IFB_6100_CLMC1077_00900_7_v1.pdf

PDF 28 MB Posted

Attached to
10108 FM812 Leachate Connections
Solicitation number
IFB 6100 CLMC1077
Issued by
Texas

About this file

This addendum document modifies the original bid requirements and contract conditions for the City of Austin's FM 812 Landfill Leachate Tank Connection project (Solicitation No. CLMC1077, C.I.P. No. 5698.017), located at 10108 FM 812 in Austin, Texas. The project involves installing approximately 4,089 linear feet of 3-inch and 6-inch HDPE and PVC piping to connect leachate storage Tank A (12,000 gallons) to Tank B (12,000 gallons) and subsequently connecting Tank B to an existing municipal manhole. Additional work includes installing new pumping systems, flow meters, level switches, motorized valves, and control panels, along with site improvements such as erosion control measures, guard posts, and monitoring stations. Addendum No. 7, dated March 25, 2026, extends the bid submission deadline from April 2, 2026, to May 2, 2026, with bids and compliance plans due at 2:00 PM Austin time and opening at 3:00 PM on May 2, 2026. The addendum incorporates 24 revised and new plan sheets addressing modifications to the site plan, utility locations, Austin Water construction details, and erosion control measures. The contract specifies a substantial completion period of 150 calendar days after Notice to Proceed, with final completion required within an additional 30 calendar days, and liquidated damages of $850 per calendar day for delays in substantial completion and $500 per calendar day for final completion delays.

The project requires bidders to submit a bid guaranty of at least 5% of the total bid amount, with performance and payment bonds required for 100% of the contract amount. The City of Austin has determined that no specific Minority- and Women-Owned Business Enterprise (MBE/WBE) goals are applicable; however, bidders must comply with the City's MBE/WBE Procurement Program if subcontracting occurs and document Good Faith Efforts to use certified MBE and WBE firms. Contractors and subcontractors must register with the City of Austin prior to contract award and before contract execution. The project site, located within a landfill that has experienced notable settlement and subsurface movement, includes groundwater monitoring wells, existing electrical and gas utilities, and portions within Federal Emergency Management Administration flood hazard Zone AE. Geotechnical investigation reports are available for review at the Owner's office, and contractors are responsible for locating all existing utilities before commencing work and maintaining proper safe working distances from utility easements.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bidding Requirements, Contract Forms and Conditions of the Contract

Rev. Date 05/10/2021 Addendum / 00900 Page 1 of 2

ADDENDUM 7

Section 00900

ADDENDUM NO. 7

Date: March 25, 2026

City of Austin

Project Name: FM 812 LANDFILL LEACHATE TANK CONNECTION

C.I.P. No. 5698.017 IFB No.: CLMC1077

This Addendum forms a part of the Contract and corrects or modifies original Bid Documents, issued on September 22, 2025. Acknowledge receipt of this addendum in space provided on bid form. Failure to do so may subject bidder to disqualification.

A. Project Manual Revisions:

Project Manual Revisions: Section 00020 Item 3. Submission of Bids:

Remove:

ALL BIDS AND COMPLIANCE PLANS ARE DUE PRIOR TO (Austin time) 2:00 PM ON April 2nd, 2026.

BIDS WILL BE OPENED AT (Austin time) 3:00 PM ON April 2nd, 2026.

Replace with:

ALL BIDS AND COMPLIANCE PLANS ARE DUE PRIOR TO (Austin time) 2:00 PM ON May 2nd, 2026.

BIDS WILL BE OPENED AT (Austin time) 3:00 PM ON May 2nd, 2026.B.

B. Drawing Revisions:

Sheet C-001 Revised sheet numbers indicated sheets under Austin Water Tap Plan approval.

Sheet C-002 Added/revised note 22 of General Notes.

Sheet C003 Added sheet.

Sheet C-004 Replaced Austin Water Construction Notes with Austin Water General Information and Construction Notes for Capital Improvement Projects.

Sheet C-005 Removed.

Sheets C-102 C-103 Identified utility pole numbers. Added note 5.

Sheet C-104 Identified private vs public sewer limits. Added notes 5 & 6.

Bidding Requirements, Contract Forms and Conditions of the Contract

Rev. Date 05/10/2021 Addendum / 00900 Page 2 of 2

Sheet C-201 Added missing sheet.

Sheets C-202, C-203, C-204, C-205, C-206, C-207, C-208 & C-209 Added note 6.

Sheet C-210 Identified private vs public sewer limits. Added note 6.

Sheet C-211 Identified private vs public sewer limits. Added jurisdiction note. Added note 6.

Sheet C-303 Modified Detail 4 - Guard Post.

Sheet C-304 Renamed sheet.

Sheet C-305 Revised sheet to show requested Austin Water details.

Sheet C-307 Added Detail 4 - Overhead Power Line Clearance Requirements.

Sheet C-308 Added column to Guide/Restraints Table.

This addendum consists of 24 plan sheet(s).

Approved by OWNER

Approved by ENGINEER/ARCHITECT (as applicable per license requirements)

END

C - 001

TITLE SHEET

DRAWING INDEX

VICINITY MAP

AUSTIN-BERGSTROM

INTERNATIONAL AIRPORT

S H

IG

H

W A

Y

PILOT

KNOB

MOORES

BRIDGE RD

FM

S

FM 812

TE

X

A S

T O

LL

R

O A

D

FM 812

PROJECT INFORMATION

STREET ADDRESS

10108 FM 812

AUSTIN, TX 78719

OWNER

MR. DONALD HARDEE

AUSTIN RESOURCE RECOVERY

2514 BUSINESS CENTER DRIVE

AUSTIN, TX 78744

TEL: 512-974-4345

CONTACT

MR. EDWARD A. SHEPARD JR., P.E.

