FIRE PROTECTION DRAWING SET.pdf

PDF 3 MB Posted

Attached to
Z2AA - Renovate Historic Building 4 Federal contract opportunity
Solicitation number
36C24624R0030
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document is a set of fire protection demolition and new construction plans for the renovation of Historic Building 4 at the Fayetteville VA Medical Center. The project involves a complete renovation of the existing building for administrative space and offices, with necessary upgrades to the mechanical, plumbing, electrical, and fire protection systems.

The key details include:

  • Removal of the existing fire sprinkler system and installation of a new automatic wet pipe fire protection system in accordance with NFPA 13 and VA requirements.
  • The new fire suppression system will include a 6-inch double check valve assembly, 6-inch underground piping, 4-inch and 2-inch distribution piping, and sprinklers throughout the building.
  • The building will be fully sprinklered with sprinklers sized based on the hazard classifications (light, ordinary hazard group 1, ordinary hazard group 2).
  • The project is designated as Mission Critical and must comply with VA Physical Security and Resiliency Design Manual requirements.
  • This project is part of Solicitation #36C24624R0030 for the "Renovate Historic Building 4" at the Fayetteville VA Medical Center.

View the file

Other files for this federal contract opportunity

Other files attached to Z2AA - Renovate Historic Building 4, newest first.
File Type Posted
36C24625C0027_1 Award Notice.docx DOCX document
230923 Direct-Digital Control System Connect to Existing N4.pdf PDF
1_b H - Renovate Building 4 IFC pages 12-14.pdf PDF
1_a G - Renovate Building 4 IFC pages 2-3.pdf PDF
1_a G - Renovate Building 4 IFC pages 4-6.pdf PDF
1_a G - Renovate Building 4 IFC pages 7-10.pdf PDF
1_a G - Renovate Building 4 IFC page 1.pdf PDF
3_Arch - Renovate Building 4 IFC pages 36-85.pdf PDF
5_Mech - Renovate Building 4 IFC pages 110-128.pdf PDF
6_Elec - Renovate Building 4 IFC pages 129-155.pdf PDF
2_C - L and S - Renovate Building 4 IFC pages 15-35.pdf PDF
4_FP and P - Renovate Building 4 IFC pages 86-109.pdf PDF
36C24624R0030 0005.docx DOCX document
Drawings.zip ZIP file
36C24624R0030 0004.docx DOCX document
INSTRUCTIONS CONDITIONS AND OTHER STATEMENTS TO BIDDERS-OFFERORS .docx DOCX document
Proposal Item I Cost Breakdown.xlsx XLSX spreadsheet
Fayetteville - Temp Fence.pdf PDF
230541 - NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.pdf PDF
230512 - GENERAL MOTOR REQUIREMENTS FOR HAVAC AND STEAM GENERATION EQUIPMENT.pdf PDF
014529 - TESTING LABORATORY SERVICES.pdf PDF
234000 - HVAC AIR CLEANING DEVICES.pdf PDF
232300 - REFRIGERANT PIPING.pdf PDF
36C24624R0030 0003.docx DOCX document
Proposal Item II Cost Breakdown.xlsx XLSX spreadsheet
Proposal Item III Cost Breakdown.xlsx XLSX spreadsheet
Proposal Item IV Cost Breakdown.xlsx XLSX spreadsheet
PL902 - PLUMBING DOMESTIC WATER ISOMETRICS.pdf PDF
232113 - Hydronic Piping.pdf PDF
233400 - HVAC FANS.pdf PDF
238216 - AIR COILS.pdf PDF
238200 - CONVECTION HEATING AND COOLING UNITS.pdf PDF
Proposal Item V Cost Breakdown.xlsx XLSX spreadsheet
Asbestos - Lead Paint Survey 12-31-2020.pdf PDF
Geotech Report_Fayetteville Bldg 4 Renovation.pdf PDF
230593 - TESTING ADJUSTING AND BALANCING FOR HVAC.pdf PDF
238129 - VARIABLE REFRIGERANT FLOW HVAC SYSTEMS.pdf PDF
230923 - DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC.pdf PDF
238143 - AIR SOURCE UNITARY HEAT PUMPS.pdf PDF
230800 - COMMISSIONING OF HVAC SYSTEMS.pdf PDF
36C24624R0030 0002.docx DOCX document
Statement of Work - Renovate Historic Building 4.pdf PDF
STRUCTRAL DRAWING SET.pdf PDF
PLUMBING DRAWING SET.pdf PDF
MECHANICAL DRAWING SET.pdf PDF
LANDSCAPE DRAWING SET.pdf PDF
ELECTRICAL DRAWING SET.pdf PDF
CIVIL DRAWING SET.pdf PDF
Specifications - Renovate Building 4 Issued For Construction.pdf PDF
Wage Determination.pdf PDF
Show all 50

