interpreted by the

Programmable Logic Controllers.

2.

All doors and gates shall be locally controlled via door control relays.

The relays shall be of the types, sizes, and ratings required for compatibility with applicable door hardware sets. Door control relays shall be mounted in Security & Communications Cabinets (SCC).

3.

All door control relays shall be activated from the PLC output modules.

4.

For a controlled swing door, the door position and the dead lock switches shall be monitored via discrete inputs to the PLC input modules. For a monitored or alarmed swing door, the door position and bolt position switches shall be monitored via discrete inputs to the PLC input modules.

DOOR CONTROL SYSTEMS 17180-3

There shall be two inputs for each door. The PLC shall monitor both inputs to determine if the door is secure or non-secure.

5.

All of the monitoring circuits shall be closed when the door is secure.

Where interposing relays are used to separate Class 1 from Class 2 monitoring circuits the relays shall be wired so that the contacts that are monitored by the PLC are closed only when the door is secure.

D.

Type A - Swing Door and Swing Gate:

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 - CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

E.

Type B - Monitored Door:

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 - CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

2.

The Armory Pass Through Door shall also have an associated strobe light above the Armory entrance door inside the Armory to reduce the possibility of the Armory Pass Through Door remaining open and unattended. While the Armory Pass Through Door is not secure, the strobe light shall be activated.

F.

Type C - Vehicle Gate:

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

G.

Type D - Sliding Door

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

H.

Type E - Alarmed Door

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 - CONTROL PANEL OPERATION. and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

DOOR CONTROL SYSTEMS 17180-4

I.

Type F - Daytime Door:

1.

This door has a half cycle lock with a door position switch.

2.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 - CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

J.

Type G - Monitored Door with Audio and Video Communications

1.

Control panel/touch screen controls and indicators shall be provided as described in SECTION 17100 CONTROL PANEL OPERATION and

SECTION 17170 - SECURITY MONITORING AND CONTROL

SYSTEM.

K.

Interlock:

1.

Function:

a.

The combination of the dead lock switch and the door position indicator switch controls an interlock with the control panel/touch screen. When the door is in the unlocked or open position, the door control logic circuits shall inhibit any other door in the interlock group from being unlocked or opened. The interlock shall not prevent a door from being closed or relocked.

In addition, to prevent the simultaneous operation of the door locks when the switches are operated simultaneously, the other outputs in the interlock group shall be inhibited when an unlock output is activated. See Table 17180-3 for the interlocked door schedule.

b.

The interlock function for facility perimeter doors and gates shall be affected with hardwired relay logic and software logic. All other interlocks shall be affected by software interlocks only.

L.

Door Bell System

1.

Where indicated in Part 3 - EXECUTION, a door bell system consisting of a push button, door bell, and power supply shall be provided.

2.

The door bell shall be activated when the push button is depressed. The bell shall sound for three seconds followed by a 15 seconds lock out period. After the 15 second lock out period, the door bell shall be ready to respond to subsequent activations.

DOOR CONTROL SYSTEMS 17180-5

PART 2 - PRODUCTS

2.1

PROGRAMMABLE LOGIC CONTROLLERS:

A.

Refer to Section 17165 - Programmable logic controllers for programmable logic controller (PLC) requirements.

B.

Multiplexed relay cards shall not be permitted to interface the door relays to the

PLC. Passive relay boards with connectorized wiring to the PLC output cards with multipin connectors shall be permitted. Relay boards shall have removable connector blocks for door wiring connections, integral door power fuses, and pluggable relays. A minimum of three spare relay boards of each type used shall be provided. Door control board shall be UL listed.

2.2

CONDUCTORS:

A.

All Conductors from "SCC" to door locks shall be minimum 14 Ga. copper

THWN. All Conductors from "SCC" to door position switches and bolt position switches shall be minimum 14 Ga. copper THWN. Number of conductors shall be installed as required to provide the control and monitoring functions specified in Divisions 8, 11, or 17.

B.

Provide a ground wire to all locks.

C.

Refer to Section 17020 for additional requirements.

2.3

INTERPOSING AND INTERLOCK LOGIC RELAYS

A.

Interposing Relays: Relays for door lock control shall be electro-mechanical plug-in type. AC or DC types shall be selected as appropriate for the application.

