This document is a comprehensive Program of Requirements (Appendix A) and Functional Data Sheets for a new U.S. Courthouse in Hartford, Connecticut, prepared by Michael Maltzan Architecture, Inc., SLAM Collaborative, and Directional Logic. It serves as a design guideline establishing detailed spatial, functional, and technical specifications for all building components and operational areas.
The document defines requirements for multiple judicial and operational spaces organized by division. Key areas include District Judge Chambers Suites (comprising judge's offices, law clerk spaces, conference rooms, private toilets, and support facilities totaling approximately 1,290 NSF per suite); Courtroom Facilities (District Judge Courtroom at 2,400 NSF with detailed specifications for judge's bench, jury box, courtroom deputy station, witness box, attorney stations, and associated jury facilities); Visiting and Senior District Judge Chambers; Magistrate Judge Courtroom (1,800 NSF); Bankruptcy Judge Courtroom (1,800 NSF); and Grand Jury facilities. Administrative support spaces include the District Clerk's Office (with public counter, records storage, evidence vault, and financial vault), Bankruptcy Clerk's Office, U.S. Probation Office (featuring interview rooms, urinalysis testing labs, and secure records storage), U.S. Federal Public Defender trial preparation areas, and U.S. Marshals Service (USMS) spaces referencing USMS Publication 64 standards for prisoner detention cells, processing rooms, and secure corridors. Building common areas specify Entry Lobby, Public Corridors, Public Toilets, Service Entry/Loading Dock, Mechanical and Electrical Rooms, Telecommunications Closets, and Fire Command Center. The specifications detail finishes (carpet, ceramic tile, terrazzo, wood paneling), ceiling heights (typically 10'-0" to 18'-0"), acoustic performance ratings (NIC ratings ranging from 25 to 60), HVAC zoning requirements, electrical outlet specifications, telecommunications infrastructure, security provisions (card readers, duress alarms, CCTV cameras), and accessibility compliance with ABAAS standards. Parking requirements total 66 spaces, with 46 for Judiciary, 13 for USMS, and allocations for U.S. Attorney's Office, GSA, U.S. Trustees, and Congress. The estimated maximum building area is 281,000 gross square feet incorporating classical or traditional architecture per Executive Order 14344.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MICHAEL
MALTZAN
ARCHITECTURE, INC.
SLAM Collaborative
Directional Logic
PROGRAM OF
REQUIREMENTS
APPENDIX A:
FUNCTIONAL DATA
SHEETS
Hartford, CT New Federal Courthouse Summer/Fall 2025
Page Intentionally Left Bank
APPENDIX A:APPENDIX A:
FUNCTIONAL FUNCTIONAL
DATA SHEETSDATA SHEETS
Michael Maltzan Architecture, Inc. | SLAM Collaborative | Directional Logic General Services Administration32
DRAFT
Functional Data Sheets
U.S. COURTS PROGRAM REQUIREMENTS
Page Intentionally Left Bank
The FDS are meant to be used as a guideline. It is essential that the A/E obtain additional information from the Courts, the General Services Administration (GSA), U.S.
Marshals Service, and other agencies to ensure the design appropriately responds to each agency’s prescribed requirements.
The FDS should be used in conjunction with other governmental facility standards and it is the responsibility of the A/E for the coordination and conformance with these standards as well as all applicable laws, codes and regulations.
Finishes indicated in the FDS show a range of acceptable finishes per space; however, this list should not be considered comprehensive. Final finish selection should be determined by the design architect, project stakeholders and budget. Further finish selection requirements can be found in the Owner’s Project Requirements (OPR).
The information in the following room data sheets comes from the U.S. Courts Design Guide (USCDG)
– 2007, including revisions through June 2008 with revised Chapters 1,2,15,16 dated June 2016 unless noted otherwise. If any of the information presented in the FDS conflicts with the USCDG – 2007, the USCDG shall take precendence.
Michael Maltzan Architecture, Inc. | SLAM Collaborative | Directional Logic General Services Administration54
B.2.2.1 District Judge Chambers Suites
B.2.2.1.1 JUDGE’S CHAMBER OFFICE
Item Specifications Division: DISTRICT JUDGE CHAMBERS SUITE
AB Code: 1041
Square Footage: 500 NSF
Adjacent to: Conference/reference room, reception area, vestibule
Ceiling Height: 10'-0”
Acoustics: NIC - 50
Floors: High grade carpet
Base: AWI premium grade wood base
Walls: Fabric wall covering above wood veneer wainscot
Ceilings: Painted gypsum board, acoustical ceiling tile
Windows: Wood window sills.
Millwork: Bookshelves: not to exceed 20 units per suite, full height, 3’ in width,12” in depth, AWI premium grade. Location and quantity are at the judge’s discretion.
HVAC:
The judge’s chamber suites must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical:
Three quadruplex receptacles for general and miscellaneous purposes (e.g., a table lamp). One dedicated computer power receptacle. One normal duplex receptacle for the judge’s printer. Provide Floor Box.
Lighting:
The entire system must be adjustable to provide for a variety of lighting levels.
Horizontal 30-50fc and Vertical 10-15fc. Provide special lighting fixtures such as track lighting, sconces and decorative accent lighting integrated with ceiling and wall design.
Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications:
Provide two duplex outlets and a dedicated outlet for the judge's printer.
Telephone and intercom outlets, as required.
One or more outlets connected to the building downlink system and cable television system.
Security: Provide infrastructure for wireless duress alarm.
B.2.2.1.2 LAW CLERK
Item Specifications Division: DISTRICT JUDGE CHAMBERS SUITE
AB Code: 1041
Square Footage: 150 NSF
Ceiling Height: 10’-0”
Acoustics: NIC-35
Floors: Carpet
Base: AWI premium grade wood base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
HVAC
HVAC system must be separately zoned to facilitate off-hours usage of the local system and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical: One quadruplex receptacle for general purposes. One dedicated computer power receptacle. One normal duplex receptacle for a printer.
