| PRIORITY | REPORTDATE | DESCRIPTION | LOCATION |
| 4 | 3-Jan-06 | Door closer on men's restroom broken. Also 2 ducts on AC #5 on the roof needs replaceing. | HYBLA |
| 4 | 9-Jan-06 | Water Fountain: to much presure. water jumps on floor when the button is pushed. | HYBLA |
| 4 | 9-Jan-06 | Button dose not work for automatic door opener. | HYBLA |
| 4 | 9-Jan-06 | one tube out in ceiling light. | HYBLA |
| 4 | 9-Jan-06 | One sensor reading 65.75 deg. | HYBLA |
| 4 | 11-Jan-06 | Water faucet dose not work. | HYBLA |
| 4 | 11-Jan-06 | Water faucet leeking. | HYBLA |
| 4 | 11-Jan-06 | Electrical Panel door on wall will not close. | HYBLA |
| 4 | 11-Jan-06 | Emergency light dose not work. | HYBLA |
| 4 | 11-Jan-06 | One sensor (A1057T) reads 67.25 deg. | HYBLA |
| 4 | 11-Jan-06 | One sensor (A1032T) reads 67 deg. | HYBLA |
| 4 | 11-Jan-06 | One sensor (A4219T) reads 67 deg. | HYBLA |
| 4 | 12-Jan-06 | AHU #3 mix temp. is jumping from 25 to 48 deg. | HYBLA |
| 4 | 12-Jan-06 | 2Sensors (A4251 and 52) reads 79 deg. | HYBLA |
| 4 | 12-Jan-06 | One sensor reads 67.50 deg. | HYBLA |
| 4 | 27-Jan-06 | Sign in parking lot has been hit and is leaning. Needs to be reatached to pavement. | HYBLA |
| 4 | 27-Jan-06 | 2 sensors at 64.75 deg. Also 1 at 66.75, and 12 between 60.00 and 66.75. | HYBLA |
| 4 | 27-Jan-06 | 2 sensors reads 66.75 deg. Also 10 reads between 67.00 and 67.75 deg. | HYBLA |
| 4 | 27-Jan-06 | One sensor reads 61.00 deg. Also 5 sensors read between 65.75 and 67.00 deg. | HYBLA |
| 4 | 27-Jan-06 | Reading from temperature gun, Conference Room B read 66.00 deg. | HYBLA |
| 4 | 30-Jan-06 | Vents blowing down on Guards at front desk too cold. | HYBLA |
| 4 | 30-Jan-06 | One sensor (A1032T) reads 67 deg. | HYBLA |
| 4 | 30-Jan-06 | One sensor reads 67.25 and one reads 67.75 deg. | HYBLA |
| 4 | 30-Jan-06 | Two sensors reads 66.75 deg. | HYBLA |
| 4 | 2-Feb-06 | Sensor #A1025T and A1026T reads 67.25 deg. | HYBLA |
| 4 | 2-Feb-06 | Sensors A1025T and A1026T reads 67.25 deg. | HYBLA |
| 4 | 2-Feb-06 | One sensor reads 64.50 deg. | HYBLA |
| 4 | 2-Feb-06 | Sensors A4238T and A4239T reads 78.25 deg. | HYBLA |
| 4 | 6-Feb-06 | 3 Sensors (A4277T, 4278, and 4279) read 65.25 deg. | HYBLA |
| 4 | 6-Feb-06 | One sensor ( A4217T) reads 65.00 deg. | HYBLA |
| 4 | 6-Feb-06 | 3 sensors (A1026T, 1025, and 1021) read 66.75 deg. | HYBLA |
| 4 | 7-Feb-06 | 3 Sensors (A4279Y, 4277, and 4278) reads 65.50 deg. | HYBLA |
| 4 | 7-Feb-06 | 2 Sensors (A1049T and 1050) reads 67.00 deg. | HYBLA |
| 4 | 7-Feb-06 | 2 Sensors (A3183T and 3159) reads 67.75 deg. | HYBLA |
| 4 | 7-Feb-06 | One sensor ( A4217T) reads 65.50 deg. | HYBLA |
| 4 | 7-Feb-06 | One sensor (A1021T) reads 66.75 deg. | HYBLA |
| 4 | 8-Feb-06 | One sensor (A4217T) reads 63.50 deg. | HYBLA |
| 4 | 8-Feb-06 | One sensor (A1035T) reads 67.50 deg. | HYBLA |
| 4 | 8-Feb-06 | One sensor (A2097) reads 67.00 deg. | HYBLA |
| 4 | 10-Feb-06 | 4 Sensors (2093, 2092, 2098, and 2099) read 67.50 deg. | HYBLA |
| 4 | 10-Feb-06 | 4 Sensors (2092, 2093, 2098, and 2099) read 67.50 deg. | HYBLA |
| 4 | 10-Feb-06 | 4 Sensors (2092, 2093, 2098, and 2099) read 67.50 deg. | HYBLA |
| 4 | 10-Feb-06 | One sensor (A4217T) reads 63.75 deg. | HYBLA |
| 4 | 13-Feb-06 | 4 Sensors (A2142T, 2143, 2144, and 2145) read 67.75 deg. | HYBLA |
| 4 | 13-Feb-06 | One sensor (A1057T) reads 65.00 deg. | HYBLA |
| 4 | 13-Feb-06 | 2 Sensors (A3LOAT and A3LOBT) read 65.75 deg. | HYBLA |
| 4 | 13-Feb-06 | LADY RM 2ND FLOOR AWING PAPER SEAT COVER HOLDER NEED MOUNTING | HYBLA |
| 4 | 13-Feb-06 | 3 Sensors (A3159T, A4217T, and A1021T) read 65.75 deg. | HYBLA |
| 4 | 13-Feb-06 | MEN RM A WING TOILET PAPER HOLDER ABOUT TO FALL OFF WALL | HYBLA |
| 4 | 13-Feb-06 | Mix Temp. Sensor on AHU-03 reads 19.34 deg. | HYBLA |
| 4 | 13-Feb-06 | 4 Stair threads are broken. Need replacing. | HYBLA |
| 4 | 13-Feb-06 | NUMEROUS CEILING TOWLS MISSING IN SPACE [RM#232] | HYBLA |
| 4 | 13-Feb-06 | ELEVATOR AT THE END OF B WING ONE OF THE LIGHTS INSIDE IT NOT WORKING | HYBLA |
| 4 | 13-Feb-06 | LIGHT SWITCH IN RM BESIDE RM#234 NEXT TO ELEVATOR WORKS SOMETIMES | HYBLA |
| 4 | 13-Feb-06 | E WING LADYS RM ONE OF THE LIGHTS OVER SINK OUT | HYBLA |
| 4 | 13-Feb-06 | NUMEROUS LIGTH FIXTURE IN SPACE TUBES OUT RM#253 OLD TUBES IN CORNER OF RM | HYBLA |
| 4 | 13-Feb-06 | RM#258 COMPLETE LIGHT FIXTURES NOT LIT MORE THEN 4EACH MISSING CEILING TOWLS | HYBLA |
| 4 | 13-Feb-06 | RM#257 FURNITURE BLOCKING LIGTH SWITCHS | HYBLA |
| 4 | 13-Feb-06 | CEILING TOWLS NEED REPLACEMENT THU OUT SPACE RM#257 | HYBLA |
| 4 | 13-Feb-06 | STAIRWELL #2 SOME LAMPS [LIGHTS] ARE OUT | HYBLA |
| 4 | 13-Feb-06 | 2ND FLR HALLWAY NEAREST TO STAIRWELL#2 LIGTH CENTER TUBE OUT | HYBLA |
| 4 | 13-Feb-06 | rm#224 light fixtures look to be falling down | HYBLA |
| 4 | 13-Feb-06 | CEILING TOWLS MISSING OR BADLY DAMAGED RM#224 | HYBLA |
| 4 | 13-Feb-06 | RM#241& ADJOINTING [RM WITH IN RM] RELAMPING TUBES BALLAST IS NEEDED | HYBLA |
| 4 | 13-Feb-06 | RM#241& ADJOINTING RMS SPEAKERS ABOVE CEILING AND TOWLS MISSING | HYBLA |
| 4 | 13-Feb-06 | RM#247 CEILING TOWLS MISSING OR BADLY DAMAGED RELAMPING NEEDED ALSO | HYBLA |
| 4 | 13-Feb-06 | RM#222 LIGHT SWITCH UP SIDE DOWN [ON IS WHERE OFF SHOULD BE] | HYBLA |
