IFB 27011 Drawings Godwin Pilot Part 3.pdf

PDF 10 MB Posted

Attached to
27011-JS Godwin - Pilot Building Renovation
Solicitation number
IFB-123940
Issued by
Suffolk City, Virginia

About this file

This is a technical specification document for IFB 27011, a plumbing scope of work for the Godwin-Virginian Pilot Building Renovation project in Virginia. The document provides detailed plumbing installation requirements and standards for the building renovation, including specifications for vent extensions, piping materials, fixture connections, and coordination with other trades. The specifications mandate compliance with state and local plumbing codes and require contractors to verify existing site conditions prior to bidding. All plumbing work must be completed as a first-class installation, with contractors responsible for furnishing and installing all equipment, fixtures, trim hardware, and devices necessary for satisfactory completion as determined by the architect, even if not explicitly shown on drawings.

The document establishes technical requirements for domestic hot and cold water systems, sanitary waste and vent piping, floor drains, and fire protection piping, with specific insulation requirements for pipes ranging from 0 to 6 feet above finished floors using rigid fiberglass pipe insulation with corrugated or smooth aluminum jackets complying with ASTM C1136. The specifications include fixture hot water discharge temperature limits and establish that any contractor proposing equipment with different physical or electrical characteristics than the basis of design equipment is responsible for coordinating with other trades and bearing all associated costs. The document includes a comprehensive legend of abbreviations and symbols for interpreting plumbing drawings and designates areas for new work, existing work to remain, and demolition requirements. Contractors are explicitly cautioned that failure to conduct a site visit and familiarize themselves with existing conditions shall not be a basis for change orders.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ALL PLUMBING VENTS WITHIN A 10'-0" RADIUS OF ANY ROOF TOP UNIT SHALL BE EXTENDED

TO A HEIGHT OF 3'-0" ABOVE THE FRESH AIR INTAKE.

ALL PLUMBING & PLUMBING MATERIALS SHALL MEET THE REQUIREMENTS OF THE STATE &

LOCAL PLUMBING CODES.

ALL WALL HYDRANTS SHALL BE MOUNTED 24" ABOVE FINISHED GRADE UNLESS OTHERWISE

SPECIFIED.

SLOPES & INVERT ELEVATIONS OF ALL INTERIOR PIPING SHALL BE ESTABLISHED BEFORE

ANY PIPING IS INSTALLED, IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED. ALL PIPING

SHALL BE RUN TO AVOID CONFLICTS WITH OTHER TRADES.

COORDINATE WITH ARCHITECTURAL WORKING DRAWINGS BEFORE ROUGHING-IN PLUMBING

FIXTURES.

MAKE PROPER HOT & COLD WATER, HOT WATER RECIRCULATING, WASTE, & VENT, ETC.,

PIPING CONNECTIONS TO ALL FIXTURES & EQUIPMENT EVEN THOUGH ALL BRANCHES,

FITTINGS & CONNECTIONS ARE NOT SHOWN.

COORDINATE LOCATION OF ALL EQUIPMENT, FIXTURES & PIPING WITH STRUCTURAL & ALL

OTHER TRADES. PIPING RUN AC SHALL BE RUN AS HIGH AS POSSIBLE.

ALL OPENINGS IN CEILINGS & PLENUM WALLS FOR PLUMBING PIPES SHALL BE SEALED AIR

TIGHT.

ALL HOT & COLD WATER PIPING INDICATED TO RUN ABOVE FINISHED CEILINGS OR IN

EXTERIOR WALLS SHALL BE INSTALLED ON THE CONDITIONED SPACE SIDE OF THE BUILDING

INSULATION.

SLOPES & INVERT ELEVATIONS OF EXTERIOR SEWERS, MANHOLES, ETC., SHALL BE

ESTABLISHED & VERIFIED BY PLUMBING CONTRACTOR BEFORE ANY PIPING IS INSTALLED IN

ORDER THAT PROPER SLOPES WILL BE MAINTAINED & NECESSARY INVERT ELEVATIONS

OBTAINED.

PROVIDE AUTOMATIC TRAP GUARDS FOR ALL FLOOR DRAINS.

IT IS THE INTENTION OF THESE DRAWINGS TO COVER ALL WORK & MATERIAL FOR A

COMPLETE FIRST CLASS INSTALLATION. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM

HARDWARE &/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT

SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT WHICH MAY BE NECESSARY

FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT)

SHALL BE FURNISHED & INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.

THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY FAMILIARIZE

HIMSELF/HERSELF WITH THE EXISTING CONDITIONS. NOT ALL EQUIPMENT AND

APPURTENANCES ARE SHOWN. FAILURE TO FOLLOW THIS STEP SHALL NOT BE A BASIS FOR

CHANGE ORDERS.

VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT,

PIPING, FIXTURES, ETC.

SEAL AROUND ALL WALL PENETRATIONS AIR TIGHT AT MECHANICAL ROOM, & FILL ANY VOIDS

WITH MORTAR.

INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS &

ALL APPLICABLE LISTING REQUIREMENTS.

INTERDISCIPLINARY COORDINATION

IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS DIFFERENT

PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO THE BASIS OF

DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING THESE

CHANGES WITH THE OTHER TRADES PRIOR TO ORDERING OF EQUIPMENT. IF THERE SHOULD

BE ANY ADDITIONAL WORK INCURRED BY THE OTHER TRADES AS A RESULT OF THIS

CONTRACTOR'S EQUIPMENT SELECTION, ALL COSTS ASSOCIATED WITH THE ADDITIONAL

WORK SHALL BE BORNE BY THIS CONTRACTOR.

GENERAL NOTES

DOMESTIC HOT WATER RETURN (HWR)

NEW POINT OF CONNECTION

SANITARY WASTE PIPE (WP)

SANITARY VENT PIPE (VP)

FLOOR DRAIN (FD)

PIPE TURN UP

PIPE TURN DOWN (DN)

PIPE CAPPED

BALL VALVE (BV)

WALL CLEAN OUT (WCO)

CLEAN OUT (CO)

LIMIT OF DEMOLITION WORK

SHEET WHERE SHOWN/CUT

DETAIL/RISER/ENLARGED PLAN

DEMOLITION NOTE DESIGNATION

NEW WORK NOTE DESIGNATION

FLOOR CLEAN OUT (FCO)

FIRE PROTECTION PIPING

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

DOMESTIC COLD WATER (CW)

DOMESTIC HOT WATER (HW)

GROUND CLEAN OUT (GCO)

WASTE STACK

LAVATORY

PLUMBING FIXTURE MARK

WATER COLUMN/WATER CLOSET

AUTOMATIC TRAP GUARD

WALL MOUNTED

KILOWATTS

MIN MINIMUM

WS

GALLONS PER HOURGPH

P-#

TYP TYPICAL

WC

W/ WITH

TG

WM

EXISTINGEXIST

ELEV ELEVATION

FDC

FLUSH TANK/FEETFT

CT COUNTER TOP

ELECTRICELEC

COMP COMPARTMENT

HWRP HOT WATER RECIRCULATING PUMP

GAL GALLON

HP HORSE POWER

GPM GALLONS PER MINUTE

INVERTINV

FIRE DEPARTMENT CONNECTION

LAV

MAX MAXIMUM

ADA

AC ABOVE CEILING

KW

AMERICANS WITH

DISABILITIES ACT COMPLIANT

ETR EXISTING TO REMAIN

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

WATER HEATER MARKWH-#

DFU DRAINAGE FIXTURE UNIT

SUPPLY FIXTURE UNITSFU

ASSE

LEGEND & ABBREVIATIONS

A/E ARCHITECT/ENGINEER

RIGID FIBER GLASS PIPE INSULATION SCHEDULE

PIPING SYSTEM SYSTEM TEMPERATURE

RANGE (°F)

DOMESTIC HW & HWR

DOMESTIC CW

HORIZONTAL RL & ORL

110 - 140

48 - 80

35 - 80

NOTE: PROVIDE CORRUGATED OR SMOOTH ALUMINUM JACKET FOR ALL INSULATED PIPES 0'-0"

TO 6'-0" ABOVE FINISHED FLOORS & MEZZANINES FOR INSULATION PROTECTION. ALL SERVICE JACKET SHALL BE WHITE KRAFT BONDED TO 0.025mm (1 MIL) THICK ALUMINUM FOIL, FIBERGLASS REINFORCED, WITH PRESSURE SENSITIVE ADHESIVE CLOSURE. COMPLY WITH ASTM

C1136. PROVIDE PREFORMED MOISTURE BARRIER JACKETS OVER FITTINGS AND VALVES.

PIPING INSULATION THICKNESS

LESS 1"

1"

1/2"

1/2"

1" TO LESS 1-1/2"

1"

1/2"

1/2"

1-1/2" & MORE

1-1/2"

1"

1/2"

FIXTURE HW DISCHARGE TEMPERATURES

PLUMBING FIXTURE MAXIMUM DISCHARGE

TEMPERATURE

REFERENCE STANDARD

PUBLIC HAND-WASHING FACILITIES

INDIVIDUAL SHOWER VALVES

>85°F & <110°F

≤120°F

ASSE 1070

ASSE 1016 OR CSA B125

NOTE: PROVIDE LISTED TEMPERING DEVICE FOR EACH FIXTURE PER TABLE.

SPRINKLER NOTE:

THIS BUILDING IS CURRENTLY PROTECTED BY A FULLY AUTOMATIC WET PIPE

SPRINKLER SYSTEM. THIS CONTRACTOR SHALL MODIFY THE EXISTING

SPRINKLER SYSTEM INSTALLATION AS REQUIRED TO SUIT NEW FLOOR PLANS

AND REFLECTED CEILING PLANS WITHIN THE LIMITS OF CONSTRUCTION.

