NIWTP - Physical Security SPECS.xlsx
XLSX spreadsheet 16 KB Posted
- Attached to
- Security System Upgrade
- Solicitation number
- FY254361002
About this file
The file is a detailed Excel spreadsheet (NIWTP - Physical Security SPECS.xlsx) specifying hardware and equipment components for a comprehensive security system upgrade at the Nogales Field Office of the International Boundary and Water Commission (IBWC). The security system upgrade includes access control, video surveillance, alarm systems, and network/communication infrastructure, utilizing equipment from manufacturers such as Software House, HID, American Dynamics, DSC, and Comnet. Key system components include network switches, power supplies, electric strike locks, card readers, fingerprint readers, cameras, alarm panels, intercoms, and related mounting hardware.
The associated federal contract opportunity (Solicitation Number: FY254361002) is a 100% small business set-aside for Security System Upgrade, with a NAICS code of 561621 and a small business standard of $25.0 million. The solicitation requires an ALL or NONE quote submission by June 25, 2025, at 3:00 pm MST, with quotes valid for 90 days. The government will award the contract using a lowest price technically acceptable (LPTA) evaluation methodology, considering technical acceptability, technical approach, and past performance. The site is located at 865 Rio Rico Industrial Park, Rio Rico, AZ 85648, and a site visit is recommended, with visits closing on 6/13/25.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Updated WD 2015-5481_Rev. 27_5.20.25.pdf | ||
| QAs 6-23-25.odt | ODT document | |
| QA 6-22-25.odt | ODT document | |
| QAs 6-13-25.odt | ODT document | |
| PWS-CIP-Physical Security Enhancements Project-NIWTP (2025).docx | DOCX document | |
| QAs-5-29-25.odt | ODT document | |
| Conceptual Design-Physical Security Project-NIWTP (2025).pdf | ||
| Wage Determination.pdf | ||
| CLIN Structure.docx | DOCX document | |
| APPENDIX A - NIWTP - System_Hardening_Requirements.docx | DOCX document | |
| PWS-CIP-Physical Security Enhancements Project-NIWTP (2025).docx | DOCX document | |
| Clauses and Provisions.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| System | Brand | Model | Location | Function |
| Access Control System | Altronix | SMP3 Power Supply | Access Control Head Ends | Converts 120VAC into 24VDC lock power. |
| Altronix | PMK1 Pole Mounting Kit | Security Site Poles | Pole mounting kit for outdoor enclosures. | |
| Altronix | WP2 Nema 4 Enclosure | Access Site Pole Enclosures | Houses security equipment outdoors. | |
| Bosch | DS160 Request‐To‐Exit | Doors w/ Electric Strike Locks | Request‐to‐exit motion sensor above the access control door. | |
| Comnet | CWGE2FE8MSPOE Network Switch | 8‐Port Network Switch for Lab & Chlorine Bldgs | Provides network communication and POE power for (8) ports for access control, CCTV & wireless. | |
| Comnet | CWGE26FX2TX24MSPOE Network Switch | 24‐Port Network Switch for Admin Bldg | Provides network communication and POE power for (24) ports for access control, CCTV & wireless. | |
| Comnet | CNGE2FE8MSPOE+ Network Switch | 8‐Port Hardened Network Switch at Vehicle Gates | Provides network communication and POE power for (8) ports for access control, CCTV & wireless. | |
| Comnet | CNFE5SMSPOE Network Switch | 4‐Port Hardened Network Switch at Site Security Poles | Provides network communication and POE power for (4) ports for CCTV & wireless. | |
| Comnet | PS48VDC‐5A Power Supply | Power supply for network switch at vehicle gates and site security poles | Provides the required 48VDC to the network POE switches. | |
| Dell | P2014H 19” Monitor | Security Rack in Admin Bldg | Monitor is used to view the Access Control & CCTV Server | |
| Dell | SonicWall TZ300 | Security Rack in Admin Bldg | Firewall appliance that protects the security network from attack. | |
| Digital Persona | 5160 Fingerprint Reader | Security Server, Access Control Client Workstation & CCTV Client Workstation | Provides fingerprint authentication before gaining access to server or client workstations. | |