APTIM ENVIRONMENTAL &

INFRASTRUCTURE LLC

12005 FORD ROAD, SUITE 600

DALLAS, TX 75234

TEL: 972-773-8400

SUBMITTAL PREPARED BY

APTIM ENVIRONMENTAL &

INFRASTRUCTURE LLC

12005 FORD ROAD, SUITE 600

DALLAS, TX 75234

TEL: 972-773-8400

MAYOR

KIRK WATSON

COUNCIL MEMBER DISTRICT 1

NATASHA HARPER-MADISON

COUNCIL MEMBER DISTRICT 3

JOSÉ VELÁSQUEZ

COUNCIL MEMBER DISTRICT 5

RYAN ALTER

COUNCIL MEMBER DISTRICT 7

LESLIE POOL

COUNCIL MEMBER DISTRICT 9

ZOHAIB QADRI

COUNCIL MEMBER DISTRICT 2

VANESSA FUENTES

COUNCIL MEMBER DISTRICT 4

JOSÉ VELA

COUNCIL MEMBER DISTRICT 6

MACKENZIE KELLY

COUNCIL MEMBER DISTRICT 8

PAIGE ELLIS

COUNCIL MEMBER DISTRICT 10

ALISON ALTER

FM 812 LANDFILL

LEACHATE TANK CONNECTION

C.I.P. NO. 5698.017

SOLICITATION NO. CLMC1077

PROPOSED

LEACHATE

PIPELINE

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

C-001* TITLE SHEET

C-002* GENERAL NOTES

C-003 ENVIRONMENTAL NOTES

C-004* AUSTIN WATER GENERAL INFORMATION AND CONSTRUCTION

NOTES FOR CAPITAL IMPROVEMENT PROJECTS

C-101 EXISTING SITE PLAN

C-102* EXISTING SITE PLAN AREAS A AND B

C-103 ENLARGED SITE PLAN WEST

C-104* ENLARGED SITE PLAN EAST

C-201 LINE A PLAN/PROFILE VIEWS STATIONS 0+00 TO 4+00

C-202 LINE A PLAN/PROFILE VIEWS STATIONS 4+00 TO 8+00

C-203 LINE A PLAN/PROFILE VIEWS STATIONS 8+00 TO 12+00

C-204 LINE A PLAN/PROFILE VIEWS STATIONS 12+00 TO 16+00

C-205 LINE A PLAN/PROFILE VIEWS STATIONS 16+00 TO 20+00

C-206 LINE A PLAN/PROFILE VIEWS STATIONS 20+00 TO 24+04

C-207 LINE B PLAN/PROFILE VIEWS STATIONS 24+38 TO 28+00

C-208 LINE B PLAN/PROFILE VIEWS STATIONS 28+00 TO 32+00

C-209 LINE B PLAN/PROFILE VIEWS STATIONS 32+00 TO 36+00

C-210 LINE B PLAN/PROFILE VIEWS STATIONS 36+00 TO 39+80

C-211* MANHOLE CONNECTION STATIONS 39+30 TO 41+00

C-301 TANK A DETAIL SHEET EXISTING AND PROPOSED

C-302 TANK B DETAIL SHEET EXISTING AND PROPOSED

C-303 TANK SECTION VIEWS, EXPANSION LOOPS, AND GUARD POSTS

C-304 GENERAL DETAILS

C-305 * AUSTIN WATER DETAILS

C-306 PIPE SUPPORT DETAILS

C-307 MISCELLANEOUS DETAILS

C-308 PIPELINE ALIGNMENT POINTS AND GUIDE/RESTRAINT TABLE

C-309 EROSION CONTROL DETAILS

C-401 TANK AREA A POWER AND CONTROL SUMMARY

C-402 TANK AREA B POWER AND CONTROL SUMMARY

C-403 TANK AREA A AND B CONDUIT LAYOUT

C-404 CONDUIT SCHEDULE

C-405 TANK AREA A AND B CONTROL PANEL

C-501 EROSION CONTROL SITE PLAN - WEST

C-502 EROSION CONTROL SITE PLAN - EAST

* SHEETS UNDER AUSTIN WATER REVIEW

FLOOD HAZARD NOTE

PORTIONS OF THE SITE ARE IN THE 1% ANNUAL CHANCE FLOOD WITH AVERAGE DEPTH LESS THAN ONE FOOT OR WITH DRAINAGE AREAS OF LESS THAN ONE SQUARE MILE. ZONE AE. IN ACCORDANCE WITH FEDERAL EMERGENCY MANAGEMENT ADMINISTRATION (FEMA) FLOOD INSURANCE RATE MAP (FIRM) NUMBER 48453C0620K EFFECTIVE DATE 22 JANUARY 2020. THE BASE FLOOD ELEVATIONS

ARE BETWEEN 465.9 AND 470.3.

THE FLOOD HAZARD INFORMATION IS DERIVED DIRECTLY FROM THE AUTHORITATIVE NFHL WEB SERVICES PROVIDED BY FEMA. THIS INFORMATION WAS EXPORTED ON 8/21/2025 AT 3:46 PM AND DOES NOT REFLECT CHANGES OR AMENDMENTS SUBSEQUENT TO THIS DATE AND TIME. THE NFHL AND EFFECTIVE INFORMATION MAY CHANGE OR BECOME SUPERSEDED BY NEW DATA OVER TIME.

TANK A

TANK B

PROJECT LOCATION MAP

NOTE

PORTIONS OF THE SITE

ARE IN PART OF CITY

OF AUSTIN GRIDS M13,

M14, N13, & N 14

CERTIFICATION STATEMENT:

I certify that all of the information contained within this tap plan is accurate and correct to the best of my knowledge. This site is not covered under a site plan and the proposed improvements qualify for a Site Plan Exemption as noted by City Code Section 25-5-2. I understand that this tap plan will become null and void should City staff determine the proposed developments meet the requirements for a site plan.

SITE PLAN EXEMPTION CASE NUMBER:

2025 047639 DA

SHEET

NUMBER SHEET TITLE

C - 002

GENERAL NOTES

SECTIONS AND DETAIL KEY

D#

GENERAL NOTES

1. ALL WORK UNDER THIS CONTRACT SHALL BE PERFORMED IN ACCORDANCE WITH THE PLANS AND PROJECT SPECIFICATIONS. IN THE EVENT OF A DISCREPANCY BETWEEN THE PLANS AND THE PROJECT SPECIFICATIONS, THE SPECIFICATIONS SHALL GOVERN SEE SECTION 00700 ARTICLE 6.2.4.

2. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO THE START OF WORK.

3. GROUNDWATER AT THE SITE WILL VARY DEPENDING ON RAINFALL, AND SUBSURFACE CONDITIONS. THERE SHALL NOT BE ANY ADDITIONAL PAYMENT OR EXTENSION OF CONTRACT TIME FOR WORKING WITH SATURATED SOILS OR HANDLING GROUNDWATER SEEPAGE DUE TO RAINFALL, RUNOFF OR INFILTRATION.

4. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT EXISTING ROADS, BENCHMARKS, GAS PROBES, GROUNDWATER MONITORING WELLS, AND OTHER SITE FEATURES DURING THE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL BE SOLEY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE INCURRED BY THE CONTRACTOR'S FAILURE TO EXACTLY LOCATE AND PROTECT EXISTING ROADS, BENCHMARKS, GAS PROBES, GROUNDWATER MONITORING WELLS, AND OTHER SITE FEATURES.

5. THE LOCATIONS OF EXISTING UNDERGROUND UTILITIES HAVE NOT BEEN ESTABLISHED BY THE OWNER OR HIS REPRESENTATIVES. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK, AND AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE OCCASIONED BY THE CONTRACTORS FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UTILITIES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER SAFE WORKING

DISTANCE FROM ALL UTILITY EASEMENTS OR LINES.

6. EXCAVATION BY "BLASTING" IS NOT PERMITTED ON THIS PROJECT.

7. FINISHED GROUND ELEVATIONS SHALL MATCH EXISTING GROUND ELEVATIONS EXCEPT AS SHOWN ON THE PLANS. ALL EXCESS SOIL FROM THE EXCAVATION AND GRADING SHALL BE PLACED IN DESIGNATED STOCKPILE LOCATIONS AS SHOWN IN PLANS OR AS APPROVED BY THE OWNER. IF WASTE IS ENCOUNTERED DURING EXCAVATION, WORK SHALL STOP, THE OWNER SHALL BE NOTIFIED AND THE WASTE REMOVED AND PLACED IN AREAS DESIGNATED AS APPROVED BY THE OWNER. IN AREAS NOT OVER WASTE, THE EXISTING GROUND MAY BE GRADED TO EVEN OUT MINOR SURFACE IRREGULARITIES WITH OWNER’S APPROVAL. ALL DISTURBED SURFACES MUST BE RESTORED WITH THE SAME OR SIMILAR MATERIAL AS

APPROVED BY THE OWNER.

8. GEOTECHNICAL INVESTIGATION REPORTS FOR THE LANDFILL ARE AVAILABLE FOR REVIEW AT OWNER'S OFFICE. THE CONTRACTOR MAY PERFORM ADDITIONAL GEOTECHNICAL INVESTIGATIONS, AS HE DEEMS NECESSARY FOR CONSTRUCTION ACTIVITIES, PROVIDED ALL NECESSARY PERMITS AND APPROVALS ARE OBTAINED FROM OWNER PRIOR TO INITIATING SUCH WORK. HOWEVER, THERE SHALL BE NO ADDITIONAL PAYMENT TO THE CONTRACTOR FOR ADDITIONAL GEOTECHNICAL INVESTIGATIONS.

9. THE CONTRACTOR SHALL CONSTRUCT, AND UPON COMPLETION OF THE PROJECT, REMOVE TEMPORARY CONSTRUCTION ACCESS ROADS. SUCH ROADS SHALL BE LOCATED AS APPROVED BY THE OWNER. DRAINAGE PATTERNS AT THE SITE SHALL NOT BE ALTERED BY CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION AND MAINTENANCE OF TEMPORARY DRAINAGE STRUCTURES, INCLUDING CULVERTS, AT NO ADDITIONAL COST TO THE OWNER.

10. TEMPORARY CONSTRUCTION SLOPES SHALL NOT BE GREATER THAN 3H:1V. STEEPER SLOPES WILL ONLY BE ALLOWED IF THE CONTRACTOR PROVIDES A GEOTECHNICAL ENGINEERING REPORT SPECIFYING MAXIMUM SLOPES AND THE DURATION FOR WHICH SUCH SLOPES SHALL REMAIN IN PLACE.

11. THE CONTRACTOR SHALL REMOVE ALL VEGETATION WITHIN THE CONSTRUCTION EXCAVATION LIMITS AS REQUIRED TO CONSTRUCT THE PROJECT. ALL VEGETATION SHALL BE SEGREGATED AND STOCKPILED BY CONTRACTOR AT NO ADDITIONAL EXPENSE TO OWNER. CONTRACTOR TO MOW THE PIPELINE ALIGNMENT PRIOR TO PLACING THE PIPE AND SLEEPERS. WHERE SLEEPERS ARE PLACED ON THE GROUND, ALL VEGETATION MUST BE REMOVED SO THE WOOD IS IN CONTACT WITH THE UNDERLYING SOIL.

