FP2.09_ PENTHOUSE - FIRE PROTECTION PLAN Rev.5 markup.pdf
PDF 482 KB Posted
- Solicitation number
- BD-27-1053-1053C-CSR-132423
- Issued by
- Hampden County, Massachusetts
About this file
This is a Fire Protection Plan document for the Soldiers' Home in Holyoke, a Massachusetts state agency long-term care facility, prepared by Payette Associates Inc. and BR+A Consulting Engineers. The plan details the penthouse-level fire suppression system design for the 234-bed facility located at 110 Cherry Street in Holyoke, Massachusetts. The document specifies fire protection requirements across multiple penthouse areas including the West Penthouse, East Penthouse, mechanical rooms, stairwells, elevator lobbies, and telecommunication rooms. The plan includes specifications for both wet pipe and dry pipe sprinkler systems, roof hydrant installations with detailed valve configurations, supervisory piping, and future-use capped sprinkler connections. The design plan was originally issued on January 10, 2023, and has undergone four revisions through Bulletins #91 (January 31, 2025), #123 (June 11, 2025), #136 (August 18, 2025), and #172R1 (March 13, 2026). The plan is drawn at a scale of 1/16 inch equals 1 foot and coordinates with associated floor plans and ceiling plans referenced in drawing FP3.01.
The fire protection system design must comply with NFPA 25, NFPA 101, and 527 CMR Massachusetts Comprehensive Fire Safety Code standards with regulatory oversight from the Department of Public Health, Centers for Medicare & Medicaid Services, and the Department of Veterans Affairs. The plan specifies non-combustible, non-accessible areas that do not require sprinklers, areas requiring full sprinkler and piping protection coordinated with architectural plans, and designated areas where code variances have been acquired by others for specialized applications such as elevator shaft and MRL control room protection. All work associated with this fire protection system must comply with prevailing wage rates established in the Massachusetts Department of Labor Standards wage schedule, with primary facility contacts identified as Jeremy Meade, Institutional Foreman (413-552-4765), and John Fydenkevez, Third Class Engineer (413-552-4748).
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BW
DW
EW
FW
GW
HW
JW
KW
LW
BE
CE
DE
EE
FE
GE
HE
JE
CS
DS
ES
FS
GS
HS
JS
PC
LS
3E
2W
3N
4N
4E
1W
3W
2N
2E
1E
4W
1N
AW
AS
2W.2
AE
NW
MS
KE
6"FSP UP&DN
3"SD UP&DN
4"FCVA - ZONE 1
2-1/2"FDV
4" S P
R -1
6"FSP RISE&DN
3"SD RISE&DN
2-1/2"FDV
4”PRV
4”FCVA
6" FS
P
6" FSP
6" FSP
6"NRS GATE VALVE.
6"FSP UP TO ROOF HYDRANT.
6" NRS GATE VALVE.
WALL POST TYPE
HYDRANT VALVE CONTROL.
6" FSP-DROP .
6" X2-1/2" X 2-1/2"
WALL MOUNTED ROOF HYDRANT.
POST-TYPE HYDRANT
VALVE CONTROL.
6"X2-1/2"X2-1/2" FREESTANDING ROOF
HYDRANT, SECURED TO SIDE OF
MECHANICAL WELL WALL. HYDRANT
OUTLETS SHALL BE AT CENTERLINE
ELEVATION 36" TO 60" ABOVE
ADJACENT PENTHOUSE ROOF
4" SPR-2
6" FSP
6" NRS GATE VALVE.
WALL POST TYPE
HYDRANT VALVE CONTROL.
6" FSP-DROP .
6" X2-1/2" X 2-1/2"
WALL MOUNTED ROOF HYDRANT.
6"NRS GATE VALVE.
6"FSP UP TO ROOF HYDRANT.
BS
5N
4N.1
SEE FP 3.01 FOR ENLARGED PLAN
SEE FP 3.01 FOR ENLARGED PLAN
4" SPR-1
4" SPR-1
6" FSP
4" S
PR
-2
6"NRS GATE VALVE.
6"FSP UP TO ROOF OVER
WEST PENTHOUSE.
NON-COMBUSTIBLE
NON-ACCESSIBLE
NO SPRINKLERS NEEDED
4" SPR-1
4" SPR-1
PROVIDE SPRINKLERS AND PIPING
THROUGHOUT ALL AREAS AS REQUIRED.
COORDINATE WITH FLOOR PLAN
AND CEILING PLAN.
FNR
FDV4
W960
WEST
PENTHOUSE
E1
STAIR
W1
STAIR
W910A
SERVICE
ELEVATOR
LOBBY
SERVICE
ELEV.
W961
VEST.
E901
EAST
PENTHOUSE
E900
VEST.
W962
MECHANICAL
E902
MECHANICAL
W951
MRL
CONTROL
ROOM
W9D1
TELECOMMUNICATION
ROOM
2"SPR CAPPED FOR FUTURE USE
2"SUPERVISED VALVE
2"SPR TO INTENDED TO PROVIDE
PROTECTION TO TOP OF
ELEVATOR SHAFT BY OTHERS
SPRINKLERS IN SHAFT SHALL
REQUIRE CODE VARIANCE
AQUIRED BY OTHERS
2" SPR-1
2"SPR CAPPED FOR FUTURE USE
2"SUPERVISED VALVE
2"SPR TO INTENDED TO PROVIDE
PROTECTION TO MRL CONTROL
ROOM W951 BY OTHERS
SPRINKLERS IN MRL CONTROL
ROOM SHALL REQUIRE CODE
VARIANCE AQUIRED BY OTHERS
N1
W1
E1
W2
N2
E2
S1
0'
Project Name:
DCAMM Project Number:
Project Location
Project Architect
Site Number:
CAMIS Number:
Building Number:
Secretariat:
F ile
P a th
Original Issue Date
Revisions
Drawing Title:
Drawing Number:
Project Consultant
HLY2102
Payette Associates Inc.
290 Congress Street, Fifth Floor Boston, MA 02210-1005 Tel: 617-895-1000 www.payette.com
Project Number:
40158.00
10' 20' 40'
HLY 00
N/A
256 HLY 0010
E.O.H.H.S
BR+A CONSULTING ENGINEERS
10 Guest Street, 4th Floor
Boston, MA 02135
617.254.0016 brplusa.com
B
IM
/H o ly o k e S o ld ie rs
H o m e /3
H
S H
C
S B
R
A P
F P
O
R .r v t
PENTHOUSE - FIRE
PROTECTION PLAN
FP2.09
01/10/2023
SOLDIERS' HOME
IN HOLYOKE
LONG-TERM
CARE PACKAGE
110 Cherry Street Holyoke, MA 01040
1/16" = 1'-0"
PENTHOUSE - FIRE PROTECTION PLAN
No. Description Date
1 BULLETIN #91 01/31/2025
2 BULLETIN #123 06/11/2025
3 BULLETIN #136 08/18/2025
4 BULLETIN #172R1 03/13/2026
https://app.procore.com/1526478/project/drawing_areas/1845139/drawing_log/329743190