SPRINKLER SYSTEM DESIGN, MATERIALS AND INSTALLATION SHALL BE IN

ACCORDANCE WITH NFPA 13, STATE, AND LOCAL AUTHORITIES. SPACING AND

LOCATION OF SPRINKLERS SHALL NOT EXCEED THAT PERMITTED FOR LIGHT

HAZARD OCCUPANCY. IN ACCORDANCE WITH NFPA 25, CONTRACTOR SHALL

TEMPORARILY TURN SPRINKLER HEADS UP DURING CONSTRUCTION AND AS

REQUIRED TO ACHIEVE A FULLY FUNCTIONAL SPRINKLER SYSTEM. ANY FIRE

WATCH REQUIRED WILL BE PERFORMED BY THE CONTRACTOR.

SPRINKLER SCHEDULE:

USE SPRINKLER TYPES BELOW FOR THE FOLLOWING APPLICATIONS:

ROOMS WITHOUT CEILINGS: UPRIGHT SPRINKLERS

ROOMS WITH SUSPENDED CEILINGS: CONCEALED SPRINKLERS.

MANUFACTURER'S RECOMMENDATIONS:

ALL MATERIAL AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH

THE MANUFACTURER'S RECOMMENDATION FOR THE INTENDED PURPOSE. USE

THE MORE STRINGENT METHODS WHEN MANUFACTURER'S

RECOMMENDATIONS, PLANS & SPECIFICATION REQUIREMENTS DIFFER. BRING

ANY CONFLICTS BETWEEN MANUFACTURER'S RECOMMENDATIONS, PLANS &

SPECIFICATION REQUIREMENTS TO THE OWNER'S ATTENTION.

FIRE STOPPING NOTE:

CONTRACTOR SHALL PROVIDE AN APPROPRIATE LISTED THROUGH-

PENETRATION FIRE STOPPING ASSEMBLY AT EACH PENETRATION OF FIRE

RATED CONSTRUCTION (I.E. WALLS AND SLABS, ETC.). FIRE STOPPING OF DUCT

PENETRATIONS THROUGH RATED ASSEMBLIES ARE ONLY PERMITTED WHEN

FIRE AND/ OR SMOKE DAMPERS ARE NOT REQUIRED. SLEEVES SHALL ONLY BE

PERMITTED WHERE INDICATED IN THE CONTRACTOR SELECTED THROUGH-

PENETRATION FIRE STOPPING ASSEMBLY. REFER TO ARCHITECTURAL

DRAWINGS FOR LOCATION OF ALL RATED ASSEMBLIES AND ASSOCIATED UL

DESIGNATIONS. DEVICES INSTALLED RECESSED WITHIN FIRE RATED

CONSTRUCTION (I.E. LIGHT SWITCHES, RECEPTACLES, ICE MAKER BOXES, ETC.)

ARE ONLY PERMITTED WHEN AN APPROVED LISTED FIRE STOPPING SYSTEM

EXISTS FOR THE APPLICATION. IF AN APPROVED LISTED FIRE STOPPING

SYSTEM IS NOT AVAILABLE, THE CONTRACTOR SHALL BRING THE CONDITION TO

THE ATTENTION OF THE A/E FOR RESOLUTION PRIOR TO PROCEEDING WITH

WORK.

SAW CUT NOTE:

CONTRACTOR SHALL VERIFY PIPE INVERTS PRIOR TO SAW CUTTING.

CONTRACTOR SHALL SAW CUT, REMOVE AND PATCH CONCRETE FLOOR AS

REQUIRED TO PERFORM WORK INDICATED. PATCH FLOOR TO MATCH ADJACENT

EXISTING CONDITIONS AND NEW CONDITIONS.

WALL WORK NOTE:

PLUMBING CONTRACTOR SHALL REMOVE PORTIONS OF EXISTING WALLS AS

REQUIRED FOR ACCESS TO EXISTING PLUMBING PIPING FOR REMODELING

WORK. CONTRACTOR SHALL PATCH TO MATCH EXISTING ADJACENT

CONDITIONS AND RATINGS. REFER TO ARCHITECTURAL PLAN FOR PATCHING

DETAILS AND NOTES.

PLUMBING COORDINATION NOTE:

CONTRACTOR SHALL COORDINATE CLOSELY WITH ALL TRADES TO ENSURE

PLUMBING IS INSTALLED WITHOUT CONFLICTING WITH OTHER BUILDING

SYSTEMS.

CONTRACTOR SHALL VERIFY AND COORDINATE THE EXACT LOCATION OF ALL

MECHANICAL, ELECTRICAL, PLUMBING, AND STRUCTURAL SYSTEMS AND

COMPONENTS (EXISTING AND NEW) PRIOR TO COMMENCING WORK.

REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION DETAILS.

CONTRACTOR SHALL VERIFY ALL POINTS OF CONNECTION TO EXISTING

SYSTEMS, PRIOR TO BEGINNING ANY WORK. THE FAILURE TO COMPLY WITH

THESE DIRECTIONS SHALL NOT CONSTITUTE THE BASIS FOR A CHANGE ORDER

SHOULD REWORK BE REQUIRED.

ANY CONDITIONS FOUND THAT WILL PROHIBIT MAKING THE FINAL

CONNECTIONS(S) OR EXECUTIONS OF THE WORK SHALL BE REPORTED TO THE

A/E IMMEDIATELY.

CONTRACTOR TO FIELD COORDINATE ALL PIPING LOCATIONS. WHERE THE

EXACT LOCATIONS OF SANITARY PIPING NOT KNOWN, CONTRACTOR TO FIELD

TRACE EXACT ROUTING PRIOR TO ANY SAW CUTTING.

ANY SHUT DOWNS OR INTERRUPTIONS IN SERVICE SHALL BE APPROVED BY

THE OWNER AT LEAST 7 DAYS BEFORE THE WORK IS TO BE EXECUTED. THE

CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR ANY DELAYS TO THE

PROJECT THAT ARISE DUE TO HIS FAILURE TO COMPLY WITH THESE

REQUIREMENTS.

SANITARY SEWER LINE SCOPE NOTE:

AS INDICATED IN THESE CONTRACT DOCUMENTS, CONTRACTOR SHALL SCOPE

AND SCAN ALL SEWER LINES WITHIN THE PROJECT LIMITS TO DETERMINE AND

DOCUMENT APPROXIMATE LOCATION, ROUTING, DEBRIS MATTER AND CLOGS

PRIOR TO COMMENCEMENT OF WORK. PROVIDE DRAWINGS AND DVD TO

OWNER AND ENGINEER FOR REVIEW.

OCCUPANCY NOTE:

BUILDING SHALL REMAIN OCCUPIED IN OTHER AREAS OF THE BUILDING.

CONTRACTOR SHALL TAKE CARE TO NOT INTERRUPT POWER, WATER, HVAC,

ETC. IF SHUT DOWNS OR SHUT OFFS ARE REQUIRED CONTRACTOR SHALL

NOTIFY FACILITIES IN WRITING WITH TIME AND SCHEDULE A MINIMUM OF 72

HOURS PRIOR TO COMMENCING WORK.

AMERICAN SOCIETY OF

SANITARY ENGINEERING

ROOF DRAIN SUMPS

(INCLUDING OVERFLOW)

35 - 80 1/2" 1/2" 1/2" A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U L

E

N U

M B

R

D

A T

S

C R

IP

T

IO

10015069.02

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

LEGEND, NOTES AND

ABBREVIATIONS

P-001

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

W

D

L W

D

30" HOSE

HOSE

BRACKET

DETAIL BASED ON AQUA BATH

48" MAX

38" MIN

30"

BOTTLE FILLER

DETAIL BASED ON ELKAY EX5TL8WS

WALL

MOUNTED

DETAIL BASED ON AMERICAN STANDARD, "LUCERNE" SERIES

FRP

WL

H

60"

36"

MOP BASINADA - KITCHEN SINK UNDER MOUNT

ADA - ROLL IN SHOWER

ADA - DUAL BASIN WATER COOLER

ADA - WALL MOUNTED LAVATORYADA - UNDERMOUNT LAVATORYADA - WATER CLOSET

FLOOR1-1/2"3"1/2"

MOUNTING

PIPE SIZES

HW CW WP VP

TRAPMARK DESCRIPTION

FLOOR MOUNTED MOP BASIN 'P'-TRAP 1/2"

DETAIL BASED ON FIAT, "MOLDED STONE" SERIES

SPECIFICATIONS:

1. MOP BASIN SHALL BE 24"Wx24"Lx10"H SINGLE PIECE MOLDED STONE.

2. FAUCET SHALL BE EXPOSED YOKE WALL MOUNT UTILITY FAUCET WITH CAST BRASS

BODY, 1/4 TURN CERAMIC VALVE CARTRIDGES, INTEGRAL VACUUM BREAKER & WALL

BRACE. PROVIDE WITH OFFSET SHANKS WITH INTEGRAL STOPS.

3. MOUNT FAUCET 36" AFF.

4. PROVIDE WALL MOUNTED MOP BRACKET, STAINLESS STEEL STRAINER, QUICK DRAIN

CONNECTIONS, 30" HOSE & HOSE BRACKET.

5. FRP SHALL EXTEND 2'-0" PAST EDGE OFF FIXTURE.

MOP BRACKET

P-7

KITCHEN SINK (2 COMPARTMENT)

[32" L x 22" W x 6" D ]

UNDER

MOUNT

1-1/2"2"1/2"1/2"'P'-TRAP

SPECIFICATIONS:

1. SEAMLESS DIE DRAWN 18 GAUGE STAINLESS STEEL ADA COMPLIANT SINK WITH

EXPOSED SURFACE POLISHED TO A NON-POROUS FINISH. FULLY COATED UNDERSIDE

INSULATED FOR SOUND AND CONDENSATE.