12. THE CONTRACTOR SHALL IMMEDIATELY REPORT TO THE ENGINEER ANY ERROR OR DISCREPANCY FOUND ONCE THE CONTRACT DOCUMENT IS CAREFULLY REVIEWED AND ALL

ASPECTS OF FIELD WORK HAVE BEEN VERIFIED.

13. THE DRAWINGS AND SPECIFICATIONS SHOULD AGREE WITH EACH OTHER, AND WORK CALLED FOR BY DRAWINGS AND NOT MENTIONED IN SPECIFICATION, OR VICE VERSA, SHALL BE FURNISHED BY BOTH. WHEN DISCREPANCIES EXIST BETWEEN SCALE AND DIMENSIONS, THE DIMENSIONED FIGURE SHALL BE USED.

14. CONTRACTORS AND EACH SUB CONTRACTOR SHALL VERIFY ALL GRADES, LINES, LEVELS, AND DIMENSIONS AS INDICATED ON DRAWINGS, AND SHALL REPORT ERRORS TO THE ENGINEER BEFORE COMMENCING WORK. THE CONTRACTOR SHALL ESTABLISH ADDITIONAL BENCHMARKS AS NEEDED TO EXECUTE THE WORK, AND AS WORK PROGRESSES THE

CONTRACTOR WILL MAINTAIN ADEQUATE HORIZONTAL AND VERTICAL CONTROL.

15. STORMWATER AND GROUNDWATER WHICH HAS COME INTO CONTACT WITH WASTE IS TO BE CONSIDERED CONTAMINATED. CONTRACTOR WILL CONTROL THE WATER ON-SITE.

16. CONTRACTOR SHALL PROVIDE EROSION CONTROL BY SEEDING FOR ALL AREAS DISTURBED BY CONTRACTOR DURING THE CONSTRUCTION OF THIS PROJECT. THE CONTRACTOR SHALL NOT DISTURB ANY AREA WITHOUT THE APPROVAL OF THE ENGINEER. EROSION CONTROL BY SEEDING SHALL CONFORM TO STANDARD SPECIFICATION 604S. USE NON-NATIVE

SEED BY THE BROADCAST METHOD WITH STRAW MULCH.

17. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.

18. HORIZONTAL AND VERTICAL CONTROL IS BASED ON DATA FROM THE CITY OF AUSTIN PROJECT: FM 812 LANDFILL / ECO-INDUSTRIAL PARK, DRAWING:FM812 LANDFILL REMAINDER

(2013).DWG, DATED AUGUST 16, 2013 AS FOLLOWS:

BEARINGS SHOWN HEREON ARE BASED ON THE TEXAS STATE PLANE COORDINATE SYSTEM, CENTRAL ZONE, NAD 83. THE CONTROLLING MONUMENTS FOR THIS PROJECT WERE ESTABLISHED UTILIZING MULTIPLE VRS GPS OBSERVATIONS AND ARE A COTTON SPINDLE FOUND IN ASPHALT AT THE INTERSECTION OF MOORE'S BRIDGE ROAD AND F.M. 973 HAVING GRID COORDINATE VALUES OF N=10,034,381.64, E=3,141,102.59 AND A 1/2" REBAR W/CAP STAMPED "COA PUBLIC WORKS" SET ALONG THE WESTERLY INTERIOR OF THE CITY OF AUSTIN

293.94 ACRE LANDFILL TRACT HAVING GRID COORDINATE VALUES OF N=10,032,847.01, E=3,137,395.06. THE DISTANCES SHOWN ARE SURFACE DISTANCES. THE COMBINED SCALE

FACTOR IS 0.99996749

19. LEACHATE SHALL REFER TO ALL CONTAMINATED WATER, GAS CONDENSATE AND ANY WATER THAT HAS BEEN IN CONTACT WITH WASTE, LEACHATE OR GAS CONDENSATE.

20. NOT ALL FITTINGS ARE SHOWN OR ANTICIPATED ALONG THE PIPELINE ALIGNMENT. CONTRACTOR TO PROVIDE FITTINGS AS NEEDED FOR A PROPER INSTALLATION AND MUST PRESENT ANY CHANGES OR ADDITIONS TO THE OWNER FOR APPROVAL. HDPE PIPE MAY BE LAID IN A MINIMUM 100-FOOT RADIUS IN LIEU OF ANGLE FITTINGS WITH OWNER'S

PERMISSION.

21. CONTRACTOR TO PROVIDE INITIAL ALIGNMENT SURVEY PRIOR TO DETAILED CONSTRUCTION SURVEY IN ACCORDANCE WITH SPECIFICATION 01050.

22. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL POLES.

BENCHMARKS:

BENCHMARK #1: MAP COORDINATE N=10029588.21, E=3138251.73

A 1/2" REBAR WITH CAP STAMPED "MM TRAV" FOUND (MM PNT #23).

REFERENCED ON McGRAY & McGRAY F.M. 812 LANDFILL PRIMARY CONTROL LIST ELEVATION = 541.90' - DATUM UNKNOWN.

COA PNT #111 NAVD 88, GEOID 03 ELEVATION = 542.34'

BENCHMARK #2: GRID COORDINATE N=10031603.78, E=3139571.64

BOLT FOUND w/WASHER "MW-19 TOC 536.44" IN CONCRETE PAD OF MONITORING WELL #19 - COA PNT #9684 NAVD 88, GEOID 03 ELEVATION = 534.07'

BENCHMARK #3: GRID COORDINATE N=10033477.92, E=3140510.98

BOLT FOUND w/WASHER "MW-21 TOC 512.47" IN CONCRETE PAD OF MONITORING WELL #21 - COA PNT #21591 NAVD 88, GEOID 03 ELEVATION = 510.68'

BENCHMARK #4: GRID COORDINATE N=10032609.78, E=3140099.50

BOLT FOUND w/WASHER "MW-16 TOC 537.32" IN CONCRETE PAD OF MONITORING WELL #16 - COA PNT #9759 NAVD 88, GEOID 03 ELEVATION = 535.93'

BENCHMARK #5: GRID COORDINATE N=10034381.64, E=3141102.59

COTTON SPINDLE SET IN ASPHALT ON SOUTH SIDE OF MOORE'S BRIDGE ROAD NEAR ITS INTERSECTION WITH F.M 973 (NE COR OF LANDFILL SITE) - COA

PNT #21 NAVD 88, GEOID 03 ELEVATION = 473.25'

BENCHMARK #6: GRID COORDINATE N=10031080.89, E=3139300.15

BOLT FOUND w/WASHER "MW-20 TOC 560.79" IN CONCRETE PAD OF MONITORING WELL #20 - COA PNT #9642 NAVD 88, GEOID 03 ELEVATION = 558.93'

BENCHMARK #7: GRID COORDINATE N=10033825.80, E=3140718.14

BOLT FOUND w/WASHER "MW-13 TOC 485.07" IN CONCRETE PAD OF MONITORING WELL #13 - COA PNT # 10598 NAVD 88, GEOID 03 ELEVATION = 483.25'

BENCHMARK #8: GRID COORDINATE N=10034624.97, E=3140524.64

BOLT FOUND w/WASHER "MW-12 TOC 476.80" IN CONCRETE PAD OF MONITORING WELL #12 - COA PNT # 10599 NAVD 88, GEOID 03 ELEVATION = 475.29'

BENCHMARK #9: GRID COORDINATE N=10034762.05, E=3140024.69

BOLT FOUND w/WASHER "MW-17 TOC 479.89" IN CONCRETE PAD OF MONITORING WELL #17 - COA PNT # 9440 NAVD 88, GEOID 03 ELEVATION = 478.37'

BENCHMARK #10: GRID COORDINATE N=10034947.57, E=3139266.35

BOLT FOUND w/WASHER "MW-18 TOC 500.35" INCONCRETE PAD OF MONITORING WELL #18 - COA PNT #9425 NAVD 88, GEOID 03 ELEVATION = 498.60'

BENCHMARK #11: GRID COORDINATE N=10035211.82, E=3138817.09

BOLT FOUND w/WASHER "MW-10R TOC 453.85" IN CONCRETE PAD OF MONITORING WELL #10R - COA PNT # 21704 NAVD 88, GEOID 03 ELEVATION = 452.93'

BENCHMARK #12: GRID COORDINATE N=10035216.66, E=3137083.14

BOLT FOUND w/WASHER "MW-3R TOC 521.66" IN CONCRETE PAD OF MONITORING WELL #3R - COA PNT # 9400 NAVD 88, GEOID 03 ELEVATION = 519.84'

BENCHMARK #13: GRID COORDINATE N=10034470.27, E=3136727.32

2.5 " BRASS DISK FOUND "GP-05" IN CONCRETE PAD - COA PNT # 9373 NAVD 88, GEOID 03 ELEVATION = 521.08'