Z2AA - Renovate Historic Building 4 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CRAWL SPACE

003A

MECHANICAL

OFFICE

ASSOCIATE CHIEF, CPS

PHARMACY RESIDENTS

FEMALE TOILET

MALE TOILET

AFGE STORAGE OFFICE

MECHANICAL

TRAINING ROOM

AFGE LIASISON OFFICE

STORAGE

STORAGE

007A

MECHANICAL ROOM

007B

STORAGE

STAIRS

4" FP

4" FP

4" FP4" FP

4" FP UP

1 1/2" FP

FP DRAIN

FP HOSE

CONNECTION

UG 4" FP

A. REMOVE ALL FIRE SPRINKLER PIPING AND ACCESSORIES IN ENTIRE BUILDING. A NEW AUTOMATIC

WET PIPE FIRE SPRINKLER SYSTEM WILL BE INSTALLED IN THE NEW WORK PHASE OF

CONTRCUTION. REFER TO FX DRAWINGS.

B. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:5

P

M

FD100

BASEMENT FIRE PROTECTION

DEMOLITION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

BASEMENT FIRE PROTECTION DEMOLITION PLAN

G E N E R A L N O T E S :

D R A W I N G N O T E S :

1 REFER TO SITE UTILITY DRAWINGS FOR CONTINUATION.

2 PATCH FLOOR PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.

3 REMOVE FIRE SPRINKLER PIPING AND ASSOCIATED VALVES AND HOSE CONNECTIONS.

4 REMOVE FIRE DEPARTMENT CONNECTION AND ASSOCIATED PIPING. PATCH WALL TO MATCH

EXISTING.

No. Revisions: Date:

REV 0 07/24/2023

07/24/2023

OFFICE

STORAGE

RESTROOM

OFFICE

STAIRS

OFFICE

RESTROOM

HOUSEKEEPING

OFFICE

CLOSET

109A

CLOSET

108A

CLOSET

107A

OFFICE

OFFICE

OFFICE

CLOSET

105A

BREAK

OFFICE

107B

OFFICE

CLOSET

104A

OFFICE

OFFICE

OFFICE

WAITING/ENTRY

OFFICE

CLASSROOM

CLASSROOM

OFFICE

4" FP UP & DN

1 2

A. REMOVE ALL FIRE SPRINKLER PIPING AND ACCESSORIES IN ENTIRE BUILDING. A NEW AUTOMATIC

WET PIPE FIRE SPRINKLER SYSTEM WILL BE INSTALLED IN THE NEW WORK PHASE OF

CONTRCUTION. REFER TO FX DRAWINGS.

B. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:0

P

M

FD101

FIRST FLOOR FIRE PROTECTION

DEMOLITION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN

G E N E R A L N O T E S :

D R A W I N G N O T E S :

1 PATCH FLOOR PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.

2 REMOVE FIRE SPRINKLER PIPING AND ASSOCIATED VALVES AND HOSE CONNECTIONS.

No. Revisions: Date:

OFFICE

CLOSET

216A

OFFICE

CLOSET

215A

RESTROOM

215B

OFFICE

RESTROOM

213B

CLOSET

213A

KITCHEN

STAIRS

114MEN

WOMEN

HOUSEKEEPING

OFFICE

CLOSET

208A

OFFICE

CLOSET

207A

CLOSET

206A

OFFICE

OFFICE

CLOSET

205A

RESTROOM

205B

RESTROOM

203B

OFFICE

CLOSET

203A

OFFICE

CLOSET

202A

RESTROOM

202B OFFICE

OFFICE

CLOSET

219A

RESTROOM

219B

CLOSET

201A

RESTROOM

218B

CLOSET

218A

OFFICE

OFFICE

4" FP UP & DN

A. REMOVE ALL FIRE SPRINKLER PIPING AND ACCESSORIES IN ENTIRE BUILDING. A NEW AUTOMATIC

WET PIPE FIRE SPRINKLER SYSTEM WILL BE INSTALLED IN THE NEW WORK PHASE OF

CONTRCUTION. REFER TO FX DRAWINGS.

B. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:0

P

M

FD102

SECOND FLOOR FIRE

PROTECTION DEMOLITION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN

G E N E R A L N O T E S :

D R A W I N G N O T E S :

1 PATCH FLOOR PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.

2 REMOVE FIRE SPRINKLER PIPING AND ASSOCIATED VALVES AND HOSE CONNECTIONS.

No. Revisions: Date:

2" FP

2" FP

1 1/2" FP

1 1/2" FP

2" FP

2" FP2" FP

2" FP

4" FP DN 1

A. REMOVE ALL FIRE SPRINKLER PIPING AND ACCESSORIES IN ENTIRE BUILDING. A NEW AUTOMATIC

WET PIPE FIRE SPRINKLER SYSTEM WILL BE INSTALLED IN THE NEW WORK PHASE OF

CONTRCUTION. REFER TO FX DRAWINGS.

B. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:1

P

M

FD103

ATTIC FIRE PROTECTION

DEMOLITION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

ATTIC FIRE PROTECTION DEMOLITION PLAN

G E N E R A L N O T E S :

D R A W I N G N O T E S :

1 PATCH FLOOR PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.

2 REMOVE FIRE SPRINKLER PIPING AND ASSOCIATED VALVES AND HOSE CONNECTIONS.

No. Revisions: Date:

6" DOUBLE

CHECK VALVE

6" SWING CHECK VALVE &

ALARM FLOW SWITCH

FPFP

STAIR A

S000A

ELEVATOR

E000

ELEC RM

E001

PIV VISITOR

GROUND DEFENSE TRAINING

PIV STAFF

STORAGE

DETECTIVE

TRAINING SARGENT

COMM DEVICE STO.

EVIDENCE STO.

PIV PICTURE RM

DEPUTY CHIEF

CHIEF

ADMIN/PIV/CHECK IN

EAST CORRIDOR

EMERGENCY MANAGER

BREAK/WORK RM

TOILET

007B

STAIR B

S000B

ELEC/UTILITY

F I R E H A Z A R D L E G E N D

LIGHT HAZARD

ORDINARY HAZARD GROUP 1

ORDINARY HAZARD GROUP 2

PIV STORAGE

ARMORY

SECURE CAGE

TOILET

006B

SHOWER

006A

H.C.SUPP.

WOMEN

SHOWER

007A

MEN

H.C.

FX501

UG 6" FP

FIRE DEPARTMENT

CONNECTION

6" FP

MAJOR OFFICE

SOUTH CORRIDOR

SUPPLY

FX501

6" FP

4" FP UP

2" FP DRAIN UP

FP

SOUTH CORRIDOR

NORTH CORRIDOR

STORAGE

ELEV LOBBY

2" FP DRAIN

4" FP

6" FP

FX501

UTILITY

2" FP

1" FP DRAIN

DRAIN

ELEV MACHINE RM

E002

6'x6'x2' PLUMBING

DRAINAGE PIT

4" BYPASS

PIPE

4" NC CONTROL VALVE WITH

SUPERVISORY SWITCH

A. INSTALL COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA

13 AND VA FIRE PROTECTION MANUAL.

B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH

EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF

SYSTEM PIPING THROUGH MAIN DRAIN VALVE.