2. VIBRANT STAINLESS FINISH SIMPLICE PULL-DOWN KITCHEN SINK FAUCET WITH

THREE-FUNCTION SPRAYHEAD.

3. CHROME FINISH CAST BRASS LOOSE KEY ANGLE STOPS WITH CHROME FINISH RIGID

SUPPLY RISERS. OFFSET GRID STRAINER AND ADJUSTABLE 'P'-TRAP.

4. PROVIDE WITH IN-SINK-ERATOR (ISE) "BADGER" MODEL 5 GARBAGE DISPOSAL, 1/2 HP,

120 V, 6.3 A.

MOUNTING

PIPE SIZES

HW CW WP VP

TRAPMARK DESCRIPTION

P-6

SPECIFICATIONS:

1. PROVIDE PRESSURE BALANCING VALVE & SWIVEL SHOWER HEAD.

2. PROVIDE ADAWN6036 60" X 36" HUNTINGTON TERRAZO SHOWER FLOOR.

3. ADA COMPLIANT PRESSURE BALANCING VALVE WITH HAND SPRAY & SLIDE BAR

(SYMMONS 1--25-FSB FIXED HAND SHOWER WITH SLIDE BAR)

MOUNTING

FRAMED

ENCLOSURE

PIPE SIZES

HW

1/2"

CW

1/2"

WP

2"

VP

1-1/2"

TRAP

'P'-TRAP

MARK DESCRIPTION

TRANSFER SHOWERP-4

MOUNTING

WALL

MOUNTED

PIPE SIZES

HW

CW

1/2"

WP

1-1/2"

VP

1-1/2"

TRAP

'P'-TRAP

MARK DESCRIPTION

ADA - DUAL BASIN ELECTRIC

WATER COOLER

SPECIFICATIONS:

1. TWO LEVEL WALL MOUNT STAINLESS STEEL FOUNTAIN WITH RECESSED

REFRIGERATION SYSTEM WITH VANDAL RESISTANT BUBBLER, FRONT PANEL GRILL &

WALL MOUNTING FRAME. LEAD FREE CONSTRUCTION WITH SATIN STAINLESS FINISH

TO SUPPLY 8 GALLONS PER HOUR @ 50°F WITH 80°F ROOM TEMPERATURE. PROVIDE

WITH BOTTLE FILLER.

2. CHROME FINISH CAST BRASS LOOSE KEY ANGLE STOPS WITH CHROME FINISH RIGID

SUPPLY RISERS. GRID STRAINER & ADJUSTABLE 'P'-TRAP.

3. MOUNT PER MANUFACTURERS INSTRUCTIONS FOR ADA COMPLIANCE.

P-5

ADA - WALL MOUNTED LAVATORY 1-1/2"2"1/2"1/2"

SPECIFICATIONS:

1. VITREOUS CHINA ADA COMPLIANT WALL MOUNTED LAVATORY WITH FRONT

OVERFLOW AND FAUCET HOLES ON 4" CENTERS AND SELF DRAINING DECK.

2. VIBRANT BRUSHED NICKEL CAST BRASS SINGLE CONTROL CENTERSET FAUCET

POLISH VIBRANT BRUSHED NICKEL FINISH, CERAMIC VALVE, ADA COMPLIANT LEVER

HANDLE WITH COLOR INDEX, 0.5 GPM VANDAL RESISTANT AERATING SPRAY OUTLET,

LESS POP-UP. AS MANUFACTURED BY DELTA. PROVIDE THERMOSTATIC MIXING VALVE

SET AT 110°F MAX (ASSE 1070).

3. CHROME FINISH CAST BRASS LOOSE KEY ANGLE STOPS WITH CHROME FINISH RIGID

SUPPLY RISERS. OFFSET GRID STRAINER AND CAST BRASS ADJUSTABLE 'P'-TRAP

WITH ANSI AND ADA APPROVED, VINYL MOLDED INSULATION WITH NYLON FASTENER

KITS, PAINTED AS DIRECTED BY THE ARCHITECT.

4. CONCEALED FLOOR MOUNT SUPPORT. WALL BRACKETS SHALL NOT BE USED.

MOUNTING

PIPE SIZES

HW CW WP VP

TRAPMARK DESCRIPTION

P-3

MOUNTING

PIPE SIZES

HW CW WP VP

TRAPMARK DESCRIPTION

UNDER

MOUNT

1-1/2"2"1/2"1/2"'P'-TRAP

SPECIFICATIONS:

1. KOHLER, VERTICYL 17-1/8" ADA COMPLIANT UNDERMOUNT, RECTANGULAR VITREOUS

CHINA SINK, WHITE 2089.

2. KOHLER, TOUCHLESS SINGLE HOLE BATHROOM FAUCET, VIBRANT STAINLESS,

MODEL: K-13466-VS. CHROME PLATED SOLID BRASS ELECTRONIC FAUCET WITH

PROXIMITY OPERATION SENSORS, POLISH CHROME PLATED FINISH, CERAMIC VALVE,

0.5 GPM VANDAL RESISTANT AERATOR, INTEGRATED STRAINER TO PROTECT

SOLENOID VALVE & AERATOR, LESS POP-UP. BELOW DECK THERMOSTATIC MIXING

VALVE SET AT 110°F MAX (ASSE 1070). BATTERY OPERATED FAUCET.

3. CHROME FINISH CAST BRASS LOOSE KEY ANGLE STOPS WITH CHROME FINISH RIGID

SUPPLY RISERS. OFFSET GRID STRAINER AND ADJUSTABLE 'P'-TRAP.

HAND SINK 20"Wx17"Lx6-1/2"D (MIN. BOWL 14"Wx14L"x6-1/2"D)

P-2

34"

FLOOR

ADA - FLUSH VALVE WATER

CLOSET

INTEGRAL 1" 4" 2" FLOOR

MOUNTING

PIPE SIZES

HW

CW WP VP

TRAPMARK DESCRIPTION

SPECIFICATIONS:

1. VITREOUS CHINA ADA COMPLIANT FLOOR MOUNTED FLUSH VALVE WATER CLOSET

WITH FULLY GLAZED 2" TRAPWAY, ELONGATED SIPHON JET BOWL, 1.6 GALLONS PER

FLUSH.

2. PROVIDE TOTO FLUSH VALVE, MODEL TETIGNC-32. MATERIALS SHALL BE

CHLORAMINE RESISTANT.

3. WHITE SOLID PLASTIC OPEN FRONT ELONGATED SEAT WITH EXTERNAL CHECK

HINGES, INTEGRAL BUMPERS, LESS COVER.

PROVIDE TOTO, CT705L

P-1

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

FIXTURE PLATES

P-002

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

UP

UP

1 REMOVE EXISTING WATER CLOSETS COMPLETE. REMOVE WATER TO EXTENT

INDICATED ON PLAN. REMOVE VENT PIPING TO PENETRATION OF SECOND FLOOR

AND RETAIN FOR EXTENSION TO NEW FIXTURES. REMOVE WASTE PIPING TO BELOW

FLOOR AND CAP. PATCH FLOOR TO MATCH EXISTING ADJACENT CONDITIONS.

REMOVE EXISTING LAVATORY COMPLETE. REMOVE WATER TO EXTENT INDICATED ON

PLAN. REMOVE VENT PIPING TO PENETRATION OF SECOND FLOOR AND RETAIN FOR

EXTENSION TO NEW FIXTURES. REMOVE WASTE PIPING TO BELOW FLOOR AND CAP.

PATCH FLOOR TO MATCH EXISTING ADJACENT CONDITIONS.

REMOVE EXISTING WATER HEATER COMPLETE. REMOVE WATER TO EXTENT

INDICATED ON PLAN.

REMOVE EXISTING SERVICE SINK COMPLETE. REMOVE WATER TO EXTENT INDICATED

ON PLAN. REMOVE VENT PIPING TO PENETRATION OF SECOND FLOOR AND RETAIN

FOR EXTENSION TO NEW FIXTURES. REMOVE WASTE PIPING TO BELOW FLOOR AND

CAP. PATCH FLOOR TO MATCH EXISTING ADJACENT CONDITIONS.

REMOVE EXISTING COUNTERTOP SINK COMPLETE. MOVE WASTE PIPING TO BELOW

FLOOR AND CAP. PATCH FLOOR TO MATCH EXISTING ADJACENT CONDITIONS.

REMOVE EXISTING URINAL COMPLETE. REMOVE WASTE PIPING TO BELOW FLOOR

AND CAP. PATCH FLOOR TO MATCH EXISTING ADJACENT CONDITIONS.

REMOVE CW AND HW COMPLETE TO TOP OF EXISTING WATER SERVICE RISER.

REMOVE EXISTING FIXTURE COMPLETE. RETAIN EXISTING ROUGH IN FOR FUTURE

NEW WORK CONNECTION.

REMOVE 4" STACK FROM ABOVE CEILING TO BELOW FLOOR. PREPARE REMAINING

PIPING FOR OFFSET TO NEW LOCATION PER NEW WORK PLAN.

REMOVE EXISTING WATER AND WASTE ROUGH-IN PIPING SERVING PREVIOUS DENTAL

EQUIPMENT. REMOVE WATER AND VENT PIPING TO MAINS. REMOVE WASTE PIPE TO

BELOW FLOOR AND CAP.

