FP3.00_ FIRE PROTECTION ENLARGED VIEWS Rev.2.pdf
PDF 559 KB Posted
- Solicitation number
- BD-27-1053-1053C-CSR-132423
- Issued by
- Hampden County, Massachusetts
About this file
This is a fire protection system technical drawing document prepared by Payette Associates Inc. for the Soldiers' Home in Holyoke, a Massachusetts state agency facility located at 110 Cherry Street. The drawing set, designated FP3.00 (Fire Protection Enlarged Views, Revision 2), provides detailed specifications and layouts for the fire suppression system installation at this 234-bed long-term care facility. The technical drawings illustrate fire protection components across multiple levels including the north stairwell areas (Levels 0 through 8) and the fire pump room, showing the configuration of sprinkler systems, standpipe isolation and drain valves, fire department connections, pressure reducing valves, and related infrastructure. Key equipment specifications detailed in the drawings include a horizontal split case fire pump rated at 1,250 gallons per minute at 185 PSI boost, fire pump test headers, fire department inlet connections, jockey pump controllers with automatic transfer switches, and a nitrogen generator system. The drawings reference civil engineering documents for additional water service information and specify installation requirements such as pipe diameters, valve orientations, and connection locations relative to building features like the driveway and hydrants. The document was originally issued on January 10, 2023, with subsequent revisions documented in two bulletins (Bulletin #75 dated September 25, 2024, and Bulletin #91 dated January 29, 2025), indicating ongoing design refinements for this long-term care facility project.
The technical specifications and design standards reflected in these drawings are intended to comply with the preventative maintenance and inspection requirements outlined in the related Massachusetts Operational Services Division TRD03 contract opportunity, which mandates compliance with NFPA 25, NFPA 101, and 527 CMR Massachusetts Comprehensive Fire Safety Code standards. The drawings serve as the technical foundation for the fire suppression system scope of work that includes annual inspection, testing, and maintenance of wet pipe and dry pipe systems, control valve operation, supervisory switch testing, waterflow alarm testing, and pressure gauge testing and replacement, with work subject to prevailing wage requirements and regulatory oversight from the Department of Public Health, Centers for Medicare & Medicaid Services, and the Department of Veterans Affairs.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EX
LW
2W
1W
2N
1N
3"SD UP
6"FSP UP
6"FSP DROP
2-1/2"FDV
2"STANDPIPE DRAIN VALVE
6"STANDPIPE ISOLATION VALVE
4"PRV
4"FCVA
N1
STAIR
LW
2W1W 2N1N
6"FSP UP&DN
3"SD UP&DN
2-1/2"FDV
4"PRV
4"FCVA - ZONE 2
N1
STAIR
LW
2W
2N 1N
6"FSP UP&DN
3"SD UP&DN
2-1/2"FDV
4"PRV
4"FCVA - ZONE 2
N1
STAIR
LW
2W1W
2N1N
6"FSP UP&DN
4"SD UP&DN
2 1/2"FDV
4"PRV
4"FCVA
N1
STAIR
LW
2W1W 2N1N
6"FSP DN&RISE
3"SD DN&RISE
2-1/2"FDV
4"PRV
4"FCVA - ZONE 2
N1
STAIR
BW
1W
AW
W054
FIRE PUMP
ROOM
W1
STAIR
10" F
10" X 2-1/2" X 6"-WAY WALL MOUNTED FIRE
PUMP TEST HEADER FACING DRIVEWAY.
INSTALL IN VERTICAL ORIENTATION. AS
TIGHT AS POSSIBLE TO NORTHWEST
CORNER OF FIRE PUMP ROOM
8" X 2-1/2" X 4"-WAY WALL MOUNTED FIRE
DEPARTMENT INLET CONNECTION. FACING
DRIVEWAY, WITHIN 50-FT OF A HYDRANT
IN VERTICAL ORIENTATION
HORIZONTAL SPLIT CASE FIRE PUMP
1,250 GPM AT 185 PSI BOOST
10"SUCTION
PIPE TO RUN 10xPIPE DIAMTERS
BEFORE ENTERING FIRE PUMP
8"DISCHARGE
8"BYPASS
8"METER LOOP
JOCKEY PUMP CONTROLLER
10"F INCOMING FIRE PROTECTION WATER
SERVICE. REFER TO CIVIL ENGINEERING
DOCUMENTS FOR ADDITIONAL INFORMATION.
PROVIDE 10"DCVA AT FIRE PUMP ROOM
8" FSP
SOLID STATE SOFT START FIRE PUMP
CONTROLLER WITH AUTOMATIC
TRANSFER
SWITCH
4" DS
8"F DROP
8"MACV
8"FSP DROP
6"PRV
6"DACV FOR LOADING DOCK AND
MAINTENANCE GARAGE AREAS
6"DS RISE
4"DACV FOR CANOPY
4"DS RISE
4"SD TEST
NITROGEN GENERATOR MOUNTED ON WALL
8' - 4"
10" TH
10" F
10" F
8" FDC
INSTALL DRY VALVE DRAINS THROUGH
EXISTING SLAB AND EXTEND HORIZONTALLY
UNDERGROUND TO CLOSEST STORM WATER
LINE. MAKE NEW CONNECTION TO STORM
WATER LINE PER VALVE
FHYD UG1
UG2
FPI FPO
FP04
MAVI
MAVO
FP05
FP03
DVI
DVO
D1
FP06
DCVO
DCVI
D2
FW0
W045C
RECEIVING
ENTRY
W010
CORRIDOR
0'
Project Name:
DCAMM Project Number:
Project Location
Project Architect
Site Number:
CAMIS Number:
Building Number:
Secretariat:
F ile
P a th
Original Issue Date
Revisions
Drawing Title:
Drawing Number:
Project Consultant
HLY2102
Payette Associates Inc.
290 Congress Street, Fifth Floor Boston, MA 02210-1005 Tel: 617-895-1000 www.payette.com
Project Number:
40158.00
10' 20' 40'
HLY 00
N/A
256 HLY 0010
E.O.H.H.S
BR+A CONSULTING ENGINEERS
10 Guest Street, 4th Floor
Boston, MA 02135
617.254.0016 brplusa.com
B
IM
/H o ly o k e S o ld ie rs
H o m e /3
H
S H
C
S B
R
A P
F P
O
R .r v t
FIRE PROTECTION
ENLARGED VIEWS
FP3.00
01/10/2023
SOLDIERS' HOME
IN HOLYOKE
LONG-TERM
CARE PACKAGE
110 Cherry Street Holyoke, MA 01040
1/4" = 1'-0"
LEVEL 0 ENLARGED NORTH STAIR PART PLAN - FIRE PROTECTION PLAN
1/4" = 1'-0"
LEVEL 1 ENLARGED NORTH STAIR PART PLAN - FIRE PROTECTION PLAN -
1/4" = 1'-0"
LEVEL 2 ENLARGED NORTH STAIR PART PLAN - FIRE PROTECTION PLAN
1/4" = 1'-0"
LEVEL 3-7 ENLARGED NORTH STAIR PART PLAN - FIRE PROTECTION PLAN
1/4" = 1'-0"
LEVEL 8 ENLARGED NORTH STAIR PART PLAN - FIRE PROTECTION PLAN
1/4" = 1'-0"
LEVEL 0 ENLARGED FIRE PUMP ROOM PART PLAN - FIRE PROTECTION PLAN
No. Description Date
1 BULLETIN #75 09/25/2024
2 BULLETIN #91 01/29/2025
File details come from the government source that posted it. Updated .