Each door lock power circuit shall be individually fuse protected for each door to isolate shorted circuits. DC relays shall be provided with diodes across the coil for transient suppression.

B.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering Products that may be incorporated in the Work include, but are not limited to, the following:

1.

Potter & Brumfield

2.

Struthers-Dunn

3.

Square D

4.

Allen Bradley

2.4

STROBE LIGHT

A.

Strobe light shall be low power xenon flash tube with not less than one strobe per second and minimum of 20,000 peak candle power. Provide power supply as required.

DOOR CONTROL SYSTEMS 17180-6

2.5

DOOR BELL SYSTEM

A.

A door bell system shall be provided where indicated in Part - 3 EXECUTION consisting of the following:

1.

Door Bell: EST Model 340A or approved equal. Unit shall be 24VAC and have adjustable volume control with maximum volume of at least

70dB at 3 meters. Provide with tamper-proof hardware and 14 gauge steel grill painted white. Unit shall be completely flush mounted.

2.

Push button: Push button switch shall be flush mounted, security type installed in locations shown on the drawings. Faceplate shall be 11 gauge stainless steel with beveled edges installed with approved security fasteners. Switch shall be momentary contact type. Switch assembly shall be Atlas/Soundolier VPB-1 or approved equal

3.

Transformer: 24VAC transformer shall be provided in the SCC cabinet and fused for each circuit.

4.

The door bell system shall be connected to and controlled by the PLC system.

2.6

POWER SUPPLIES:

A.

Provide power supplies as required to power low voltage locks.

PART 3 - EXECUTION

3.1

INSTALLATION

A.

Install all conductors and make final connections to the locking system hardware and controls as required to effect the locking and control functions defined in these specifications and those in Division 8 and Division 11.

B.

Power interruptions or power transients shall result in a fail-secure door lock status. This may be accomplished through the system hardware and software, and a UPS system.

C.

Verify that any DC solenoid loads are provided with diode transient suppression.

Coordinate with Division 11 as required.

D.

Evenly distribute electrical loads in each SCC over all three phases (where applicable) to avoid overloading one phase.

E.

Each door lock circuit shall be individually fuse protected to isolate shorted circuits.

F.

Furnish and install all panel boards, breakers, wiring, etc. to provide protected branch circuits for the required power distribution beyond the main SCC feeder furnished and installed by Division 16.

DOOR CONTROL SYSTEMS 17180-7

G.

Programmable Logic Controllers (PLC) shall be utilized to perform functions as specified.

H.

The door control requirements in the section shall be coordinated with the hardware schedules in Division 8 and Division 11. Installation of systems shall be in accordance with shop drawings for Division 8 and Division 11. If a conflict exists between information in this section and that of Division 8 and

Division 11, the discrepancy shall be brought to the attention of the Contract

Officer in writing.

I.

All locks, door position switches, and bolt monitor switches shall be wired with connectors to facilitate troubleshooting at the PLC and to facilitate replacement in the field.

J.

To permit future revision in control logic, all door control and monitoring functions shall be effected via the PLC. No direct wiring between the control switch and the interposing relay shall be permitted. No direct wiring between the door status contacts and the panel indicators shall be permitted.

3.2

INTERLOCKING

A. The facility perimeter sally ports shall have hardwired relay interlock control.

PLC software interlocking may be used in addition to the relay logic, but shall not exclude relay interlocking logic.

B. Each interlock for an electrically operated door must utilize the unlock command signal for the lock, in addition to the door secure status, to block the unlock signal to all other doors in the interlock group. This shall prevent bypassing the interlock by depressing two or more unlock or open switches at the same time.

3.3 DOOR BELL SYSTEMS

A. The door bell shall be activated when the push is depressed. The bell shall sound for three seconds followed by a 15 second lock out period. After the 15 second lock out period, the door bell shall be ready to respond to subsequent activations.