Telecommunications: Provide two duplex outlets.
Security:
Provide infrastructure for card reader, electric strike, audio or audio/video intercom and a fixed camera at the front entrance to the Judge’s suite entering the receptionist space from the public corridor. The audio or audio/video intercom is required to integrate with all entrance control packages (ECP) within the suite. Provide infrastructure for a wireless duress alarm. (Provide these security provisions at one Law Clerks station/office)
B.2.2.1.3 CONFERENCE / REFERENCE ROOM
Division: DISTRICT JUDGE’S CHAMBERS SUITE
AB Code: 1041
Square Footage: 240 NSF
Adjacent to: Judge’s chambers, staff circulation
Ceiling Height: 10'-0”
Acoustics: NIC - 55
Floors: High grade carpet
Base: AWI premium grade wood base
Walls: Fabric wallcovering above wood veneer wainscot
Ceilings: Acoustical ceiling tile, painted gypsum board
Millwork: Bookshelves: not to exceed 20 units per suite, full height, 3’ in width, 12" in depth, AWI premium grade. Location and quantity are at the judge’s discretion
HVAC:
The conference room must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air must be ducted directly toward the return-air shaft for a minimum distance of 15 feet.
Electrical: Convenience outlets spaced at a maximum of 6 feet on center should be provided along the walls. Provide a floor box under the desk.
Lighting: Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications: Provide two duplex outlets. One or more outlets connected to the building downlink system and cable television system.
Security: Provide infrastructure for wireless duress alarm and door contact.
Audio Visual:
Further guidance will be provided see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom Technology and Structured Cabling Systems.
B.2.2.1.4 JUDGE’S PRIVATE TOILET
Division: DISTRICT JUDGE CHAMBERS SUITE
AB Code: 1041
Square Footage: 50 NSF
Adjacent to: Judge’s chambers, vestibule
Ceiling Height: 10'-0”
Floors: Ceramic tile
Base: Ceramic tile
Walls: 3’ high ceramic tile wainscot on wet wall only with remaining walls painted gypsum board.
Ceilings: Painted gypsum board
Millwork: Plastic laminate base cabinet with storage below and a solid surface countertop with integral sink and backsplash. Adaptable for ABAAS in future if required.
HVAC: Exhaust ventilation.
Electrical: One GFI duplex wall outlet near the sink.
Lighting: Switch controlled LED and decorative lighting at the mirror.
Plumbing: ABAAS compliant water closet with quiet flush, lavatory and floor drain with trap primer.
Accessories:
Medicine cabinet with mirror, paper towel dispenser, toilet paper holder, soap dispenser, trash receptacle, coat hook and towel bar. All equipment to be ABAAS compliant.
B.2.2.1.5 SERVICE UNIT
AB Code: 1041
Square Footage: 20 NSF
Adjacent to: Location of the service unit should be adjacent to the conference room.
Ceiling Height: 10'-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Millwork:
Plastic laminate base and upper cabinets with plastic laminate countertop, sink and backsplash. Adaptable for ABAAS in future if required. Space to be provided for tenant supplied refrigerator, microwave, and coffee machine.
HVAC: Exhaust ventilation
Electrical: Two duplex outlets. Make GFI if it is near the sink. Dedicated outlets for small appliances.
Lighting: Separately switched LED fixtures and under cabinet LED lighting.
Plumbing: ABAAS compliant stainless-steel sink and floor drain with trap primer.
B.2.2.1.6 COPY / FAX / STORAGE ROOM
AB Code: 1041
Square Footage: Copier Area-50 NSF, Fax Area-10 NSF, Storage Area-80 NSF
Ceiling Height: 10'-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Millwork:
Plastic laminate counter and base cabinet with built-in drawers for small office supplies with open and closed shelves for paper and other large supplies.
Accommodate a fax machine with additional working area.
HVAC: Exhaust ventilation
Electrical: Dedicated duplex outlet for each copy and fax machine. Coordinate outlet types with tenant- supplied equipment.
Telecommunications: Provide two duplex outlets.
B.2.2.1.7 FILING ROOM
AB Code: 1041
Square Footage: 140 NSF
Adjacent to: Near judicial assistant
Ceiling Height: 10'-0”
Floors: Solid/premium vinyl tile or carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Electrical: One duplex outlet each wall.
Telecommunications: One duplex outlet.
B.2.2.1.8 VESTIBULE
Division: DISTRICT JUDGE CHAMBERS SUITE
AB Code: 1041
Square Footage: 50 NSF
Adjacent to: Judge’s chamber office, restricted corridor
Ceiling Height: 10'-0”
Floors: High Grade Carpet
Base: AWI premium grade wood base
Walls: Painted gypsum board
Ceilings: Painted gypsum board, acoustical ceiling tile
Lighting: Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
B.2.2.1.9 COAT CLOSET
AB Code: 1041
Square Footage: 10 NSF
Ceiling Height: 10'-0”
Floors: Carpet
Base: Wood wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Millwork: Provide a coat rod with shelf above
B.2.2.1.10 RECEPTION AREA
AB Code: 1041
Square Footage: 100 NSF
Adjacent to: Restricted circulation
Ceiling Height: 10'-0”
Floors: Carpet
Base: AWI premium grade wood base
Walls: Fabric wall covering above wood veneer wainscot
Ceilings: Acoustical ceiling tile
Electrical: One quad outlet.
Lighting: Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications: One telecommunications outlet.
Security:
Provide infrastructure for card reader, electric strike, audio or audio/video intercom and a fixed camera at the front entrance to the Judge’s suite entering the receptionist space from the public corridor. The audio or audio/video intercom is required to integrate with all entrance control packages (ECP) within the suite. Provide infrastructure for a wireless duress alarm.