5 5 5 5

EXISTING WATER

SERVICE TO REMAIN

3 3

WP-AC

WP-DN, ETR

WP-UP, ETR

8 8

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

GRAPHIC SCALE:

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

OVERALL FIRST FLOOR

PLAN - DEMOLITION

PD-101

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

NNOTES THIS SHEET

SCALE: 1/8" = 1'-0"

OVERALL DEMOLITION PLAN

B1

PLAN NORTH

EXISTING VTR TO REMAIN

1 REMOVE EXISTING ROOF DRAIN BODY COMPLETE. RETAIN

EXISTING RAIN LEADER PIPING FOR CONNECTION TO NEW

ROOF DRAIN PER NEW WORK PLAN.

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

OVERALL ROOF PLAN -

DEMOLITION

PD-102

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

SCALE: 1/8" = 1'-0"

OVERALL ROOF PLAN - DEMOLITION

B1

NOTES THIS SHEET

FCO

3" WP AC

FCO

WCO

P-1 P-1 P-4

P-2P-2

P-5

P-1

P-2

P-6

P-7

P-5

P-4

P-6

1 1

P-2

P-1

P-2

P-1

P-2

P-1

P-2

P-1

P-3

P-3

P601

P601

P-5

P-2

3" FD

W/TG

WP UP TO

SECOND FLOOR

FCO

1 1

157156 158155

138137

124 123 122 121 120 119 118

166167

127 126

132131130 134133 135

1 INSTALL NEW FIXTURE. CONNECT TO

EXISTING ROUGH-IN PIPING.

EXTEND 4" FROM EXISTING STACK

LOCATION TO NEW STACK LOCATION.

NEW 4" STACK.

EXTEND NEW 4" TO EXISTING PIPE

BELOW FLOOR.

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

OVERALL FIRST FLOOR

SANITARY PLAN - NEW

WORK

P-101

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

SCALE: 1/8" = 1'-0"

OVERALL NEW CONSTRUCTION SANITARY PLAN

B1

NOTES THIS SHEET

PLAN NORTH

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

101 VESTIBULE

102 LOBBY

103 CLOSET

104 VICTIM WITNESS CONFERENCE

105 COPY AREA

106 STAIR 1

107 STOR

108 CONFERENCE

109 VICTIM WITNESS DIRECTOR

110 TLT

111 ADA TLT

112 CORRIDOR

113 VICTIM WITNESS SUITE

114 INVESTIGATOR SUITE

115 STORAGE

116 CHIEF INVESTIGATOR

117 ASSISTANT CW ATTORNEY

118 ASSISTANT CW ATTORNEY

119 ASSISTANT CW ATTORNEY

120 ASSISTANT CW ATTORNEY

121 ASSISTANT CW ATTORNEY

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

141 ASSISTANT CW ATTORNEY

142 ASSITANT CW ATTORNEY

143 CORRIDOR

144 BREAK ROOM

145 COPY

146 ASSISTANT CW ATTORNEY

147 CORRIDOR

148 BREAK

149 STORAGE

150 CONFERENCE

151 STORAGE

152 ADA TLT

153 TLT

154 JANITOR

155 CHIEF ANIMAL CONTROL

OFFICER

156 SARGEANT

157 SARGEANT

158 HEAD POLICE OFFICER -

TRAINING COORD.

159 POLICE DEPT. OPEN OFFICE

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

122 DEPUTY CA

123 DEPUTY CA

124 DEPUTY CA

125 CHIEF DEPUTY CA

126 ADA TLT

127 TLT

128 STAFF ENTRY

129 CONFERENCE

130 HEAD CW ATTORNEY OFFICE

131 CHIEF ADMIN MANAGER

132 SUPERVISOR

133 ASSISTANT CW ATTORNY

134 ASSISTANT CW ATTORNEY

135 ASISSTANT CW ATTORNEY

136 COMMONWEALTH ATTORNEY

OPEN OFFICE

137 ASSISTANT CW ATTORNEY

138 CEASE FIRE CA

139 CONFERENCE

140 ASSISTANT CW ATTORNEY

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

160 SPRINKLER

161 ELEV

162 STORAGE

163 STORAGE

164 COMM/DATA /ELEC

165 STORAGE

166 WOMENS SHOWER

167 MENS SHOWER

168 CORRIDOR

169 ADA TLT

170 POLICE WELLNESS

171 ELEC

172 ELEC

173 STAIR 3

174 STORAGE

175 CORRIDOR

176 MOTHERS ROOM

177 STORAGE

178 STAIR 2

EXISTING VTR TO REMAIN

1 PROVIDE 4" ROOF DRAIN BODY

COMPLETE. MODIFY EXISTING RAIN

LEADER PIPING AS REQUIRED TO SUIT

NEW ROOF DRAIN ASSEMBLY

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

OVERALL ROOF PLAN -

NEW WORK

P-102

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

SCALE: 1/8" = 1'-0"

OVERALL ROOF PLAN - NEW WORK

B1

NOTES THIS SHEET

1 INSTALL NEW FIXTURE, EXTEND NEW

WATER TO EXISTING FIXTURE ROUGH

IN ABOVE CEILING.

PROVIDE NEW WATER HEATER. SEE

DETAIL ON SHEET P501 FOR MORE

INFORMATION.

EXTEND NEW CW FROM EXISTING CW

ABOVE CEILING.

P-1

P-2 P-2

P-5

P-4

P-1

P-6

P-7

P-5

P-4

P-6

P-2

P-1 P-1

P-2

P-2 P-1

P-2

P-3

P-1

P-3

TO HWRP-1

WH-1/HWRP-1

6" SPRINKLER

RISER, ETR

FDC,

ETR

P-5

EXISTING INCOMING

WATER SERVICE

P-2

157156 158155

138137

124 123 122 121 120 119 118

125 109

166167

111127 126 110

132131130 134133 135

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

OVERALL FIRST FLOOR

DOMESTIC WATER PLAN -

NEW WORK

P-201

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

NOTES THIS SHEET

SCALE: 1/8" = 1'-0"

OVERALL NEW CONSTRUCTION DOMESTIC WATER PLAN

B1

PLAN NORTH

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

101 VESTIBULE

102 LOBBY

103 CLOSET

104 VICTIM WITNESS CONFERENCE

105 COPY AREA

106 STAIR 1

107 STOR

108 CONFERENCE

109 VICTIM WITNESS DIRECTOR

110 TLT

111 ADA TLT

112 CORRIDOR

113 VICTIM WITNESS SUITE

114 INVESTIGATOR SUITE

115 STORAGE

116 CHIEF INVESTIGATOR

117 ASSISTANT CW ATTORNEY

118 ASSISTANT CW ATTORNEY

119 ASSISTANT CW ATTORNEY

120 ASSISTANT CW ATTORNEY

121 ASSISTANT CW ATTORNEY

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

141 ASSISTANT CW ATTORNEY

142 ASSITANT CW ATTORNEY

143 CORRIDOR

144 BREAK ROOM

145 COPY

146 ASSISTANT CW ATTORNEY

147 CORRIDOR

148 BREAK

149 STORAGE

150 CONFERENCE

151 STORAGE

152 ADA TLT

153 TLT

154 JANITOR

155 CHIEF ANIMAL CONTROL

OFFICER

156 SARGEANT

157 SARGEANT

158 HEAD POLICE OFFICER -

TRAINING COORD.

159 POLICE DEPT. OPEN OFFICE

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

122 DEPUTY CA

123 DEPUTY CA

124 DEPUTY CA

125 CHIEF DEPUTY CA

126 ADA TLT

127 TLT

128 STAFF ENTRY

129 CONFERENCE

130 HEAD CW ATTORNEY OFFICE

131 CHIEF ADMIN MANAGER

132 SUPERVISOR

133 ASSISTANT CW ATTORNY

134 ASSISTANT CW ATTORNEY

135 ASISSTANT CW ATTORNEY

136 COMMONWEALTH ATTORNEY

OPEN OFFICE

137 ASSISTANT CW ATTORNEY

138 CEASE FIRE CA

139 CONFERENCE

140 ASSISTANT CW ATTORNEY

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

160 SPRINKLER

161 ELEV

162 STORAGE

163 STORAGE

164 COMM/DATA /ELEC

165 STORAGE

166 WOMENS SHOWER

167 MENS SHOWER

168 CORRIDOR

169 ADA TLT

170 POLICE WELLNESS

171 ELEC

172 ELEC

173 STAIR 3

174 STORAGE

175 CORRIDOR

176 MOTHERS ROOM

177 STORAGE

178 STAIR 2

1-1/4" CW

SERVICE

1 1/4"

P-2

1/2"

P-1

1/2"

P-2 P-1 WH-1

1"

P-4 P-2 P-1 P-5 P-2 P-1 P-2 P-1 P-4

1-1/4" CW

SERVICE P-5 P-6 P-7 P-3 P-1 P-1 P-3 P-6 P-2 P-1 P-5 P-2

1 1/4"

1 1/4"1 1/4"

1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

1" 1"

1-1/4" SHUT

OFF VALVE

1-1/4" SHUT

OFF VALVE

RM 126 RM 127 RM 167 RM 166RM 168 RM 169 RM 166 RM 102 RM 148 RM 154 RM 153 RM 152 RM 144

P-1

1/2"

RM 110 RM 111

TO HRWP-13/4" HWR

RM 112

WATER RISER DIAGRAM

NO SCALE

WASTE RISER DIAGRAM - BATHROOM GROUP 1 WASTE RISER DIAGRAM - CORRIDOR

P-4

P-4

FCO

WCO

P-1

P-1

P-1

P-2

P-2

P-5

P-2

P-2

4", ETR

4"

FCO

P-6

4", ETR

4"

P-5

3" FD

W/TG

4"

2"

4"

2"

3"

2"

NO SCALE NO SCALE

FLOOR MOUNTED ELECTRIC WATER HEATER DETAIL

NO SCALE

EXPANSION TANK

HW SUPPLY

CW SUPPLY

UNION (TYP.)