B. Provide a door bell system for the following areas:

1. General Housing Unit entrances (USP & FCI);

a. From courtyard

b. From perimeter corridor (USP only)

2. Special Housing Unit entrances (USP & FCI);

a. From Health Services

b. From outside

DOOR CONTROL SYSTEMS 17180-8

c. From Recreation yard cages

3. Food Service entrances (USP, FCI & Camp)

a. Loading Dock

b. Meat preparation

c. Vegetable preparation

d. Special Diet

e. Multi-purpose food preparation

4. Personnel services loading dock entrance (USP & FCI);

5. Maintenance services loading dock entrance (USP & FCI);

6. UNICOR - In the UNICOR factory, the door bell shall be accomplished by a strobe light to provide visual indication that the door bell has been activated. The strobe light shall be activated when the push button is depressed. The strobe light shall be illuminated for 15 seconds followed by a three second lock out period. After the three second lock out period, the strobe light shall be ready to respond to subsequent activations. (USP

& FCI only);

a. Loading dock entrance

b. Factory entrance

7. Camp Housing - dormitory entrance

3.4

COMPLETION

A. General: Upon completion of the work, remove excess debris, materials, equipment, apparatus, tools and the like and leave the premises clean, neat and orderly.

B.

Testing: The completed system shall be tested by the Contractor prior to the acceptance test.

3.5 TABLES

A. The system shall be installed in accordance with the following tables:

DOOR CONTROL SYSTEMS 17180-9

TABLE 17180-1 USP

LEGEND FOR DOOR CONTROL SCHEDULES

HARDWARE

FUNCTION = Letter designations refer to types of door control described in this

Section.

EOL

= Electrically Operated Lock Control.

DPS

= Door Position Switch and latch bolt monitor switch monitoring. Doors with electric locks shall include roller bolt monitoring.

SCC

= Security and Communications Cabinet. See security and communications drawings for cabinet locations.

Control Station = Control panel/touch screen having control or monitoring responsibility of door.

See drawings for abbreviations and locations of control panels.

Remarks:

1.

Coordinate with Division 8 and Division 11 for installation of intercom station in the door frame for indicated door.

2.

Coordinate with Division 8 and Division 11 for installation of push-button in door frame for indicated door.

3.

There is not an intercom associated with the indicated door.

4.

Indicated doors also closed by the Emergency Lockdown Function.

5.

"*" Represents housing building numbers 1, 2, 3, 4, 5, or 6 where applicable.

6.

"**" Represents tower numbers 1, 2, 3, 4, 5 or 6 where applicable.

DOOR CONTROL SYSTEMS 17180-10

TABLE 17180-2 USP

DOOR CONTROL SCHEDULE

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-002

CY-101 A X X GT7 GT7

QE-002

CY-102 A X X GT7 GT7

QE-002

CY-103 A X X GT7 GT7

QE-002

CY-104 A X X GT7 GT7

QE-002

CY-105 A X X GT7 GT7

QE-002

CY-106 A X X GT7 GT7

QE-101

H*-A114A D X X H* CC 4, 5

QE-101 H*-A114B B X H* CC 5

QE-101 H*-A162A D X X H* CC 4, 5

QE-101 H*-A162B B X H* CC 5

QE-101 H*-C114A D X X H* CC 4, 5

QE-101 H*-C114B B X H* CC 5

QE-101 H*-C162A D X X H* CC 4, 5

QE-101 H*-C162B B X H* CC 5

QE-102 H*B203 E X H* CC 5

QE-103 RE-101A D X X RE CC 4

QE-103 RE-104D D X X RE CC 4

QE-103 RE-121 E X RE CC

QE-104 EM-105D D X X EM CC 4

QE-104 EM-143 E X EM CC

QE-104 EM-160A D X X EM CC 4

QE-104 EM-1795 D X X EM CC 4

QE-105 SH-A1012A B X SH CC

QE-105 SH-A1012B D X X SH CC

QE-105 SH-D102C A X X SH CC

QE-105 SH-D104A C X X SH CC, GT1

QE-105 SH-D104B A X X SH CC, GT1

QE-105 SH-D104C D X X SH CC, GT1

QE-105 A1029 D X X SH SHD 3

QE-105 A1031 D X X SH SHD 3

QE-105 A1032 D X X SH SHD 3

QE-105 A1034 D X X SH SHD 3

QE-105 A1035 D X X SH SHD 3

QE-105 A1037 D X X SH SHD 3

QE-105 A1038 D X X SH SHD 3

QE-105 A1040 D X X SH SHD 3

QE-105 A1041 D X X SH SHD 3

QE-105 A1043 D X X SH SHD 3

QE-105 A1044 D X X SH SHD 3

QE-105 A1046 D X X SH SHD 3

QE-105 A1047 D X X SH SHD 3

QE-105 A1049 D X X SH SHD 3

QE-105 A1050 D X X SH SHD 3

QE-105 A1052 D X X SH SHD 3

TABLE 17180-2 USP

DOOR CONTROL SYSTEMS 17180-11

DOOR CONTROL SCHEDULE (Continued)