B.2.2.1.11 JUDICIAL ASSISTANT WORKSPACE
AB Code: 1041
Square Footage: 120 NSF
Adjacent to: Reception Area
Ceiling Height: 10'-0”
Floors: Carpet
Base: AWI premium grade wood base
Walls: Fabric wall covering above wood veneer wainscot
Ceilings: Acoustical ceiling tile
HVAC
HVAC system must be separately zoned to facilitate off-hours usage of the local system and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical: Four duplex outlets, one dedicated duplex outlet.
Emergency power for the entry control package equipment.
Telecommunications: Provide two duplex outlets and one dedicated outlet for the printer.
Security:
Provide infrastructure for card reader, electric strike, audio or audio/video intercom and a fixed camera at the front entrance to the Judge’s suite entering the receptionist space from the public corridor. The audio or audio/video
B.2.2.1.12 COURTROOM DEPUTIES
AB Code: 1041
Square Footage: 150 NSF
Location: Clerk’s Office
Ceiling Height: 10'-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
HVAC
HVAC system must be separately zoned to facilitate off-hours usage of the local system and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical:
One quadruplex receptacle (general use). Duplex receptacles, two minimum, for PC, monitor, printer, FAX. Feed to the powered furniture panel, if systems furniture is used.
Telecommunications:
Provide two duplex outlets, dedicated outlets for printer, fax, and telecommunications feed to powered furniture panel if systems furniture is used.
B.2.2.2 Visiting District Judge Chambers Suite
B.2.2.2.1 JUDGE’S CHAMBER OFFICE
Division: VISITING JUDGE CHAMBER SUITE
AB Code: 1041
Square Footage: TBD (900 NSF total for the suite)
Adjacent to: Conference/reference room, reception area, vestibule
Ceiling Height: 10'-0”
Acoustics NIC - 55
Floors: High grade carpet
Base: AWI premium grade wood base
Walls: Fabric wall covering above wood veneer wainscot
Ceilings: Painted gypsum board, acoustical ceiling tile
Windows: Wood window sills
Millwork: Bookshelves: not to exceed 20 units per suite, full height, 3’ in width, 12" in depth, AWI premium grade. Location and quantity are at the judge’s discretion.
HVAC:
The judge’s chamber suites must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical:
Three quadruplex receptacles for general and miscellaneous purposes (e.g., a table lamp). One dedicated computer power receptacle. One normal duplex receptacle for the judge’s printer.
Lighting:
The entire system must be adjustable to provide for a variety of lighting levels.
Horizontal 30-50fc and Vertical 10-15fc. Provide special lighting fixtures such as track lighting, sconces and decorative accent lighting integrated with ceiling and wall design.
Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications:
Provide two duplex outlets and a dedicated outlet for the judge's printer.
One or more outlets connected to the building downlink system and cable
Security: Provide infrastructure for a wireless duress alarm
B.2.2.2.2 LAW CLERK OFFICE
Division: VISITING JUDGE CHAMBERS SUITE
AB Code: 1041
Square Footage: TBD
Ceiling Height: 10’-0”
Acoustics: NIC-35
Floors: Carpet
Base: AWI premium grade wood base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
HVAC
HVAC system must be separately zoned to facilitate off-hours usage of the local system and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air from the chamber suites must be ducted directly to the return air shaft.
Electrical: One quadruplex receptacle for general purposes. One dedicated computer power receptacle. One normal duplex receptacle for a printer.
Telecommunications: Provide two duplex outlets and a dedicated outlet for the printer.
Security: CCTV monitor, wireless duress alarm., security intercom, remote door release mechanism. (Provide these security provisions at one Law Clerks station/office)
B.2.2.2.3 COPY/FAX/STORAGE
Division: VISITING JUDGE’S CHAMBERS SUITE
AB Code: 1041
Square Footage: TBD
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Millwork:
Plastic-laminate counter and base cabinet with built-in drawers for small office supplies and open shelves for paper and other large supplies. Accommodate a fax machine with additional working area.
HVAC: Exhaust ventilation
Electrical: Dedicated duplex outlet for each copy and fax machine. Coordinate outlet types
Telecommunications: Provide two duplex outlets
B.2.2.2.4 JUDGE’S PRIVATE TOILET
AB Code: 1041
Square Footage: 50 NSF
Adjacent to: Judge’s chambers, vestibule
Ceiling Height: 10’-0”'
Floors: Ceramic tile
Base: Ceramic tile
Walls: 3’ high ceramic tile wainscot on wet wall only with remaining walls painted gypsum board
Ceilings: Painted gypsum board
Millwork: Plastic laminate base cabinet with storage below and a solid surface countertop with integral sink and backsplash. Adaptable for ABAAS in future if required.
HVAC: Exhaust Ventilation.
Electrical: One GFI duplex wall outlet near the sink.
Lighting: Switch controlled LED and decorative lighting at the mirror.
Plumbing: ABAAS compliant water closet with quiet flush, lavatory and floor drain with trap primer.
Equipment:
Medicine cabinet with mirror, paper towel dispenser, toilet paper holder, soap dispenser, coat hook, trash receptacle and towel bar. All equipment to be
B.2.2.2.5 RECEPTION AREA
AB Code: 1041
Square Footage: TBD
Adjacent to: Restricted circulation
Ceiling Height: 10'-0”
Floors: Carpet
Base: AWI premium grade wood base
Walls: Fabric wall covering above wood veneer wainscot
Ceilings: Acoustical ceiling tile
Electrical: One quad outlet.
Lighting: Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications: One duplex outlet.