3/4"

FINISH FLOOR FINISH FLOOR

FLOOR DRAIN

HWRP-1

CHECK VALVE

VACUUM RELIEF VALVE

DRAIN VALVE

BALL VALVE (TYP.)

DRAIN PAN & RELIEF PIPE TO FLOOR DRAIN.

SUPPORT TIGHT TO WALL AND PROVIDE

FITTINGS AS NECESSARY FOR NEAT OFFSET

3/4" TEMPERATURE PRESSURE RELIEF

VALVE AND LINE

NOTE: PROVIDE HEAT TRAP ON SUPPLY AND

DISCHARGE PIPING ASSOCIATED WITH WATER

HEATER

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

Lic. No. 058039

06/17/2026

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

P lu m bi ng .r vt

6/

/2

:4 4:

A

M

RISERS, SCHEDULES, AND

DETAILS

P-501

N. MARIANO

D. BOGGS

D. BOGGS

06/17/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

P101

P101

1. NOTE: ELECTRIC TANK WATER HEATERS 12 KW OR LESS REQUIRED EFFICIENCY RATING: UNDER 20 GAL = NO RATING. 20-55 GAL = 0.92-0.95 UEF. 56-119 GAL = UEF GREAT THAN 1 REQUIRED.

NOTES:

WH-1 TANK RM 172 80 46 36 9.0 208 3 1.8 0.8 FLOOR SEE NOTES

TAG TYPE LOCATION (GAL) 80°F 100°F KILOWATTS VOLTS PHASE VOLUME (GAL) VOLUME (GAL) MOUNTING REMARKS

STORAGE (GPH) TOTAL ACCEPTANCE

RECOVERY ELECTRICAL DATA EXPANSION TANK

ELECTRIC WATER HEATER SCHEDULE

2. DOMESTIC HOT WATER CIRCULATION PUMPS SHALL BE CONTROLLED WITH AN AQUASTAT. PUMP SHALL BE ENERGIZED IF TEMPERATURE FALLS 10°F BELOW WATER HEATER SETPOINT. PUMP SHALL BE DE-ENERGIZED IF TEMPERATURE EXCEEDS 5°F BELOW WATER HEATER SETPOINT. PROVIDE 7-DAY PROGRAMMABLE TIME CLOCK TO TURN PUMP OFF DURING NON OCCUPIED HOURS AN...

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS

NOTES:

HWRP-1 INLINE CIRCULATOR 2 15 RM 172 1/8 115 SINGLE SEE NOTES

TAG TYPE GPM HEAD LOCATION HP VOLTS PHASE REMARKS

DOMESTIC HOT WATER RECIRCULATING PUMP SCHEDULE

DEMOLITION

EXISTING HVAC PIPING, DUCTWORK, AND EQUIPMENT SHOWN IS BASED ON EXISTING

PLANS AND FIELD OBSERVATION WITHOUT DEMOLITION. AFTER DEMOLITION, ANY

CLARIFICATION REQUIRED TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO

THE ATTENTION OF THE ARCHITECT.

THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE

HIMSELF WITH THE EXISTING CONDITIONS.

DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR

SHALL TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY

PIPES, DUCTS, ETC. BEFORE REMOVAL.

REMOVAL OF ITEMS SHALL INCLUDE ASSOCIATED HANGERS, ANCHOR BOLTS AND

OTHER APPURTENANCES. WHERE SUCH REMOVAL RESULTS IN OPEN HOLES, VOIDS

OR EXPOSURE OF DAMAGED SURFACES, THE CONTRACTOR SHALL BE RESPONSIBLE

FOR REPAIRING AND FINISHING THE SURFACE TO MATCH ADJACENT CONDITIONS.

THIS WORK SHALL BE COORDINATED WITH ARCHITECTURAL FINISH SCHEDULES

WHERE APPLICABLE.

REMOVE EXISTING DUCTWORK AND PIPING NOT TO BE REUSED.

ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR

DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOME THE PROPERTY

OF THE CONTRACTOR, UNLESS OTHERWISE NOTED, AND SHALL BE REMOVED

COMPLETELY FROM THE SITE.

WHERE CEILINGS ARE REMOVED TO SUPPORT THE MECHANICAL WORK OUTLINED IN

THESE CONTRACT DOCUMENTS, CONTRACTOR SHALL INCLUDE THE COST TO

TEMPORARILY SUPPORT AND REINSTALL ALL CEILING MOUNTED DEVICES IN THE NEW

OR REINSTALLED CEILINGS, INCLUDING BUT NOT LIMITED TO, GRILLES, REGISTERS

AND DIFFUSERS, LIGHTS, FIRE ALARM DEVICES, CAMERAS, EXIT SIGNS, WIRELESS

ACCESS POINTS, ETC.

GENERAL ITEMS

GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH HVAC DRAWING OF

THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING.

COORDINATE THAT OUTSIDE AIR INTAKE OPENINGS FOR VENTILATION AIR ARE

LOCATED AT LEAST 10 FEET MEASURED IN ANY DIRECTION FROM ANY HAZARDOUS OR

NOXIOUS CONTAMINANT SOURCE SUCH AS FLUES, VENTS, CHIMNEYS, GAS METERS,

GAS REGULATORS, PLUMBING VENTS, ETC., UNLESS TOP OF SUCH INTAKE OPENING

IS 3 FEET OR GREATER BELOW ANY OF THE LISTED ITEMS.

OVERHEAD PIPING IN SPACES WITHOUT HUNG CEILINGS SHALL BE RUN AS CLOSE TO

ROOF DECK AS PRACTICAL, AS CLOSE TO PARALLEL JOISTS AS POSSIBLE AND ABOVE

LIGHTING FIXTURES TO CONCEAL PIPING.

OVERHEAD DUCTWORK AND PIPING IN SPACES WITH CEILINGS SHALL BE CONCEALED

UNLESS OTHERWISE NOTED.

PROVIDE PIPE SLEEVES LARGE ENOUGH TO ALLOW FOR REQUIRED LATERAL

MOVEMENT OF PIPING.

EXERCISE DUE CAUTION IN INSTALLING RUNOUTS AND BRANCH PIPING FROM MAINS

FOR EXPANSION MOVEMENT.

COORDINATE LOCATION OF GRILLES, REGISTERS, DIFFUSERS, THERMOSTATS AND

OTHER WALL OR CEILING MOUNTED HVAC ACCESSORIES WITH REFLECTED CEILING

PLAN, LIGHTING FIXTURE LAYOUT AND ACCESSORIES INSTALLED BY OTHER TRADES

SO AS TO PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE

ENTIRE BUILDING. IT IS THE INTENT FOR GRILLES, REGISTERS AND DIFFUSERS TO BE

INSTALLED IN THE CENTER OF CEILING PANELS.

EQUIPMENT ON THE ROOF SHALL BE INSTALLED SO AT LEAST 10 FEET OF CLEARANCE

SHALL BE MAINTAINED BETWEEN EQUIPMENT AND THE ROOF EDGE.

THE DIAMETER OF THE SUPPLY PIPE AT ANY GAS FIRED EQUIPMENT SHALL NOT BE OF

A SMALLER SIZE THAN THE INLET CONNECTION TO THE EQUIPMENT.

ARRANGE PIPING AND DUCTWORK, PARTICULARLY ABOVE CEILING AS REQUIRED TO

CLEAR STRUCTURE, DUCTS, CONDUITS, ETC. ALLOWING SPACE FOR PIPE HANGERS,

EXPANSION LOOPS AND ACCESS TO VALVES, FILTERS, AND MAINTENANCE OF

EQUIPMENT.

CONTRACTOR SHALL VERIFY REQUIRED REFRIGERANT PIPE SIZES AND QUANTITIES

WITH EQUIPMENT MANUFACTURER FOR THE INDICATED INSTALLATION.

COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES.

DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF

DOORS, WINDOWS, ETC.

THERMOSTATS AND SENSORS SHALL BE LOCATED IN THE ROOMS INDICATED.

INSTALL AT APPROXIMATELY 46" ABOVE FINISH FLOOR TO MATCH THE HEIGHT OF

WALL SWITCHES OR OTHER WALL MOUNTED DEVICES.

PIPING, DUCTWORK, VENTS, ETC., EXTENDING THROUGH EXTERIOR WALLS AND ROOF

SHALL BE FLASHED AND COUNTER FLASHED IN A WEATHERPROOF MANNER.

EXTEND DRAIN LINES AS INDICATED. ROUTING SHALL NOT INTERFERE WITH

PASSAGEWAYS AND MAINTENANCE. DRAINS FROM AIR CONDITIONING CONDENSATE

DRAIN PANS SHALL BE TRAPPED. SLOPE CONDENSATE DRAIN PIPING AT 1/4" PER

FOOT. VERIFY INVERT IS ESTABLISHED AFTER AIR HANDLING UNIT IS INSTALLED BUT

PRIOR TO DUCTWORK INSTALLATION.

ROOFTOP UNITS CONTAINING AIR CONDITIONING COILS SHALL BE OUTFITTED WITH A

MOISTURE SENSOR IN THE PRIMARY DRAIN PAN. THE SENSOR SHALL BE WIRED TO

DE-ENERGIZE THE EQUIPMENT IF WATER IS SENSED IN THE DRAIN PAN. INDOOR

MECHANICAL EQUIPMENT CONTAINING AIR CONDITIONING COILS SHALL BE OUTFITTED

WITH A MOISTURE SENSOR LOCATED IN THE DRAIN LINE.

ON DOWNFLOW UNITS AND UNITS WITHOUT A SECONDARY DRAIN PAN OR

PROVISIONS TO INSTALL A SECONDARY DRAIN PAN, A MOISTURE SENSOR SHALL BE

LOCATED IN THE PRIMARY DRAIN PAN (DEVICES INSTALLED IN THE DRAIN LINE ARE

NOT PERMITTED). THE SENSOR SHALL BE WIRED TO DE-ENERGIZE THE EQUIPMENT IF

WATER RISES ABOVE THE DRAIN OUTLET.