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-105

A1057 D X X SH SHE 3

QE-105 A1059 D X X SH SHE 3

QE-105 A1060 D X X SH SHE 3

QE-105 A1062 D X X SH SHE 3

QE-105 A1063 D X X SH SHE 3

QE-105 A1065 D X X SH SHE 3

QE-105 A1066 D X X SH SHE 3

QE-105 A1068 D X X SH SHE 3

QE-105 A1069 D X X SH SHE 3

QE-105 A1071 D X X SH SHE 3

QE-105 A1072 D X X SH SHE 3

QE-105 A1074 D X X SH SHE 3

QE-105 A1075 D X X SH SHE 3

QE-105 A1077 D X X SH SHE 3

QE-105 A1078 D X X SH SHE 3

QE-105 A1080 D X X SH SHE 3

QE-105 A1081 D X X SH SHE 3

QE-105 A1083 D X X SH SHE 3

QE-105 A1084 D X X SH SHE 3

QE-105 A1086 D X X SH SHE 3

QE-105 A1087 D X X SH SHE 3

QE-105 A1089 D X X SH SHE 3

QE-105 A1090 D X X SH SHE 3

QE-105 A1092 D X X SH SHE 3

QE-105 A1097 D X X SH SHF 3

QE-105 A1099 D X X SH SHF 3

QE-105 A1100 D X X SH SHF 3

QE-105 A1102 D X X SH SHF 3

QE-105 A1103 D X X SH SHF 3

QE-105 A1105 D X X SH SHF 3

QE-105 A1106 D X X SH SHF 3

QE-105 A1108 D X X SH SHF 3

QE-105 A1109 D X X SH SHF 3

QE-105 A1111 D X X SH SHF 3

QE-105 A1112 D X X SH SHF 3

QE-105 A1114 D X X SH SHF 3

QE-105 A1115 D X X SH SHF 3

QE-105 A1117 D X X SH SHF 3

QE-105 A1118 D X X SH SHF 3

QE-105 A1120 D X X SH SHF 3

QE-105 A1121 D X X SH SHF 3

QE-105 A1123 D X X SH SHF 3

QE-105 A1124 D X X SH SHF 3

QE-105 A1126 D X X SH SHF 3

QE-106 SH-A2003 E X SH CC

QE-106 A2081 D X X SH SHG 3

TABLE 17180-2 USP

DOOR CONTROL SYSTEMS 17180-12

DOOR CONTROL SCHEDULE (Continued)