Security:
Provide infrastructure for card reader, electric strike, audio or audio/video intercom and a fixed camera at the front entrance to the Judge’s suite entering the receptionist space from the public corridor. The audio or audio/video
B.2.2.3 District Judge Courtroom, Assoc. Spaces & Jury Facilities
B.2.2.3.1 DISTRICT JUDGE COURTROOM
Division: DISTRICT COURTROOM FACILITIES
AB Code: 1041
Square Footage: 2,400 NSF
Adjacent to: Public waiting area
Ceiling Height: 16’-0”
Acoustics: NIC 55-60
Floors: Carpet
Base: AWI premium grade wood base
Walls: Front: Stained wood veneer paneling flanked by WC above wood veneer wainscot with architectural trim. Side: Painted GB above wood veneer wainscot/ architectural trim. Back: Acoustic fabric wrapped panel above wood veneer wainscot with architectural trim
Ceilings:
Painted gypsum board, acoustical plaster designed to meet acoustical performance requirements. Ceiling elements such as soffits, coffers, perimeter coves, recesses and reveals must be provided as required to integrate HVAC, lighting and sound systems into a harmonious design.
Millwork:
AWI premium grade millwork for courtroom paneling, doors, moldings, trim and built-in furniture, which includes:
(1) Judge’s bench (1-2) Courtroom deputy clerk station(s) Evidence cabinet
(1) Court reporter/recorder station Recording equipment cabinet
(1) Law clerk station (1-2) Witness box(s) (16 seat) Jury Box Lectern (height adjustable, movable, ABAAS compliant lectern with built-in lighting), accommodate a microphone and task lighting (65 plus 4 wheelchair spaces) Spectator Seating with railing
(4) Attorney tables, considered movable furniture, should match built-in courtroom millwork AV equipment, security equipment, and courtroom technology systems will be integrated into the millwork. Provide necessary drilled or cored openings at work surfaces to accommodate cabling, grommets and cable raceways for wire management.
See the individual station description/criteria at the end of this section for further clarification. Note that actual heights of the built-in structures and the depths and lengths of workspaces may vary slightly from the dimensions below based on the findings in the mockup process.
Finish Hardware: All finish hardware in courts and chambers must be durable and consistent in finish and must conform to AWI Standards for Premium Grade.
Accessibility:
The judge’s bench, courtroom deputy, law clerk, and court reporter stations need not be accessible when constructed but must be adaptable for accessibility without significant structural reconfiguration or extension of the courtroom or extension of the electrical system. Other publicly accessible areas such as the litigant and counsel stations, witness station, jury box, lectern, and public seating must be accessible and have an accessible route.
Spectator Area:
Area to accommodate 65 people in pew-type hardwood bench seating or fixed chairs. Provide ABAAS compliant space for four wheelchair accessible seating locations. Benches to match courtroom millwork finish.
Railing: Provide 30" high decorative spectator rail separating spectators from the courtroom. Rail should have an accessible gate or opening.
Windows: Windows are allowed. See security, acoustical and aesthetic requirements in the USCDG.
Window Treatments:
If windows are provided, including electronically operated window coverings with blackout capability may be required. Judiciary to provide funding source
(RWA).
Jury Seating:
Provide jury seating for 16. One chair must be removable to provide an ABAAS compliant space for a wheelchair and an accessible route to the wheelchair seating space. Jury box to be designed to allow enough clearance to rock and swivel chairs without interference from walls, jury box panels, monitors, and other jurors. Foot rails must be provided. Jury chairs to be purchased and installed by CMc after review and approval by the Government. At minimum one row of the jury box may be a raised platform above the finish floor.
HVAC:
System must facilitate off-hours usage of the local system. Provide USCDG requirement for 3 HVAC zones within courtroom, one each for judge/attorney area in front, one for jury area, one for spectator area. Air distribution in the spectator area must be sized to serve the maximum allowable seating capacity, plus 25%. Return air from the courtroom and associated areas must be ducted directly to the HVAC unit.
HVAC system must be designed to meet the acoustic performance requirements in Chapter 14 of the US Courts Design Guide. Mechanical units must not be placed above or near courtrooms where noise will affect court proceedings.
Temperature controls must be located in areas that are not accessible to the public. Provide humidity sensors.
Electrical:
Coordinate electrical requirements with the AV designer, USMS, ALS system, and court staff. Courtroom floor boxes must be flush mounted with carpet covered or metal inserts. Provide connections for voice, data and power within the floor boxes below the surface of the courtroom floor. Wall face plates must match veneer panels or be typical hardware metal finish. Provide switch and power for monitor. Provide a clock power outlet directly opposite the bench wall, above the entry door(s). Provide power for sound recording equipment, amplifiers, video monitors, video recorders, cameras, computers, X-ray viewers, court reporter steno machines, etc. Electrical outlets or junction boxes will be required at the judge’s bench, court reporter, courtroom deputy, jury box, witness box, walls, ceilings, attorney tables and law clerk and courtroom well.
Provide duplex outlets located at approximately 20- intervals along the walls of the courtroom.foot Provide three-phase, four-wire panelboard(s) to serve courtroom, trial jury suite, miscellaneous areas, and circulation spaces. Serve normal lighting and general power requirements. Size to accommodate 25% growth.
See the individual station description/criteria at the end of this section for additional information.
Lighting:
Lighting design may incorporate pendant-mounted fixtures with matching wall-mounted luminaires or complementary sconces as well as direct and indirect LED luminaires as required to meet foot-candle requirements and to complement the overall design.
The lighting must be dimmable using a lighting control system that is fully adjustable and allows for the creation of preset lighting level schemes. Lighting control system to be integrated with the AV control systems. The lighting control system must also provide control over the emergency circuits during normal operation. Light control switches must be located in areas that are not accessible to the public. Lighting over the bench will not be tied to emergency lighting to avoid “spotlighting” the judge.
Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications:
Infrastructure pathway to include, but not be limited to, appropriately sized conduit, boxes, pull string, cable trays, per EIA TIA industry standards.
Telecommunications wiring will be connected to closets placed within industry standard distances. Coordinate pathway and outlets for cable TV connections.
Provide data and phone outlets for sound recording equipment, amplifiers, video monitors, cameras, computers, court reporter steno machines, etc, as required.
Data outlet is defined as two category 6A twisted pair cables.
Provide wireless access points (WAP) installed throughout court spaces. See the individual station description/criteria at the end of this section for additional information.