PIPING AND DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH NON-

RATED FLOORS, WALLS, ROOF AND PARTITIONS, UNLESS OTHERWISE INDICATED.

NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.

FOR PIPE SIZES NOT INDICATED ON PLANS, SEE FLOW DIAGRAMS.

RELIEF VALVE PIPING SHALL BE EXTENDED TO THE NEAREST FLOOR DRAIN.

FLOOR MOUNTED EQUIPMENT IN THE MECHANICAL ROOMS SHALL BE LOCATED ON 4"

THICK CONCRETE HOUSEKEEPING PADS UNLESS OTHERWISE INDICATED.

PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS.

ADDITIONAL SUPPORTS OR HANGERS SHALL BE ADJACENT TO ELBOWS, TO PREVENT

WEIGHT OF PIPING BEING PLACED ON THE EQUIPMENT.

CORRECT SETTING ON BALANCING FITTINGS SHALL BE PERMANENTLY MARKED.

LOCATE AND SIZE CURBS FOR MECHANICAL EQUIPMENT IN ACCORDANCE WITH

ACTUAL EQUIPMENT PURCHASED.

FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS.

THROUGH-PENETRATION FIRESTOP ASSEMBLIES

PROVIDE UL LISTED THROUGH-PENETRATION ASSEMBLIES FOR FIRE RATED

PARTITIONS, WALLS, AND FLOORS. REVIEW ARCHITECTURAL DRAWINGS FOR FIRE

PARTITION LOCATIONS AND UL LISTINGS.

SHEET METAL

PROVIDE INTERNAL SOUND ABSORPTIVE DUCT LINING FOR EXTENT NOTED. DUCT

DIMENSIONS ARE CLEAR INSIDE DUCT LINING DIMENSIONS.

PROVIDE ACCESS DOORS IN DUCTWORK WHERE INDICATED OR REQUIRED FOR

ACCESS TO SYSTEM COMPONENTS INCLUDING THE FOLLOWING:

DAMPER MOTORS AND/OR MOTOR OPERATED DAMPERS

FIRE DAMPERS

HIGH SIDEWALL REGISTERS OR GRILLES SHALL BE LOCATED 6" FROM CEILING TO TOP

OF REGISTER OR GRILLE.

INSTALL CEILING REGISTERS A MINIMUM OF 4" FROM EXTERIOR WALL.

PROVIDE A MINIMUM OF THREE TIMES THE FAN DIAMETER OF STRAIGHT DUCTWORK

OFF THE SUPPLY AIR FAN DISCHARGE BEFORE ANY TAKEOFFS OR ELBOWS.

DUCTWORK SHALL BE CONSTRUCTED TO THE SMACNA STATIC PRESSURE

CLASSIFICATION OF 2 IN. WG AND SEAL CLASS "A".

PROVIDE EXTENDED VOLUME DAMPER CONTROL RODS AND STAND-OFF BRACKETS

SO THAT HANDLES ARE WELL CLEAR OF DUCT INSULATION.

A2L PIPING REQUIREMENTS

REFRIGERANT PIPING LOCATED IN AREAS OTHER THAN THE ROOM OR SPACE WHERE

THE REFRIGERATING EQUIPMENT IS LOCATED SHALL BE LABELED. THE PERMANENT

PIPE LABELS SHALL BE LOCATED AT INTERVALS NOT EXCEEDING 20 FEET. MINIMUM

TEXT SHALL BE 1/2 INCH AND SHALL INDICATE THE REFRIGERANT DESIGNATION AND

SAFETY GROUP CLASSIFICATION OF REFRIGERANT USED IN THE PIPING SYSTEM AND

INCLUDE “DANGER— RISK OF FIRE OR EXPLOSION. FLAMMABLE REFRIGERANT.”

REFRIGERANT PIPING USED WITH GROUP A2L REFRIGERANTS AND LOCATED IN

CONCEALED LOCATIONS WHERE TUBING IS INSTALLED IN STUDS, JOISTS, RAFTERS

OR SIMILAR MEMBER SPACES, AND LOCATED LESS THAN 1-1/2 INCHES FROM THE

NEAREST EDGE OF THE STRUCTURAL MEMBER, SHALL BE CONTINUOUSLY

PROTECTED BY SHIELD PLATES. PROTECTIVE STEEL SHIELD PLATES SHALL HAVE A

MINIMUM THICKNESS OF 0.0575 INCH ((NO. 16 GAGE) AND SHALL COVER THE AREA OF

THE TUBE PLUS THE AREA EXTENDING NOT LESS THAN 2 INCHES BEYOND BOTH SIDES

OF THE TUBE.

MAINTENANCE

EQUIPMENT WITH FILTERS SHALL BE INSTALLED SO THAT FILTERS CAN BE EASILY

REMOVED AND REPLACED.

EQUIPMENT INSTALLED ABOVE CEILINGS SHALL BE MOUNTED APPROXIMATELY 12"

ABOVE CEILING (UON) FOR MAINTENANCE ACCESS.

INSTALL PIPE RUNS AT LEAST 6" ABOVE CEILING TILES. WHERE PRACTICAL INSTALL

VALVES, AND OTHER MAINTAINABLE DEVICES LOW ENOUGH TO REACH WITH A 6'

LADDER.

PROVIDE ACCESS TO ANY INSPECTION OR MAINTAINABLE DEVICE, EQUIPMENT, ETC. -

ACCESS OR ACCESS DOOR SHALL BE OF ADEQUATE SIZE TO WORK ON DEVICE.

EXAMINE MANUFACTURER'S LITERATURE TO DETERMINE RECOMMENDED

CLEARANCES. THESE CLEARANCES, IN ADDITION TO MINIMUM CLEARANCES

REQUIRED BY THE NATIONAL ELECTRICAL CODE, SHALL BE ESTABLISHED AND

MAINTAINED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THESE

REQUIREMENTS WITH ALL OTHER TRADES.

INTERDISCIPLINARY COORDINATION

IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS

DIFFERENT PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO

THE BASIS OF DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR

COORDINATING THESE CHANGES WITH THE OTHER TRADES PRIOR TO BID AND AGAIN

AFTER ORDERING OF EQUIPMENT. IF THERE SHOULD BE ANY ADDITIONAL WORK

INCURRED BY THE OTHER TRADES AS A RESULT OF THIS CONTRACTOR'S EQUIPMENT

SELECTION, ALL COSTS ASSOCIATED WITH THE ADDITIONAL WORK SHALL BE BORNE

BY THIS CONTRACTOR.

TESTING, ADJUSTING, AND BALANCING (TAB)

AIRSIDE AND WATERSIDE TAB SHALL BE PERFORMED ON ALL DUCTED AND NON-

DUCTED HVAC SYSTEMS. NON-DUCT HVAC SYSTEMS, INCLUDE, BUT ARE NOT LIMITED

TO, UNIT HEATERS, CABINET UNIT HEATERS, BASEBOARD HEATERS, DUCTLESS MINI-

SPLITS, DESTRATIFICATION FANS, LARGE CEILING FANS, INFRARED SPACE HEATERS,

AIR CURTAINS, ETC. IT SHALL BE THE RESPONSIBILITY OF THE TAB CONTRACTOR TO

DETERMINE APPROPRIATE TESTING, ADJUSTING AND BALANCING PROCEDURES FOR

SYSTEMS NOT LISTED BY THE PROCEDURAL STANDARDS CERTIFYING BODY (NEBB,

AABC, ETC.).

NEW POINT OF CONNECTION PIPE CAPPED

LIMIT OF DEMOLITION WORK

SHEET WHERE SHOWN/CUT

DETAIL/RISER/ENLARGED PLAN

DEMOLITION NOTE DESIGNATION

NEW WORK NOTE DESIGNATION

CONDENSATE DRAIN PIPINGD

EF-1 EXHAUST FAN DESIGNATION

FCU-1 FAN COIL UNIT DESIGNATION

LV-1 LOUVER DESIGNATION

UH-1 UNIT HEATER DESIGNATION

PIPE TURNING UP

PIPE TURNING DOWN

REFRIGERANT LIQUID PIPINGRL

REFRIGERANT SUCTION PIPINGRS

1 HOUR EXIT ENCLOSURE

FAN SWITCH

WALL THERMOSTAT/TEMPERATURE SENSOR

BACKDRAFT DAMPER

MOTORIZED DAMPER

VOLUME DAMPER

DOOR UNDERCUT (1")

BDD

UC

SMOKE DETECTOR

X

XXX

GRILLE, REGISTER, OR DIFFUSER MARK

(CFM AS INDICATED)

SUPPLY AIR/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST AIR DUCT SECTION

SUPPLY AIR/OUTSIDE AIR DUCT SECTION THROUGH FLOOR/ROOF

RETURN AIR DUCT SECTION THROUGH FLOOR/ROOF

EXHAUST AIR DUCT SECTION THROUGH FLOOR/ROOF

DUCT TURNING UP

DUCT TURNING DOWN

CEILING DIFFUSER WITH FLEXIBLE DUCTWORK

RETURN REGISTER WITH DUCTWORK

EXHAUST GRILLE WITH DUCTWORK

MITERED ELBOW WITH TURNING VANES

FLEXIBLE DUCT CONNECTOR

FS

T

S

M

DOAS-1 DEDICATED OUTSIDE AIR SYSTEM DESIGNATION

DSS-1 DUCTLESS SPLIT SYSTEM DESIGNATION

VRF-1 VARIABLE REFRIGERANT FLOW CONDENSING UNIT DESIGNATION

AFF ABOVE FINISHED FLOOR

A/P ACCESS PANEL

APD AIR PRESSURE DROP

APPROX APPROXIMATELY

CALC CALCULATED

CFM CUBIC FEET PER MINUTE

CO CLEANOUT

CSR CURRENT SENSING RELAY

db DECIBELS

DB DRY BULB TEMPERATURE

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB TEMPERATURE

EL ELEVATION

EWB ENTERING WET BULB TEMPERATURE

ETR EXISTING TO REMAIN

ESP EXTERNAL STATIC PRESSURE

FA FREE AREA

FLA FULL LOAD AMPS

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FT FEET

FV FACE VELOCITY

HP HORSEPOWER

IN INCH

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LDB LEAVING DRY BULB TEMPERATURE