| Elo Tech Solutions | 2201L 22” Touchscreen Monitor | Access Control Client Workstation | Provides viewing capability of the access control system’s software. | |
| General Locks | C9016‐689 Door Closer | Lab Bldg ‐ Entry Door | Controls door closing. | |
| HES | 4500 Electric Strike Lock | Access control doors | Provides electric locking/unlocking to access control doors with mortise or cylindrical lock. | |
| HES | 9600 Electric Strike Lock | Access control doors | Provides electric locking/unlocking to access control doors with exit bars. | |
| HID | RP40 Card Reader | Access Control Doors | Accepts/Denies users credential for gaining access to door. | |
| HID | 1326 Credential Cards | Employee/Contractor | Provides user identification at access control doors. | |
| Kaspersky | Business Select Anti‐Virus Software | Security Server, Access Control & CCTV Client Workstations, NVR & any additional clients | Provides virus protection to equipment operating on the security network. | |
| Magnasphere | HS‐L1.5 Door Contact | Access Control and Alarm Monitoring Doors | Provides monitoring of door position to security systems. | |
| Marray | Transfer Hinge | Access control doors with electromechanical mortise locks | Provides power and communication pass through from door frame to door. | |
| Middle Atlantic | UPS‐S2200R Power Supply | Security rack at each auxiliary building | Provides power and backup battery to access control, CCTV and wireless equipment. | |
| Middle Atlantic | CWR‐12‐22PD Rack Wall Cabinet | Head end at Chlorine & Lab Bldgs | Provides 12U of space for mounting equipment. | |
| Middle Atlantic | WRK‐37SA‐32 Standalone Rack | Head end at Admin Bldg | Provides 37U of space for mounting equipment. | |
| Minuteman | EN900 Power Supply | Security head ends at vehicle gates and site poles | Provides power & backup battery to access control, CCTV and wireless equipment. | |
| Securitron | AQD6 Switching Power Supply | Access control power supply head ends | Provides up to 6 Amps at 12VDC or 24VDC output. | |
| Securitron | AQM20 Power Supply | Access control power supply head ends | Provides up to 20 Amps at 12VDC and 24VDC output | |
| Securitron | PDB‐8F1 Power Distribution Board | Access control head ends | Provides (8) 12VDC outputs to power access control devices & modules. | |
| Securitron | EEB2 Exit Button | Access control doors | Secondary form of egress if REX IR would fail. | |
| Seneca | S1000 Server | Admin Building ‐ Security Rack | Controls C‐Cure 9000 and Victor software. | |
| Seneca | 3250 Workstation | Admin Building ‐ Reception | Workstation that allows users to view and operate the access control & CCTV system software. | |
| StarTech | DP2DVI Adapter | Admin Building - Client Workstation | Adapter that allows monitor to be connected to workstation. | |
| Software House | iStar Ultra‐8 | Admin Building ‐ Access Control Head End | Main controller for operating the access control system. | |
| Software House | iStar Edge | Auxilary building and vehicle gate access control head ends | Edge controller for up to (2) card reader doors and/or gates. | |
| Software House | I8 Input Module | Access control head ends | Module provides up to (8) monitoring inputs. | |
| Software House | R8 Module | Personnel Building ‐ Access control head end | Module provides up to (8) monitoring outputs. | |
| Software House | RM‐DCM‐CAN | Access control head ends | Enclosure for mounting SWH I8 & R8 module boards. | |
| Software House | C‐Cure 9000 Software | Security Server | Software House operating software for access control. | |
| Safety Technology International | STI‐7081 Universal Pole Mount | Site security poles | Universal mount that allows security equipment to be pole mounted. | |
| Sargent | Electromechanical Cylindrical Lock | Access control doors | Provides electric locking/unlocking to access control to door. | |
| Seco‐Larm | SEL‐SD969S18 Armored Door Cord | Access control doors | Provides power and communication pass through from door frame to door. | |
| The Housing Company | PS042B Pedestal | Vehicle Gates | 42” pedestal for mounting card reader at accessible height for users in vehicles. | |