BENCHMARK #14: GRID COORDINATE N=10033477.92, E=3140510.98

2.5" BRASS DISK FOUND "GP-04R" IN CONCRETE PAD - COA PNT # 9362 NAVD 88, GEOID 03 ELEVATION = 538.92'

BENCHMARK #15: GRID COORDINATE N=10035139.64, E=3137673.45

BOLT FOUND w/WASHER "MW-8R TOC 480.00" IN CONCRETE PAD OF MONITORING WELL #8R - COA PNT # 9402 NAVD 88, GEOID 03 ELEVATION = 477.84'

BENCHMARK #16: GRID COORDINATE N=10032108.86, E=3139831.62

2.5" BRASS DISK FOUND "GP-11" IN CONCRETE PAD - COA PNT # 9694 NAVD 88, GEOID 03 ELEVATION = 515.37'

BENCHMARK ELEVATIONS SHOWN ARE BASED ON GPS VRS OBSERVATIONS PERFORMED BY THE CITY OF AUSTIN PUBLIC WORKS DEPARTMENT SURVEY GROUP. VARIOUS BOUNDARY AND TOPOGRAPHIC SURVEY PROJECTS WERE PERFORMED ON THIS SITE FROM 2012-2016. DUE TO THE SOIL CONDITIONS AT THIS LANDFILL SITE AND COMPOUNDED BY PERIODS OF DROUGHT AND HEAVY RAIN THAT WERE EXPERIENCED DURING THIS PERIOD OF TIME IT HAS CAUSE NOTICEABLE HORIZONTAL AND VERTICAL MOVEMENT OF CONTROL POINTS AND BENCHMARKS AND SHOULD BE TAKEN INTO ACCOUNT WHEN USING THIS DATA. HORIZONTAL ACCURACY CAN BE EXPECTED TO BE WITHIN APPROXIMATELY 0.05' WHILE VERTICAL ACCURACY MAY

BE IN THE RANGE OF 010' - 0.15'.

SECTION OR

DETAIL LABEL

DRAWING ON WHICH

SECTION OR DETAIL

IS SHOWN

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

EROSION CONTROL NOTES

1. InsTALL EROSION/SEDIMENTATION CONTROLS, PRIOR TO ANY SITE WORK INCLUDING CLEARING, GRUBBING AND/OR

EXCAVATION.

2. PLACE EROSION/SEDIMENTATION CONTROLS IN ACCORDANCE WITH THE ENVIRONMENTAL CRITERIA MANUAL AND THE APPROVED EROSION AND SEDIMENTATION CONTROL PLAN. THE COA ESC PLAN MUST BE CONSULTED AND USED AS THE BASIS FOR A TPDES REQUIRED SWPPP. IF A SWPPP IS REQUIRED, IT MUST BE AVAILABLE FOR REVIEW BY THE CITY OF AUSTIN ENVIRONMENTAL INSPECTOR DURING CONSTRUCTION, INCLUDING AT THE PRE-CONSTRUCTION MEETING.

· INSTALL PERIMETER CONTROLS, THEN TEMPORARY STABILIZATION, AND THEN PERMANENT STABILIZATION.

· EXCAVATION CANNOT START UNTIL UTILITY LOCATES ARE COMPLETE AND EROSION/SEDIMENT CONTROLS ARE

INSTALLED.

· REMOVE EROSION CONTROLS AFTER PERMANENT MEASURES ARE ESTABLISHED. PERMANENT VEGETATION COVERAGE

MUST MEET OR EXCEED 70%.

· TEMPORARY EROSION CONTROL MEASURES MUST BE INSPECTED AND REPAIRED AFTER EACH RAINFALL EVENT AND

WEEKLY DURING DRY CONDITIONS.

3. THE PLACEMENT OF TREE/NATURAL AREA PROTECTIVE FENCING SHALL BE IN ACCORDANCE WITH THE CITY OF AUSTIN STANDARD NOTES FOR TREE AND NATURAL AREA PROTECTION AND THE APPROVED GRADING/TREE AND NATURAL AREA

PLAN.

4. A PRE-CONSTRUCTION CONFERENCE SHALL BE HELD ON-SITE WITH THE CONTRACTOR, DESIGN ENGINEER/PERMIT APPLICANT AND ENVIRONMENTAL INSPECTOR AFTER INSTALLATION OF THE EROSION/SEDIMENTATION CONTROLS, TREE/NATURAL AREA PROTECTION MEASURES AND "PRE-CONSTRUCTION" TREE FERTILIZATION (IF APPLICABLE) PRIOR TO BEGINNING ANY SITE PREPARATION WORK. THE OWNER OR OWNER'S REPRESENTATIVE SHALL NOTIFY THE DEVELOPMENT SERVICES DEPARTMENT, 512-974-2278 OR BY EMAIL AT ENVIRONMENTAL.INSPECTIONS@AUSTINTEXAS.GOV, AT LEAST THREE DAYS PRIOR TO THE MEETING DATE. COA APPROVED ESC PLAN AND TPDES SWPPP (IF REQUIRED) SHOULD BE

REVIEWED BY COA EV INSPECTOR AT THIS TIME.

5. ANY MAJOR VARIATION IN MATERIALS OR LOCATIONS OF CONTROLS OR FENCES FROM THOSE SHOWN ON THE APPROVED PLANS WILL REQUIRE A REVISION AND MUST BE APPROVED BY THE REVIEWING ENGINEER, ENVIRONMENTAL SPECIALIST OR CITY ARBORIST AS APPROPRIATE. MAJOR REVISIONS MUST BE APPROVED BY AUTHORIZED COA STAFF. MINOR CHANGES TO BE MADE AS FIELD REVISIONS TO THE EROSION AND SEDIMENTATION CONTROL PLAN MAY BE REQUIRED BY

THE ENVIRONMENTAL INSPECTOR DURING CONSTRUCTION TO CORRECT CONTROL INADEQUACIES.

6. THE CONTRACTOR IS REQUIRED TO PROVIDE A CERTIFIED INSPECTOR THAT IS EITHER A LICENSED ENGINEER (OR PERSON DIRECTLY SUPERVISED BY THE LICENSED ENGINEER) OR CERTIFIED PROFESSIONAL IN EROSION AND SEDIMENT CONTROL (CPESC OR CPESC - IT), CERTIFIED EROSION, SEDIMENT AND STORMWATER - INSPECTOR (CESSWI OR CESSWI - IT) OR CERTIFIED INSPECTOR OF SEDIMENTATION AND EROSION CONTROLS (CISEC OR CISEC - IT) CERTIFICATION TO INSPECT THE CONTROLS AND FENCES AT WEEKLY OR BI-WEEKLY INTERVALS AND AFTER ONE-HALF (½) INCH OR GREATER RAINFALL EVENTS TO INSURE THAT THEY ARE FUNCTIONING PROPERLY. THE PERSON(S) RESPONSIBLE FOR MAINTENANCE OF CONTROLS AND FENCES SHALL IMMEDIATELY MAKE ANY NECESSARY REPAIRS TO DAMAGED AREAS. SILT ACCUMULATION AT CONTROLS MUST BE REMOVED WHEN THE DEPTH REACHES SIX (6) INCHES OR ONE-THIRD (⅓) OF THE INSTALLED

HEIGHT OF THE CONTROL WHICHEVER IS LESS.

7. PRIOR TO FINAL ACCEPTANCE BY THE CITY, HAUL ROADS AND WATERWAY CROSSINGS CONSTRUCTED FOR TEMPORARY CONTRACTOR ACCESS MUST BE REMOVED, ACCUMULATED SEDIMENT REMOVED FROM THE WATERWAY AND THE AREA RESTORED TO THE ORIGINAL GRADE AND REVEGETATED. ALL LAND CLEARING DEBRIS SHALL BE DISPOSED OF IN

APPROVED SPOIL DISPOSAL SITES.

8. ALL WORK MUST STOP IF A VOID IN THE ROCK SUBSTRATE IS DISCOVERED WHICH IS; ONE SQUARE FOOT IN TOTAL AREA;

BLOWS AIR FROM WITHIN THE SUBSTRATE AND/OR CONSISTENTLY RECEIVES WATER DURING ANY RAIN EVENT. AT THIS TIME IT IS THE RESPONSIBILITY OF THE PROJECT MANAGER TO IMMEDIATELY CONTACT A CITY OF AUSTIN ENVIRONMENTAL INSPECTOR FOR FURTHER INVESTIGATION. IN ADDITION, IF THE PROJECT SITE IS LOCATED WITHIN THE EDWARDS AQUIFER, THE PROJECT MANAGER MUST NOTIFY THE TRAVIS COUNTY BALCONES CANYONLANDS CONSERVATION PRESERVE (BCCP) BY EMAIL AT BCCP@TRAVISCOUNTYTX.GOV. CONSTRUCTION ACTIVITIES WITHIN 50 FEET OF THE VOID MUST STOP.

