Text version
210 WINDY POINT DR
GLENDALE HEIGHTS,IL.60139-3805
Service Dispatch: (800)843-9433 www.eaton.com/powerquality
Field Activity Report
PMB - EESDUS
For
HAMMOND FEDERAL COURTHOUSE
5400 FEDERAL PLAZA
HAMMOND,IN 46320
BASEMENT
Attention: BILL AUGLE Phone: 219-933-7473 Email: ba3056@gmail.com
Inspection Date: 01/18/2017
Service Performed By: Richards, Mr. Terell
Service Request: Serial Number: Customer ID#
4625212 EF415CAB15 9390-120
CSE Signature Digitally Signed by Richards, Mr. Terell Date 01/18/2017
Customer Signature Date 01/18/2017
BILL AUGLE
http://www.eaton.com/powerquality
Date 01/18/2017
SR# 4625212
Party # 2519126 Contract
Expiration Customer ID 9390-120
Field Activity Report
Site Information: Equipment Information:
Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0
Address 5400 FEDERAL PLAZA Serial # EF415CAB15 CTO or PN# TC10A2201A30010
City HAMMOND ST IN Zip 46320 Location BASEMENT
QOS Information: Battery Information:
POC BILL AUGLE Manufacturer Eaton
Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4
Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet
ALT TEL
Email: ba3056@gmail.com
Service Information Service Type: MAJOR PM Billing Type: QUOTED PM Frequency: Semi Annual
Battery Maintenance Type: Semi Annual
Notes:
CSE PERFORMED THE FOLLOWING:
-DOWNLOADED EEPROM
-DOWNLOADED/REVIEWED HISTORY FILE
-REVIEWED UNIT CONFIGURATION
-VERIFIED ALL APPROPRIATE FIELD SERVICE BULLITENS (FSBS) INSTALLED
-VERIFIED THAT NO SIGNS OF HEATING EXIST
-VERIFIED FAN OPERATION
-PERFORMED TEMPERTURE CHECK
-VERIFIED UPS METERING
-PERFORMED FIRMWARE UPDATE TO DSP 6.08
-PERFORMED FSB-606D
-CSE VERFIED EEP361=200, EEP375=360, EEP377=45, AND EEP378=190
-CSE ADJUSTED EEP374 TO 96, AND EEP376 TO 240
-CSE ADJUSTED OPP CHARGE LEVEL TO 2.07 VOLTS/CELL
-CSE PERFORMED BATTERT TEST USING THE FRON PANEL DISPLAY. THE BATTERY TEST PASSED.
BATTERY TESTING PERFORMED
CSE CONDUCTED THE FOLLOWING:
-REVIEWED HISTORY LOG AND VERIFIED NO UNUSUAL ENTRIES
-CLEANED ALL BATTERIES
-VERIFIED ALL BATTERY CONNECTIONS FOR PROPER TORQUE
-CONDUCTED BATTERY TESTING USING THE ALBER CELLCORDER.
-VERIFIED THE UPS WAS RESTORED TO NORMAL OPERATIONS
-ALL BATTERIES PASSED, NO FAULTS DISCOVERED.
Party # 2519126 Contract
Expiration Customer ID 9390-120
Field Activity Report
Site Information: Equipment Information:
Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0
Address 5400 FEDERAL PLAZA Serial # EF415CAB15 CTO or PN# TC10A2201A30010
City HAMMOND ST IN Zip 46320 Location BASEMENT
QOS Information: Battery Information:
POC BILL AUGLE Manufacturer Eaton
Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4
Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet
ALT TEL
Email: ba3056@gmail.com
Service Information Service Type: MAJOR PM Billing Type: QUOTED PM Frequency: Semi Annual Battery Maintenance Type: Semi Annual
Times shown are estimates only. Billing will be based on actual time entered after final completion of service and applicable material expenses.