| The Housing Company | PCH196 Card Reader Housing | Vehicle Gates | Provides security location on pedestal for mounting card reader. | |
| Wiegmann | J201608CHQR Outdoor Rated Enclosure | Vehicle gate head ends | Houses security equipment outdoors. | |
| Wiegmann | MP2016SS Back Plate | Vehicle gate outdoor rated enclosures | Back plate for mounting security equipment in enclosure. | |
| Video Survelance System | American Dynamics | Pro PTZ Camera | Site Poles & Vehicle Gate Poles | Provides 2MP of pan‐tilt‐zoom viewing capability. |
| American Dynamics | 610 Bullet Camera | Poles at Vehicle Gates | Converts 115VAC into 24VAC or 28VAC supply current. | |
| American Dynamics | RHOWPA Mount | Camera Poles | Allows PTZ to be pole mounted. | |
| American Dynamics | RHOSW Mount | Camera Poles | PTZ mounting bracket from camera to pole mount. | |
| American Dynamics | ADSPOT Power Supply | PTZ cameras | Provides power to PTZ camera. | |
| American Dynamics | NVR | Admin Building ‐ Security Rack | Records video of all security cameras. | |
| American Dynamics | AS2089 Joystick | CCTV Client Workstation | Allows operator to move PTZ cameras for different viewing angles. | |
| Ditek | DTK‐MRJPOE Surge Protector | Security Cameras | Provides surge protection from security camera to network switch. | |
| Elo Tech Solutions | 2201L 22” Touchscreen Monitor | CCTV Client Workstation | Provides viewing capability of the CCTV system’s software. | |
| Seneca | 3250 Workstation | Admin Building ‐ Location TBD | Workstation that allows users to view and operate the CCTV software. | |
| Alarm System | DSC | HS2128 Alarm Panel | Admin Building ‐ Security Head End | Main controller for alarm system. |
| DSC | HS2LCD Alarm Keypad | Admin Building | Keypad is used to program and arm/disarm system. | |
| DSC | HSM2108 Zone Expander | Admin Building ‐ Alarm System Head End | Provides (8) additional alarm monitoring inputs. | |
| DSC | HSM2204 Output Module | Admin Building ‐ Alarm System Head End | Provides (8) alarm monitoring outputs. | |
| DSC | TL2803G Cellular Communicator | Alarm Control Panel | Utilizes cellular connection to ensure reliable alarm communications. | |
| DSC | TL280 Network Communicator | Alarm Control Panel | Utilizes internet connection to ensure reliable alarm communications. | |
| DMP | 322 Transformer | Alarm Control Panel | Converts 120VAC into 16.5VAC power to alarm control panel. | |
| DMP | 335 Indoor Siren | Admin Bldg | Provides audible notification of alarm. | |
| Magnasphere | HS‐L1.5 Door Contact | Access Control and Alarm Monitoring Doors | Provides monitoring of door position to security systems. | |
| Optex | FX‐360 Motion Detector | Personnel Building ‐ Operations Room & Operations Building ‐ Control Room | Provides 360 degree motion detection. | |
| USP | HUB2SA Duress Button | Personnel Building | Button alerts alarm system of an emergency when pushed. | |
| Securitron | AQD6 Switching Power Supply | Access control power supply head ends | Provides up to 6 Amps at 12VDC or 24VDC output. | |
| Potter | 4150026 Siren w/ Blue Strobe | Admin Building | Provides audible and visual notification of alarm. | |
| UTC | 5815NT‐313 Glass Break Sensor | Admin & Lab Bldgs | Detects if when glass is broken. | |
| Wireless Communication | Comnet | NWK1 Network Transceiver | Site building and security site poles | Provides 50Mps of wireless network communication. |
| Ditek | DTK‐MRJPOE Surge Protector | Access control head end near network switches | Provides surge protection from outdoor network equipment. | |
| Intercom System | Aiphone | IX‐DA IP Door Station w/ Camera | Main Gate | Provides two‐way communication and visual capability for Main Gate. |
| Aiphone | IX‐MV Master Station | 100 Administration Building | Provides two‐way communication and allows user to open gates remotely. | |
| Aiphone | RY‐IP44 Input & Output Adaptor | Main Gate head end | Provides (4) inputs and (4) outputs to trigger Main Gate. |
Wireless Communication
Intercom System
File details come from the government source that posted it. Updated .