Seismic.pdf
PDF 119 KB Posted
- Attached to
- Mechanicsburg RF EOL Equipment Upgrade Federal contract opportunity
- Solicitation number
- HC102825R0076
- Issued by
- Defense Information Systems Agency
About this file
This technical specification document (Section 23 05 48.00 40) details vibration and seismic controls for HVAC piping and equipment at the DISA Building 308 Raised Floor End of Life Equipment project located at Naval Support Activity, Mechanicsburg, PA. The document provides comprehensive requirements for vibration isolation provisions, including specific mounting and base types for different equipment such as reciprocating compressors and centrifugal pump locations. It specifies technical details like material requirements (natural rubber, chloroprene elastomer), durometer measurements, and minimum deflection standards for various installation scenarios across different floor spans and building grades, with precise guidelines for floor-mounted and vertical piping isolation systems. The specification requires government approval for submittals and mandates that equipment be installed according to manufacturer recommendations, with detailed performance data and test reports to be submitted within 15 working days of contract award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 26 24 15 - Computer Room PDUs.pdf | ||
| Q and A HC102825R0076 Part 3 Full.docx | DOCX document | |
| Q and A HC102825R0076 Part 2.docx | DOCX document | |
| Specifications - FY25 RF EOL.pdf | ||
| Installation 1.pdf | ||
| Q and A HC102825R0076 Part 1.docx | DOCX document | |
| 832571388 QASP Attachment 3.docx | DOCX document | |
| 832571388 PWS Mechanicsburg Raise Floor Attachment 1.docx | DOCX document | |
| HC102825R0076 Solicitation.pdf | ||
| Wage Decision 2015 4225 Attachment 5.docx | DOCX document | |
| 832571388 CLIN Pricing Sheet Attachment 2.xlsx | XLSX spreadsheet |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 23 05 48.00 40 Page 1
DISA BUILDING 308 RAISED FLOOR END OF LIFE EQUIPMENT
NAVAL SUPPORT ACTIVITY, MECHANICSBURG, PA
SECTION 23 05 48.00 40
VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
02/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACOUSTICAL SOCIETY OF AMERICA (ASA)
ASA S2.71 (1983; R 2006) Guide to the Evaluation of Human Exposure to Vibration in Buildings
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE HVAC APP IP HDBK (2011) HVAC Applications Handbook, I-P Edition
NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB)
NEBB PROCEDURAL STANDARDS (2005) Procedural Standards for TAB (Testing, Adjusting and Balancing) Environmental Systems
1.2 ADMINISTRATIVE REQUIREMENTS
Section 23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS applies to work specified in this section to the extent applicable.
Ensure all vibration-control apparatus is the product of a single manufacturing source, where possible. Human exposure levels should be considered using ASA S2.71 and NEBB PROCEDURAL STANDARDS.
Scheduled isolation mounting is in inches and is a minimum static deflection.
Spans referred to in Part 2, "Vibration-Isolation Systems Application," means longest bay dimension.
Determine exact mounting sizes and number of isolators by the isolator manufacturer based on equipment that will be installed. Check equipment revolutions per minute (rpm) and spring deflections to verify that resonance cannot occur.
Within ten 15 working days of Contract Award, submit equipment and performance data for vibration isolator systems including equipment base design; inertia-block mass relative to support equipment weight; spring loads and free, operating, and solid heights of spring; spring diameters;
nonmetallic isolator loading and deflection; disturbing frequency; natural frequency of mounts; deflection of working member; and anticipated amount of physical movement at the reference points.
SECTION 23 05 48.00 40 Page 2
Ensure data includes the following:
a. Mountings
b. Bases
c. Isolators
d. Floor-Mounted Piping
e. Vertical Piping
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Equipment and Performance Data; G
Isolators; G
Type of Isolator; G
Type of Base; G
Allowable Deflection; G
Measured Deflection; G
PART 2 PRODUCTS
2.1 TYPE OF VIBRATION-ISOLATION PROVISIONS
Design for vibration isolation using ASHRAE HVAC APP IP HDBK, Chapter 48, as applicable to the following sections.
Submit test reports for testing vibration isolation for each type of isolator and each type of base, and meet referenced standards contained within this section. Include in test reports allowable deflection and measured deflection also meeting referenced standards within this section.
2.1.1 Materials
Ensure rubber is natural rubber and elastomer is chloroprene. Shore A durometer measurement of both materials and range between 40 and 60.
Inorganic materials such as precompressed, high-density, fibrous glass encased in a resilient moisture-impervious membrane may be used in lieu of specified natural rubber and elastomers. Where this substitution is made, ensure specified deflections are modified by the manufacturing source to accommodate physical characteristics of inorganic materials and to provide equal or better vibration isolation.
Ensure weather-exposed metal vibration-isolator parts are corrosion
SECTION 23 05 48.00 40 Page 3 protected. Chloroprene coat springs.
2.1.2 Mountings
Provide the following mountings:
Type A: Composite pad, with 0.25-inch thick elastomer top and bottom layers, molded to contain a pattern with nonslip characteristics in all horizontal directions. Elastomer loading is not to exceed 40 pounds per square inch (psi). Ensure minimum overall thickness is 1 inch.
Maximum deflections up to 0.25-inch are allowed.