| 4 | 13-Feb-06 | STAIRWELL C NEEDS RELAMPING | HYBLA |
| 4 | 13-Feb-06 | HALLWAY LIGHTS FOR C WING DON,T OPERATE CORRECTLY BY SWITCH | HYBLA |
| 4 | 14-Feb-06 | A WING CONFLUENCE AREA AND ADJOINTED [RMS] NEED RELAMPING | HYBLA |
| 4 | 14-Feb-06 | A WING BEYOND DOUBLE DOORS BATH[ RM] GFI TYPE REC NEEDED OVER SINK CODE | HYBLA |
| 4 | 15-Feb-06 | 1 Light tube out in hall close to room B-25. | HYBLA |
| 4 | 15-Feb-06 | 1 Emergency light out. | HYBLA |
| 4 | 15-Feb-06 | One light tube out. | HYBLA |
| 4 | 15-Feb-06 | 2 Sensors (a4238T and A4239T) reading 77.50 deg. | HYBLA |
| 4 | 22-Feb-06 | 4 Sensors read 67.25 deg. 1 Sensor reads 66.25 deg. | HYBLA |
| 4 | 22-Feb-06 | ONE SENSOR READS 65.50 DEG. | HYBLA |
| 4 | 22-Feb-06 | 2 Sensors ( A2119T & A2123T) read 65.50 deg. 5 more read under 68.00 deg. | HYBLA |
| 4 | 22-Feb-06 | 7 Sensors read from 66.50 to 67.75 deg. | HYBLA |
| 4 | 22-Feb-06 | 2 Sensors (A2098T & A2099T) read 67.50 deg. | HYBLA |
| 4 | 22-Feb-06 | One sensor (A4217T) reads 60.50 deg. and One sensor (A4242T) reads 67.50 deg. | HYBLA |
| 4 | 22-Feb-06 | One light tube out. | HYBLA |
| 4 | 22-Feb-06 | 1 tube out. 2 lights do not work. | HYBLA |
| 4 | 22-Feb-06 | 2 Tubes out. One row of lights will not come on. | HYBLA |
| 4 | 22-Feb-06 | 1 Sensor (A4217T) reads 64.75 deg. | HYBLA |
| 4 | 22-Feb-06 | MiX Temp. Sensor for AHU #3 reads 6.00 | HYBLA |
| 4 | 8-Mar-06 | One sensor (A1074T) reads 67.00 deg. | HYBLA |
| 4 | 8-Mar-06 | One sensor (A1021T) reads 66.75 deg. | HYBLA |
| 4 | 8-Mar-06 | Re-install one window valance and repair 1 sf. of wall covering. | HYBLA |
| 4 | 9-Mar-06 | 3 (4277 4278 & 4279) Sensors read 67.75 deg. | HYBLA |
| 4 | 13-Mar-06 | 2 Sensors(A2138T & A3LOJT) read 77.50 deg. | HYBLA |
| 4 | 13-Mar-06 | 3 Sensors (A3202T A3192T and A3193T) not in range. | HYBLA |
| 4 | 13-Mar-06 | One sensor (A1021T) reads 66.75 deg. | HYBLA |
| 4 | 14-Mar-06 | One sensor (A1021T) needs repair always reads to cold. | HYBLA |
| 4 | 14-Mar-06 | 2 sq. in. of wall coverning needs repair. | HYBLA |
| 4 | 14-Mar-06 | 9 Sensors to hot. | HYBLA |
| 4 | 16-Mar-06 | One Sensor (A1021) needs repair. | HYBLA |
| 4 | 24-Mar-06 | 2 Sensors (A3203T and A3201T) read 77.75 deg. | HYBLA |
| 4 | 24-Mar-06 | 3 Sensors (A4277T- 4278 and 4279) read 67.50 deg. | HYBLA |
| 4 | 24-Mar-06 | 5 Sensors (4287-4288-4289-4290-and 4291) reads from 60 deg. to 64.75 deg. | HYBLA |
| 4 | 27-Mar-06 | 2 Sensors(A4251T and 4252) read 78.50 deg. | HYBLA |
| 4 | 28-Mar-06 | Metal stair thred loose. | HYBLA |
| 4 | 29-Mar-06 | 2 Sensors ( A3202T and 3201 ) read 77.75 deg. | HYBLA |
| 4 | 3-Apr-06 | Light switch dose not work. | HYBLA |
| 4 | 3-Apr-06 | Door will not close properly. | HYBLA |
| 4 | 3-Apr-06 | 2 Sensors (A3201T and 3202 ) read 77.50 deg. | HYBLA |
| 4 | 3-Apr-06 | 3 Sensors (A4232T-4233- and 4234) read 77.50 deg. | HYBLA |
| 4 | 5-Apr-06 | Perimeter molding of ceiling pulled out of line/uneven. | HYBLA |
| 4 | 5-Apr-06 | One Ceiling tile not seated in grid. | HYBLA |
| 4 | 5-Apr-06 | One sensor (A3202T) reads 77.00 deg. | HYBLA |
| 4 | 5-Apr-06 | One sensor (A1032T) reads 67.75 deg. | HYBLA |
| 4 | 6-Apr-06 | Three sensor (A4277T-4278-and 4279) read 67.50 deg | HYBLA |
| 4 | 6-Apr-06 | One sensor (A3202T) reads 77.00 deg. | HYBLA |
| 4 | 6-Apr-06 | One sensor (A1032T) reads 67.75 deg. | HYBLA |
| 4 | 7-Apr-06 | One sensor (A3202T) reads 79.00 deg. | HYBLA |
| 4 | 7-Apr-06 | Uranil dose not flush properly. | HYBLA |
| 4 | 10-Apr-06 | 3 Sensors (A4277T-4278 and 4279) read 67.75 deg. Needa reheat coil in area. | HYBLA |
| 4 | 10-Apr-06 | One sensor (A3202T) reads 77.00 deg. | HYBLA |
| 4 | 10-Apr-06 | One sensor (A1032T) reads 66.75 deg. | HYBLA |
| 4 | 10-Apr-06 | Ceiling tile needs to be pushed down in grid. | HYBLA |
| 4 | 10-Apr-06 | One ceiling tile missing and right beside it there is a stained ceiling tile. | HYBLA |
| 4 | 10-Apr-06 | 2 Tubes out in ceiling light. | HYBLA |
| 4 | 11-Apr-06 | One sensor (A1074T) reads 67.50 deg. | HYBLA |
| 4 | 11-Apr-06 | One sensor (A1032T) reads 67.75 deg. | HYBLA |
| 4 | 12-Apr-06 | To much water pressure in water fountain. Squerts over fountain onto floor. | HYBLA |
| 4 | 12-Apr-06 | 4 Sensors (A2139T-2140-2157-and 2158) read 66.75 deg. | HYBLA |
| 4 | 12-Apr-06 | 4 Sensors (A4262T-4263-4249-and 4250) read from 66.25 to 66.75 deg. | HYBLA |
| 4 | 12-Apr-06 | 3 Sensors (A2094T-2095- and 2097) read 65.25 deg. | HYBLA |
| 4 | 13-Apr-06 | 3 Sensors (A2156T-2157-and 2158) read 66.50 deg. | HYBLA |
| 4 | 13-Apr-06 | 2 Sensors (A2094T and 2095) read 67.25 deg. | HYBLA |
| 4 | 13-Apr-06 | One ceiling tile not seated in grid. | HYBLA |
| 4 | 17-Apr-06 | 6 Sensors (A2139T-2140-2155-2156-2157-and 2158) read 64.75 | HYBLA |
| 4 | 17-Apr-06 | 7 Sensors under 68 deg. | HYBLA |
| 4 | 17-Apr-06 | 2 Sensors (A3194 & 3195) read 79 deg. Also A3204T reads 66.75 deg. | HYBLA |
| 4 | 17-Apr-06 | 4 Sensors (A4254T-4255-4260-and 4261) read 66.75 deg. | HYBLA |
| 4 | 17-Apr-06 | 3 Sensors (A2094T-2095-and 2097) One at 62.75 and two at 65.25 deg. | HYBLA |
| 4 | 17-Apr-06 | 3 sensors (A4221T-4222-nad 4219) read 66.00 deg. | HYBLA |
| 4 | 17-Apr-06 | One Sensor (A3184T) reads 78.25 deg. | HYBLA |