E. CONTRACTOR SHALL DETERMINE PIPE SIZES BY HYDRAULIC CALCULATION AND SUBMIT

SPRINKLER DESIGN.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES.

EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON PLANS IS TO CONVEY DESIGN INTENT AND

DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD

CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE

PARTITIONS, AND FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.

I. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

FIRE SPRINKLER HAZARD SCHEDULE

CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES

LIGHT HAZARD

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

0.10 GPM/SF OVER 1500 SF

0.15 GPM/SF OVER 1500 SF

0.20 GPM/SF OVER 1500 SF

100 GPM

250 GPM

250 GPM

30 MIN

60 MIN

90 MIN

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

BASE AREA

BASE AREA

BASE AREA

SPRINKLER DENSITY

1 SPRINKLER PER 225 SF

1 SPRINKLER PER 130 SF

1 SPRINKLER PER 130 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:1

P

M

FX100

BASEMENT FIRE SUPPRESSION

PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

BASEMENT FIRE SUPPRESSION PLAN

G E N E R A L N O T E S :D R A W I N G N O T E S :

1 REFER TO SITE UTILITY DRAWINGS FOR CONTINUATION.

2 CORE DRILL THROUGH FOUNDATION WALL FOR INSTALLATION OF NEW UNDERGROUND PIPING.

PROVIDE PIPE SLEEVE AND SEAL AROUND PENETRATION. REFER TO PIPE PENETRATION THROUGH

WALLS BELOW GRADE DETAIL ON SHEET PL501.

3 REFER TO FIRE SERVICE SECTIONS ON SHEET FX501 FOR WORK IN THIS AREA.

4 CORE DRILL THROUGH WALL FOR PIPE PENETRATION. PROVIDE PIPE SLEEVE AND SEAL AROUND

PENETRATION.

5 REFER TO FIRE RISER SECTION ON SHEET FX501 FOR WORK IN STAIRWELL.

6 INSTALL SIDEWALL SPRINKLER NOT MORE THAN 2'-0" ABOVE FLOOR OF ELEVATOR PIT. REFER TO

PLUMBING DRAWINGS FOR ELEVATOR PIT SUMP PUMP.

7 PIPING DISCHARGES TO PLUMBING DRAINAGE PIT. REFER TO ARCHITECTURAL AND STRUCTURAL

DRAWINGS FOR LOCATION OF PLUMBING DRAINAGE PIT.

8 REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR PLUMBING DRAINAGE PIT.

No. Revisions: Date:

4" FP UP & DN

FP

FP

FP

STAIR A

S100A

ELEVATOR

E100

ELEV LOBBY

SECURITY SCREEN AREA

QUALITY SAFETY STAFF

SYSTEM REDESIGN STAFF

QUALITY SAFETY SUP

WEST CORRIDOR

QUALITY MANAGER

CONFERENCE/INCIDENT

COMMAND

VOLUNTARY SERVICE

TR

SOUTH CORRIDOR

SHAFTELEC

STAIR B

S100B

MEN

WOMEN

BREAK/WORK RM

CHIEF, SYSTEM REDESIGN

EAST CORRIDOR

LEAF COORD OFFICE

LEAF COORD STAFF

F I R E H A Z A R D L E G E N D

LIGHT HAZARD

ORDINARY HAZARD GROUP 1

ORDINARY HAZARD GROUP 2

ENCLOSURE

SUPPLY

FX501

FP

2" FP DRAIN UP & DN

NORTH CORRIDOR

PORTICO NORTH

PORTICO SOUTH

A. INSTALL COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA

13 AND VA FIRE PROTECTION MANUAL.

B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH

EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF

SYSTEM PIPING THROUGH MAIN DRAIN VALVE.

E. CONTRACTOR SHALL DETERMINE PIPE SIZES BY HYDRAULIC CALCULATION AND SUBMIT

SPRINKLER DESIGN.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES.

EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON PLANS IS TO CONVEY DESIGN INTENT AND

DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD

CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE

PARTITIONS, AND FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.

I. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

FIRE SPRINKLER HAZARD SCHEDULE

CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES

LIGHT HAZARD

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

0.10 GPM/SF OVER 1500 SF

0.15 GPM/SF OVER 1500 SF

0.20 GPM/SF OVER 1500 SF

100 GPM

250 GPM

250 GPM

30 MIN

60 MIN

90 MIN

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

BASE AREA

BASE AREA

BASE AREA

SPRINKLER DENSITY

1 SPRINKLER PER 225 SF

1 SPRINKLER PER 130 SF

1 SPRINKLER PER 130 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:1

P

M

FX101

FIRST FLOOR FIRE SUPPRESSION

PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

FIRST FLOOR FIRE SUPPRESSION PLAN

G E N E R A L N O T E S :D R A W I N G N O T E S :

1 REFER TO FIRE RISER SECTION ON SHEET FX501 FOR WORK IN STAIRWELL.

No. Revisions: Date:

FP

FP

STAIR A

S200B

ELEV LOBBY

ELEVATOR

E200

ELEV LOBBY

CHIEF OF STAFF

SECRETARY

SECRETARY

ASSISTANT DIRECTOR

VISITOR

SECRETARY

NURSE EXECUTIVE

HSS

HSS

HSS

HSS

PUBLIC AFFAIRS

COMPLIANT OFFICER

ASSOCIATE DIRECTOR

SECRETARY

SECRETARY

SUPPLY

PRIVATE TOILET

DIRECTOR

STAIR B

S201B

SHAFTELEC

WOMEN

BREAK/WORK RM

RECEP/WAITING

F I R E H A Z A R D L E G E N D

LIGHT HAZARD

ORDINARY HAZARD GROUP 1

ORDINARY HAZARD GROUP 2

EAST CORRIDOR

4" FP UP & DN

NORTH CORRIDOR

NORTH CORRIDOR-3

216-3

NORTH CORRIDOR-2

216-2

NORTH CORRIDOR-1

216-1

ENCLOSURE

SOUTH CORRIDOR-1

216-1

SUPPLY

FX501 1 1/2" FP DRAIN UP & DN

NORTH CORRIDOR

SOUTH CORRIDOR

A. INSTALL COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA

13 AND VA FIRE PROTECTION MANUAL.

B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH

EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF

SYSTEM PIPING THROUGH MAIN DRAIN VALVE.

E. CONTRACTOR SHALL DETERMINE PIPE SIZES BY HYDRAULIC CALCULATION AND SUBMIT

SPRINKLER DESIGN.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES.

EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON PLANS IS TO CONVEY DESIGN INTENT AND

DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD

CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE

PARTITIONS, AND FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.

I. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

FIRE SPRINKLER HAZARD SCHEDULE

CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES

LIGHT HAZARD

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

0.10 GPM/SF OVER 1500 SF

0.15 GPM/SF OVER 1500 SF

0.20 GPM/SF OVER 1500 SF

100 GPM

250 GPM

250 GPM

30 MIN

60 MIN

90 MIN

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

BASE AREA

BASE AREA

BASE AREA

SPRINKLER DENSITY

1 SPRINKLER PER 225 SF

1 SPRINKLER PER 130 SF

1 SPRINKLER PER 130 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:2

P

M

FX102

SECOND FLOOR FIRE

SUPPRESSION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

SECOND FLOOR FIRE SUPPRESSION PLAN

G E N E R A L N O T E S :D R A W I N G N O T E S :

1 REFER TO FIRE RISER SECTION ON SHEET FX501 FOR WORK IN STAIRWELL.

No. Revisions: Date:

4" FP DN

FX501

F I R E H A Z A R D L E G E N D

ORDINARY HAZARD GROUP 1

1 1/2" FP DRAIN DN

FP

FPFP

FP

FPFP

FP FP FP

ATTIC

FX501

A. INSTALL COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA

13 AND VA FIRE PROTECTION MANUAL.

B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH

EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF

SYSTEM PIPING THROUGH MAIN DRAIN VALVE.