LWB LEAVING WET BULB TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS PER HOUR

MCA MINIMUM CIRCUIT AMPS

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

NC NOISE CRITERIA

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

PD PRESSURE DROP

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SENS SENSIBLE

SF SQUARE FEET

SP STATIC PRESSURE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

W WATT

WB WET BULB TEMPERATURE

WG WATER GAUGE

°F DEGREE FAHRENHEIT

Ø PHASE/DIAMETER

AHU-1 AIR HANDLING UNIT DESIGNATION

HP-1 HEAT PUMP UNIT DESIGNATION

1 HOUR FIRE BARRIER

SMOKE PARTITION

FIRE / SMOKE DAMPER [120 VOLT]F/S

A I

N I

G

RI

VFOHTLAE

WN

O M

M O

C

P R

O F

ESS I ONAL ENG

I N

E E

R

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

Lic. No. 058039

05/22/26

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

M ec ha ni ca l.r vt

5/

/2

2:

:3

P

M

LEGEND, NOTES AND

ABBREVIATIONS

M-001

JZ

TNH

JZ

05/22/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

GENERAL NOTES LEGENDS AND ABBREVIATIONS

10015069.02

O F

E N E

E

Lic. No. 061125

06.17.26

06/17/2026

UP

T

T

T

T

T

T

T

T

T

1 REMOVE AIR HANDLING UNIT, HANGERS, AND SUPPORTS COMPLETE.

REMOVE DUCTWORK, HANGERS, AND SUPPORTS COMPLETE.

REMOVE AIR TERMINAL DEVICES COMPLETE.

REMOVE LOUVER AND ASSOCIATED DUCTWORK COMPLETE. SEE ARCHITECTURAL DRAWINGS FOR WALL REPAIR.

REMOVE EXHAUST FAN, HANGERS, SUPPORTS, AND CONTROL WIRING COMPLETE.

REMOVE EXHAUST WALL VENT TERMINATION. SEE ARCHITECTURAL DRAWINGS FOR WALL REPAIR.

REMOVE VENTILATION DUCTWORK, HANGERS, SUPPORTS, AND TAKEOFFS COMPLETE.

REMOVE CONDENSATE DRAIN PIPING, HANGERS, AND SUPPORTS COMPLETE. SEE ARCHITECTURAL DRAWINGS FOR WALL REPAIR.

REMOVE REFRIGERANT PIPING, HANGERS, AND SUPPORTS WITHIN PLENUM. ABONDON IN PLACE REFRIGERANT PIPING THROUGH SECOND FLOOR.

AND CAP.

REMOVE WALL EXHAUST FAN COMPLETE. SEE ARCHITECTURAL DRAWINGS FOR WALL REPAIR.

REMOVE UNIT HEATER AND SUPPORTS COMPLETE.

REMOVE THERMOSTAT AND ASSOCIATED CONTROL WIRING COMPLETE.

REMOVE AIR HANDLING UNIT SUSPENDED APPROXIMATLY 12'-0" ABOVE FINISHED FLOOR, HANGERS, AND ASSOCIATED APPURTENANCES

COMPLETE.

30"x30"4 30"x24"

48"x16"

48"x16" 36"x16" 30"x16"24"x16"

16"x12"

36"x16"

7 (TYP)

12"x12", (TYP)

EF10

6"x6"

EF5 6"ø 6"ø

EF5

5 EFWALL VENT, (TYP)

5 EF

5 EF

24"x20"

14"x14"

14"x10"

10"x10"

2 (TYP)

36"x20"28"x20"

18"x18"12"x12"

12"x12"

6"ø

6"ø

EF5

20"x10"

12"x8"

14"x10"

24"x20"

30"x20" 20"x10"

12"x12"

24"x24"

22"x22"

5 EF

5 EF

5 EF

3 (TYP)

6"ø6"ø

8 1", (TYP)

R S

/ R L

20"x18"

12"x12"

20"x20"

18"x18" 14"x14"

30"x16"

8 1", (TYP)

10"x10"

18"x18"

9 (TYP)

RS/RL 12"x12" 14"x14"

24"x24"

10"x10"

12"x12"

24"x16"

24"x14"

10"x10"

7.5 TONS

7.5 TONS

5 TONS

5 TONS

5 TONS

5 TONS

3 TONS

7.5 TONS

11 UH

11 UH

D

RS/RL

12 (TYP)

8 1", (TYP)

RS/RL

RS/RL

WALL

VENT,

(TYP)

8 1", (TYP)

D

D

REFRIGERANT RECOVERY NOTE:

REFRIGERANT FROM EXISTING MECHANICAL SYSTEMS SHALL BE RECOVERED

AND RECYCLED FOR RECLAIM. EQUIPMENT CAPABLE OF PULLING A VACUUM OF

LESS THAN 1000 MICRONS OF MERCURY SHALL BE USED TO RECOVER

REFRIGERANT. MECHANICAL SYSTEMS SHALL NOT BE OPENED TO

ATMOSPHERE UNTIL ALL REFRIGERANT IS FULLY RECOVERED. THE

CONTRACTOR SHALL PROVIDE CONTAINERS FOR THE STORAGE OF THE

REFRIGERANT. REFRIGERANT SHALL BECOME THE PROPERTY OF THE

CONTRACTOR.

A I

N I

G

RI

VFOHTLAE

WN

O M

M O

C

P R

O F

ESS I ONAL ENG

I N

E E

R

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

Lic. No. 058039

05/22/26

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

M ec ha ni ca l.r vt

5/

/2

2:

:4

P

M

OVERALL FIRST FLOOR

MECHANICAL PLAN -

DEMOLITION

MD-101

JZ

TNH

JZ

05/22/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

NOTES THIS SHEET

SCALE: 1/8" = 1'-0"

OVERALL FIRST FLOOR MECHANICAL PLAN - DEMOLITIONB1

PLAN NORTH

10015069.02

O F

E N E

E

Lic. No. 061125

AREA NOT

IN SCOPE

20"x14"

20"x12", ETR

12"x12"

3 3

1 REMOVE ABANDONED IN PLACE DUCTWORK, HANGERS, AND SUPPORTS COMPLETE TO LIMIT

INDICATED. CAP OPEN EDNDED DUCTWORK.

BATHROOM EXHAUST DUCT, EXHAUST FAN, AND ASSOCIATED GRILLES ARE EXISTING TO

REMAIN.

REMOVE REFRIGERANT PIPING, INSULATION, HANGERS, AND SUPPORTS TO THE EXTENT

SHOWN. CAP, SEAL, AND ABANDON IN PLACE REFRIGERANT PIPING ROUTED TO THE FIRST

FLOOR.

A I

N I

G

RI

VFOHTLAE

WN

O M

M O

C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

Lic. No. 058039

12/05/25

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

M ec ha ni ca l.r vt

5/

/2

2:

:4

P

M

OVERALL SECOND FLOOR

MECHANICAL PLAN -

DEMOLITION

MD-102

JZ

TNH

JZ

05/22/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

SCALE: 1/8" = 1'-0"

OVERALL SECOND FLOOR MECHANICAL PLAN - DEMOLITIONB1

PLAN NORTH

NOTES THIS SHEET

10015069.02

O F

E N E

E

Lic. No. 061125

1 REMOVE RTU-21 (CARRIER MODEL 50FCQM08, 7.5 TON, ROOFTOP UNIT). DISCONNECT UNIT AND TRANSITION CURB FROM ROOF CURB, DUCTWORK, CONTROL WIRING, AND ASSOCIATED APPURTENANCES COMPLETE. PROTECT, RETAIN, AND STORE UNIT AND TRANSITION CURB FOR RE-INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR BLOCKING/FLASHING REQUIREMENTS, COVER/SEAL ROOF PENETRATION AND DUCT OPENINGS WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE RTU-22 (CARRIER MODEL 50FCQM08, 7.5 TON, ROOFTOP UNIT). DISCONNECT UNIT AND TRANSITION CURB FROM ROOF CURB, DUCTWORK, CONTROL WIRING, AND ASSOCIATED APPURTENANCES COMPLETE. PROTECT, RETAIN, AND STORE UNIT AND TRANSITION CURB FOR RE-INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR BLOCKING/FLASHING REQUIREMENTS, COVER/SEAL ROOF PENETRATION AND DUCT OPENINGS WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE RTU-25 (CARRIER MODEL 50FCQM08, 7.5 TON, ROOFTOP UNIT). DISCONNECT UNIT AND TRANSITION CURB FROM ROOF CURB, DUCTWORK, CONTROL WIRING, AND ASSOCIATED APPURTENANCES COMPLETE. PROTECT, RETAIN, AND STORE UNIT AND TRANSITION CURB FOR RE-INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR BLOCKING/FLASHING REQUIREMENTS, COVER/SEAL ROOF PENETRATION AND DUCT OPENINGS WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE RTU-26 (CARRIER MODEL 50FCQM08, 7.5 TON, ROOFTOP UNIT). DISCONNECT UNIT AND TRANSITION CURB FROM ROOF CURB, DUCTWORK, CONTROL WIRING, AND ASSOCIATED APPURTENANCES COMPLETE. PROTECT, RETAIN, AND STORE UNIT AND TRANSITION CURB FOR RE-INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR BLOCKING/FLASHING REQUIREMENTS, COVER/SEAL ROOF PENETRATION AND DUCT OPENINGS WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE ROOF MOUNTED EXHAUST FAN AND DISCONNECT POWER/CONTROL WIRING, AND DUCTWORK FOR DURATION OF RE-ROOFING, ROOF CURB SHALL BE MODIFIED IN ACCORDANCE WITH THE ARCHITECTURAL DRAWINGS. SALVAGE FAN FOR REINSTALLATION.