| 4 | 17-Apr-06 | 2 Sensors (A1061T and 1062) read 67 deg. | HYBLA |
| 4 | 18-Apr-06 | One light switch does not work. | HYBLA |
| 4 | 18-Apr-06 | Replace two water damaged ceiling tiles. | HYBLA |
| 4 | 20-Apr-06 | One sensor (A2138T) reads 78.75 deg. | HYBLA |
| 4 | 20-Apr-06 | One sensor (A3202T) reads 80.25 deg. | HYBLA |
| 4 | 20-Apr-06 | Two sensor (A3184T-3159) reads 78.25 deg. | HYBLA |
| 4 | 24-Apr-06 | 4 Sensors (A2155T-2156-2157-and 2158) read 65.25 deg. | HYBLA |
| 4 | 24-Apr-06 | 9 Sensors read under 68 deg. | HYBLA |
| 4 | 24-Apr-06 | 6 Sensors read under 68 deg. | HYBLA |
| 4 | 24-Apr-06 | 3 sensors under 68 deg. | HYBLA |
| 4 | 24-Apr-06 | 10 Sensors under 68 deg. | HYBLA |
| 4 | 24-Apr-06 | Urnal dose not flush. | HYBLA |
| 4 | 24-Apr-06 | Replace two ceililg tiles that has recently been painted. | HYBLA |
| 4 | 24-Apr-06 | Replace one water stained ceiling tile. | HYBLA |
| 4 | 25-Apr-06 | Fitting on water pipe in ceiling leaking. | HYBLA |
| 4 | 25-Apr-06 | Replace one water stained ceiling tile. | HYBLA |
| 4 | 25-Apr-06 | Re-attach loose vinyle base to wall. | HYBLA |
| 4 | 25-Apr-06 | One Sensors (A3204T) reads 66.50 | HYBLA |
| 4 | 25-Apr-06 | 2 Sensors (A4249T and 4250) read 66.25 deg. | HYBLA |
| 4 | 25-Apr-06 | 2 Sensors (A2077T and 2078) read 66.25 deg. | HYBLA |
| 4 | 26-Apr-06 | 2 Sensors (A4249T and 4250) read 66.50 deg. | HYBLA |
| 4 | 26-Apr-06 | 2 Sensors (A2077T and 2078) read 67.00 deg. | HYBLA |
| 4 | 26-Apr-06 | One Sensor (A4217T) reads 79.00 deg. | HYBLA |
| 4 | 26-Apr-06 | Replace 4 stained ceiling tiles. | HYBLA |
| 4 | 26-Apr-06 | Sand and paint window seal. | HYBLA |
| 4 | 26-Apr-06 | Sensor in alarm on chill water pump. S2CHP12SS--P12 | HYBLA |
| 4 | 26-Apr-06 | One Sensor (A3184T) reads 78.00 deg. | HYBLA |
| 4 | 27-Apr-06 | One water stained ceiling tile. | HYBLA |
| 4 | 1-May-06 | 6 Sensors read 66.25 deg. | HYBLA |
| 4 | 1-May-06 | One sensor (A4276T) reads 65.25 deg. | HYBLA |
| 4 | 1-May-06 | One sensor (A1032T) reads 67.75 deg. | HYBLA |
| 4 | 1-May-06 | Two sensors (A3160T and 3161) read 66.75 deg. | HYBLA |
| 4 | 1-May-06 | Three sensors (A4232T-4233- and 4234) read 78.75 deg. | HYBLA |
| 4 | 1-May-06 | Pump P-12 is in crit. alarm. | HYBLA |
| 4 | 1-May-06 | Ceiling light not properly seated in ceiling. | HYBLA |
| 4 | 1-May-06 | Paint window seal. | HYBLA |
| 4 | 2-May-06 | One sensor (A1070T) reads 67.75 deg. | HYBLA |
| 4 | 2-May-06 | One sensor (A3LOJT) reads 78.25 deg. | HYBLA |
| 4 | 2-May-06 | One sensor (A1032T) reads 67.25 deg. | HYBLA |
| 4 | 2-May-06 | Three sensors (A4232T-4233 and 4234) read 78.75 deg. | HYBLA |
| 4 | 2-May-06 | Tolets flushing to long ( 25 seconds) and to much pressure. | HYBLA |
| 4 | 3-May-06 | 4 Sensors (A3194T-3495- and 3202) read 78.25 deg. | HYBLA |
| 4 | 3-May-06 | 2 Sensors (A3159T and 3184) read 78.00 deg. | HYBLA |
| 4 | 8-May-06 | 2 Sensors (A4294T and 4296) read 67.00 deg. | HYBLA |
| 4 | 8-May-06 | One Sensor (A3LOET) reads 81 deg. | HYBLA |
| 4 | 8-May-06 | 4 Sensors (A3192T-3193-3194-and 3195) read 80.00 deg. | HYBLA |
| 4 | 8-May-06 | One Sensor (A4251T) reads 79.50 deg. | HYBLA |
| 4 | 8-May-06 | 3 Sensors (A3159T-3177 and 3179) read 79.00 deg. | HYBLA |
| 4 | 8-May-06 | One emergency light not working. Also some light tubes are out. | HYBLA |
| 4 | 8-May-06 | One 2x2 light tube out and there are 4 water stained ceiling tiles. | HYBLA |
| 4 | 8-May-06 | One water stained ceiling tile. | HYBLA |
| 4 | 8-May-06 | One light out. | HYBLA |
| 4 | 8-May-06 | Check for leek. One water stained ceiling tile. | HYBLA |
| 4 | 8-May-06 | There is a wet 2x2 ceiling tile in this area. Please check for pipe leek above ceiling. | HYBLA |
| 4 | 9-May-06 | One sensor (A4251T) reads 79.75 deg. | HYBLA |
| 4 | 9-May-06 | One sensor (A2080T) reads 77.50 deg. | HYBLA |
| 4 | 9-May-06 | One sensor (A4217T) reads 77.25 deg. | HYBLA |
| 4 | 9-May-06 | There is 2 water stained ceiling tiles in room 160. | HYBLA |
| 4 | 9-May-06 | Two water stained tiles and one ceiling light out. | HYBLA |
| 4 | 9-May-06 | One water stained tile. | HYBLA |
| 4 | 9-May-06 | One tube out in a 2x2 ceiling light. | HYBLA |
| 4 | 9-May-06 | One water stained ceiling tile. | HYBLA |
| 4 | 10-May-06 | One sensor (A3202T) reads 80.25 deg. | HYBLA |
| 4 | 10-May-06 | One sensor (A4551T) reads 77.50 deg. | HYBLA |
| 4 | 15-May-06 | 5 sensors under 70.00 deg. | HYBLA |
| 4 | 15-May-06 | One sensor reads 79.75 deg. | HYBLA |
| 4 | 15-May-06 | 6 sensors read under 70.00 deg. | HYBLA |
| 4 | 15-May-06 | 7 sensors read under 70.00 deg. | HYBLA |
| 4 | 15-May-06 | 11 sensors under 70.00 deg and onr reads 77.50 deg. | HYBLA |
| 4 | 15-May-06 | Tolet flushes to long (35 sec.) Please adjust. | HYBLA |
| 4 | 16-May-06 | 2 Sensors (A2139T and 2140) read 68.50 deg. | HYBLA |
| 4 | 16-May-06 | 2 Sensors (A4287T and 4289) read 68.00 deg. | HYBLA |
| 4 | 16-May-06 | 2 Sensors (A2077T and 2078) read 68.00 deg. | HYBLA |
| 4 | 16-May-06 | 1 Sensors (A4217T) reads 68.25 deg. | HYBLA |
| 4 | 16-May-06 | 1 Sensor (A4217) reads 68.25 deg. | HYBLA |
| 4 | 17-May-06 | 10 sensors read under 70 deg. | HYBLA |