E. CONTRACTOR SHALL DETERMINE PIPE SIZES BY HYDRAULIC CALCULATION AND SUBMIT

SPRINKLER DESIGN.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES.

EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON PLANS IS TO CONVEY DESIGN INTENT AND

DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD

CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE

PARTITIONS, AND FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.

I. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

FIRE SPRINKLER HAZARD SCHEDULE

CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES

LIGHT HAZARD

ORDINARY HAZARD GROUP I

ORDINARY HAZARD GROUP II

0.10 GPM/SF OVER 1500 SF

0.15 GPM/SF OVER 1500 SF

0.20 GPM/SF OVER 1500 SF

100 GPM

250 GPM

250 GPM

30 MIN

60 MIN

90 MIN

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

QR; K = 5.6 OR K = 8.0

BASE AREA

BASE AREA

BASE AREA

SPRINKLER DENSITY

1 SPRINKLER PER 225 SF

1 SPRINKLER PER 130 SF

1 SPRINKLER PER 130 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:2

P

M

FX103

ATTIC FIRE SUPPRESSION PLAN

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

ATTIC FIRE SUPPRESSION PLAN

G E N E R A L N O T E S :D R A W I N G N O T E S :

1 REFER TO FIRE SERVICE SECTIONS ON SHEET FX501 FOR WORK IN THIS AREA.

No. Revisions: Date:

1ST FLOOR

0'-0"

BASEMENT

-10'-0"

6" DOUBLE CHECK

DETECTOR VALVE

WITH SUPERVISORY

SWITCHES UG 6" FP

FROM SITE

6" SWING CHECK VALVE

WITH PRESSURE GAUGES &

DRAIN CONNECTION

MAIN DRAIN VALVE

6" WATER FLOW ALARM

SWITCH WITH RETARD

UTILITY ROOM FLOOR

2" DRAIN OUTLET

TO PLUMBING

DRAINAGE PIT

EXTERIOR FIRE

DEPARTMENT CONNECTION

6" FP

GRADE

1" DRAIN OUTLET TO

PLUMBING DRAINAGE PIT

1" FP DRAIN

BALL DRIP VALVE

4" CHECK VALVE

FX501

EXTERIOR WALL

CRAWL SPACE

-8'-0"

6" FP

4" FP

NORMALLY CLOSED CONTROL

VALVE WITH SUPERVISORY SWITCH

FOR FORWARD FLOW BACKFLOW

PREVENTER TESTING

4" BYPASS PIPE

1ST FLOOR

0'-0"

BASEMENT

-10'-0"

2ND FLOOR

11'-0"

ATTIC

21'-2"

FIRE HOSE

CONNECTION VALVE

FIRE HOSE

CONNECTION VALVE

FIRE HOSE

CONNECTION VALVE

6" FP

2" FP DRAIN

4" FP

4" FP

4" FP

4" FP

4" FP TO ATTIC

INSPECTOR'S TEST AND

DRAIN CONNECTION

1 1/2" FP

DRAIN

1 1/2" FP DRAIN

1 1/2" FP DRAIN

2" FP DRAIN RISER

2" FP DRAIN RISER

4" FP RISER

INSPECTOR'S TEST AND

DRAIN CONNECTION

INSPECTOR'S TEST AND

DRAIN CONNECTION

INDICATING TYPE

CONTROL VALVE WITH

SUPERVISORY SWITCH

CHECK VALVE

PRESSURE GAUGE

WATERFLOW SWITCH

INDICATING TYPE

CONTROL VALVE WITH

SUPERVISORY SWITCH

CHECK VALVE

PRESSURE GAUGE

WATERFLOW SWITCH

INDICATING TYPE

CONTROL VALVE WITH

SUPERVISORY SWITCH

CHECK VALVE

PRESSURE GAUGE

WATERFLOW SWITCH

1 1/2" FP DRAIN RISER

FROM ATTIC

6" FP

2" FP DRAIN TO

UTILITY 002

4" FP

1 1

ATTIC

21'-2"