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-106 A2083 D X X SH SHG 3

QE-106 A2084 D X X SH SHG 3

QE-106 A2086 D X X SH SHG 3

QE-106 A2087 D X X SH SHG 3

QE-106 A2089 D X X SH SHG 3

QE-106 A2090 D X X SH SHG 3

QE-106 A2092 D X X SH SHG 3

QE-106 A2093 D X X SH SHG 3

QE-106 A2095 D X X SH SHG 3

QE-106 A2096 D X X SH SHG 3

QE-106 A2098 D X X SH SHG 3

QE-106 A2099 D X X SH SHG 3

QE-106 A2101 D X X SH SHG 3

QE-106 A2102 D X X SH SHG 3

QE-106 A2104 D X X SH SHG 3

QE-106 A2076 D X X SH SHH 3

QE-106 A2074 D X X SH SHH 3

QE-106 A2073 D X X SH SHH 3

QE-106 A2071 D X X SH SHH 3

QE-106 A2070 D X X SH SHH 3

QE-106 A2068 D X X SH SHH 3

QE-106 A2067 D X X SH SHH 3

QE-106 A2065 D X X SH SHH 3

QE-106 A2064 D X X SH SHH 3

QE-106 A2062 D X X SH SHH 3

QE-106 A2061 D X X SH SHH 3

QE-106 A2059 D X X SH SHH 3

QE-106 A2058 D X X SH SHH 3

QE-106 A2056 D X X SH SHH 3

QE-106 A2055 D X X SH SHH 3

QE-106 A2053 D X X SH SHH 3

QE-106 A2052 D X X SH SHH 3

QE-106 A2050 D X X SH SHH 3

QE-106 A2049 D X X SH SHH 3

QE-106 A2047 D X X SH SHH 3

QE-106 A2046 D X X SH SHH 3

QE-106 A2044 D X X SH SHH 3

QE-106 A2043 D X X SH SHH 3

QE-106 A2041 D X X SH SHH 3

QE-106 A2036 D X X SH SHI 3

QE-106 A2034 D X X SH SHI 3

QE-106 A2033 D X X SH SHI 3

QE-106 A2031 D X X SH SHI 3

QE-106 A2030 D X X SH SHI 3

QE-106 A2028 D X X SH SHI 3

QE-106 A2027 D X X SH SHI 3

DOOR CONTROL SYSTEMS 17180-13

TABLE 17180-2 USP

DOOR CONTROL SCHEDULE (Continued)

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-106 A2025 D X X SH SHI 3

QE-106 A2024 D X X SH SHI 3

QE-106 A2022 D X X SH SHI 3

QE-106 A2021 D X X SH SHI 3

QE-106 A2019 D X X SH SHI 3

QE-106 A2018 D X X SH SHI 3

QE-106 A2016 D X X SH SHI 3

QE-106 A2015 D X X SH SHI 3

QE-106 A2013 D X X SH SHI 3

QE-106 A2012 D X X SH SHI 3

QE-106 A2010 D X X SH SHI 3

QE-106 A2009 D X X SH SHI 3

QE-106 A2007 D X X SH SHI 3

QE-107 AI-1000A E X SH CC

QE-107 AI-B169A A X X SH CC

QE-107 AI-B170A A X X SH CC

QE-107 AI-D102B D X X SH CC 4

QE-108 AI-101D D X X AI CC 4

QE-108 AI-B101 D X X AI CC 4

QE-108 AI-B114 E X AI CC

QE-108 AI-B126A D X X AI CC

QE-108 AI-B126B D X X AI CC

QE-108 AI-B126C F X X AI CC

QE-108 AI-D101A D X X AI CC 4

QE-108 AI-D102A D X X AI CC 4

QE-109 FS-D101B D X X MS CC 4

QE-110 MS-E101A D X X MS CC 4

QE-110 MS-E101B D X X MS CC 4

QE-110 MS-E114 E X MS CC

QE-111 UF-108B G X UF CC

QE-111 UF-108C G X UF CC

QE-111 UF-108E D X X UF CC 4

QE-111 UF-108F D X X UF CC 4

QE-111 UF-F101A D X X UF CC 4

QE-111 UF-F121 E X UF CC

QE-113 SC-102D D X X H2 CC

QE-113 SC-103D D X X H2 CC

QE-113 SC-106D D X X H2 CC

QE-113 SC-107D D X X H2 CC

QE-114 GT**-101 A X X GT** GT** 6

QE-114 GT**-102 E X GT** CC 6

QE-114 GT7-101 A X X GT7 CC, GT3

QE-114 GT7-102 E X GT7 CC

QE-114 GT7-103 A X X GT7 CC, GT7

QE-114 GT7-104 A X X GT7 GT7

QE-120 AO-101A F X X AO CC 2

QE-120 AO-121 A X X AO CC

DOOR CONTROL SYSTEMS 17180-14

TABLE 17180-2 USP

DOOR CONTROL SCHEDULE (Continued)