| 4 | 17-May-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 17-May-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 17-May-06 | 13 Sensors under 70 deg. | HYBLA |
| 4 | 17-May-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 18-May-06 | 1 Sensor (A1058T) reads 69.50 deg. | HYBLA |
| 4 | 18-May-06 | 3 Sensors(4253-244-42254-and 4255) read 69.50 deg. | HYBLA |
| 4 | 18-May-06 | 4 Sensors (A2083T-2084-2096-and 2097) read 69.25 deg. | HYBLA |
| 4 | 18-May-06 | 1 Sensor (A3183T) reads 68.75 deg. | HYBLA |
| 4 | 19-May-06 | 3 water stained ceiling tiles. | HYBLA |
| 4 | 19-May-06 | 12 ceiling tiles out of grid. | HYBLA |
| 4 | 19-May-06 | 15 Sensors under 70 deg. | HYBLA |
| 4 | 19-May-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 19-May-06 | 6 sensors under 70 deg. | HYBLA |
| 4 | 22-May-06 | 1 light tube out. | HYBLA |
| 4 | 22-May-06 | 4 sensors under 70.00 deg. | HYBLA |
| 4 | 22-May-06 | 3 Sensors over 80.00 deg. | HYBLA |
| 4 | 22-May-06 | 2 Sensors under 70.00 deg. | HYBLA |
| 4 | 23-May-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 23-May-06 | 16 Sensors under 70 deg. | HYBLA |
| 4 | 23-May-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 23-May-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 24-May-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 24-May-06 | Carpet- Rubber transition strip loose from floor. Please glue down. | HYBLA |
| 4 | 24-May-06 | 3 Sensors read 79 deg. | HYBLA |
| 4 | 24-May-06 | 2 Sensors reads 69 deg. | HYBLA |
| 4 | 25-May-06 | 1 Broken ceiling tile and 2 out of grid. | HYBLA |
| 4 | 25-May-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 25-May-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 25-May-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 30-May-06 | 4 water stained ceiling tiles. | HYBLA |
| 4 | 30-May-06 | 1 water stained ceiling tile. | HYBLA |
| 4 | 30-May-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 30-May-06 | 3 Sensors under 70 deg. | HYBLA |
| 4 | 30-May-06 | 2 Sensors over 80 deg. | HYBLA |
| 4 | 30-May-06 | 1 Sensor reads 80.50 deg. | HYBLA |
| 4 | 31-May-06 | 2 Sensors (A2139T & 2140) read 68.75 deg. | HYBLA |
| 4 | 31-May-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 31-May-06 | 2 Sensors (A3194T & 3195) read 78.75 deg. | HYBLA |
| 4 | 31-May-06 | 1 Sensor (A3159T) reads 80.50 deg. | HYBLA |
| 4 | 1-Jun-06 | 3 Sensors read 69.50 deg. | HYBLA |
| 4 | 1-Jun-06 | 12 Ceiling tiles not in grid. | HYBLA |
| 4 | 1-Jun-06 | 2 Sensors read 80.50 deg. | HYBLA |
| 4 | 2-Jun-06 | Total of 3 lights out. | HYBLA |
| 4 | 2-Jun-06 | One light out. | HYBLA |
| 4 | 2-Jun-06 | 2 Sensors (A4274T & 4275) read 63.75 deg. | HYBLA |
| 4 | 2-Jun-06 | 2 Sensors read 78.75 deg. | HYBLA |
| 4 | 2-Jun-06 | One sensor feads 80.50 deg. | HYBLA |
| 4 | 5-Jun-06 | One emergency light not working. | HYBLA |
| 4 | 5-Jun-06 | One exit light not working. | HYBLA |
| 4 | 5-Jun-06 | One ceiling light flickering. | HYBLA |
| 4 | 5-Jun-06 | One ceiling light out. | HYBLA |
| 4 | 5-Jun-06 | 7 water stained ceiling tiles. | HYBLA |
| 4 | 5-Jun-06 | One light tube out. | HYBLA |
| 4 | 5-Jun-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 5-Jun-06 | 2 Sensors (A4274T and 4275) read 61.50 deg. | HYBLA |
| 4 | 6-Jun-06 | 9 Sensors under 70 deg. | HYBLA |
| 4 | 6-Jun-06 | 8 Sensors under 70 deg. | HYBLA |
| 4 | 6-Jun-06 | 2 Sensors (A3194T and 3195) read 78.75 deg. | HYBLA |
| 4 | 6-Jun-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | 8 Sensors under 70 deg. | HYBLA |
| 4 | 7-Jun-06 | One urnal in mens restroom flushes too long. ( 30 sec. ) | HYBLA |
| 4 | 8-Jun-06 | 3 Sensors read under 70 deg. | HYBLA |
| 4 | 8-Jun-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 8-Jun-06 | 4 Sensors read under 70 deg. | HYBLA |
| 4 | 12-Jun-06 | One sensor reads 66.75 deg. and one reads 69.75 deg. | HYBLA |
| 4 | 12-Jun-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 12-Jun-06 | 2 Sensors (A4274T and 4275) read 63.75 deg. | HYBLA |
| 4 | 13-Jun-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 13-Jun-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 13-Jun-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 13-Jun-06 | Faucet leeks. | HYBLA |
| 4 | 13-Jun-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 14-Jun-06 | 8 ceiling tiles out of grid. | HYBLA |
| 4 | 14-Jun-06 | A loose cover on Sanyo AC unit. | HYBLA |
| 4 | 14-Jun-06 | 3 water stained ceiling tiles. | HYBLA |
| 4 | 14-Jun-06 | Urnal dose not flush. | HYBLA |
| 4 | 14-Jun-06 | 2 sf. of wall needs to be painted where it was patched. | HYBLA |
| 4 | 14-Jun-06 | 5 Sensors read under 70 deg. | HYBLA |
| 4 | 14-Jun-06 | REPLACE BROKEN SOAP DISPENSER | HYBLA |
| 4 | 15-Jun-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 15-Jun-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 15-Jun-06 | 5 Sensors read under 70 deg. | HYBLA |
| 4 | 15-Jun-06 | The handy cap door open button on bathroom door dose not work. | HYBLA |
| 4 | 15-Jun-06 | 5 Sensors read under 70 deg. | HYBLA |
| 4 | 16-Jun-06 | 2 Sensors read under 70 deg. | HYBLA |
| 4 | 16-Jun-06 | 2 Sensors read 78 deg. | HYBLA |
| 4 | 16-Jun-06 | 2 Sensors read under 70 deg. | HYBLA |
| 4 | 26-Jun-06 | Loose ceiling light fixture bracket. | HYBLA |