9. TEMPORARY AND PERMANENT EROSION CONTROL: ALL DISTURBED AREAS SHALL BE RESTORED AS NOTED BELOW:

A. ALL DISTURBED AREAS TO BE REVEGETATED ARE REQUIRED TO PLACE A MINIMUM OF SIX (6) INCHES OF TOPSOIL [SEE

STANDARD SPECIFICATION ITEM NO. 601S.3(A)]. DO NOT ADD TOPSOIL WITHIN THE CRITICAL ROOT ZONE OF EXISTING

TREES.

TOPSOIL SALVAGED FROM THE EXISTING SITE IS ENCOURAGED FOR USE, BUT IT SHOULD MEET THE STANDARDS SET

FORTH IN 601S.

AN OWNER/ENGINEER MAY PROPOSE USE OF ONSITE SALVAGED TOPSOIL WHICH DOES NOT MEET THE CRITERIA OF STANDARD SPECIFICATION 601S BY PROVIDING A SOIL ANALYSIS AND A WRITTEN STATEMENT FROM A QUALIFIED PROFESSIONAL IN SOILS, LANDSCAPE ARCHITECTURE, OR AGRONOMY INDICATING THE ONSITE TOPSOIL WILL PROVIDE AN EQUIVALENT GROWTH MEDIA AND SPECIFYING WHAT, IF ANY, SOIL AMENDMENTS ARE REQUIRED.

SOIL AMENDMENTS SHALL BE WORKED INTO THE EXISTING ONSITE TOPSOIL WITH A DISC OR TILLER TO CREATE A

WELL-BLENDED MATERIAL.

THE VEGETATIVE STABILIZATION OF AREAS DISTURBED BY CONSTRUCTION SHALL BE AS FOLLOWS:

TEMPORARY VEGETATIVE STABILIZATION:

1. FROM SEPTEMBER 15 TO MARCH 1, SEEDING SHALL BE WITH OR INCLUDE A COOL SEASON COVER CROP: (WESTERN

WHEATGRASS (PASCOPYRUM SMITHII) AT 5.6 POUNDS PER ACRE, OATS (AVENA SATIVA) AT 4.0 POUNDS PER ACRE, CEREAL RYE GRAIN (SECALE CEREALE) AT 45 POUNDS PER ACRE. CONTRACTOR MUST ENSURE THAT ANY SEED APPLICATION REQUIRING A COOL SEASON COVER CROP DOES NOT UTILIZE ANNUAL RYEGRASS (LOLIUM MULTIFLORUM) OR PERENNIAL RYEGRASS (LOLIUM PERENNE). COOL SEASON COVER CROPS ARE NOT PERMANENT EROSION CONTROL.

2. FROM MARCH 2 TO SEPTEMBER 14, SEEDING SHALL BE WITH HULLED BERMUDA AT A RATE OF 45 POUNDS PER ACRE OR A

NATIVE PLANT SEED MIX CONFORMING TO ITEM 604S OR 609S.

A. FERTILIZER SHALL BE APPLIED ONLY IF WARRANTED BY A SOIL TEST AND SHALL CONFORM TO ITEM NO. 606S, FERTILIZER.

FERTILIZATION SHOULD NOT OCCUR WHEN RAINFALL IS EXPECTED OR DURING SLOW PLANT GROWTH OR DORMANCY.

CHEMICAL FERTILIZER MAY NOT BE APPLIED IN THE CRITICAL WATER QUALITY ZONE.

B. HYDROMULCH SHALL COMPLY WITH TABLE 1, BELOW.

C. TEMPORARY EROSION CONTROL SHALL BE ACCEPTABLE WHEN THE GRASS HAS GROWN AT LEAST 1½ INCHES HIGH WITH

A MINIMUM OF 95% TOTAL COVERAGE SO THAT ALL AREAS OF A SITE THAT RELY ON VEGETATION FOR TEMPORARY STABILIZATION ARE UNIFORMLY VEGETATED, AND PROVIDED THERE ARE NO BARE SPOTS LARGER THAN 10 SQUARE

FEET.

D. WHEN REQUIRED, NATIVE PLANT SEEDING SHALL COMPLY WITH REQUIREMENTS OF THE CITY OF AUSTIN

ENVIRONMENTAL CRITERIA MANUAL, AND STANDARD SPECIFICATION 604S OR 609S.

PERMANENT VEGETATIVE STABILIZATION:

1. FROM SEPTEMBER 15 TO MARCH 1, SEEDING IS TEMPORARY STABILIZATION ONLY. IF COOL SEASON COVER CROPS EXIST WHERE PERMANENT VEGETATIVE STABILIZATION IS DESIRED, THE GRASSES SHALL BE MOWED TO A HEIGHT OF LESS THAN ONE-HALF (½) INCH AND THE AREA SHALL BE RE-SEEDED IN ACCORDANCE WITH TABLE 2 BELOW. ALTERNATIVELY, THE COOL SEASON COVER CROP CAN BE MIXED WITH BERMUDAGRASS OR NATIVE SEED AND INSTALLED TOGETHER, UNDERSTANDING THAT GERMINATION OF WARM-SEASON SEED TYPICALLY REQUIRES SOIL TEMPERATURES OF 60 TO 70

DEGREES.

2. FROM MARCH 2 TO SEPTEMBER 14, SEEDING SHALL BE WITH HULLED BERMUDA AT A RATE OF 45 POUNDS PER ACRE WITH A PURITY OF 95% AND A MINIMUM PURE LIVE SEED (PLS) OF 0.83. BERMUDA GRASS IS A WARM SEASON GRASS AND IS CONSIDERED PERMANENT EROSION CONTROL. PERMANENT VEGETATIVE STABILIZATION CAN ALSO BE ACCOMPLISHED

WITH A NATIVE PLANT SEED MIX CONFORMING TO ITEM 604S OR 609S.

A. FERTILIZER USE SHALL FOLLOW THE RECOMMENDATION OF A SOIL TEST. SEE ITEM 606S, FERTILIZER. APPLICATIONS OF FERTILIZER (AND PESTICIDE) ON CITY-OWNED AND MANAGED PROPERTY REQUIRES THE YEARLY SUBMITTAL OF A PESTICIDE AND FERTILIZER APPLICATION RECORD, ALONG WITH A CURRENT COPY OF THE APPLICATOR'S LICENSE. FOR CURRENT COPY OF THE RECORD TEMPLATE CONTACT THE CITY OF AUSTIN'S IPM COORDINATOR.

B. HYDROMULCH SHALL COMPLY WITH TABLE 2, BELOW.

C. WATER THE SEEDED AREAS IMMEDIATELY AFTER INSTALLATION TO ACHIEVE GERMINATION AND A HEALTHY STAND OF PLANTS THAT CAN ULTIMATELY SURVIVE WITHOUT SUPPLEMENTAL WATER. APPLY THE WATER UNIFORMLY TO THE PLANTED AREAS WITHOUT CAUSING DISPLACEMENT OR EROSION OF THE MATERIALS OR SOIL. MAINTAIN THE SEEDBED IN A MOIST CONDITION FAVORABLE FOR PLANT GROWTH. ALL WATERING SHALL COMPLY WITH CITY CODE CHAPTER 6-4 (WATER CONSERVATION), AT RATES AND FREQUENCIES DETERMINED BY A LICENSED IRRIGATOR OR OTHER QUALIFIED PROFESSIONAL, AND AS ALLOWED BY THE AUSTIN WATER UTILITY AND CURRENT WATER RESTRICTIONS AND WATER

CONSERVATION INITIATIVES.

D. PERMANENT EROSION CONTROL SHALL BE ACCEPTABLE WHEN THE GRASS HAS GROWN AT LEAST 1½ INCHES HIGH WITH A MINIMUM OF 95 PERCENT FOR THE NON-NATIVE MIX, AND 95 PERCENT COVERAGE FOR THE NATIVE MIX SO THAT ALL AREAS OF A SITE THAT RELY ON VEGETATION FOR STABILITY MUST BE UNIFORMLY VEGETATED, AND PROVIDED THERE

ARE NO BARE SPOTS LARGER THAN 10 SQUARE FEET.