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-120 AO-124A B X AO CC

QE-120 AO-124B B X AO CC

QE-120 AO-124C B X AO CC

QE-120 AO-147 B X AO CC

QE-120 AO-148 A X X AO CC

QE-120 AO-150A B X AO CC

QE-120 AO-151A D X X AO CC

QE-120 AO-151B D X X AO CC

QE-120 GL1 A X X AO CC

QE-122 UP-104 E X UP CC

QE-123 MW-A118 E X MW CC

QE-125 LG-113 E X LG CC

QE-127 CC-112 E X CC CC

QE-128 CH-116 E X CH CC

QE-500 VSP-1 A X X GT1 CC, GT1

QE-500 VSP-2 C X X GT1 CC, GT1

QE-500 VSP-3 C X X GT1 CC, GT1

QE-500 VSP-4 A X X GT1 CC, GT1

QE-500 GL2 A X X GT1 CC, GT1

DOOR CONTROL SYSTEMS 17180-15

INTERLOCK SCHEDULE

TABLE 17180-3 USP

IL TYPE

SHEET # GROUP # SW/HW DESCRIPTION DOORS

QE-101

1 SW GENERAL HOUSING 1A H1-A162A, H1-A114A

QE-101 2 SW GENERAL HOUSING 1B H1-C162A, H1-C114A

QE-101 3 SW GENERAL HOUSING 2A H2-A162A, H2-A114A

QE-101 4 SW GENERAL HOUSING 2B H2-C162A, H2-C114A

QE-101 5 SW GENERAL HOUSING 3A H3-A162A, H3-A114A

QE-101 6 SW GENERAL HOUSING 3B H3-C162A, H3-C114A

QE-101 7 SW GENERAL HOUSING 4A H4-A162A, H4-A114A

QE-101 8 SW GENERAL HOUSING 4B H4-C162A, H4-C114A

QE-101 9 SW GENERAL HOUSING 5A H5-A162A, H5-A114A

QE-101 10 SW GENERAL HOUSING 5B H5-C162A, H5-C114A

QE-101 11 SW GENERAL HOUSING 6A H6-A162A, H6-A114A

QE-101 12 SW GENERAL HOUSING 6B H6-C162A, H6-C114A

QE-105 13 SW SHU SALLYPORT SH-A1012A, SH-A1012B

QE-105 14 SW BUS SALLYPORT SH-D104A, SH-D104C

QE-105 15 SW BUS SALLYPORT SH-D104B, SH-D104C

QE-107 16 SW RECIVING SALLYPORT AI-B169A, AI-A1000A,

AI-B170A

QE-108 17 SW VISITING SALLYPORT AI-B126A, AI-B126B, AI-

B126C.

QE-111 18 SW EMER. VEH. PASS UF-108B, UF-108E

QE-111 19 SW EMER. VEH. PASS UF-108B, UF-108F

QE-111 20 SW EMER. VEH. PASS UF-108C, UF-108E

QE-111 21 SW EMER. VEH. PASS UF-108C, UF-108F

QE-114 22 SW COMPOUND TOWER GT7-101, GT7-103

QE-120 23 HW MAIN SALLYPORT AO-151A, AO-151B

QE-120 24 SW CENTRAL CONTROL AO-147, AO-150A, AO-

QE-120 25 SW SQUAD ROOM AO-121, AO-124C

QE-500 26 HW VEHICLE SALLYPORT VSP-1, VSP-2, VSP-3,

VSP-4

LEGEND:

HW - Hardwired interlock required.

SW - Software interlock. Hardwired interlock optional.

NOTES:

1) None.

DOOR CONTROL SYSTEMS 17180-16

TABLE 17180-1 FCI

LEGEND FOR DOOR CONTROL SCHEDULES

HARDWARE

FUNCTION = Letter designations refer to types of door control described in this

Section.

EOL

= Electrically Operated Lock Control.

DPS

= Door Position Switch and latch bolt monitor switch monitoring. Doors with electric locks shall include roller bolt monitoring.

SCC

= Security and Communications Cabinet. See security and communications drawings for cabinet locations.

Control Station = Control panel/touch screen having control or monitoring responsibility of door.

See drawings for abbreviations and locations of control panels.

Remarks:

1.

Coordinate with Division 8 and Division 11 for installation of intercom station in the door frame for indicated door.

2.

Coordinate with Division 8 and Division 11 for installation of pushbutton in door frame for indicated door.

3.

'*' Represents housing units 1, 2, and 3.