Security:
Coordinate all security criteria and equipment with the USMS Office of Security Systems. Public Courtroom entrance to have a keyed lock. If a secondary egress door leads to a restricted circulation area, equip doors with a fail-safe delayed egress device tied to the fire alarm system. Provide infrastructure to Judge's courtroom entrance doors with an electrified lockset, card reader, door contact, and request-to-exit (REX) devices. A secondary card reader is located at the Courtroom Deputy Desk Infrastructure at the rear of the courtroom for a CCTV camera to view the well and the judge’s point of egress out of the room. A second camera will be placed on opposing corners to view all entrances and the gallery.
Audio Visual System:
Further guidance will be provided, see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom Technology and Structured Cabling Systems. Provide conduit and outlets as required to accommodate a Government furnished audio and video system. All conduits must return to AV control rack location. For all individual sections listed below further guidance will be provided, see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom Technology and Structured Cabling Systems.
Judge’s Bench:
The height of the judge’s bench is determined by the court. Generally, the judge’s bench should be elevated three steps (18”) above the courtroom well.
Provide ballistic material (UL Standard 752, Level III) on all vertical surfaces.
Millwork: The bench work surface should be 28”-30” above the floor level of the judge’s station and 30” deep. The front of the work surface should have a rail or barrier a maximum of 4” high around the top. Space for a computer should not obstruct essential sight lines. Provide a lockable drawer and six linear feet of shelf space. Additionally, the judge’s bench must be able to accommodate a sidebar conversation with attorneys without being overheard by the jury.
Provide foot rail.
Electrical: One quadruplex receptacle (general use), one dedicated duplex receptacle. Include electrical service for future platform lift.
Lighting: Task lighting. Override switch to allow instantaneous override of all dimming in an emergency.
Telecommunications: Two duplex outlets.
Audio Visual: One microphone with mute capability. Audio Visual display control station and evidence monitor Security – Provide infrastructure for a duress button.
Courtroom Deputy Clerk Station:
This station is recommended to be at courtroom level or 6” A.F.F with access to the judge. Provide a pass-thru to the judge’s bench. Provide ballistic material (UL Standard 752, Level III) on all vertical surfaces. Controls for temperature, light levels and audiovisual equipment typically are typically housed at this station.
Millwork: 24” deep work surface at desk height, accommodating computer without obstructing sightlines. Provide a 4” raised cap around the work surface.
Provide two built-in, 20” deep file drawers, a lockable drawer for writing instruments and paper (legal size), storage for AV equipment supplies and an adjustable shelf in the station a minimum of 18” deep by 36” long. Provide a securable cabinet near the deputy clerk’s station for letter- or legal-size documents or large, bulky objects.
Electrical: One quadruplex receptacle (general use), one duplex receptacle (general use), one dedicated duplex receptacle, and one special purpose receptacle. Include electrical service for future platform lift.
Lighting: Override switch to allow instantaneous override of all dimming in an emergency.
Telecommunications: Two duplex outlets.
Audio Visual: One microphone with mute capability. Audio Visual display control station, light control station, equipment control station and evidence screen.
Security: Provide infrastructure for card reader to control judge’s courtroom door and for a wireless duress alarm.
Witness Box:
Floor level of the witness box may be one or two steps A.F.F. An accessible ramp must be provided.
Millwork: 14”-16” deep work surface at desk height with 4” max height rail.
Electrical: One duplex receptacle (general use) and one dedicated outlet.
Lighting: Task lighting.
Audio Visual: Two microphones.
Jury Box:
One row at floor level, second (rear) row elevated 6” A.F.F.
Millwork: Perimeter modesty panels, footrest Electrical: Sixteen duplex (one for each jury monitor).
Lighting: Task lighting.
Telecommunications: Provide two duplex outlets.
Audio Visual: One microphone with mute capability, 16 video monitors integrated into modesty panels
Court Reporter Station:
This station is recommended to be at courtroom level or 6” A.F.F.
Millwork: 24” deep work surface at desk height, accommodating computer and reporter equipment. Provide lockable built-in cabinets for stenographic equipment.
Electrical: One quadruplex receptacle (general use), one duplex receptacle (general use), one dedicated duplex receptacle. Include electrical service for future platform lift.
Telecommunications: Two duplex outlets.
Audio Visual: One microphone with mute capability plus jack for court reporter speaker and evidence screen. Note: This mobile station may be continuous with the Courtroom Deputy Clerk Station.
Law Clerk:
Elevated 6” A.F.F. Provide pass-through to the judge's bench.
Millwork: 24” deep, 60” wide work surface at desk height accommodating computer without obstructing sightlines. Provide a 4” raised cap around the work surface. Provide one pencil drawer and two 20” deep lockable file drawers.
Electrical: One quadruplex receptacle (general use), one dedicated duplex receptacle.
Telecommunications: Two duplex outlets.
Audio Visual: One microphone with mute capability. One connection for evidence monitor.
Security: Provide infrastructure for a duress button.
Attorney Stations:
Provide four 3’-6” x 9’-0” work surface/tables at desk height with modesty panels shielding manacled defendants from jurors. Provide lockable doors for AV wiring under the table.
Electrical: Multiple quadruplex receptacles (general use). Multiple dedicated computer power receptacles in recessed floor boxes.
Lighting: Task lighting.
Telecommunications: One outlet at each table.
Audio Visual: Three microphones with mute capability. Two computer video outlets at each table.
Note: Provide two complete sets of additional floor outlet connections to accommodate alternate table arrangements. Coordinate locations with court.
Each table incorporates recessed trough with cover plate to allow for all required devices to be plugged into the tabletop.
Lectern:
Millwork: Height adjustable, movable, ABAAS compliant lectern with built-in lighting.
Electrical: Three duplex receptacles in recessed floor box.
Lighting: Built-in task lighting.
Telecommunications: Two duplex outlets.
Audio Visual: One microphone with mute capability. One computer video outlet.