| 4 | 26-Jun-06 | 2 sensors under 70 deg. | HYBLA |
| 4 | 27-Jun-06 | 4 sensors read under 70 deg. | HYBLA |
| 4 | 27-Jun-06 | 4 sensors read under 70 deg. | HYBLA |
| 4 | 27-Jun-06 | 3 Sensors read 68.00 deg. | HYBLA |
| 4 | 27-Jun-06 | 3 Sensors read 68.50 deg. | HYBLA |
| 4 | 28-Jun-06 | Door does not close. | HYBLA |
| 4 | 28-Jun-06 | Handycap button dose not work. | HYBLA |
| 4 | 28-Jun-06 | 3 Sensors read under 70 deg. | HYBLA |
| 4 | 28-Jun-06 | 3 Sensors read under 70 deg. | HYBLA |
| 4 | 28-Jun-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 29-Jun-06 | 9 Sensors are under 70 deg. | HYBLA |
| 4 | 29-Jun-06 | 4 Sensors under 70 deg. | HYBLA |
| 4 | 29-Jun-06 | 2 Sensors read under 70 deg. | HYBLA |
| 4 | 29-Jun-06 | One sensor (A3159Y) reads 77.75 deg. | HYBLA |
| 4 | 30-Jun-06 | 5 sensors under 70 deg | HYBLA |
| 4 | 30-Jun-06 | Sensor (A1051 reads 68.50 deg. | HYBLA |
| 4 | 30-Jun-06 | 2 Sensors (A1008T and 1009) read 68.50 deg. | HYBLA |
| 4 | 30-Jun-06 | 12 Sensors read under 70 deg. | HYBLA |
| 4 | 30-Jun-06 | Chiller point name ACHO1S PR13 has alarm. | HYBLA |
| 4 | 3-Jul-06 | 8 Sensors read from 77.25 to 79.00 deg. | HYBLA |
| 4 | 3-Jul-06 | 12 Sensors read from 77 to 80.50 deg. | HYBLA |
| 4 | 3-Jul-06 | 4 Sensors read 80.50 and 2 read 77.25 deg. | HYBLA |
| 4 | 3-Jul-06 | 10 Sensors read from 77.25 to 78 deg. | HYBLA |
| 4 | 3-Jul-06 | 2 Sensors read 79.75 and 2 read 77.25. | HYBLA |
| 4 | 3-Jul-06 | One Sensor (A3159T) reads 81.25 deg. | HYBLA |
| 4 | 3-Jul-06 | One sensor reads 68.75 and one reads 69.75. | HYBLA |
| 4 | 3-Jul-06 | One Sensor (A3159T) reads 81.25 deg. | HYBLA |
| 4 | 3-Jul-06 | 2 Sensors reads 69.00 deg. | HYBLA |
| 4 | 5-Jul-06 | 7 Sensors read under 70 deg. | HYBLA |
| 4 | 5-Jul-06 | 6 Sensors read 70 deg. or under. | HYBLA |
| 4 | 5-Jul-06 | 7 Sensors read 70 deg. or under. | HYBLA |
| 4 | 5-Jul-06 | 2 Sensors (A2094T and 2095) read 69.50 deg. | HYBLA |
| 4 | 5-Jul-06 | One Sensor (A1008T) reads 66.75 deg. | HYBLA |
| 4 | 5-Jul-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 5-Jul-06 | 7 Sensors 70 deg. or under. | HYBLA |
| 4 | 5-Jul-06 | 9 Sensors 70 deg. or under. | HYBLA |
| 4 | 10-Jul-06 | 3 Sensors under 70 deg. | HYBLA |
| 4 | 10-Jul-06 | 1 Sensor (A3LOKT) reads 77.75 deg. | HYBLA |
| 4 | 10-Jul-06 | 1 Sensor (A4275T) reads 67.25 deg. | HYBLA |
| 4 | 11-Jul-06 | One sensor (A2139T) reads 69.25 deg. | HYBLA |
| 4 | 11-Jul-06 | One sensor (A3209T) reads 67.75 deg. | HYBLA |
| 4 | 11-Jul-06 | Two sensors (A4274T and 4275) read 69.25 deg. | HYBLA |
| 4 | 11-Jul-06 | One sensor (A3159T) reads 80.00 deg. | HYBLA |
| 4 | 11-Jul-06 | One tube out in ceiling light. | HYBLA |
| 4 | 12-Jul-06 | One ceiling tile out of grid in each room. | HYBLA |
| 4 | 12-Jul-06 | Two ceiling tiles out of grid. | HYBLA |
| 4 | 12-Jul-06 | Two ceiling tiles out of grid. | HYBLA |
| 4 | 12-Jul-06 | 2 Sensors (A4290T and 4291) read 78.25. | HYBLA |
| 4 | 12-Jul-06 | 3 sensors read 77 deg. | HYBLA |
| 4 | 12-Jul-06 | One sensor (A1008T) reads 67 deg. | HYBLA |
| 4 | 12-Jul-06 | One sensor (A3159T) reads 82 deg. | HYBLA |
| 4 | 13-Jul-06 | 3 wet ceiling tiles. | HYBLA |
| 4 | 13-Jul-06 | One ceiling light not working. | HYBLA |
| 4 | 13-Jul-06 | One sensor (A2139T) reads 67.25. | HYBLA |
| 4 | 13-Jul-06 | 2 Sensors (A4174T and 4175) read 69.25. | HYBLA |
| 4 | 14-Jul-06 | One sensor reads 67 deg and one reads 77 deg. | HYBLA |
| 4 | 14-Jul-06 | One sensor reads 67 deg. | HYBLA |
| 4 | 17-Jul-06 | One sensor (A3202T) reads 78 deg. | HYBLA |
| 4 | 17-Jul-06 | 5 Sensors from 78 to 80 deg. | HYBLA |
| 4 | 17-Jul-06 | One sensor (A3159T) reads 78.25 deg. | HYBLA |
| 4 | 17-Jul-06 | One sensor (A1017T) reads 79.50. | HYBLA |
| 4 | 18-Jul-06 | 2 Sensors A4290T and 4291) read 78.25 deg. | HYBLA |
| 4 | 18-Jul-06 | One sensor (A2119T) reads 78.50 deg. | HYBLA |
| 4 | 18-Jul-06 | One sensor (A3209T) reads 68.75 deg. | HYBLA |
| 4 | 18-Jul-06 | Two sensors (A4274T and 4275) read 69.00 deg. | HYBLA |
| 4 | 18-Jul-06 | One sensor (A2087T) reads 78 deg. | HYBLA |
| 4 | 18-Jul-06 | Door dose not close all the way. | HYBLA |
| 4 | 19-Jul-06 | Door slams shut. Please adjust. | HYBLA |
| 4 | 19-Jul-06 | Urnal will not flush properly. | HYBLA |
| 4 | 19-Jul-06 | 4 Sensors 70 deg. | HYBLA |
| 4 | 19-Jul-06 | 4 Sensors at 70 deg. | HYBLA |
| 4 | 19-Jul-06 | One sensor (A3209T) reads 68.75 deg. | HYBLA |
| 4 | 19-Jul-06 | One sensor (A4275T) reads 65 deg. | HYBLA |
| 4 | 20-Jul-06 | Broken Floor Tile. | HYBLA |
| 4 | 20-Jul-06 | Two sensors (A2143T and 2144) read 69.50 deg. | HYBLA |
| 4 | 20-Jul-06 | Two sensors (A1069T and 1070) One 68 deg and one 69 deg. | HYBLA |
| 4 | 20-Jul-06 | One sensor (A3191T) reads 77.50 deg. | HYBLA |
| 4 | 20-Jul-06 | Urnal dose not flush properly. | HYBLA |
| 4 | 24-Jul-06 | 2 Tubes out in ceiling light. | HYBLA |
| 4 | 24-Jul-06 | Two Lights Out. | HYBLA |
| 4 | 24-Jul-06 | 5 lights out on left side of office. No light switch for right side of same office. | HYBLA |
| 4 | 24-Jul-06 | 5 Sensors from 68.50 to 69.00 deg. | HYBLA |
| 4 | 24-Jul-06 | One sensor reads 69.25 and one 70 deg. | HYBLA |
| 4 | 24-Jul-06 | 2 Sensors (A4274T & 4275) read 66.25 deg. | HYBLA |
| 4 | 25-Jul-06 | Urnal dose not flush. | HYBLA |