Labor Service Date CSE Last Name Labor Item Start Time End Time Duration 22-JAN-17 Richards 1 PHASE - TRAVEL REG 08:00 10:45 2.75 22-JAN-17 Richards 3 PHASE - LABOR REG 10:45 12:00 1.25 22-JAN-17 Richards 3 PHASE - TRAVEL REG 12:00 14:45 2.75
Expense Service Date CSE Last Name Expense Item QTY UOM Amount Justification
Material Service Date CSE Last Name Item Description QTY UOM
Party # 2519126 Contract
Expiration Customer ID 9390-120
Field Activity Report Site Information: Equipment Information:
Name HAMMOND FEDERAL COURTHOUSE Unit / Model 9390-120 KVA 100.0 KW 90.0 Address 5400 FEDERAL PLAZA Serial # EF415CAB15
CTO or PN# TC10A2201A30010 City HAMMOND ST IN Zip 46320 Location BASEMENT
QOS Information: Battery Information:
POC BILL AUGLE Manufacturer Eaton
Company HAMMOND FEDERAL COURTHOUSE Battery Model PWHR12390W4FR Address 5400 FEDERAL PLAZA # of Strings 1 Trays/Str 10 Jars/Tray 4
Date Code 02/2012 Age (Years) 4.91 City HAMMOND ST IN Zip 46320 Battery Type Sealed TEL 219-933-7473 FAX Battery Cabinet Type Cabinet
ALT TEL
Email: ba3056@gmail.com
Input Readings
Nominal 480.0
A-B VAC 478.6
B-C VAC 479.3
C-A VAC 476.4
A-N VAC 274.6
B-N VAC 278.0
C-N VAC 275.5
A-I 37.9 B-I 38.0 C-I 37.9
Frequency 60.0
Output Readings
Nominal 277.1
A-B VAC 477.9
B-C VAC 478.8
C-A VAC 478.7
A-N VAC 276.3
B-N VAC 276.1
C-N VAC 276.2
A-I 38.3 B-I 26.2 C-I 19.7 N-I 0
Frequency 60.0 Percent Load 23.3
Output KVA 23.3 Output KW 22.1
Bypass Readings
Nominal 277.1
A-B VAC 480.1
B-C VAC 481.8
C-A VAC 479.2
A-N VAC 275.7
B-N VAC 278.7
C-N VAC 277.6
DC Readings
DC Link Volts 777.9 Battery Volts 515.5
Inverter Readings
Nominal 480.0
A-B VAC 477.9
B-C VAC 478.8
C-A VAC 478.7
A-N VAC 276.3
B-N VAC 276.1
C-N VAC 276.2
Electronic Visual Inspection Remote Monitor Panel Operation Good Electronic Room Temperature 70 Electronic Fans - Monitor Panel Function Good Electronic Room Ventilation Good
Electronic Metering Good Communication Function Good Electronic Room Cleanliness - Ctrl & Pwr Wire Heating Good Mimic Screen Good Electronic Room Floor Type Good
AC/DC Caps - Cellwatch / Battery Monitor N/A Electronic Air Filters - Static Switch Fuses Good Time and Date Set Correctly Good Battery Room Temperature
Output Fuses Good Download/Check Event Log Good Battery Room Ventilation Good Connector (Crimp&Bolt) Good Download EEPS Good Battery Room Cleanliness Good
Waveform Distortion Good Download Configuration Report Good Battery Room Floor Type Good System Transfers Good Download Unit Stats N/A Battery Visual Inspection Good
FSB's checked Good
Notes from the Equipment Inspection Test Result Form
-ELECTRONIC METERING: CSE VERIFIED ALL METERING TO BE ACCURATE AND CALIBRATED.
-TIME AND DATE: CSE SET TIME AND DATE
-DOWNLOAD/CHECK EVENT LOG: NO UNUSUAL EVENTS
-BATTERY VISUAL INSPECTION: CSE VERIFIED ALL BATTERIES IN GOOD CONDITION (ie NO SWELLING, NO CORROSION, ALL
POSTS TORQUED PROPERLY).