Note: Provide one complete additional outlet connection to accommodate alternate arrangement. Coordinate locations with court.
Digital Signage: Outside Courtrooms provide power for and network connection infrastructure for Digital Signage. Final locations TBD by AV designer and the Courts.
Evidence Cart:
Millwork: Height adjustable, movable, ABAAS compliant lectern with built-in lighting.
Electrical: Three duplex receptacles in recessed floor box.
Lighting: Built-in task lighting.
Telecommunications: Duplex outlets.
Audio Visual: One microphone with mute capability. One computer video outlet.
Note: Provide one complete additional outlet connection to accommodate alternate arrangement. Coordinate locations with court.
B.2.2.3.2 TRIAL JURY SUITE SOUND LOCK ENTRY
Division: DISTRICT COURTROOM JURY FACILITIES
AB Code: 1041
Square Footage: 50 NSF
Ceiling height: 10’-0”
Acoustics: NIC-55
Floors: Carpet
Base: Wood base to match courtroom.
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Lighting: Provide emergency lighting backup to maintain camera and direct visual
Security: Provide infrastructure for a wireless duress alarm.
B.2.2.3.3 TRIAL JURY SUITE COAT CLOSET
AB Code: 1041
Square Footage: 20 NSF
Ceiling height: 10’-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Acoustics: NIC - 55
B.2.2.3.4 LARGE TRIAL JURY ROOM
AB Code: 1041
Square Footage: 500 NSF
Ceiling Height: 10'-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Fabric wallcovering
Ceilings: Acoustical ceiling tile
Acoustics: NIC - 55
Equipment: Monitor, whiteboard/display board, assistive listening devices
HVAC: The room must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements of Chapter 14 of the USCDG. Return air must be ducted directly back to the exhaust air riser.
Electrical:
Distributed convenience outlets, including provisions for cleaning/housekeeping. Outlets (GFI) on a separate circuit for kitchen type service unit equipment (microwave, coffee maker, refrigerator). Dedicated outlets for projection units, TV monitor, DVD player, and audio tape recorder/player. Outlet for wall mounted clock. Provide a floor box with power and AV.
Lighting: Direct/Indirect lighting. Dimmer controlled direct lighting. On/Off controlled indirect lighting.
Telecommunications:
Provide basic infrastructure.
NOTE: This space should not have means of communication to the outside world.
Audio Visual:
Further guidance will be provided see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom Technology and Structured Cabling Systems.
Security:
Provide infrastructure for a wireless duress alarm leading back to USMS Control Center. Sworn Jury Custodian function is to be incorporated into Trial Jury Room. Provide one push- button and buzzer system between the sworn-jury custodian and foreperson stations.
B.2.2.3.5 TRIAL JURY ROOM
AB Code: 1041
Square Footage: 350 NSF
Adjacent to: Restricted corridor, away from public, attorneys, and litigants
Ceiling Height: 10'-0”
Floors: Carpet
Base: Vinyl/rubber wall base.
Walls: Painted gypsum board, fabric wallcovering
Ceilings: Acoustical ceiling tile
Acoustics: NIC - 55
Equipment: Monitor, whiteboard/display board and assistive listening devices
HVAC:
The room must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements of Chapter 14 of the USCDG. Return air must be ducted directly back to the exhaust air riser.
Electrical:
Distributed convenience outlets, including provisions for cleaning/housekeeping. Outlets (GFI) on a separate circuit for kitchen type service unit equipment (microwave, coffee maker, refrigerator). Dedicated outlets for projection units, TV monitor, DVD player, and audio tape recorder/player. Outlet for wall mounted clock. Floor box with power and AV.
Lighting: Direct/Indirect lighting. Dimmer controlled direct lighting. On/Off controlled indirect lighting.
Telecommunications:
Provide basic infrastructure - WAP NOTE: This space should not have means of communication to the outside world.
Audio Visual:
Further guidance will be provided see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom Technology and Structured Cabling Systems.
Security:
Provide infrastructure for a wireless duress alarm. leading back to USMS Control Center. Sworn Jury Custodian function is to be incorporated into Trial Jury Room. Provide one push- button and buzzer system between the
B.2.2.3.6 JUROR TOILETS
AB Code: 1041
Square Footage: 100 NSF (2 @50 NSF each)
Ceiling height: 10’-0”
Floors: Ceramic tile
Base: Match Corridor
Walls: Ceramic tile wainscot with painted gypsum board above
Ceilings: Painted gypsum board
HVAC: Exhaust ventilation.
Electrical: One GFI duplex wall outlet near sink.
Lighting: Switch controlled LED.
Plumbing:
ABAAS compliant water closet with quiet flush, lavatory and floor drain with trap primer.
Accessories:
ABAAS compliant wall-mounted toilet paper holder, mirror, recessed paper towel dispenser/disposal, sanitary napkin dispenser (women only), liquid soap dispenser, coat hook and toilet grab bars with blocking.
B.2.2.3.7 SWORN JURY CUSTODIAN
AB Code: 1041
Square Footage: 50 NSF
Adjacent to: Outside soundlock entrance
Ceiling height: 10’-0”
Floors: Carpet
Base: To match the corridor.
Walls: Painted gypsum board- millwork countertop
Ceilings: Acoustical ceiling tile
Electrical: Two duplex outlets.
Telecommunications: Provide two duplex outlets.
Security:
Provide one push-button and buzzer system between the sworn-jury custodian and foreperson stations and provide infrastructure for a wireless duress alarm.
B.2.2.3.8 TRIAL JURY SUITE SERVICE UNIT
AB Code: 1041
Square Footage: 20 NSF
Ceiling height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile
Acoustics: NIC - 55
Millwork:
ABAAS compliant durable plastic laminate base and upper cabinets with plastic laminate counter and sink. Space to be provided for tenant supplied under-counter refrigerator (full-size optional), microwave and coffee maker.
HVAC Exhaust ventilation
Electrical: Two duplex outlets. Make GFI if near sink. Dedicated outlets for small appliances.
Plumbing: ABAAS compliant stainless-steel sink and floor drain with trap primer..
B.2.2.3.9 PUBLIC WAITING AREA
AB Code: 1041
Square Footage: 400 NSF
Adjacent to: Courtroom
Ceiling Height: Integral with design intent for public lobby and circulation, over 10’.
Acoustics: NIC-25
Floors: Stone, tile, terrazzo - consistent with design intent for public lobby and circulation
Base: Stone, tile, terrazzo - consistent with design intent for public lobby and circulation
Walls: Stone veneer, wood paneling, painted gypsum board - consistent with design intent for public lobby and circulation
Ceilings: Acoustical ceiling tile, painted gypsum board - consistent with design intent for public lobby and circulation
Electrical: Provide duplex convenience outlets. Provide power for electronic signage and wall mounted clocks.
Lighting: Provide natural light. Artificial LED light to provide minimum 30 FTC.
Telecommunications: Provide data connection for electronic signage.
Security: Provide infrastructure for CCTV system cameras.
Digital signage: Provide electronic signage for docket display system
B.2.2.3.10 SOUNDLOCK
AB Code: 1041
Square Footage: 80 NSF
Adjacent to: Courtroom, public waiting area
Ceiling Height: Integral with design intent for courtroom, over 10’.
Acoustics: NIC 55-60
Floors: Carpet
Base: AWI premium grade wood base
Walls: AWI premium grade wood paneling, painted gypsum board.
Ceilings: Painted gypsum board
Doors and Frames:
Provide two sets of acoustically rated double doors. Design of doors and door trim to be integral with courtroom millwork. Doors into the courtroom must have rectangular view windows with impact-resistant glass. Hardware must allow for silent operation.
B.2.2.3.11 ATTORNEY / WITNESS ROOM
AB Code: 1041
Square Footage: 150 NSF
Adjacent to: Sound lock, public waiting area
Ceiling Height: 10’-0”
Acoustics: NIC 55
Floors: Carpet
Base: AWI premium grade wood base
Walls: Painted gypsum board with AWI premium grade wood wainscot, acoustic fabric wrapped panels as required
Ceilings: Acoustical ceiling tile
HVAC
System must facilitate off-hours usage of the local system. Provide individual temperature control and acoustic privacy, meeting the acoustic performance requirements in Chapter 14 of the USCDG.
Electrical: Provide outlets for video conferencing, TV monitor, personal computers, electronic equipment, and projectors.Provide distributed convenience outlets.
Telecommunications: Provide two duplex outlets.
Audio Visual:
Further guidance will be provided see Facilities and Security Office Space and Facilities Division Facilities Infrastructure Design Guide for Courtroom
General: An occupancy indicator must be provided or a view panel adjacent to the door.
B.2.2.3.12 EQUIPMENT STORAGE
AB Code: 1041
Square Footage: 100 NSF
Adjacent to: Courtroom
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
B.2.2.3.13 EXHIBITS STORAGE
AB Code: 1041
Square Footage: 50 NSF
Adjacent to: Courtroom
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
B.2.2.3.14 COURTROOM VIDEO EQUIPMENT CLOSET
AB Code: 1041
Square Footage: 10 NSF
Adjacent to: Courtroom
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile.
Electrical: Multiple duplex outlets (as required).
B.2.2.3.15 PUBLIC / ATTORNEY COAT CLOSET
AB Code: 1041
Square Footage: 20 NSF
Ceiling Height: 10’-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
B.2.2.3.16 AV ROOM
Division: DISTRICT COURTROOM ASSOCIATED SPACES
AB Code: 1041
Square Footage: 120 NSF
Adjacent to: Courtroom
Ceiling Height: 10'-0”
Floors: Anti-static Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board. Provide fire rated plywood (4’x8’x3/4”) on two walls starting at 6” A.F.F.
Ceilings: Acoustical ceiling tile
HVAC:
Provide supplementary cooling systems to provide air conditioning while the main building mechanical systems are shut down or provide independent 24/7 cooling as required for equipment. Provide temperature sensors to ensure room temperatures do not exceed sensitive electronic operating temperatures.
Electrical:
Two dedicated duplex receptacles for each AV equipment cabinet. Circuits providing power for the AV equipment cabinet must be on the same phase as the electrical circuits providing power to the associated courtroom AV equipment.
Provide power to HVAC equipment serving the room from emergency circuits.
Telecommunications:
Connect to the nearest telecommunications room, on the same floor, with 2-2” (min) conduits. Provide a secondary bonding busbar connected to telecommunications bonding backbone.
Security: Provide infrastructure for USMS (judicial) card reader.
B.2.2.3.17 EXHIBITS DISPLAY
AB Code: 1041
Square Footage: 50 NSF
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Electrical: One duplex outlet.
B.2.2.3.18 STAFF TOILETS
AB Code: 1041
Square Footage: 100 NSF (2 @50 NSF)
Ceiling Height: 10’-0”
Floors: Ceramic tile
Base: Ceramic tile
Walls: Ceramic tile wainscot with painted gypsum board above
Ceilings: Painted gypsum board
HVAC: Exhaust ventilation
Electrical: One GFI duplex wall outlet near the sink.
Lighting: Switch controlled LED lighting.
Plumbing: ABAAS compliant water closet, lavatory and floor drain with trap primer.
Accessories:
ABAAS compliant wall-mounted toilet paper holder, mirror, recessed paper towel dispenser/disposal, sanitary napkin dispenser, liquid soap dispenser, coat hook and toilet grab bars with blocking.
B.2.2.3.19 TRANSCRIBER / TYPIST WORKSTATION
AB Code: 1041
Square Footage: 50 NSF
Ceiling Height: 10’-0”
Workstation: Modular
Floors: Match adjacent
Base: Match adjacent
Walls: Match adjacent
Ceilings: Acoustical ceiling tile
Electrical: Two duplex outlets. One outlet/feed to the powered furniture panel.