| 4 | 25-Jul-06 | One sensor (A3194T) reads 79.00 deg. | HYBLA |
| 4 | 25-Jul-06 | 5 Sensors read 70 deg. | HYBLA |
| 4 | 25-Jul-06 | 3 Sensors read 69.00 deg. | HYBLA |
| 4 | 25-Jul-06 | 2 Sensors 70 deg. | HYBLA |
| 4 | 25-Jul-06 | 2 Sensors read 70 Deg. | HYBLA |
| 4 | 25-Jul-06 | 8 Sensors at 70 deg. | HYBLA |
| 4 | 25-Jul-06 | 9 sensors read from 68.50 to 71.50 deg. | HYBLA |
| 4 | 25-Jul-06 | 8 Sensors read from 70 to 71 deg. | HYBLA |
| 4 | 25-Jul-06 | 4 Sensors read 71.50 deg. | HYBLA |
| 4 | 26-Jul-06 | 9 sensors read 70 deg. | HYBLA |
| 4 | 26-Jul-06 | 8 Sensors read 70 deg. or under. | HYBLA |
| 4 | 26-Jul-06 | 7 Sensors 71 deg. or under. | HYBLA |
| 4 | 26-Jul-06 | 7 Sensors 71 deg. or under. | HYBLA |
| 4 | 26-Jul-06 | 6 Sensors 71 deg. or under. | HYBLA |
| 4 | 26-Jul-06 | 9 Sensors 71 deg. or under. | HYBLA |
| 4 | 27-Jul-06 | One Sensor (A1074T) reads 68.75 deg. | HYBLA |
| 4 | 27-Jul-06 | One Sensor (A3204T) flashing reads 79.50. deg. | HYBLA |
| 4 | 27-Jul-06 | One Sensor (A4299T) reads 68.50. | HYBLA |
| 4 | 27-Jul-06 | One Sensor Reads 69.50 deg. | HYBLA |
| 4 | 28-Jul-06 | Two tubs out in ceiling light. | HYBLA |
| 4 | 28-Jul-06 | Please move pallet with furniture parts out of hallway. | HYBLA |
| 4 | 28-Jul-06 | One sensor (A3LOLT) reads 68.75 deg. | HYBLA |
| 4 | 28-Jul-06 | One sensor flashing 77.50 deg. | HYBLA |
| 4 | 31-Jul-06 | 4 Sensors flashing 80 to 81 deg. | HYBLA |
| 4 | 31-Jul-06 | 4 Sensors flashing three at 78 and 1 at 83 deg. | HYBLA |
| 4 | 31-Jul-06 | 10 Sensors flashing from 77.75 to 79 deg. | HYBLA |
| 4 | 31-Jul-06 | 13 Sensors flashing fron77 to 79.75 deg. | HYBLA |
| 4 | 31-Jul-06 | 10 Sensors flashing 77 to 79.50 deg. | HYBLA |
| 4 | 31-Jul-06 | One sensor (A3194T) reads 81 deg. | HYBLA |
| 4 | 31-Jul-06 | One sensor 81 deg. and two flashing 80 deg. | HYBLA |
| 4 | 31-Jul-06 | 6 Sensors read 78 and 79 deg. | HYBLA |
| 4 | 1-Aug-06 | One Sensor (A2119T) reads 79 deg. | HYBLA |
| 4 | 3-Aug-06 | One Sensor (A2120T) reads 69.50 deg. | HYBLA |
| 4 | 7-Aug-06 | One Sensor (A2119T) reads 80.50 deg. | HYBLA |
| 4 | 7-Aug-06 | One sensor (A4276T) reads 68.75 deg. | HYBLA |
| 4 | 7-Aug-06 | One sensor (A1071T) reads 81.50 deg. | HYBLA |
| 4 | 8-Aug-06 | Cab Failure on building computer. DDC dose not show temputure readings on 4 areas. | HYBLA |
| 4 | 9-Aug-06 | One Sensor (A1074T) reads 69.75 deg. | HYBLA |
| 4 | 9-Aug-06 | 4 Sensors read 68 and 69 deg. | HYBLA |
| 4 | 9-Aug-06 | 4 Sensors read 69 deg. | HYBLA |
| 4 | 9-Aug-06 | One sensor (A4299T) reads 69 deg. | HYBLA |
| 4 | 10-Aug-06 | One senser (A4263T) reads 69.75 deg. | HYBLA |
| 4 | 10-Aug-06 | Two sensors (A2094T and 2095) read 69 deg. | HYBLA |
| 4 | 11-Aug-06 | 2 Sensors (A4289T and 4290) read 77 deg. | HYBLA |
| 4 | 11-Aug-06 | 2 Sensors (A1070T and 1074) read 69.75 deg. | HYBLA |
| 4 | 11-Aug-06 | 5 Sensors read 69 deg. | HYBLA |
| 4 | 11-Aug-06 | 10 Sensors read 69 deg. or under. | HYBLA |
| 4 | 21-Aug-06 | one sensor (1017) reads 78 deg. and One (1021) reads 69.75 deg. | HYBLA |
| 4 | 21-Aug-06 | One sensor (A4285T) reads 68.25 deg. | HYBLA |
| 4 | 22-Aug-06 | One sensor (A4235T) reads 69 deg. | HYBLA |
| 4 | 23-Aug-06 | 4 Sensors read 69.75 deg. | HYBLA |
| 4 | 23-Aug-06 | 2 Sensors read 69.75 deg. | HYBLA |
| 4 | 23-Aug-06 | 2 Sensors read 69.75 deg. | HYBLA |
| 4 | 24-Aug-06 | 3 Sensors under 70 deg. | HYBLA |
| 4 | 24-Aug-06 | One tube out. | HYBLA |
| 4 | 24-Aug-06 | One Tube out. | HYBLA |
| 4 | 24-Aug-06 | One tube out. | HYBLA |
| 4 | 24-Aug-06 | Two ceiling lights out. One on each end of room. | HYBLA |
| 4 | 28-Aug-06 | One sensor reads 79.50 deg. | HYBLA |
| 4 | 28-Aug-06 | Two sensors read 81 deg. | HYBLA |
| 4 | 28-Aug-06 | One sensor reads 69.00 deg. | HYBLA |
| 4 | 28-Aug-06 | One tube blinking on and off in light. | HYBLA |
| 4 | 29-Aug-06 | One sensor (A4285T) reads 68.50 deg. | HYBLA |
| 4 | 30-Aug-06 | 2 Tubes out. | HYBLA |
| 4 | 5-Sep-06 | 2nd. Floor to cold. 31 Sensors read under 70 deg. | HYBLA |
| 4 | 12-Sep-06 | One sensor (A4299T) reads 68.75 deg | HYBLA |
| 4 | 12-Sep-06 | One sensor (A4265T) reads 68.50 deg. | HYBLA |
| 4 | 12-Sep-06 | 17 Sensors read under 70 deg. | HYBLA |
| 4 | 12-Sep-06 | 27 Sensors read under 70 deg. | HYBLA |
| 4 | 12-Sep-06 | Tolet seat cover holder off wall. Please re-attach. | HYBLA |
| 4 | 13-Sep-06 | 3 Sensors flashing 78 deg. | HYBLA |
| 4 | 13-Sep-06 | A total of 17 Sensors under 70 deg. | HYBLA |
| 4 | 13-Sep-06 | One tube out in ceiling light. | HYBLA |
| 4 | 18-Sep-06 | One tube out in ceiling light. | HYBLA |
| 4 | 18-Sep-06 | One tube out. Ceiling light. | HYBLA |
| 4 | 19-Sep-06 | One sensor (A1032T) reads 68.75 deg. | HYBLA |
| 4 | 19-Sep-06 | 22 Sensors on 2nd floor read under 70 deg. | HYBLA |
| 4 | 20-Sep-06 | One sensor (A4265T) reads 69.75 deg. | HYBLA |
| 4 | 20-Sep-06 | 27 Sensors under 70 deg. | HYBLA |
| 4 | 21-Sep-06 | Two sensors (A4293T and 4294) read 69.50 deg. | HYBLA |
| 4 | 25-Sep-06 | 2 Sensors read 77 deg. | HYBLA |
| 4 | 25-Sep-06 | One Sensor (A4285T) reads 77.75 deg. | HYBLA |
| 4 | 25-Sep-06 | 2 Sensors read 69 deg. | HYBLA |
| 4 | 26-Sep-06 | 3 Sensors read under 70 deg. | HYBLA |