COVER/SEAL ROOF PENETRATION WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE ROOF VENT AND DISCONNECT POWER/CONTROL WIRING AND DUCTWORK FOR DURATION OF RE-ROOFING, ROOF CURB SHALL BE MODIFIED IN ACCORDANCE WITH THE ARCHITECTURAL DRAWINGS. SALVAGE FOR REINSTALLATION. COVER/SEAL ROOF PENETRATION

WEATHERTIGHT FOR THE DURATION OF THE RE-ROOFING EFFORT.

REMOVE HEAT PUMP, EQUIPMENT RAILS, SUPPORT STEEL, AND ASSOCIATED APPURTENANCES COMPLETE. REFER TO ARCHITECTURAL

DRAWINGS FOR ROOF REPAIR.

REMOVE REFRIGERANT PIPING AND ROOF PENETRATION. CAP AND SEAL REFRIGERANT PIPING BELOW ROOF. SEE ARCHITECTURAL

DRAWINGS FOR ROOF REPAIR.

EF

EQUIPMENT

RAILS, (TYP)

, ETRRTU-27

RTU-26

RTU-25

, ETRRTU-23

RTU-21

RTU-22

6 RV

RD

7 7

8 8

RD RD

RD

ROOFTOP EQUIPMENT REMOVAL:

ROOFTOP EQUIPMENT SHALL BE REMOVED COMPLETELY FROM THE ROOF TO

PERMIT INSTALLATION OF NEW ROOF. COORDINATE STORAGE LOCATION WITH

OWNER/CONTRACTING OFFICER. REFER TO SPEC SECTION 23 0000 - 1.13 D FOR

TESTING AND INSPECTION OF ROOF MECHANICAL EQUIPMENT PRIOR TO REMOVAL.

REFRIGERANT RECOVERY NOTE:

REFRIGERANT FROM EXISTING MECHANICAL SYSTEMS SHALL BE RECOVERED

AND RECYCLED FOR RECLAIM. EQUIPMENT CAPABLE OF PULLING A VACUUM OF

LESS THAN 1000 MICRONS OF MERCURY SHALL BE USED TO RECOVER

REFRIGERANT. MECHANICAL SYSTEMS SHALL NOT BE OPENED TO

ATMOSPHERE UNTIL ALL REFRIGERANT IS FULLY RECOVERED. THE

CONTRACTOR SHALL PROVIDE CONTAINERS FOR THE STORAGE OF THE

REFRIGERANT. REFRIGERANT SHALL BECOME THE PROPERTY OF THE

CONTRACTOR.

A I

N I

G

RI

VFOHTLAE

WN

O M

M O

C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

05/22/26

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

M ec ha ni ca l.r vt

5/

/2

2:

:5

P

M

OVERALL ROOF PLAN -

DEMOLITION

MD-103

JZ

TNH

JZ

05/22/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

NOTES THIS SHEET

PLAN NORTH

SCALE: 1/8" = 1'-0"

OVERALL ROOF PLAN - DEMOLITION

B1

10015069.02

O F

E N E

E

Lic. No. 061125

S

30"x16" RA 20"x16" OA

FCU-1B

FCU-3

FCU-4

FCU-6

FCU-10

FCU-11

FCU-22A

FCU-9

FCU-12

FCU-18

FCU-17

FCU-15

FCU-14

FCU-5

FCU-13

F

C

C

C

C

B

B

B

B

B

B

A

A

A

80 A

F

F

F

F

F

F

FCU-8

C

A

C

A

FCU-1A

FCU-16

FCU-19

FCU-20

FCU-21

FCU-23

FCU-2

FCU-24

B

B

A

F

F

AA

AA

A

A

A

A

A

A

A

A

B

C

A

A

A

B

A

A

A

B

B

B

A

A 50

G

A

A

A

A

A

A

AA

AA

E

(TYP OF 4)

14"ø12"ø10"ø

E

K

8"ø6"ø

6"ø

12"x10"

6"ø

8"ø

14"x12"

10"ø

10"x10"

10"ø

20"x14"

G

G

G

8"x6"

8"x8"

14"x12"

J 940

DSS-1A

1 (TYP)

2 (TYP)

3 (TYP)

OPEN DUCT

WITH WIRE MESH

24"x14"

UH-16

UH-26

BC-1

BC-3

BC-4

BC-2

A

6 UH-3

FCU-22B

J

12"x12"12"x12"

10"ø

H 90

H 90

H 90 H 90

10"ø

10"x8"

10"ø

10"x6"

10"x6"

H 90

10"x8" 8"x8"10"x6"

10"x6" H

H

8"ø H

FCU-7

B

H

L

L

10"x10"

12"x10"

J

16"x8"

10"x6"H

H 230

10"x6" 10"x8"

10"ø

6"ø

8"ø

H

H

A

G

M

16"x8" 12"x14"

CF-1 CF-27 7

A

G

10"ø

12"x12"

J

16"x10"

B

B

12"x12"

J

16"x10"

A

8"ø

H

10"x6"

6"ø

6"ø

8"ø

8"ø H 200

8"ø

6"ø

J

8"ø

G

G

8"x8"

8"x8"

8"x6"

8"ø 8"ø

G

50 G 50 G 50

8"x8" 8"x6"

8"x8"

G 150

6"ø

10"ø

G

G

8"x6"

G

G

8"x6"

10"x8"

G

8"x6" 8"ø

6"ø

L

10"ø

L

L

J

16"x8"

L

L

14"x12"

J

G

10"x8"

G 65 G 65 G 65 G 65

8"x6"10"x8"

10"ø 8"ø

F

8"ø

A

10"ø

G

G

4 DSS-2A

A/P

A/P

2 (TYP) 3 (TYP)

F/S F/S

138137

157156 158155

124 123 122 121 120 119 118

106107

115 114

166167

111127 126 110

164 162

176169

1 PROVIDE VRF FAN COIL UNIT, DRAIN PAN, HANGERS, AND

SUPPORTS COMPLETE.

PROVIDE DUCTWORK, INSULATION, HANGERS, AND

SUPPORTS COMPLETE.

PROVIDE AIR TERMINAL DEVICES AND VOLUME DAMPERS

COMPLETE. ALL VOLUME DAMPERS SHALL BE LOCATED

ABOVE ACCESSIBLE CEILINGS OR ACCESS PANELS.

PROVIDE DUCTLESS SYSTEM INDOOR UNIT. MOUNT

BOTTOM OF UNIT 7"-6" ABOVE FINISHED FLOOR.

PROVIDE DOUBLE WALL, INTERSTITIALLY INSULATED,

SOLID INNER LINER, EXPOSED SPIRAL DUCTWORK.

PROVIDE UNIT HEATER, HANGERS, AND SUPPORTS

COMPLETE.

PROVIDE CEILING FAN, MOUNTING ROD, AND ASSOCIATED

APPURTENANCES COMPLETE. MOUNT 11'-0" ABOVE

FINISHED FLOOR.

A I

N I

G

RI

VFOHTLAE

WN

O M

M O

C

P R

O F

ESS I ONAL ENG

I N

E E

R

24'16'8'4'0

1/8"=1'-0"

ARCHITECTURE ENGINEERING GEOSPATIAL│ │

4433 CORPORATION LANE

SUITE 125

VIRGINIA BEACH, VA 23462

800.414.1045

1 2 3 4 5 6

A

B

C

D

E

SHEET NAME:

PROJECT NO:

DATE ISSUED:

SHEET NO:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

IS

S

U A

N C

E S

C H

E D

U

M B

S

C R

IP

T

TIMOTHY N. HAHN

Lic. No. 058039

05/22/26

A ut od es k D oc s:

//S uf fo lk

V A

C ity P ro je ct s

H U

B _B

0_

R

/2

M ec ha ni ca l.r vt

5/

/2

2:

:0

P

M

OVERALL FIRST FLOOR

DUCTWORK PLAN - NEW

WORK

M-101

JZ

TNH

JZ

05/22/2026

G O

D W

IN

V

IR

G

IN

IA

N

P

IL

O T

B U

IL

D

IN

G

C

IT

Y O

F S

U F

F O

LK

, V

A

N . M

A

IN

S T

. S U

F F

O

LK

V A

R E

N O

V A

T

IO

N

SCALE: 1/8" = 1'-0"

OVERALL FIRST FLOOR DUCTWORK PLAN - NEW WORKB1

NOTES THIS SHEET

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

101 VESTIBULE

102 LOBBY

103 CLOSET

104 VICTIM WITNESS CONFERENCE

106 STAIR 1

107 STOR

108 CONFERENCE

109 VICTIM WITNESS DIRECTOR

110 TLT

111 ADA TLT

112 CORRIDOR

113 VICTIM WITNESS SUITE

114 INVESTIGATOR SUITE

115 STORAGE

116 CHIEF INVESTIGATOR

OVERALL ROOM

SCHEDULE

RM # ROOM NAME

117 ASSISTANT CW ATTORNEY

118 ASSISTANT CW ATTORNEY

119…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .