FAR_4625212_HAMMOND_FEDERAL_COURTHOUSE_EF415CAB15_9390-120_PMB_-_EESDUS_01222017_(1).pdf

PDF 55 KB Posted

Attached to
Hammond and South Bend Operations and Maintenance
Solicitation number
GS-05-P-17-SL-D-0007
Issued by

About this file

Service Report

View the file

Other files

File Type Posted
PowerLogic_ION_7550_ION7650_Verifying_Accuracy_Technical_Note_032009.pdf PDF
Section_B_Pricing_Pages.pdf PDF
Amend_006.pdf PDF
RFI_3.pdf PDF
Amend_004.pdf PDF
Amend_003.pdf PDF
Questions-_Hammond.pdf PDF
Chiller_2_evaporator_bundle_tag.jpg JPG image
South_Bend_Sprinkler_insp._(1).pdf PDF
IN0300ZZ_2016_October_quarterly_tampers_and_flows.pdf PDF
IN0300ZZ_2016_annual_fire_device_testing.pdf PDF
South_Bend_Fire_Alarm_Insp..pdf PDF
chiller_2_condenser,_bottom_bundle_tag..jpg JPG image
Chiller_1_condenser_-_bottom_bundle_tag.jpg JPG image
Submitted_Questions-_South_Bend.pdf PDF
Chiller_1_evaporator_bundle_tag.jpg JPG image
RFI_2.pdf PDF
Amend_003.pdf PDF
Amend_002.pdf PDF
IN0096ZZ_CBA.pdf PDF
Q&A.pdf PDF
IN0300ZZ_CBA.pdf PDF
IN0096ZZ_-_R._Grant_FB_&_CTHSE_-_Asbestos_&_Lead_Based_Paint_Report_2007_(1).pdf PDF
Amend_001_GS05P17SLD0007.pdf PDF
SF33-14a_(3).pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

210 WINDY POINT DR

GLENDALE HEIGHTS,IL.60139-3805

Service Dispatch: (800)843-9433 www.eaton.com/powerquality

Field Activity Report

PMB - EESDUS

For

HAMMOND FEDERAL COURTHOUSE

5400 FEDERAL PLAZA

HAMMOND,IN 46320

BASEMENT

Attention: BILL AUGLE Phone: 219-933-7473 Email: ba3056@gmail.com

Inspection Date: 01/18/2017

Service Performed By: Richards, Mr. Terell

Service Request: Serial Number: Customer ID#

4625212 EF415CAB15 9390-120

CSE Signature Digitally Signed by Richards, Mr. Terell Date 01/18/2017

Customer Signature Date 01/18/2017

BILL AUGLE

http://www.eaton.com/powerquality

Date 01/18/2017

SR# 4625212

Party # 2519126 Contract

Expiration Customer ID 9390-120

Field Activity Report

Site Information: Equipment Information:

Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0

Address 5400 FEDERAL PLAZA Serial # EF415CAB15 CTO or PN# TC10A2201A30010

City HAMMOND ST IN Zip 46320 Location BASEMENT

QOS Information: Battery Information:

POC BILL AUGLE Manufacturer Eaton

Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4

Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet

ALT TEL

Email: ba3056@gmail.com

Service Information Service Type: MAJOR PM Billing Type: QUOTED PM Frequency: Semi Annual

Battery Maintenance Type: Semi Annual

Notes:

CSE PERFORMED THE FOLLOWING:

-DOWNLOADED EEPROM

-DOWNLOADED/REVIEWED HISTORY FILE

-REVIEWED UNIT CONFIGURATION

-VERIFIED ALL APPROPRIATE FIELD SERVICE BULLITENS (FSBS) INSTALLED

-VERIFIED THAT NO SIGNS OF HEATING EXIST

-VERIFIED FAN OPERATION

-PERFORMED TEMPERTURE CHECK

-VERIFIED UPS METERING

-PERFORMED FIRMWARE UPDATE TO DSP 6.08

-PERFORMED FSB-606D

-CSE VERFIED EEP361=200, EEP375=360, EEP377=45, AND EEP378=190

-CSE ADJUSTED EEP374 TO 96, AND EEP376 TO 240

-CSE ADJUSTED OPP CHARGE LEVEL TO 2.07 VOLTS/CELL

-CSE PERFORMED BATTERT TEST USING THE FRON PANEL DISPLAY. THE BATTERY TEST PASSED.

BATTERY TESTING PERFORMED

CSE CONDUCTED THE FOLLOWING:

-REVIEWED HISTORY LOG AND VERIFIED NO UNUSUAL ENTRIES

-CLEANED ALL BATTERIES

-VERIFIED ALL BATTERY CONNECTIONS FOR PROPER TORQUE

-CONDUCTED BATTERY TESTING USING THE ALBER CELLCORDER.

-VERIFIED THE UPS WAS RESTORED TO NORMAL OPERATIONS

-ALL BATTERIES PASSED, NO FAULTS DISCOVERED.

Party # 2519126 Contract

Expiration Customer ID 9390-120

Field Activity Report

Site Information: Equipment Information:

Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0

Address 5400 FEDERAL PLAZA Serial # EF415CAB15 CTO or PN# TC10A2201A30010

City HAMMOND ST IN Zip 46320 Location BASEMENT

QOS Information: Battery Information:

POC BILL AUGLE Manufacturer Eaton

Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4

Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet

ALT TEL

Email: ba3056@gmail.com

Service Information Service Type: MAJOR PM Billing Type: QUOTED PM Frequency: Semi Annual Battery Maintenance Type: Semi Annual

Times shown are estimates only. Billing will be based on actual time entered after final completion of service and applicable material expenses.

Labor Service Date CSE Last Name Labor Item Start Time End Time Duration 22-JAN-17 Richards 1 PHASE - TRAVEL REG 08:00 10:45 2.75 22-JAN-17 Richards 3 PHASE - LABOR REG 10:45 12:00 1.25 22-JAN-17 Richards 3 PHASE - TRAVEL REG 12:00 14:45 2.75

Expense Service Date CSE Last Name Expense Item QTY UOM Amount Justification

Material Service Date CSE Last Name Item Description QTY UOM

Party # 2519126 Contract

Expiration Customer ID 9390-120

Field Activity Report Site Information: Equipment Information:

Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0 Address 5400 FEDERAL PLAZA Serial # EF415CAB15

CTO or PN# TC10A2201A30010 City HAMMOND ST IN Zip 46320 Location BASEMENT

QOS Information: Battery Information:

POC BILL AUGLE Manufacturer Eaton

Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4

Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet

ALT TEL

Email: ba3056@gmail.com

Input Readings

Nominal 480.0

A-B VAC 478.6

B-C VAC 479.3

C-A VAC 476.4

A-N VAC 274.6

B-N VAC 278.0

C-N VAC 275.5

A-I 37.9 B-I 38.0 C-I 37.9

Frequency 60.0

Output Readings

Nominal 277.1

A-B VAC 477.9

B-C VAC 478.8

C-A VAC 478.7

A-N VAC 276.3

B-N VAC 276.1

C-N VAC 276.2

A-I 38.3 B-I 26.2 C-I 19.7 N-I 0

Frequency 60.0 Percent Load 23.3

Output KVA 23.3 Output KW 22.1

Bypass Readings

Nominal 277.1

A-B VAC 480.1

B-C VAC 481.8

C-A VAC 479.2

A-N VAC 275.7

B-N VAC 278.7

C-N VAC 277.6

DC Readings

DC Link Volts 777.9 Battery Volts 515.5

Inverter Readings

Nominal 480.0

A-B VAC 477.9

B-C VAC 478.8

C-A VAC 478.7

A-N VAC 276.3

B-N VAC 276.1

C-N VAC 276.2

Electronic Visual Inspection Remote Monitor Panel Operation Good Electronic Room Temperature 70 Electronic Fans - Monitor Panel Function Good Electronic Room Ventilation Good

Electronic Metering Good Communication Function Good Electronic Room Cleanliness - Ctrl & Pwr Wire Heating Good Mimic Screen Good Electronic Room Floor Type Good

AC/DC Caps - Cellwatch / Battery Monitor N/A Electronic Air Filters - Static Switch Fuses Good Time and Date Set Correctly Good Battery Room Temperature

Output Fuses Good Download/Check Event Log Good Battery Room Ventilation Good Connector (Crimp&Bolt) Good Download EEPS Good Battery Room Cleanliness Good

Waveform Distortion Good Download Configuration Report Good Battery Room Floor Type Good System Transfers Good Download Unit Stats N/A Battery Visual Inspection Good

FSB's checked Good

Notes from the Equipment Inspection Test Result Form

-ELECTRONIC METERING: CSE VERIFIED ALL METERING TO BE ACCURATE AND CALIBRATED.

-TIME AND DATE: CSE SET TIME AND DATE

-DOWNLOAD/CHECK EVENT LOG: NO UNUSUAL EVENTS

-BATTERY VISUAL INSPECTION: CSE VERIFIED ALL BATTERIES IN GOOD CONDITION (ie NO SWELLING, NO CORROSION, ALL

POSTS TORQUED PROPERLY).