| 4 | 26-Sep-06 | 29 Sensors under 70 deg. | HYBLA |
| 4 | 27-Sep-06 | 2 Sensors (A2145T and 2146) read 77.75 deg. | HYBLA |
| 4 | 27-Sep-06 | One sensor (A4285T) reads 68.25 deg. | HYBLA |
| 4 | 27-Sep-06 | Two sensors (A1061T and 1062) read 69.75 deg. | HYBLA |
| 4 | 27-Sep-06 | 2 Sensors (A4263T and 4265) read 66.50 deg. | HYBLA |
| 4 | 27-Sep-06 | A lot of sensors under 70 deg. on 2nd floor. | HYBLA |
| 4 | 27-Sep-06 | One sensor (A4265T) reads 67 deg. | HYBLA |
| 4 | 28-Sep-06 | 3 Sensors (A4277T--4278--and 4279) read 68.75. | HYBLA |
| 4 | 28-Sep-06 | Check sensors on 2nd floor. | HYBLA |
| 4 | 2-Oct-06 | 11 Sensors under 70 deg. | HYBLA |
| 4 | 2-Oct-06 | 8 Sensors under 70 deg. | HYBLA |
| 4 | 2-Oct-06 | 13 Sensors under 70 deg. | HYBLA |
| 4 | 2-Oct-06 | 24 Sensors under 70 deg. | HYBLA |
| 4 | 2-Oct-06 | 19 Sensors under 70 deg. | HYBLA |
| 4 | 3-Oct-06 | 6 Sensors at 77 deg. | HYBLA |
| 4 | 3-Oct-06 | 3 Sensors under 70 deg. | HYBLA |
| 4 | 3-Oct-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 3-Oct-06 | Take out pink tube in ceiling light and put in building standard tube. | HYBLA |
| 4 | 3-Oct-06 | One tube out in ceiling light. | HYBLA |
| 4 | 3-Oct-06 | One tube out in ceiling light. | HYBLA |
| 4 | 3-Oct-06 | One ceiling light out. | HYBLA |
| 4 | 3-Oct-06 | One tube out in two different lights. | HYBLA |
| 4 | 3-Oct-06 | One ceiling light out. | HYBLA |
| 4 | 3-Oct-06 | 4 Tubes out in two different ceiling lights. | HYBLA |
| 4 | 3-Oct-06 | Two tubes out in ceiling light. | HYBLA |
| 4 | 3-Oct-06 | One ceiling light out. | HYBLA |
| 4 | 4-Oct-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 4-Oct-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 4-Oct-06 | 22 Sensors read from 66.25 to 69.75 deg. | HYBLA |
| 4 | 6-Oct-06 | 5 Sensors 69.75 deg. | HYBLA |
| 4 | 6-Oct-06 | 9 Sensors under 70 deg. | HYBLA |
| 4 | 6-Oct-06 | 22 Sensors read from 67.25 to 69.75 deg. | HYBLA |
| 4 | 10-Oct-06 | Sign leaning over in parking lot. Please reattach to pavement. | HYBLA |
| 4 | 10-Oct-06 | Drain down sprinkler system for TEDAC rommm in MDA rooms 40554 to 40556. | HYBLA |
| 4 | 11-Oct-06 | 2 Sensors (A2157T and 2158) read 69 deg. | HYBLA |
| 4 | 11-Oct-06 | 4 sensors read 69 deg. | HYBLA |
| 4 | 11-Oct-06 | 22 Sensors read from 67.25 to 69.75 deg. | HYBLA |
| 4 | 11-Oct-06 | One tube out. | HYBLA |
| 4 | 12-Oct-06 | 2 Sensors (A4267T and 4268) read 69.75 deg. | HYBLA |
| 4 | 12-Oct-06 | 14 Sensors under 70 deg. | HYBLA |
| 4 | 16-Oct-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 16-Oct-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 16-Oct-06 | 1 Tube out in ceiling light. | HYBLA |
| 4 | 16-Oct-06 | 1 Ceiling light out. | HYBLA |
| 4 | 17-Oct-06 | One tube out in ceiling light. | HYBLA |
| 4 | 17-Oct-06 | Urnal will not flush. | HYBLA |
| 4 | 18-Oct-06 | 10 Sensors under 70 deg. | HYBLA |
| 4 | 19-Oct-06 | 3 Stained and one broken ceiling tile. | HYBLA |
| 4 | 19-Oct-06 | 4 Stained ceiling tiles. | HYBLA |
| 4 | 19-Oct-06 | One wet spot on a ceiling tile. | HYBLA |
| 4 | 23-Oct-06 | 2 Sensors (A4293T and 4294) read 68 deg. | HYBLA |
| 4 | 23-Oct-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 23-Oct-06 | 3 Sensors Flashing 77.25 deg. | HYBLA |
| 4 | 24-Oct-06 | 2 Sensors (A4293T and 4294) read 68 deg. | HYBLA |
| 4 | 24-Oct-06 | 1 Sensor (A4251T) reads 67.25 deg. and 2 (A4249T & 4250) read 69.25 deg. | HYBLA |
| 4 | 24-Oct-06 | 1 Sensor (A4251T) reads 67.25 deg. and 2 (A4249T & 4250) read 69.25 deg. | HYBLA |
| 4 | 24-Oct-06 | One ceiling light out of grid. | HYBLA |
| 4 | 25-Oct-06 | Mix Temp. on AHU #1 reads 122.46 | HYBLA |
| 4 | 25-Oct-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 25-Oct-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 25-Oct-06 | 3 Sensors Flashing 77.25 deg. | HYBLA |
| 4 | 26-Oct-06 | 5 Sensors 69 deg. | HYBLA |
| 4 | 26-Oct-06 | One sensor (A4251T) reads 66 deg. | HYBLA |
| 4 | 30-Oct-06 | Two sensors (A4293T and 4294) read 69.75 deg. | HYBLA |
| 4 | 30-Oct-06 | Two sensors (A4269T and 4270) read 69.75 deg. | HYBLA |
| 4 | 30-Oct-06 | 10 Sensors under 70 deg. | HYBLA |
| 4 | 30-Oct-06 | Two sensors (A4221T and 4222) read 80.75 deg. | HYBLA |
| 4 | 31-Oct-06 | Reflecting strip loose from door frame. Please re-glue it. | HYBLA |
| 4 | 31-Oct-06 | 1 Tube out in ceiling light. | HYBLA |
| 4 | 2-Nov-06 | 2 Sensors (A4249T and 4250) read 68 deg. | HYBLA |
| 4 | 6-Nov-06 | 9 sensors read 67 deg. | HYBLA |
| 4 | 6-Nov-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 6-Nov-06 | 25 Sensors from 61 to 68 deg. | HYBLA |
| 4 | 13-Nov-06 | TEST | HYBLA |
| 4 | 13-Nov-06 | One Sensor (A4285T) reads 78.50 deg. | HYBLA |
| 4 | 13-Nov-06 | 8 Sensors under 70 deg. | HYBLA |
| 4 | 13-Nov-06 | One Sensor flashing 78 deg. (A4229T). | HYBLA |
| 4 | 13-Nov-06 | One tube out. | HYBLA |
| 4 | 16-Nov-06 | 4 sensors read 69 deg. | HYBLA |
| 4 | 16-Nov-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 20-Nov-06 | 3 Sensors under 70 deg. | HYBLA |
| 4 | 20-Nov-06 | 2 Sensors under 68 deg. | HYBLA |
| 4 | 20-Nov-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 20-Nov-06 | 4 ceiling tiles out of grid. 2 stained and 1 broken. | HYBLA |
| 4 | 20-Nov-06 | Ceiling light tube out. | HYBLA |