E. WHEN REQUIRED, NATIVE PLANT SEEDING SHALL COMPLY WITH REQUIREMENTS OF THE CITY OF AUSTIN

ENVIRONMENTAL CRITERIA MANUAL, ITEMS 604S AND 609S.

10. DEVELOPER INFORMATION:

OWNER: MR. DONALD HARDEE

AUSTIN RESOURCE RECOVERY (CITY OF AUSTIN)

2514 BUSINESS CENTER DRIVE

AUSTIN, TX 78744

PHONE # 512-974-4345

OWNER'S REPRESENTATIVE RESPONSIBLE FOR PLAN ALTERATIONS: CHRISTINE WHITNEY

PHONE # 512-974-6085

PERSON OR FIRM RESPONSIBLE FOR EROSION/SEDIMENTATION CONTROL MAINTENANCE: _______

PHONE # _______

11. THE CONTRACTOR SHALL NOT DISPOSE OF SURPLUS EXCAVATED MATERIAL FROM THE SITE WITHOUT NOTIFYING THE DEVELOPMENT SERVICES DEPARTMENT AT 512-974-2278 AT LEAST 48 HOURS PRIOR WITH THE LOCATION AND A COPY OF

THE PERMIT ISSUED TO RECEIVE THE MATERIAL.

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

TABLE 1: HYDROMULCHING FOR TEMPORARY VEGETATIVE STABILIZATION

MATERIAL DESCRIPTION LONGEVITY TYPICAL

APPLICATIONS

APPLICATION

RATES

100% OR ANY BLEND

OF WOOD,

CELLULOSE, STRAW,

AND/OR COTTON

PLANT MATERIAL

(EXCEPT NO MULCH

SHALL EXCEED 30%

PAPER)

70% OR GREATER

WOOD/STRAW 30%

OR LESS PAPER OR

NATURAL FIBERS

0--3 MONTHS MODERATE SLOPES;

FROM FLAT TO 3:1

1,500 TO 2,000 LBS

PER ACRE

TABLE2: HYDROMULCHING FOR TEMPORARY VEGETATIVE STABILIZATION

MATERIAL DESCRIPTION LONGEVITY TYPICAL

APPLICATIONS

APPLICATION

RATES

BONDED FIBER

MATRIX (BFM)

80% ORGANIC

DEFIBRATED FIBERS

10% TACKIFIER 6 MONTHS

ON SLOPES UP TO 2:1

AND EROSIVE SOIL

CONDITIONS

2,500 TO 4,000 LBS PER

ACRE (SEE

MANUFACTURES

RECOMMENDATIONS)

FIBER REINFORCED

MATRIX (FRM)

65% ORGANIC

DEFIBRATED FIBERS

25% REINFORCING

UP TO 12 MONTHS

ON SLOPES UP TO 1:1

AND EROSIVE SOIL

CONDITIONS

3,000 TO 4,500 LBS

PER ACRE (SEE

MANUFACTURES

RECOMMENDATIONS)

C - 003

ENVIRONMENTAL NOTES

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

C - 004

AUSTIN WATER GENERAL INFORMATION AND CONSTRUCTION

NOTES FOR CAPITAL IMPROVEMENT PROJECTS

(VENT)

(VENT)

G G

G

G G

G

G G

G

G G G G

G

G

G

G

GG

GG

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G G

G

G

G

G

G

G

G

G

G

G G G G G G G

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

GGGGG

G

G

G

G

G

G G

G G

G

G

G

G G

G

G

G

G

G

G

G

G

G

G G

G G

G

E

T T T

TE

E

E

P

E

E

FM 973

FM

C-

2 C-

C-

G G

G

G G

G G

0+

5+

+0

+0

+0

+0

+0

+0

+0040

+89

C-

469.3 FEET

467.6 FEET

465.9 FEET

1%-FLOOD LIMIT

GRAPHIC SCALE

0 500'

C - 101

EXISTING SITE PLAN

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

SITE ACCESS ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

E E

T

LANDFILL ENTRANCE

UTILITY EASEMENT

WATER LINE

EASEMENT

MOORE'

S

CROSS

IN

G

ON

IO

N

CR

EE

K

FM 973

FM

TANK B

(OUTFALL 02)

12,000 gal

TANK A

(OUTFALL 01)

12,000 gal

EXISTING WWMH-273234

AREA B

AREA A

AREA C

AREA D

AREA E

EXISTING

SOIL

STOCKPILE

G

T

G

WELL13

WELL11

WELL02

WELL01

WELL03

WELL04

WELL05

WELL14

WELL12

WELL17

WELL15

WELL18

WELL16

WELL10

WELL09

WELL08

WELL07

WELL06

MW-8R

W-1

W-2

W-3

W-4

W-5

W-6

W-7

W-8

W-9

W-10

W-11

W-12

W-13

W-14

W-17

W-18

W-19

W-20

W-21

W-22

W-23

W-24

W-25

W-26

W-27

W-28

W-29

W-30

W-32

W-37

W-40

W-44

W-46

W-47

W-49

W-52 W-54

W-57

W-59

W-63

W-65

W-68

W-70

W-73

W-77

W-78

W-90

W-91

W-103

W-116

W-121

W-122

W-123W-125 W-126 W-127

W-128

W-B

W-G

W-H W-I W-J W-K

W-A

W-C W-D

W-E W-F

W-79

MW-9

MW-10R

MW-17

MW-18

LCR-02

LCR-03 LCR-01

GP-22

GP-11

GP-20

GP-4R

GP-21

GP-19

MW-3R

GP-5

GP-6

MW-7

GP-09A/09B

GP-010

MW-11

GP-12

MW-14

MW-15

MW-16

GP-17

GP-18

MW-19

MW-20

MW-21

MW-22

MW-23

MW-101

MW-102

W-31

MW-12 LEGEND

CS-02

CS-03

CS-01

CS-04

MS-03

EXISTING

MS-A2

MS-A1

MS-B1

MS-01

EXISTING

NOTES

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO THE

START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS

PART OF THE FM 812 CLOSURE CERTIFICATION.

4. LANDFILL GAS AND GAS CONDENSATE IS CONVEYED BY GRAVITY IN EXISTING PIPES TO

EXISTING CONDENSATE SUMPS (CS-1 THROUGH CS-4). FROM THERE IT IS PUMPED TO THE

EXISTING LEACHATE STORAGE TANKS FOR DISPOSAL.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

W WELL 11

MW

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

PROPOSED HDPE TO PVC TRANSITION

EXISTING

ASPHALT

MILLINGS

STOCKPILE

1%-FLOOD LIMIT

ZONE AE ZONE X

(V E

N T

G G G G

G G

G

G G

G G

G

G G

G G

G

G G

G

GG G

G G

G G

G G

G

G

G

G

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G G

G G

G

G G

G G

G

G

G

G

G

G

G

G G

G G

G G

G G

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

GG

G

G G

G G

G G

G

G

G

G

G

G

G G G G G G

G

G

G G

G G

G

G

G

G

G

G

G

G

G

G

G

G

GG

G G

G G

E T

T T

T E

E

E

E

P

E

E

E

C-305

G

C-306

G G

G

G

G G

G G

G

470.3 FEET

469.3 FEET 467.6 FEET

465.9 FEET

1%-FLOOD LIMIT

GRAPHIC SCALE

0 400'

C - 102

EXISTING SITE PLAN

AREAS A AND B

EXPANSION

LOOP A2

ONION CREEK

FM

BURLESON ROAD

AREA A

AREA B

UTILITY EASEMENT

WATER LINE EASEMENT

EXISTING

WWMH-273234

TANK B

(OUTFALL 02)

12,000 gal

GAS CONDENSATE

COLLECTION LINES

8" PVC

#2016-0019

W-124

WELL11

MW-9

MW-10R

MW-17

MW-18

WELL02

WELL01

WELL03

WELL04

WELL05

WELL14

WELL12

WELL17

WELL15

WELL18

WELL16

WELL10

WELL09

WELL08

WELL07

WELL06

GP-4R

GP-21

GP-5

GP-6

MW-7

MW-8R

GP-09A/09B

GP-010

MW-14

MW-16

GP-17

MW-21

MW-22

MW-23

W-1

W-2 W-3

W-4

W-5 W-6

W-7

W-8 W-9

W-10

W-11 W-12

W-13

W-14

W-17

W-18

W-19

W-20 W-21

W-22

W-23W-24

W-25 W-26

W-27

W-28

W-29

W-30

W-31

W-32

W-37

W-40 W-44

W-46W-47

W-49

W-52

W-54W-57

W-59

W-63 W-65

W-68 W-70

W-73

W-77 W-78

W-79

W-90 W-91

W-103

W-116

W-121

W-122

W-123

W-125

W-126

W-127

W-128

W-A W-B

W-C W-D

W-E W-F W-G

W-H W-I W-J W-K

MW-12

LCR-03

MW-11

MW-3R

MS-A1

MS-A3

MS-B1

MS-01

EXISTING

CS-01

WELL13

CS-04

EXPANSION

LOOP A6

EXPANSION

LOOP B1

EXPANSION

LOOP B2

CS-02

CS-03

NOTES

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO THE

START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS PART

OF THE FM 812 CLOSURE CERTIFICATION.