DOOR CONTROL SYSTEMS 17180-17

TABLE 17180-2 FCI

DOOR CONTROL SCHEDULE

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

QE-102

H*-144 E X H* CC 3

QE-105 AI129 D X X AI CC

QE-105 AI106 E X AI CC

QE-106 HS175A A X X HS CC

QE-106 HS175B B X HS CC

QE-106 HS137 E X HS CC

QE-107 SH104A B X SH CC

QE-107 SH104B A X X SH CC

QE-107 SH190 E X SH CC

QE-110 FS129 E X FS CC

QE-112 PS101 E X PS CC

QE-113 UF126 E X UF CC

QE-116 EM103 E X EM CC

QE-120 AO-101A F X X AO CC 2

QE-120 AO-121 A X X AO CC

QE-120 AO-124A B X AO CC

QE-120 AO-124B B X AO CC

QE-120 AO-124C B X AO CC

QE-120 AO-147 B X AO CC

QE-120 AO-148 A X X AO CC

QE-120 AO-150A B X AO CC

QE-120 AO-151A D X X AO CC

QE-120 AO-151B D X X AO CC

QE-120 GL1 A X X AO CC

QE-121 SG-105 E X UP CC

QE-122 UP-104 E X UP CC

QE-123 MW-A118 E X MW CC

QE-125 LG-113 E X LG CC

QE-127 CC-112 E X CC CC

QE-128 CH-116 E X CH CC

QE-500 VSP-1 A X X SG CC

QE-500 VSP-2 C X X SG CC

QE-500 VSP-3 C X X SG CC

QE-500 VSP-4 A X X SG CC

QE-500 GL2 A X X SG CC

DOOR CONTROL SYSTEMS 17180-18

INTERLOCK SCHEDULE

TABLE 17180-3 FCI

IL TYPE

SHEET # GROUP # SW/HW DESCRIPTION DOORS

QE-106

1 SW MEDICAL HS175A, HS175B

QE-107 2 SW SHU SH104A, SH104B

QE-120 3 HW MAIN SALLYPORT AO-151A, AO-151B

QE-120 4 SW CENTRAL CONTROL AO-147, AO-150A, AO-

QE-120 5 SW SQUAD ROOM AO-121, AO-124C

QE-500 6 HW VEHICLE SALLYPORT VSP-1, VSP-2, VSP-3,

VSP-4.

LEGEND:

HW - Hardwired interlock required (Facility Perimeter Sallyports)

SW - Software interlock. Hardwired interlock optional.

DOOR CONTROL SYSTEMS 17180-19

TABLE 17180-1 FDC

LEGEND FOR DOOR CONTROL SCHEDULES

HARDWARE

FUNCTION = Letter designations refer to types of door control described in Section

17180.04.

EOL

= Electrically Operated Lock Control.

DPS

= Door Position Switch and latch bolt monitor switch monitoring. Doors with electric locks shall include roller bolt monitoring.

SCC

= Security and Communications Cabinet. See security and communications drawings for cabinet locations.

Control Station = Control panel/touch screen having control or monitoring responsibility of door.

See drawings for abbreviations and locations of control panels.

Remarks:

1.

Coordinate with Division 8 and Division 11 for installation of intercom station in the door frame for indicated door.

2.

Coordinate with Division 8 and Division 11 for installation of pushbutton in door frame for indicated door.

3.

There is no intercom associated with the indicated door.

4.

This door is part of the emergency stair door release.

DOOR CONTROL SYSTEMS 17180-20

TABLE 17180-2 FDC

DOOR CONTROL SCHEDULE

SHEET DOOR HARDWARE

CONTROL

NO. NO. FUNCTION EOL DPS SCC NO. STATION REMARKS

FDC TABLES ARE SIMILAR BUT DIFFERENT TO THE

USP AND FCI TABLES. REVIEW TABLES CAREFULLY

WITH FBOP PRIOR TO DEVELOPING FOR

CONSTRUCTION DOCUMENTS.

DOOR CONTROL SYSTEMS 17180-21

INTERLOCK SCHEDULE

TABLE 17180-3 FDC

IL TYPE

SHEET # GROUP # SW/HW DESCRIPTION DOORS

FDC TABLES ARE SIMILAR BUT DIFFERENT TO THE

USP AND FCI TABLES. REVIEW TABLES CAREFULLY

WITH FBOP PRIOR TO DEVELOPING FOR

CONSTRUCTION DOCUMENTS.

LEGEND:

HW - Hardwired interlock required (Facility Perimeter Sallyports)

SW - Software interlock. Hardwired interlock optional.

END OF SECTION 17180