ATTIC

21'-2"

4" FP

PRESSURE GAUGE

WATERFLOW SWITCH

CHECK VALVE

INDICATING TYPE CONTROL VALVE

WITH SUPERVISORY SWITCH

INSPECTOR'S TEST AND

DRAIN CONNECTION

1-1/2" FP DRAIN

4" FP RISER

1ST FLOOR

0'-0"

BASEMENT

-10'-0"

1ST FLOOR

0"

BASEMENT

-10'-0"

STAIR LANDING

-5'-0"

CRAWL SPACE

-8'-0"

WEST STAIR GRADE

-2'-7"

FX501

4" FP

6" FP

6" FP FROM SITE

BALL DRIP

VALVE

1" FP DRAIN

4" CHECK

VALVE

4" FP TO EXTERIOR FDC & BYPASS

FOR FORWARD FLOW BACKFLOW

PREVENTER TESTING

UTILITY ROOM FLOOR

CRAWL SPACE

-8'-0"

A. INSTALL COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN ACCORDANCE WITH NFPA

13 AND VA FIRE PROTECTION MANUAL.

B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH

EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE PATTERN AND

COVERAGE.

C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A

COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.

D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF

SYSTEM PIPING THROUGH MAIN DRAIN VALVE.

E. CONTRACTOR SHALL DETERMINE PIPE SIZES BY HYDRAULIC CALCULATION AND SUBMIT

SPRINKLER DESIGN.

F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES.

EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON PLANS IS TO CONVEY DESIGN INTENT AND

DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD

CLASSIFICATIONS SHOWN.

G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE

PARTITIONS, AND FIRE EXTINGUISHER CABINETS.

H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.

I. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:0

:3

P

M

FX501

FIRE SUPPRESSION SECTIONS

AND DETAILS

07/24/2023 PP GP

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

1/2" = 1'-0"

FIRE SERVICE SECTION 1

1/2" = 1'-0"

FIRE RISER SECTION - STAIR B

1/2" = 1'-0"

FIRE RISER SECTION - ATTIC

1/2" = 1'-0"

FIRE SERVICE SECTION 2

G E N E R A L N O T E S :

D R A W I N G N O T E S :

1 CORE DRILL THROUGH FLOOR FOR INSTALLATION OF PIPE PENETRATING FLOOR. REFER TO

SUPPORT/ANCHOR FOR PIPE RISERS DETAILS ON SHEET PL501.

No. Revisions: Date:

10.00_FD100 - BASEMENT FIRE PROTECTION DEMOLITION PLAN
FD100 - BASEMENT FIRE PROTECTION DEMOLITION PLAN
10.01_FD101 - FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN
FD101 - FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN
10.02_FD102 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN
FD102 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN
10.03_FD103 - ATTIC FIRE PROTECTION DEMOLITION PLAN
FD103 - ATTIC FIRE PROTECTION DEMOLITION PLAN
10.04_FX100 - BASEMENT FIRE SUPPRESSION PLAN
FX100 - BASEMENT FIRE SUPPRESSION PLAN
10.05_FX101 - FIRST FLOOR FIRE SUPPRESSION PLAN
FX101 - FIRST FLOOR FIRE SUPPRESSION PLAN
10.06_FX102 - SECOND FLOOR FIRE SUPPRESSION PLAN
FX102 - SECOND FLOOR FIRE SUPPRESSION PLAN
10.07_FX103 - ATTIC FIRE SUPPRESSION PLAN
FX103 - ATTIC FIRE SUPPRESSION PLAN
10.08_FX501 - FIRE SUPPRESSION SECTIONS AND DETAILS
FX501 - FIRE SUPPRESSION SECTIONS AND DETAILS