4. LANDFILL GAS AND GAS CONDENSATE IS CONVEYED BY GRAVITY IN EXISTING PIPES TO

EXISTING CONDENSATE SUMPS (CS-1 THROUGH CS-4). FROM THERE IT IS PUMPED TO THE

EXISTING LEACHATE STORAGE TANKS FOR DISPOSAL.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

LEGEND

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

SITE ACCESS ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

UTILITY POLE NUMBER

E E

T

G

T

G

W WELL 11

MW

LCR-02

LCR-01

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

MS-03

EXISTING

PROPOSED HDPE

TO PVC TRANSITION

TANK A

(OUTFALL 01)

12,000 gal

EXPANSION

LOOP A1

EXPANSION

LOOP A3

EXPANSION

LOOP A5

EXPANSION

LOOP A4

MS-A2

1%-FLOOD LIMIT

ZONE AE

ZONE X

45-3 204031

45-3 203965

45-3 204043 45-3 37909745-3 204063

45-3 379096 45-3 204112

45-3 204011

50-3 204114

45-3 204119

45-3 204117

45-3 204062

45-3 402010

8-5 342503 & 35-5 416074

45-3 204103

45-3 203995

45-3 203954 45-3 203945

45-3 203931

MOORE'S

CROSSING

45-3 203914

35-5 203914

45-3 203954

O N

IO

N

C R

EE

K

50' CREEK

SETBACK

45-3 204037

G

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G

G G

G G

G G

G

GG

G

G G

G G

G

G

G

G

G

G

G

GG

G G

G

G

G G

G G

G G

G G

G G

G G

G G

G

G

G

G

G

G G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G G G G G G G G G G

G

E

E

E

T T

T T T

T

T

T

E

E

E

E

E

E

E

P

P

P

E

EE

E

E

E E

W

W W W W

W W W W

W

W W

W W

W

WW

W

R10 0.0

°' 45

R

0.

0'

R 100.0'

0+00

5+00 10+00 15+00

20+00

C-303

470.3 FEET

469.3 FEET

GRAPHIC SCALE

0 200'

C - 103

ENLARGED SITE PLAN

WEST

TANK A

(OUTFALL 01)

(SEE SHEET

C-301)

BURIED PIPES

AREA A

AREA B

ONION CREEK

C O

N

TI

N U

ED

S

H

EE

T C

-1

EXISTING

CONDENSATE

COLLECTION LINES

(TYPICAL)

WELL13

WELL11

MW-9

MW-10R

WELL02

WELL01

WELL03

WELL04

WELL05

WELL14

WELL12

WELL17

WELL15

WELL18

WELL16

WELL10

WELL09

WELL08

WELL07

WELL06

MW-3R

MW-8R

W-8 W-9

W-10

W-11 W-12

W-13

W-14

W-27

W-28

W-30

W-31

W-32

W-57 W-59

W-63

W-65

W-68 W-70

W-73

W-77

W-78 W-79

W-103

W-A

W-B

W-C

W-D

W-E W-F

W-G

W-H

W-I

W-J

W-K

MS-A1

CS-01

MS-A3

NOTES

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO THE

START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS

PART OF THE FM 812 CLOSURE CERTIFICATION.

4. LANDFILL GAS AND GAS CONDENSATE IS CONVEYED BY GRAVITY IN EXISTING PIPES TO

EXISTING CONDENSATE SUMPS (CS-1 THROUGH CS-4). FROM THERE IT IS PUMPED TO THE

EXISTING LEACHATE STORAGE TANKS FOR DISPOSAL.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

LEGEND

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

SITE ACCESS ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

UTILITY POLE NUMBER

E E

T

G

T

G

SEE DETAIL C-304

W WELL 11

MW

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

EXPANSION LOOP A1

EXPANSION LOOP A2

EXPANSION LOOP A3

EXPANSION LOOP A4

EXPANSION LOOP A5

EXPANSION LOOP A6

MS-A2

1%-FLOOD LIMIT

50' CREEK

SETBACK

45-3 204031

45-3 203965

45-3 204043

45-3 379097

45-3 204063 45-3 204011

50-3 204114

45-3 203954

G G

G G

G G

G G

G G

G

G

G

G

G

G

G

G G

G G

G G

G G

G G

G

G

G

G

G

G

G

G G

G G

G G

G G

G G

G

G

G

G G

GGG

G

G G

G G

G G G

T

T

E

E

E

E

E

E

E

G

G

G G G

G

G

G

G

G

G

G G

G G

G G

G G

G

W W

W

W

20+00

25+00

30+00 35+00

40+00 40+89

469.3 FEET 467.6 FEET

465.9 FEET

GRAPHIC SCALE

0 200'

C - 104

ENLARGED SITE PLAN EAST

TANK B

(OUTFALL 02)

(SEE SHEET

C-302)

MOORE'S CROSSING

ONION CREEK

FM

UTILITY EASEMENT

WATER LINE

EASEMENT

EXISTING

WWMH-273234

(PRIVATE)

C O

N

TI

N U

ED

S

H

EE

T C

-1

8" PVC PIPELINE

#2016-0019

(PUBLIC)

MW-17

MW-18

WELL18

WELL16

WELL10

WELL09

LCR-2

LCR-03

GP-6

GP-17

MW-22

MW-23

W-23

W-25 W-26

W-28

W-29

W-31

W-116

W-125

W-126

W-127

MW-12

MW-11

CS-04

MS-A3

EXPANSION

LOOP A6

EXPANSION

LOOP B1

EXPANSION

LOOP B2

NOTES

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO THE

START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS PART

OF THE FM 812 CLOSURE CERTIFICATION.

4. LANDFILL GAS AND GAS CONDENSATE IS CONVEYED BY GRAVITY IN EXISTING PIPES TO

EXISTING CONDENSATE SUMPS (CS-1 THROUGH CS-4). FROM THERE IT IS PUMPED TO THE

EXISTING LEACHATE STORAGE TANKS FOR DISPOSAL.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

6. THE LEACHATE LINE IS UNDER PRIVATE OPERATION TO THE RIGHT-OF-WAY LINE OF FM973.

SANITARY SEWER IS PUBLIC DOWNSTREAM OF THE FM973 RIGHT-OF-WAY LINE.

LEGEND

E E

T

G

T

G

W WELL 11

MW

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

EXISTING

MS-03

PROPOSED HDPE TO

PVC TRANSITION

PROPOSED SAMPLE

PORT (OUTFALL 003)

MS-B1

1%-FLOOD LIMIT

50' CREEK

SETBACK

45-3 379097

45-3 379096

45-3 204112

50-3 204114

45-3 204119

45-3 204117

45-3 204062

45-3 402010

8-5 342503 & 35-5 416074

45-3 204103

45-3 203995

45-3 203954

45-3 203945

45-3 203931

45-3 203914

35-5 350610

45-3 204037

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

SITE ACCESS ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

UTILITY POLE NUMBER45-3 203954

EXISTING

DRIVEWAY

& GATE

GRAVITY SEWER (PRIVATE)

FM 973 ROW

GRAVITY

SEWER

(PRIVATE)

45-3 203849

EL

EV

AT

IO

N

STATION

0+00 1+00 2+00 3+00 4+00

0+00 1+00 2+00 3+00 4+00

EDGE OF ROAD

STA:0+08.23

STA:0+91.34

EXISTING

GROUND

PROPOSED LINE A

3" x 6" HDPE

BURIED

PIPE

ARR’S PRIVATE

LANDFILL

AGGREGATE ROAD

APPROXIMATE

LIMITS OF WASTE

BEGIN LINE A

TANK A

CONTAINMENT

SEE C-301

STA:1+96.34

REPLACE WITH 0.5'

COMPACTED ASPHALT

MILLINGS AND SELECT SOIL

BACKFILL. PLACE TRACER

TAPE 3" ABOVE PIPE.

STA:1+08.88

EXISTING CONDENSATE

PIPELINE. DEPTH UNKNOWN.