Type B: Double elastomer-in-shear with molded-in steel reinforcement in top and bottom. Maximum deflections up to 0.50 inch are allowed.
Type C: Free-standing laterally stable open-spring type for deflections over 0.50 inch, with built-in bearing and leveling provisions, 0.25-inch thick Type A base elastomer pads, and accessories. Ensure outside diameter of each spring is equal to or greater than 0.9 times the operating height of the spring under rated load.
Type D: Partially housed type, containing one or more vertically restrained springs with at least 0.50 inch clearance maintained around springs, with adjustable limit stops, 0.25-inch thick Type A base elastomer pads, and accessories.
Type E: Combination spring and rubber-in-shear steel framed for hanger-rod mounting, with minimum total static deflection of 1 inch.
2.1.3 Bases
Provide the following bases:
Type U: Unit isolators without rails, structural-steel bases, or inertia blocks.
Type S: Structural-steel bases common to a supported assembly, made from welded-joint mill-rolled structural steel with closed-perimeter configuration, isolators attached to outrigger supports.
2.2 VIBRATION-ISOLATION SYSTEMS APPLICATION
Vibration isolation design per .
2.2.1 Reciprocating Compressor
ON\ABOVE ON\ABOVE ON\ABOVE
GRADE GRADE GRADE
BASEMENT 20-FOOT 30-FOOT 40-FOOT
TYPE BELOW-GRADE FLOOR-SPAN FLOOR-SPAN FLOOR-SPAN
EQUIPMENT PROVISIONS* PROVISIONS* PROVISIONS* PROVISIONS*
500 to
750 rpm D-U-1.0 D-U-1.5 D-U-2.5 D-CIB-2.75 and to over
D-U-1.0
D-U-1.0
D-U-2.0
D-CIB-2.5
SECTION 23 05 48.00 40 Page 4
ON\ABOVE ON\ABOVE ON\ABOVE
GRADE GRADE GRADE
BASEMENT 20-FOOT 30-FOOT 40-FOOT
TYPE BELOW-GRADE FLOOR-SPAN FLOOR-SPAN FLOOR-SPAN
EQUIPMENT PROVISIONS* PROVISIONS* PROVISIONS* PROVISIONS*
*TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES
2.2.2 Centrifugal Pump Locations
BASEMENT
ON\ABOVE
GRADE
20-FOOT
ON\ABOVE
GRADE
30-FOOT
ON\ABOVE
GRADE
40-FOOT
TYPE BELOW-GRADE
EQUIPMENT PROVISIONS*
FLOOR-SPAN
PROVISIONS*
FLOOR-SPAN
PROVISIONS*
FLOOR-SPAN
PROVISIONS*
Close-couple through 5 hp None
-R-0.35
C-S-1.0
C-S-1.0
Bedplate-mounted through 5 hp None
C-CIB-1.0
C-CIB-1.5
C-CIB-1.75
7-1/2 hp None C-CIB-1.0 C-CIB-1.75 C-CIB-2.5
*TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES
2.3 PIPE AND DUCT VIBRATION ISOLATION
Type G: Provide isolators with in-series contained steel springs and preformed fibrous-glass or chloroprene-elastomer elements for connecting to building-structure attachments. Load devices by supported system during operating conditions to produce a minimum spring and elastomer static deflection of 1 inch and 3/8 inch, respectively.
Type H: Provide isolators with contained chloroprene-elastomer elements for connecting to building-structure attachments. Load devices by supported system during operating conditions to produce a minimum elastomer static deflection of 3/8 inch.
Type J: Provide isolators with elastomers mounted on floor-supported columns or directly on the floor. Load devices by supported system during operating conditions to produce a minimum elastomer static deflection of 3/8 inch.
2.3.1 Floor-Mounted Piping
Type K: Provide isolators with springs mounted on floor-supported columns or directly on the floor. Load devices by supported system during operating conditions to produce a minimum spring static deflection of 1 inch.
2.3.2 Vertical Piping
Type L: Provide isolators which are pipe base-support devices with one
SECTION 23 05 48.00 40 Page 5 or more contained steel springs. Load devices by supported system during operating conditions to produce a minimum static deflection of 1 inch. Equip devices with precompression and vertical-limit features, as well as a minimum 1/4-inch thick elastomer sound pad and isolation washers, for mounting to floor.
Type M: Provide isolators which are elastomer mounted baseplate and riser pipe-guide devices, with contained double acting elastomer elements which under rated load have a minimum static deflection of 3/8 inch. Size isolator to accommodate thermal insulation within the stationary guide ring.
PART 3 EXECUTION
3.1 INSTALLATION
Install equipment in accordance with manufacturer's recommendations.
-- End of Section --
| SECTION 23 05 48.00 40 |
| PART 1 GENERAL |
| ACOUSTICAL SOCIETY OF AMERICA (ASA) |
| AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS (ASHRAE) |
| NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB) |
| 1.2 ADMINISTRATIVE REQUIREMENTS |
| 1.3 SUBMITTALS |
| PART 2 PRODUCTS |
| 2.2 VIBRATION-ISOLATION SYSTEMS APPLICATION |
| ON\ABOVE ON\ABOVE ON\ABOVE GRADE GRADE GRADE |
| ON\ABOVE ON\ABOVE ON\ABOVE GRADE GRADE GRADE |
| PART 3 EXECUTION |