| 4 | 20-Nov-06 | Change pink tube to a standard tube. | HYBLA |
| 4 | 20-Nov-06 | 2 Lights have a tube out in hallway in front of room 164. | HYBLA |
| 4 | 20-Nov-06 | 1 Tube out. | HYBLA |
| 4 | 20-Nov-06 | 1 Ceiling light out. | HYBLA |
| 4 | 20-Nov-06 | 2 Ceiling lights out. | HYBLA |
| 4 | 21-Nov-06 | 2 Sensors (A2128T and 2129) read 69 deg. | HYBLA |
| 4 | 21-Nov-06 | 2 Sensors (A4293T and 4294) read 69.75 deg. | HYBLA |
| 4 | 21-Nov-06 | 7 Sensors read from 64.50 to 68.75 deg. | HYBLA |
| 4 | 21-Nov-06 | 4 sensors under 70 deg. | HYBLA |
| 4 | 21-Nov-06 | 1 Sensor flashing 77 deg. | HYBLA |
| 4 | 21-Nov-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 21-Nov-06 | Tube Out in ceiling light. | HYBLA |
| 4 | 22-Nov-06 | Urnal will not flush. | HYBLA |
| 4 | 27-Nov-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 27-Nov-06 | 1 Sensor (A1057T) reads 66.50 and 4 are at 69 deg. | HYBLA |
| 4 | 27-Nov-06 | 3 Sensors read under 70 deg. | HYBLA |
| 4 | 28-Nov-06 | 2 Sensors (A4293T and 4294) read 69.75 deg. | HYBLA |
| 4 | 28-Nov-06 | 6 Sensors under 70 deg. | HYBLA |
| 4 | 4-Dec-06 | 2 Tubes out in a ceiling light. | HYBLA |
| 4 | 7-Dec-06 | 7 Sensors under 70 deg. | HYBLA |
| 4 | 7-Dec-06 | 1 Sensor (A3208T) reads 67.25 deg. | HYBLA |
| 4 | 7-Dec-06 | 5 Sensors under 70 deg. | HYBLA |
| 4 | 7-Dec-06 | 2 Sensors under 70 deg. | HYBLA |
| 4 | 7-Dec-06 | Lobby One Sensor (A3LOJT is 64.50) (A3LOKT is 67.60) 3 others at 69 deg. | HYBLA |
| 4 | 7-Dec-06 | Sanitary seat cover holder off the wall. | HYBLA |
| 4 | 7-Dec-06 | Water Stained ceiling tile. | HYBLA |
| 4 | 7-Dec-06 | Two small rooms the light dose not work when switch is turned on. | HYBLA |
| 4 | 7-Dec-06 | 2 Lights have a tube out. | HYBLA |
| 4 | 7-Dec-06 | 1 Tube out in a ceiling light. | HYBLA |
| 4 | 13-Dec-06 | REPLACE BURNT OUT FLOURESCENT LIGHT BULB - ROOM B50 | HYBLA |
| 4 | 13-Dec-06 | ELECTRICAL OUTLET NOT WORKING - ROOM 50 | HYBLA |
| 4 | 13-Dec-06 | REPLACE FOUR STAINED CEILING TILES - ROOM B33 | HYBLA |
| 4 | 20-Dec-06 | TOO COLD - ROOM 51 AND ROOM 53 | HYBLA |
| 4 | 5-Jan-07 | WATER FOUNTAIN OUT OF SERVICE ON 1ST FLOOR A WING CONFERENCE ROOM B | HYBLA |
| 4 | 5-Jan-07 | REPLACE STAIN CEILING TILE IN HALLWAY NEAR ROOM 224 AND CHECK FOR LEAKS | HYBLA |
| 4 | 5-Jan-07 | LIGHT OUT IN HALLWAY NEAR ROOM 258 | HYBLA |
| 4 | 5-Jan-07 | LIGHT OUT IN REAR OF ROOM B-10 AND B15 | HYBLA |
| 4 | 12-Jan-07 | CONFIRM POWER PANEL OUTSOURSE IN ROOM B-25A | HYBLA |
| 4 | 16-Jan-07 | WATER LEAK | HYBLA |
| 4 | 18-Jan-07 | TOO COLD - EAST WING ROOM 154 | HYBLA |
| 4 | 29-Jan-07 | TOO COLD - BASEMENT ROOMS 51 AND 53 | HYBLA |
| 4 | 6-Feb-07 | FAUCET LEAKING - LOCATED ON LOADING DOCK | HYBLA |
| 4 | 13-Mar-07 | NEED CEILING TILES - ROOM B55 THRU B56 | HYBLA |
| 4 | 29-Mar-07 | DDC SYSTEM HAS NUMERIOUS ALARMS ACTIVE | HYBLA |
| 4 | 8-May-07 | light out in trailer area | HYBLA |
| 4 | 16-May-07 | ROOM 126 D WING LIGHT OUT | HYBLA |
| 4 | 16-May-07 | LIGHT OUT IN HALLWAY NEAR ROOM 118 C WING | HYBLA |
| 4 | 16-May-07 | ROOM 160 E WING LIGHT OUT | HYBLA |
| 4 | 5-Jun-07 | OUTSIDE DRAIN PIPE COPPER 1 INCH BROKEN | HYBLA |
| 4 | 5-Jun-07 | CHECK ALL OUTSIDE LIGHTS SOME ARE STILL ON IN THE MIDDLE OF THE DAY | HYBLA |
| 4 | 11-Jun-07 | LOADING DOCK DOOR DOES NOT CLOSE | HYBLA |
| 4 | 11-Jun-07 | SECURITY OFFICE TEMP READING 80 DEGREES | HYBLA |
| 4 | 19-Jun-07 | METAL STRIP LOOSE ON CORNER EDGE - ROOM 125 | HYBLA |
| 4 | 19-Jun-07 | METAL STRIP LOOSE ON CORNER EDGE - ROOM 125 | HYBLA |
| 4 | 19-Jun-07 | FLOURESCENT STRIP ON WALL IS LOOSE - 2ND FLOOR ACROSS FROM MEN RESTROOM | HYBLA |
| 4 | 20-Jun-07 | TOO COLD - ROOM B-3, B-4, AND B-15 | HYBLA |
| 4 | 22-Jun-07 | A WING, SECOND FLOOR, FLORESENT STRIP LOOSE | HYBLA |
| 4 | 26-Jun-07 | ELEVATOR IS BROKEN | HYBLA |
| 4 | 8-Jun-06 | IN ROOM B-32, TOO HOT, NOT ADEQUATE COOLING, HYBLA. CHECK SPOT COOLER! | HYBLA |
| 4 | 22-Jun-07 | ROOM 125 METAL STRIP LOOSE FROM CORNER EDGE | HYBLA |
| 4 | 11-Jan-06 | repair and seal 2and 3/8 pipe on the roof also seal around base of light brackett | USCAAF |
| 4 | 23-Jan-06 | WATER LEAKING FROM CEILING | USCAAF |
| 4 | 25-Jan-06 | There is a leak in the sink in the kitchen room 309 at the US COURTS | USCAAF |
| 4 | 30-Jan-06 | Check the basement ceiling leak at the US Courts | USCAAF |
| 4 | 1-Feb-06 | REPAIR LEAKING TOILET | USCAAF |
| 4 | 6-Feb-06 | REPLACED WALL MOUNTING LIGHTS | USCAAF |
| 4 | 6-Feb-06 | BAD SMELL FROM THE TOILET ( LEAK) | USCAAF |
| 4 | 6-Feb-06 | WOODEN TILE COVERS BROKEN UNDER THE DESK | USCAAF |
| 4 | 6-Feb-06 | CHANDELIER REPLACE LIGHTS | USCAAF |
| 4 | 24-Feb-06 | Provide course proposal to correct code violations which were discovered during | USCAAF |
| 4 | 12-Jun-06 | REPLACE CEILING TILE | USCAAF |
| 4 | 10-Jul-06 | GARBAGE DISPOSAL LEAKING - NEEDS TO BE REPLACED | USCAAF |
| 4 | 12-Dec-06 | FAN COIL UNITS NOT WORKING IN THE LOADING DOCK AREA | USCAAF |
| 4 | 1-Mar-07 | ONE OF THE TWO LIGHTS IN THE FRONT OF BUILDING HAS DAMAGE | USCAAF |
| 4 | 3-Apr-07 | FIRE SPRINK SYSTEMS DRAIN OFF LINE NOT CONNECTED | USCAAF |
| 4 | 9-Apr-07 | Area where unit 9# in the court appeals causeing uncomfort to personel needs air flow adjustment | USCAAF |