DETECTABLE

MARKER TAPE

EXISTING ELECTRICAL.

DEPTH UNKNOWN.

EXISTING ELECTRICAL,

GAS, AND LEACHATE

PIPING. VERIFY DEPTH

BEFORE EXCAVATION

STA:1+28.40

STA:3+06.34

STA:3+24.79

STA:3+48.55

STA:3+86.72

EXISTING CONDENSATE

PIPELINE. DEPTH UNKNOWN.

EXISTING

ELECTRICAL.

DEPTH

UNKNOWN.

EXISTING GAS

PIPELINE.

DEPTH

UNKNOWN.

EXISTING

ELECTRICAL&

GAS PIPELINE.

DEPTH

UNKNOWN.

PROPOSED LINE A

3" x 6" HDPE

EXPANSION LOOP A1

STA:2+60.00

STA:1+51.07

MONITOR STATION A1

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

GG

G

E E

E E

E E

E E E E E

E E

E E

E

E

E

E

P

P

P

E

E

E

E

E

E

PROPOSED LINE A

3" x 6" HDPE

BEGIN

LINE A

CAUTION BURIED

ELECTRICAL AND

PIPING. VERIFY

LOCATION BEFORE

EXCAVATION

CAUTION BURIED

ELECTRICAL AND

PIPING

CAUTION BURIED

ELECTRICAL AND PIPING

LINE A

BURIED

TANK A

CONTAINMENT

CS-01

W-A

W-C W-D

GUARD POSTS (3)

AVOID EXISTING

UTILITIES

MONITORING STATION A1

ARR’S PRIVATE LANDFILL

AGGREGATE ROAD CONC PAD

R

0.

0'

0+00

EXPANSION LOOP

A1 3 EACH SIDE OF

BEND

PIPELINE

MARKER

STA:3+54.65

NOTES:

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY

DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO

THE START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS

PART OF THE FM 812 CLOSURE CERTIFICATION.

4. PROPOSED PIPE TO LAY ON TOP OF GROUND EXCEPT WHERE NOTED. PROVIDE ALL

FITTINGS NEEDED TO TRANSITION FROM BURIED TO ABOVE GROUND INSTALLATION. PLACE

PIPELINE MARKERS EVERY 50 FEET WHERE PIPE IS BURIED.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

6. THE LEACHATE LINE IS UNDER PRIVATE OPERATION TO THE RIGHT-OF-WAY LINE OF FM973.

SANITARY SEWER IS PUBLIC DOWNSTREAM OF THE FM973 RIGHT-OF-WAY LINE.

HORIZONTAL

VE

R

TI

C

AL

GRAPHIC SCALE

4'

40'

LEGEND

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

ARR’S PRIVATE LANDFILL AGGREGATE ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

UTILITY CROSSING

E E

T

W

G

T

G

WELL 11

MW

C - 201

LINE A PLAN/PROFILE VIEWS

STATIONS 0+00 TO 4+00

TANK A

(OUTFALL 01)

PROFILE VIEW LINE A

C O

N

TI

N U

ED

S

H

EE

T C

-2

C-301

C-304

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm F-5650.

C-303

C-303

C-303 3 C-306

C-307

AT

IO

N

STATION

4+00 5+00 6+00 7+00 8+00

4+00 5+00 6+00 7+00 8+00

EXISTING GROUND

PROPOSED LINE A

3" x 6" HDPE

EXPANSION LOOP A2

STA:6+75.00

G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G

T

T

T

PROPOSED LINE A

3" x 6" HDPE

CAUTION BURIED

GAS PIPELINE CAUTION

OVERHEAD

ELECTRICAL

EXPANSION

LOOP A2

CS-01

W-D

W-E

W-F

WELL14

5+00

NOTES:

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY

DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO

THE START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS

PART OF THE FM 812 CLOSURE CERTIFICATION.

4. PROPOSED PIPE TO LAY ON TOP OF GROUND EXCEPT WHERE NOTED. PROVIDE ALL

FITTINGS NEEDED TO TRANSITION FROM BURIED TO ABOVE GROUND INSTALLATION. PLACE

PIPELINE MARKERS EVERY 50 FEET WHERE PIPE IS BURIED.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POLES.

6. THE LEACHATE LINE IS UNDER PRIVATE OPERATION TO THE RIGHT-OF-WAY LINE OF FM973.

SANITARY SEWER IS PUBLIC DOWNSTREAM OF THE FM973 RIGHT-OF-WAY LINE.

HORIZONTAL

VE

R

TI

C

AL

GRAPHIC SCALE

4'

40'

LEGEND

APPROXIMATE PERMIT BOUNDARY

APPROXIMATE EXISTING WASTE BOUNDARY

GAS PIPELINE WITH CONDENSATE FLOW DIRECTION

EXISTING SITE TOPOGRAPHY

ARR’S PRIVATE LANDFILL AGGREGATE ROAD

ELECTRIC LINE

LEACHATE PIPING

PROPOSED PIPING

CONDENSATE PIPING

LEACHATE TRENCH

OVERHEAD ELECTRIC LINE

EASEMENT BOUNDARY

SLURRY WALL

GROUNDWATER MONITORING WELL

LANDFILL GAS PROBE

LEACHATE EXTRACTION WELL/TRENCH

LEACHATE SUMP RISER TIE-IN

GAS EXTRACTION WELL

SANITARY SEWER MANHOLE

CONDENSATE SUMP

MONITORING STATION

UTILITY CROSSING

E E

T

W

G

T

G

WELL 11

MW

C - 202

LINE A PLAN/PROFILE VIEWS

STATIONS 4+00 TO 8+00

PROFILE VIEW LINE A

C O

N

TI

N U

ED

S

H

EE

T C

-2

C O

N

TI

N U

ED

S

H

EE

T C

-2

C-303

CITY OF AUSTIN - FM 812 LANDFILL

TRAVIS COUNTY, TEXASAPTIM Environmental

& Infrastructure, LLC This document, and the ideas and designs incorporated herein, as an instrument of professional services, is prepared by APTIM Environmental & Infrastructure, LLC and is not to be used, in whole or in part, for any other project without the written notice to APTIM Environmental & Infrastructure, LLC.

This document is released for the purpose of Bidding and Construction under the authority of Edward A.

Shepard, Jr, PE #133722. Texas Registered Engineering Firm

AT

IO

N

STATION

8+00 9+00 10+00 11+00 12+00

8+00 9+00 10+00 11+00 12+00

STA:10+15.70

EXISTING

GROUND

PROPOSED LINE A

3" x 6" HDPE

PIPE COVERED WITH 12"

SELECT SOIL BACKFILL AND 6"

ASPHALT MILLINGS FOR

ACCESS. COORDINATE WITH

OWNER FOR EXACT LOCATION.

HIGH POINT

VENT A1

1TYP

STA:12+05.00

EXPANSION LOOP A3

G

G G

G G

G G

G G

G G

G G

G

G

G

G G G G G G G G G G

PROPOSED LINE A

PROPOSED LINE A

3" x 6" HDPE

ACCESS CROSSING

WITH SOIL AND

ASPHALT MILLINGS HIGH POINT

VENT A1

30.0' TYP

10+00

POWER POLE

EXPANSION

LOOP A3

NOTES:

1. POINT CLOUD SURFACE FROM U.S. GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017 STRATMAP17-50CM-3097514A3 LAS 2019: U.S. GEOLOGICAL SURVEY, AND U.S.

GEOLOGICAL SURVEY, 20191108, USGS LIDAR POINT CLOUD TX CENTRAL B1 2017

STRATMAP17-50CM-3097514A4 LAS 2019: U.S. GEOLOGICAL SURVEY. CURRENT TOPOGRAPHY MAY

DIFFER FROM THAT SHOWN. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO

THE START OF WORK.

2. FOR CLARITY, NOT ALL SITE FEATURES MAY BE SHOWN.

3. THE LIMITS OF WASTE WERE SURVEYED BASED ON FIELD MONUMENTS IN APRIL 2021 AS

PART OF THE FM 812 CLOSURE CERTIFICATION.

4. PROPOSED PIPE TO LAY ON TOP OF GROUND EXCEPT WHERE NOTED. PROVIDE ALL

FITTINGS NEEDED TO TRANSITION FROM BURIED TO ABOVE GROUND INSTALLATION. PLACE

PIPELINE MARKERS EVERY 50 FEET WHERE PIPE IS BURIED.

5. THE LEACHATE LINE AND APPURTENANCES MUST NOT BE WITHIN 7.5’ OF THE ELECTRICAL

POL…

This is the start of the file's text. The full file is on GovTribe.