Telecommunications: Two duplex outlets..
B.2.2.3.20 COURT REPORTER / RECORDER OFFICE
AB Code: 1044
Square Footage: 150 NSF
Location: Court Reporter suite
Ceiling Height: 10’-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile.
Electrical: Two duplex outlets, two quadruplex outlets.
B.2.2.3.21 COURT REPORTER/RECORDER STORAGE
AB Code: 1044
Square Footage: 50 NSF
Location: Court reporter suite
Ceiling Height: 10’-0”
Floors: Solid/premium vinyl tile
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile.
Electrical: One duplex outlet.
B.2.2.3.22 SHARED WORK ROOM
AB Code: 1044
Square Footage: 100 NSF
Location: Court reporter Suite
Ceiling Height: 10’-0”
Floors: Carpet
Base: Vinyl/rubber wall base
Walls: Painted gypsum board
Ceilings: Acoustical ceiling tile.
Electrical: General purpose outlets. One dedicated quadruplex outlet per workstation.
B.2.2.3.23 ROBING ROOM
AB Code: 1041
Square Footage: 200 NSF
Adjacent to: Courtroom
Ceiling Height: 10’-0”
Floors: Carpet
Base: AWI premium grade wood base
Walls: Fabric wallcovering above wood veneer wainscot
Ceilings: Acoustical ceiling tile, painted gypsum board
HVAC:
The robing room must be separately zoned to facilitate off-hours usage of the local system. Provide individual temperature control and meet the acoustic performance requirements in Chapter 14 of the USCDG. Return air must be ducted directly toward the return-air shaft for a minimum distance of 15 feet.
Electrical:
Minimum requirements for the room are established by the judge.
Convenience outlets spaced at a maximum of 6 feet on center should be provided along the walls.Floor box may be required.
Acoustics: NIC - 50
Lighting: Provide emergency lighting backup to maintain camera and direct visual surveillance in the event of a power failure.
Telecommunications:
Provide two duplex outlets.
One or more outlets connected to the building downlink system and cable
Security: Provide infrastructure for wireless duress alarm, door contact and card reader.
B.2.2.3.24 DISTRICT SPECIAL PROCEEDINGS COURTROOM
AB Code: 1041
Square Footage: 3000 NSF
Adjacent to: Public waiting area
Ceiling Height: 18’-0”
Acoustics: NIC 55-60
Floors: Carpet
Base: AWI premium grade wood base
Walls:
AWI premium grade wood paneling, painted gypsum board. Incorporate acoustical wall panels into the design to meet acoustical performance requirements.
Ceilings:
Painted gypsum board, acoustical plaster designed to meet acoustical performance requirements. Ceiling elements such as soffits, coffers, perimeter coves, recesses and reveals must be provided as required to integrate HVAC, lighting and sound systems into a harmonious design.
Millwork:
AWI premium grade millwork for courtroom paneling, doors, moldings, trim and built-in furniture, which includes:
(1) Judge’s bench (1-2) Courtroom deputy clerk station(s) Evidence cabinet
(1) Court reporter/recorder station Recording equipment cabinet
(1) Law clerk station (1-2) Witness box(s) (18 seat)) Jury Box Lectern (height adjustable, movable, ABAAS compliant lectern with built-in lighting), accommodate a microphone and task lighting (100 plus 4 wheelchair spaces) Spectator Seating with railing
(6) Attorney tables, considered movable furniture, should match built-in courtroom millwork AV equipment, security equipment, and courtroom technology systems will be integrated into the millwork. Provide necessary drilled or cored openings at work surfaces to accommodate cabling, grommets and cable raceways for wire management.
See the individual station description/criteria at the end of this section for further clarification. Note that actual heights of the built-in structures and the depths and lengths of workspaces may vary slightly from the dimensions below based on the findings in the mockup process.
Finish Hardware: All finish hardware in courts and chambers must be durable and consistent in finish and must conform to AWI Standards for Premium Grade.
Accessibility:
The judge’s bench, courtroom deputy, law clerk, and court reporter stations need not be accessible when constructed but must be adaptable for accessibility without significant structural reconfiguration or extension of the courtroom or extension of the electrical system. Other publicly accessible areas such as the litigant and counsel stations, witness station, jury box, lectern, and public seating must be accessible and have an accessible route.
Spectator Area:
Area to accommodate 100 people in pew-type hardwood bench seating or fixed chairs. Provide ABAAS compliant space for four wheelchair accessible seating locations. Benches to match courtroom millwork.
Railing: Provide 30" high decorative spectator rail separating spectators from well of courtroom. Rail should have an accessible gate or opening.
Windows:
Windows are allowed (not required) however security considerations would need to be considered and funded. See security, acoustical and aesthetic requirements in the USCDG.
Window Treatments:
If windows are provided, include electronically operated window coverings may require blackout capability. This would be considered above average and the Judiciary would provide funding via RWA.
Jury Seating:
Provide jury seating for 18. One chair must be removable to provide an ABAAS compliant space for a wheelchair and an accessible route to the wheelchair seating space. Jury box to be designed to allow enough clearance to rock and swivel chairs without interference from walls, jury box panels, monitors, and other jurors. Foot rails must be provided. Jury chairs to be purchased and installed by CMc after review and approval by the Government. At minimum one row of the jury box may be a raised platform above the finish floor.
HVAC:
System must facilitate off-hours usage of the local system. Provide USCDG requirement for 3 HVAC zones within courtroom, one each for judge/attorney area in front, one for jury area, one for spectator area. Air distribution in the spectator area must be sized to serve the maximum allowable seating capacity, plus 25%. Return air from the courtroom and associated areas must be ducted directly to the HVAC unit.
HVAC system must be designed to meet the acoustic performance requirements in Chapter 14 of the US Courts Design Guide. Mechanical units must not be placed above or near courtrooms where noise will affect court proceedings.
Temperature controls must be located in areas that are not accessible to…